Vous êtes sur la page 1sur 21

DUPLEX DOMESTIC WATER PUMPS

42 CROSBY ST
02.19.15

221000
221000-01-0
E.M.

TRITON NOTE;
ENGINEER, PLEASE PROVIDE INFORMATION REQUIRED
ON PAGE 3 REGARDING PUMP SUCTION PRESSURE.

Electrical contractor to provide 40A, 3P


circuit breaker and 4#8&1#10G-3/4"C in
lieu of 20A, 3P and 4#12 & 1#12G-3/4"C
shown on the design document

03-05-15

E. SHIPLEY

MS/BB

03/06/2015

SEE CONSULTANT COMMENTS

G. A. Fleet Associates, Inc.

G. A. Fleet Assoc., Inc.


P. O. Box 616
Harrison, NY 10528
(914) 835 - 4000
Fax (914) 835 - 1331

Important:
Drawings are not to scale, use dimensions shown.
Do not fix foundation bolts rigidly until equipment is in place, since castings vary slightly in dimensions.
Seismic restraints and or calculations are not provided unless specifically noted below.

Fleet Pump & Service


(914) 835 - 3801
Fax (914) 835 - 2946

Sold To:

Demar Plumbing Corp.


147 Attorney Street
New York, NY 10002

Engineer:

Rodkin Cardinale PC

System:

Duplex Domestic Water Booster System

Fleet Order No.

Marks:

42 Crosby Street

Sheet:

QTY

Ship To:
Demar Plumbing
C/O 42 Crosby Street
(Contractor to Confirm)
Date:

1/21/15

300-378

Customer Order No.

Of:

By:

R. DiLorenzo

DUPLEX DOMESTIC WATER BOOSTER SYSTEM BP-1,2


1-

Factory pre-piped packaged Syncroflo system consisting of factory assembling,


mounting and wiring of pumps, motors, VFD drives, valves and control panel on a
common fabricated steel base suitable for grouting. System includes:
2-

Peerless Model C610A close-coupled end suction pumps, bronze fitted


construction with mechanical seals. Each pump is rated for 80 GPM at 130 (56
PSIG) TDH when close coupled to a 7.5 HP, 208/3/60, 3500 RPM ODP motors
with 1.15 SF.

2-

Thermal safety purge valves, field piped to drain.

2-

Combination pressure regulating and check valves.

4-

Pump isolation valves.

1-

Interconnecting piping and wiring. Headers are 3 304SS with flanged ends.

1-

Duplex control panel with: 2-circuit breaker disconnect switches, 2- magnetic


across-the-line by-pass starters with three phase thermal overload protection, 2VFD Nema 1 drives, 2-HOA selector switches, 2-pump running lights, 1-control
circuit transformer, 1-automatic alternator with manual override, 2-pump failure
alarm with light, 1-low suction level alarm (from Roof Tank Control Panel) with
light, pump cut-off and automatic reset, 1-low system pressure alarm with light,
1-common audible alarm with silencing pushbutton, 4-auxiliary alarm contacts,
all mounted and prewired in a NEMA-12 enclosure. Panel wired for two
incoming power feeds and includes an automatic power transfer relay.

1-

Set of pressure gauges, pressure switches and controls for automatic operation.

1-

Differential pressure transmitters.

G. A. Fleet Associates, Inc.

Important:
Drawings are not to scale, use dimensions shown.
Do not fix foundation bolts rigidly until equipment is in place, since castings vary slightly in dimensions.
Seismic restraints and or calculations are not provided unless specifically noted below.

G. A. Fleet Assoc., Inc.


P. O. Box 616
Harrison, NY 10528
(914) 835 - 4000
Fax (914) 835 - 1331
Fleet Pump & Service
(914) 835 - 3801
Fax (914) 835 - 2946

Pre-charged hydropneumatic tank 132 gallon, 125 PSIG working pressure ASME
(shipped loose), remote mounted. Contractor to make final connections and provide
isolation and drain valves.

CONTRACTOR PLEASE NOTE:


1. Inertia base not included, to be provided by others.
2. Control wiring by others
3. Vibration isolators, flexible connectors, di-electric fittings and by-pass piping to be
provided by the Contractors, as required.
4. Contractor to verify access and advise if the system needs to be fabricated for site
disassembly.
5. The unit will be built with a split base for ease of disassembly after unloading, by the
contractor and reassembly on site. Contractor to reassemble the package and
replace sensing lines as required.
6. Please schedule equipment start-up two (2) weeks in advance, call Julia French
914-381-7921.
ENGINEER PLEASE CONFIRM / ADVISE:
1. Panel power feed arrangement, submitted as individual power feeds to each pump.
2. Tank location.
3. Suction Pressure:
45
Minimum at the pump _______
PSIG
50
Maximum in the street _______ PSIG

ENGINEER
PLEASE PROVIDE
INFORMATION

42 Crosby Street
US-2722-137

Type:
Pump Model:
Nom. Speed:
Impeller Dia.:
Curve No.:
Market :

C - End Suction Close Coupled General Purpose


Peerless - C610A
3568 RPM, 60 Hz Electric
inch
5.62
3115001/
Water

Page No : 1

Head - ft

150

NPSH - ft
Power - hp

Contact :
Phone :
Date :

Fax :
Wednesday, January 21, 2015

Item :
Impeller No.:
Fluid:
Temperature:
Viscosity:
Sp. Gravity:
Your Ref. :

D1-6.00 inch, D2-5.00 inch, D3-4.00 inch

D1

100
50

Demar Plumbing Corp.

D3

90
80
70
60
50
40
30
20
10

1
SeePtslist
Water
F
68
1.007 cSt
1.000

Duty Flow

Efficiency - %

Project :
Quote No. :

Customer :

80 US gpm

Duty Head

130 ft

Imp. Dia.

5.62 inch

Power Required

4.7 hp

NPSH Required

5.1 ft

Efficiency

57.2 %

Peak Power
Closed Valve Head
Tolerance

6 hp
137.7 ft
Hyd InstPeerless Std

15
10
5
6
4
2

Comments

Flow
(US gpm)
30.6
43.7
56.9
70.0
83.2
96.3
109.5
122.7
135.8

50

100
Flow - US gpm

Head
(ft)

Efficiency
(%)

141.7
141.3
139.7
136.8
132.8
127.6
121.3
114.0
105.6

32.8
41.9
48.9
54.2
58.0
60.5
61.6
61.5
60.2

150

200

Power Required
(hp)
3.3
3.7
4.1
4.5
4.8
5.1
5.4
5.7
6.0

Perf. curve represents typical


perf, vel. head is incld. Perf.
curves tests are performed in
accordance with H.I.Stds.

NPSH Required
(ft)
4.2
4.1
4.2
4.6
5.3
6.6
8.5
11.1
14.6

Grundfos - RAPID v8.25.9.1 (Windows 7) - 06th March 2012.

HEADER
SIZE

KEY

57"
1448mm

47"
1194mm
42 1/2"
1080mm
47 1/2"
1207mm

45"
1143mm
40"
1016mm
45"
1143mm

143 - 215JM

254 - 286JM

254 - 256JM

58"
1473mm

52"
1321mm

51"
1295mm

42"
1067mm

40"
1016mm

143 - 215JM

OW

D
OW (MAX)

1 1/2" TYP. (38mm)


BW

BW

MOTOR
FRAME SIZE

DIMENSIONAL KEY

66" (1676mm)

36" MIN. CLEARANCE REQ'D.


EXCEPT AS NOTED PER NEC
(NFPA-70) SECTION 110

44" (1118mm)

1 1/2" TYP. (38mm)

SYNCROFLO PACKAGED PUMPING SYSTEMS COMPLY WITH


OSHA REGULATIONS AND FEDERAL REGULATION 29 CFR
1910.399. THE ENTIRE PACKAGED SYSTEM IS THIRD PARTY
CERTIFIED.

1. ALL DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE.


2. PURGE VALVE DRAIN LINE TO BE PIPED TO FLOOR DRAIN IN
PROXIMITY OF BOOSTER SYSTEM (BY OTHERS).
3. SEE DATA SYSTEM SHEET FOR L/H OR R/H HEADERS
ENTRY/EXIT CONNECTION

NOTES:

10 1/2" (267mm)

24" (610mm)

SEE CONTROL
PANEL
DRAWING

ALL DIMENSIONS +/- TOLERANCE OF 1/2"

DESCRIPTION

REVISED HEADERS

DATE

ER
02/16/04

ENG. BY: ACD

12"

DWG
NO.

CHK. BY:

P27-705-4V

6\QFUR)OR

DRAWN BY: ACD

Pump i n g S y s t em S o l u t i o n s
%HVW)ULHQG5RDG1RUFURVV*$  )D[  

DATE: 6/11/2003

DUPLEX HORIZONTAL IRONHEART


STAINLESS STEEL
WITH VFD's & CHECK VALVES

REV.

NORCROSS, GEORGIA
NOT TO BE DUPLICATED WITHOUT
WRITTEN PERMISSION OR USED
IN ANY WAY DETRIMENTAL TO
THE COMPANY.

6\QFUR)OR,QF

THIS CONFIDENTIAL DOCUMENT


IS THE PROPERTY OF

PROPRIETARY DRAWING

(4) 5/8" (16mm) DIA.


BOLT HOLES

Model CC Pumps
Materials of Construction

6700 Best Friend Rd. Norcross, Ga 30071 (770) 447-4443 Fax (770)447-0230
Bulletin: 28-128
7/01/2005

BULLETIN:
EFFECTIVE:
SUPERSEDES:

MECHANICAL
THERMAL
PURGE VALVE

OPERATION
To prevent overheating and pump failure a thermal
relief valve is installed in each pump casing, discharge
head, or discharge piping. The valve will automatically
sense the rise in temperature and discharge some of
the hot fluid allowing cooler fluid to enter the pump
casing. The valve will then close. On factory built
pump systems, the thermal relief valves are piped to a
common discharge tube. After installation, this
discharge tube should be continued to a nearby drain.
The discharge tube should be piped in a manner that
discharge or leaks are visible to maintenance personnel.

SPECIFICATIONS
Pressure Rating:
Temperature Setting:

600 psi
140 F

MATERIALS OF CONSTRUCTION
Body:
Internal Seal:
External Seal:
Spring:
Mounting Connection:
Tubing Connection:

Brass
Viton
Buna
Stainless Steel
3/8 MPT
1/4 FPT

6700 Best Friend Rd. Norcross, GA 30071 (770) 447-4443 Fax (770) 447-0230

28-184
JUNE 26, 2003
DEC. 13, 2000

DOMESTIC
PRESSURE REGULATING & CHECK VALVE ANGLE TYPE

2" & larger


valves are
flanged

PRESSURE REGULATING AND CHECK


VALVE COMPONENT PARTS
ITEM
DESCRIPTION
1
VAVLE BODY
2
SEAT
3
DISC
4
SPACER WASHER
5
DIAPHRAM WASHER
6
STEM LOCK NUT
7
STEM
8
COVER
9
COVER BEARING
10
SPRING
11
COVER PLUG
12
DIAPHRAM
13
COVER BOLT
14
DISC GUIDE
15
DISC RETAINER
16
CHECK VALVE
17
ORIFICE
18
PRESSURE REGULATING PILOT
19
STRAINER
20
NEEDLE VALVE OPTIONAL

6700 Best Friend Rd. Norcross, Ga 30071 (770) 447-4443 Fax (770)447-0230
Bulletin: 27-812.2 10/27/2005

NSF 61 Butterfly Valve


Features:
x
x
x
x
x

Body:
Disc:
Seat:
Stem:

Pressure Rating: Bi-directional or dead end


service, bubble-tight shut off, 250 psig.
Pressure Profile Disc: Assures minimum torque
and longer seat life.
One-Piece Thru Stem: Blow out proof, ensures
dependability and positive disc positioning.
Seat Face: Negates need for flange gaskets.
Valve interior completely isolated from the body.
Supported Stem Seal: Blow out proof with
packing gland to prevent entry of external
substances.

Materials of Construction
Cast Iron
Nylon 11 Coated Ductile Iron
EPDM
416 Stainless Steel

6700 Best Friend Road Norcross, GA 30071 Phone: 770-447-4443 Fax: 770-447-0230 http://www.syncroflo.com
Effective: August 4, 2010

Pressure Switch

STANDARD FEATURES
x
x
x
x
x

Single Switch Output


Tamper-Resistant Set Point Lock
Small Fixed Deadband
UL listed, CSA Certified and
CE Compliance to Low Voltage
and Pressure Equipment Directive
Polished Stainless Steel Sanitary
Connection

SPECIFICATIONS
Wetted Materials:
Operating Temp.:
Set Point:
Proof Pressure:
Enclosure:

Nickel Plated Brass


-40 to 160oF
1% of adjustable range
600psi
NEMA 4X

6700 Best Friend Rd. Norcross, Ga 30071 (770) 447-4443 Fax (770)447-0230
Bulletin: 29-124
6/30/2005

Pressure Transmitter Digital


Overview
The 40-801 is a high quality all stainless steel media
isolated Pressure Sensor intended for use in the
measurement of liquids compatible with stainless steel.
40-801 pressure sensors and transducers have been
designed specifically for applications with demanding
performance requirements.

Features
x High Accuracy
x High Strength Stainless Steel Construction
x No Silicone Oil. No Internal O-rings, no welds
(50 PSI & above)
x Wide operating temperature range
x Fully welded case provides rugged design
x Compatible with wide range of gases and liquids
x Suitable for high shock and vibration applications
x Superior signal clarity compared to analog
transmitters

40-801 sensors and transducers high strength stainless


steel sensing element is machined from a solid piece of
stainless steel, resulting in construction that contains no
silicone oil, no welds and no internal O-rings.
Detailed Specifications
Performance @ 25C (77F)
Environmental Data
Accuracy: <0.25% BFSL
Temperature
Stability: (1 year) 0.25%FS,
Operating: -40 to 85C (-40 to 185F)
Over Range Protection: typ.
Storage: -40 to 125C (-40 to 250F)
Burst Pressure: 2X Rated Pressure
Thermal Limits
Compensated Range: 0 to 55C (30 to 130F)
Pressure Cycles: 5X Rated Pressure
>100 Million
TC Zero: <1.5% of FS
TC Span: <1.5% of FS
Other
Accuracy includes: Non-linearity,
Shock: 100G, 11msec, sine
Hysteresis and Non-repeatability
Vibration: 20G peak, 20 to 2400 Hz.
EMI / RFI Protection: Yes
Rating: IP-66

PHYSICAL DESCRIPTION
Wetted Material: 17-4PH stainless steel NACE compatible
Electrical Cable
Connection: 304 stainless steel
Case (housing):
ELECTRICAL DATA
Excitation: 10-28VDC, Typ.
Output: Digital Pulse
Current Consumption: <15mA
Bandwidth: (-3dB): DC to 250Hz
Zero Offset: <1% of FS
Span Tolerance: <1.5% of FS
Output Noise: <2mV RMS
Reverse Polarity Ye
Protection:

6700 Best Friend Road Norcross, GA 30071 Phone: 770-447-4443 Fax: 770-447-0230 http://www.syncroflo.com
Effective: August 4, 2010

Mitsubishi F-700 VFD


Control Specifications
Control System

High carrier frequency PWM control (V/F control)/optimum excitation


control/simple magnetic flux vector control

Output Frequency Range

0.5 to 400Hz

Frequency Setting Resolution

0.01HZ

Frequency Accuracy
Starting Torque
Acceleration / Deceleration Time Setting
DC Injection Brake
Stall Prevention Operation Level

Within 0.01% of the set output frequency


120% (3Hz) when set to simple magnetic flux vector control and slip
compensation
0 to 3600s (acceleration and deceleration can be set individually), linear or Spattern acceleration/deceleration mode can be selected
Operation Frequency (0 to 120Hz), operation time (0 to 10s), operation voltage
(0 to 30%) variable
Operation current level can be set (0 to 150% adjustable), whether to use the
function or not can be selected

Protective / Warning Function


Overcurrent during acceleration,
overcurrent during constant speed,
overcurrent during deceleration,
overvoltage during acceleration,
overvoltage during constant speed,
overvoltage during deceleration, inverter
protection thermal operation, heatsink
overheat, instantaneous power failure
occurrence, undervoltage, input phase
failure, motor overload, output side earth
(ground) fault overcurrent, output phase
failure, external thermal relay operation,
PTC thermistor operation, option alarm,
parameter error, PU disconnection, retry
count excess, CPU alarm, power supply
short for operation panel, 24VDC power
output short, output current detection
value over, inrush resistance overheat,
communication alarm (inverter), analog
input alarm, internal circuit alarm (15V
power supply), fan fault, overcurrent stall
prevention, overvoltage stall prevention,
electronic thermal prealarm, PU stop,
maintenance timer alarm*1, parameter
write error, copy operation error, operation
panel lock

Operational Environment
Ambient Temperature

-10C to +50C (non-freezing)

Ambient Humidity

90%RH or less (non-condensing)

Storage Temperature

-20C to +65C

Atmosphere
Altitude, Vibration

Indoors (without corrosive gas, flammable gas, oil


mist, dust and dirt, etc.)
Maximum 1000m above sea level, 5.9m/s or less
(conforms to JIS C 0040)

6700 Best Friend Road Norcross, GA 30071 Phone: 770-447-4443 Fax: 770-447-0230 http://www.syncroflo.com
Effective: August 9, 2010

SyncroFlo
P ump i n g S y s t em S o l u t i o n s
6700 Best Friend Road - Norcross, GA 30071
(770) 447-4443 - Fax (770) 447-0230

P ump i n g S y s t em S o l u t i o n s
6700 Best Friend Road - Norcross, GA 30071
(770) 447-4443 - Fax (770) 447-0230

SyncroFlo

SyncroFlo, Inc.

SyncroFlo, Inc.

SyncroFlo
P ump i n g S y s t em S o l u t i o n s
6700 Best Friend Road - Norcross, GA 30071
(770) 447-4443 - Fax (770) 447-0230

Model 132
HYDROCUMULATOR TANK
Features and Benefits
1. The vessel is ASME code
(Section 8. Div. 1, UG 90 C-2) and
NB stamped for 125 PSIG*.
Maximum temperature is 240 F
(consult the factory for higher
temperatures). Nominal volume
is 132 gallons.
2. The tanks shell is made of Steel.
The bladder is FDA approved
Heavy Duty Butyl.
3. The 100% draw down design of
the tank prevents the bladder from
rupturing at any storage volume
or pressure within its ratings. This
provides maximum water storage
at all conditions.
4. The vertical design and bottom
water connection eliminate water
stagnation in the tank, making it
ideal for drinking water use.
5. The specially designed distribution
tube allows the tank to be fully
pre-charged with air at the factory.
6. Water is kept inside the bladder
while air is between the bladder and
the tank shell. This keeps water rust
free and protects the tank from corrosion.
7. Tank dry weight: 330 Lbs.
* Available in higher pressures ( 150, 200, 250 PSIG )
6700 Best Friend Rd. Norcross, Ga 30071 (770) 447-4443 Fax (770)447-0230
Bulletin: 28-153.3 7/20/2007
Supersedes: 10/02/06

WARRANTY
The components of each SyncroFlo water pressure booster system, when purchased as regular
factory selections, are warranted against failure due to defects in design, material, or construction,
from date of factory shipment within the periods and under the conditions noted below:
PUMPS
All SyncroFlo pumping assemblies are warranted against mechanical failure for a period of one
(1) year. If any component of the pumping assembly fails within this period, SyncroFlo, Inc., will,
at its option, repair or replace the pumps assembly on a no charge exchange basis FOB factory,
Atlanta, Georgia.
MOTORS
Motors, when equipped with standard SyncroFlo over-temperature protection systems and
maintained according to factory instructions, are warranted for one (1) year. SyncroFlo, Inc., will
make, at its option, a no charge repair or replacement at the factory or at an authorized motor
service station.
PRESSURE REGULATING VALVES
Pressure regulating valves are warranted for one (1) year. If any mechanical component of the
regulating valve fails within this period, SyncroFlo, Inc., will, at its option, repair or replace
regulating valve component parts on a no charge exchange basis FOB factory.
COMPLETE SYSTEM
The complete SyncroFlo system as a whole, including all accessories and components not
mentioned above, is warranted functionally and mechanically for a period of one (1) year from
date of installation or 18 months from date of shipment (whichever comes first), when
installed, operated, and maintained in accordance with the Companys recommendations.
SyncroFlo, Inc., is responsible only for repairing or replacing its products in accordance with the
terms and conditions set forth above. There are no warranties, either expressed or implied,
extending beyond those stated on the face hereof, and SyncroFlo, Inc., expressly disclaims all
other warranties, including any implied warranties of mechanical ability or fitness for a particular
purpose. SyncroFlo, Inc., also disclaims any liability whatsoever for incidental or consequential
damages, including damages to property, damages for loss of use, loss of time, loss of profits, loss
of income, or any other incidental or consequential damages. SyncroFlo, Inc., neither assumes
nor authorizes any other person to furnish any warranties, or assume for it any liability in
connection with the sale of its products.
This warranty does not include mechanical seals, gauges, transportation, or labor costs for
exchange or installation of repaired or replaced material. Final determination of warranty shall be
made only by the factory upon return and inspection of returned material. No material is to be
returned without a return material authority (RMA) tag which may be obtained by calling or
writing the factory, advising what will be shipped and the reason for the return.

6700 Best Friend Road, Norcross, GA 30071


Phone: (770) 447-4443 Fax: (770) 447-0230
www.syncroflo.com

BETTER CONTROL THROUGH SYSTEMS ENGINEERING

Vous aimerez peut-être aussi