Académique Documents
Professionnel Documents
Culture Documents
Oliver Nldner
Siemens AG
P.O. Box 3240
91050 Erlangen
Germany
In legal and organisational view inner EMC is a matter of
the correct function of component combinations and their
interplay, and thus subject between manufacturer and user.
In contrast outer EMC concerns cross-link of the switchgear
with the outside electrical environment, for example the MV
grid, auxiliary power supplies, the protection system and the
control and communication networks. Thus the limitation of
emissions and minimum requirements on immunity are essential to avoid interference with other equipment, which may
be assigned to third parties.
Inner EMC
MV conductor
LV system
Control &
protection
INTRODUCTION
Outer EMC
MV network
Auxiliary supply
Communication
Other installations
ELECTROMAGNETIC CLIMATE
Susceptible equipment
The possible effects, which may occur under certain circumstances from the above mentioned sources, are defects
and faulty operation as described in the following.
1) Insulation: Overvoltage in the network due to
switching processes and similar transient disturbances frequently endanger the lifetime of equipment insulation; for
example cable terminations are especially susceptible.
2) Instrument transformers: Under specific network
conditions (isolated neutral) they can fall victim to ferroresonance initiated by transients. If not adequately damped, ferroresonance leads to failure through thermal overload.
3) Capacitors, filter units and transformers: Lowfrequency system perturbation caused by unstable loads has
many effects: inadmissible harmonic content can cause
overheating. Network resonance may occur if capacitor units
and transformers are not correctly matched to each other.
System perturbations of all types also affect the connected
measuring equipment.
4) Electronic devices: Overvoltage, transferred from
the MV side, can endanger the ports. Additionally, disturbance impulses can pervert the input signals and cause
faulty outputs.
D.
Influencing mechanisms
Between MV and LV system galvanic coupling is only relevant where they are galvanically connected, e.g. through
resistive voltage dividers. HF transients 'escaping' from the
primary circuit through the divider, against the reference potential (ground), can lead to high-frequency voltage impulses,
in proportion to the divider ratio, at the secondary side of the
divider. However, this is of minor importance only.
3) Radiated coupling: the fields from transient effects
induce disturbance currents and voltages in conductors. Not
only lines within the switchgear are affected, but also conductors within electronic devices. For tightly laid conductors this
method of coupling corresponds to the inductive or capacitive.
4) Coupling within electronic equipment: low-voltage
lines have galvanic connection within the interior of the
equipment. That is, transient phenomena can spread within
the unit, affecting electronic components. Countermeasures
can be taken (by the electronics manufacturer) only within
the equipment or at the point of cable entry.
have to be applied, EMC considerations must be ideally incorporated in the design of the switchgear and carried
through to commissioning. Observation of the following
points will ensure compatibility of the components:
- restrict or at least limit the emission of disturbances or its
effects as far as possible, even if prevention is not completely possible;
- select equipment to suit its surroundings (separation of
immunity to disturbance into zones);
- increase immunity to disturbance by adequate EMC design, assembly and wiring of the switchgear;
- ensure a definite reference potential (earth) and effective
earthing system;
- if applicable, use supplementary measures such as filters, screening etc.
Section IV of this paper describes measures to achieve
EMC in practice.
All the coupling mechanisms generally appear simultaneously and the finally transferred disturbance is the sum of the
effects. In general, it is of little importance which mechanism
contributes which proportion, or if one or the other may be
neglected, as the result of EMC counts. In detail however,
one needs information about the magnitude of each effect,
because the reduction of each one requires specific measures. Adequate switchgear design can minimise interference.
A.
E.
Legislative requirements
1. Protection requirements
Equipment shall be so designed and manufactured, having
regard to the state of the art, as to ensure that:
(a) the electromagnetic disturbance generated does not exceed the level above which radio and telecommunications equipment or other equipment cannot operate as intended;
(b) it has a level of immunity to the electromagnetic disturbance to be expected in its intended use which allows it
to operate without unacceptable degradation.
2. Specific requirements for fixed installations
Installation and intended use of components
A fixed installation shall be installed applying good engineering practices and meeting the protection requirements.
Those good engineering practices shall be documented and
the documentation shall be held at the disposal of the relevant national authorities for inspection purposes as long as
the fixed installation is in operation.
The directive covers any electrical equipment and fixed installations, in particular those which may generate disturbance and be susceptible to interference, thus mainly
equipment containing active electronics. In contrast, equipment which does due to its design not produce interference and operates without degradation in the presence of
disturbances is explicitly excluded as inherently benign in
terms of EMC; see Table I.
Temporary switching actions are not relevant to EMC [2];
refer also to section III.E.3. Therefore switching devices and
other components which do not contain active electronics are
The route to electromagnetic compatibility comprises several steps. To avoid the situation that incompatibility is first
discovered during commissioning and that retrofit measures
TABLE I
Classification of switchgear and its components
under the EMC Directive
Equipment
Switching devices
Circuit-breaker, switch,
disconnector, earthing switch,
contactor, HRC fuse
(x)
Switchgear assemblies
Air-insulated and gas-insulated
switchgear assemblies,
automatic circuit-recloser
LV secondary electronics
Protection relay, control electronics, communication equipment
Other components
Instrument transformer, sensor,
surge arrester, insulator, earthing
transformer, reactor, capacitor
B.
C.
Realisation (examples)
a) Permanent use at
predefined location
normally given;
mobile switchgear may need
special consideration
d) Up-to-date documentation
of the technical status
No CE-marking of MV switchgear
D.
Normative requirements
Professional commissioning
and maintenance by qualified
personnel, refer for example
to EN 50110
Part 1
Part 2
Part 3
Part 4
Part 5
Part 6
The design of switchgear contributes substantially to prevent the propagation of interferences, to limit the effects of
disturbances and also to create the conditions for appropriate
interference immunity. The following sections give practical
guidelines of measures to archive EMC. Gas-insulated MV
switchgear is used as an example. However, the guidelines
presented here apply to every type of switchgear. The rules
also apply if equipment or components are changed, added
or retrofitted at a later stage on site.
E
E
D
A
A
(D) Cabling and wiring
(E) Electronic devices
Regarding EMC, the MV part of switchgear is almost passive; the main circuit does not generate interference under
normal operation, but conducts electromagnetic interference
from the grid. Nevertheless, some measures which may
commonly not be associated with EMC should be considered already in the planning stage.
Insulation coordination shall be ensured and, if necessary, surge protection shall be installed [9].
All components and the electrical environment of the installation shall be reviewed comprehensively - from the incomer to the outgoing circuits. Some switching duties may
require special measures.
(3)
(1)
(2)
each electronic device has its own tape; (1) and (2);
a protective conductor (3) realises equipotential bonding
between door and LV compartment;
Support insulators
Secondary systems must on the one hand withstand interferences from the MV system without damage or faulty operation, and on the other hand be designed such that interferences within the secondary system itself are minimised.
1) Auxiliary and control circuits
The wiring of auxiliary and control circuits must be segregated from the main circuit, e.g. by earthed metallic partitions
(pipe, flexible metallic tube) or by means of partitions from
insulating material (e.g. tubes). Item 3 shows an example
with instrument transformer cables.
Inductive loads of auxiliary and control circuits, such as
contactor, relay, motor, tripping solenoid should be fitted with
a surge protection circuit (freewheeling diode, varistor) if the
auxiliary voltage is 60 VDC or higher.
Flexible tubes
on metal sheet
2) Low-voltage cabinet
The LV cabinet accommodates most of the electronics for
protection, control and communication. The cabinet should
be subdivided into zones, e.g. areas reserved for terminals
and built-in devices. If applicable, built-in devices should be
grouped into those being susceptible and less or nonsusceptible to electromagnetic disturbances.
Where cubicle lighting is required, non-fluorescent lamps
or LED should be used preferably.
E.
1) Layout guidelines
The objective of making a suitable wiring arrangement is to
avoid undesirable coupling between different lines and to
avoid influence from outside. Measures to minimise interferences are:
spatial loops should be avoided, i.e. wiring should preferably be designed radially;
Wiring ducts
Space for secondary devices
Terminal blocks
- switching devices
- earthing
- instrument transformers
Incoming / outgoing cables
- switchgear internal (right)
- outside (left)
TABLE IV
Cables in the secondary system of switchgear
Group
Type
Application
Cables
- DC voltage 60 V
- AC voltage 25 V
Shielded cables
- Analogue signals
(e.g. sensors)
- Data transfer (bus systems)
Coaxial cables
Cables
- DC voltage > 60 V
(up to max. 400 V)
- AC voltage > 25 V
(up to max. 400 V)
2) Screened conductors
The quality of contact between screens and switchgear frame
has important influence on the effectiveness of the screen.
All screen connections must be "high-frequency proof" (HFproof), that is, coaxial, low resistance and low inductive.
A secure screen termination with low-resistance contact to
earth is ideally achieved with an all-round 360, large surface
connector between screen and the reference potential of the
earth. This can be accomplished by clamping the screen with
spring loaded or shell clamps. Unthreading and twisting the
screen braid into a pig tail (plait), which is attached to an
earth terminal is not sufficient.
For measurement sensor connections and coaxial leads from
voltage detecting systems follow manufacturer's advice regarding single or both end screen bonding and earthing.
3) Examples
Figure 12 shows the entry of external LV cables into the connection compartment of a switchgear cubicle. The metal
duct, whose cover is removed for the photo (left), separates
the LV and MV cables. Insulating tubes group wires of different function.
TABLE V
Example of wiring in
an MV connection
compartment:
Requirement
EMC
Different types of LV
cables are grouped by
flexible tubes (right)
Interference
emission
IEC 60255-26
IEC 61000-6-4
Tables 1 and 2
Tables 1 to 3
IEC-CISPR 11
Group 1, Class A
Interference
immunity
IEC 60255-26
IEC 61000-6-2
Tables 3 to 7
Tables 1 to 4
IEC 61000-4-12
100 kHz, Table 1, Level 3
no interface to the
MV conductor
IEC 61000-4-18
100 kHz and 1 MHz,
Table 1, Level 3 with Note "a"
* e.g. via instrument transformer, sensor or capacitive electrode
For devices and components without interface to mediumvoltage circuits the immunity specifications of industrial environment suffice, supplemented with typical disturbance phenomena which appear at switching operations.
VIII. REFERENCES
ELECTROMAGNETIC FIELDS
V.
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
< 1 T
Grid dimension 20 cm
[9]
Switchgear
assembly
[10]
[11]
Front side
[12]
[13]
Electromagnetic compatibility is a multifaceted issue involving functional, legal and safety requirements. Metal-enclosed medium voltage switchgear inhere good preconditions
to meet all of them and to achieve an intact electromagnetic
climate. The design of metal-enclosed switchgear must realise continuous equipotential bonding and earthing as well as
an effective separation between medium voltage and secondary system. Electronic devices should comply with international standards to ensure adequate interference emission
and immunity. The installation and wiring of the internal components should follow the guidelines presented in this paper.
An accurate documentation proves design and manufacture
of the switchgear according to the applicable rules of electrical equipment engineering. In the end, EMC of mediumvoltage switchgear is not a big challenge, but a matter of the
design in detail and the quality of manufacture.
VII. ACKNOWLEDGEMENTS
The authors thank Dr. Bernd Jkel, Erlangen, and Andreas
Werner, Frankfurt/Main, for their contributions to the EMC
guidelines and the assessment of switchgear.