IRDH265-4..
VDE IEC
ISO 9001
Product Description
A1(+)
A2(-)
A-ISOMETER
Serie 260
L1 (L/+) L2 (L/-) L3
1 ALARM
KE M+ M <LT> <PT> B A
TEST
RESET
AK
k
MONITOR
11 12 14 21 22 24
Operational Information
The A-ISOMETER IRDH265 is connected between the
ungrounded system and the equipment grounding conductor.
Via the buttons on the faceplate of the unit, setting of the set-point
values and other parameters can be carried out. The parameters
are displayed on the LCD-display and are stored in a non-volatile
memory (EEPROM) after setting.
74
112,5
105
Mounting
support rails
to screw
For supporting
DINonto
35/15mm
rail.acc.For
DIN EN 50 022
mounting, a mounting plate, #990056 is available.
LCD display
RS485 Interface
Connection monitoring
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll-free: (800) 356-4266 - Fax: (610) 383-7100
Please Note:
AC 630 V
6 kV / 3
continuous
3AC 0...690 V
0...1.15 UN
50...400 Hz
DC 0...500 V
0...1.3 UN
Supply Voltage
Supply voltage US
10 ... 990 k
10 ... 990 k
approx. 25%
approx. 5 sec.
1 ... 10s
0.1 ... 5mA
< 1sec.
max. 500F
27 V
max. 225 A
120k
> 250 k
Outputs
Measuring instrument SKMP
120 k
Current output (max. load)
400 A (12.5 k)
Terminal [AK] for high-voltage coupling device
Yes
Serial Communication Interface
EIA RS485
Contact Configuration
Type
2 voltage-free SPDT contacts
Rated contact voltage
AC 250 V / DC 300 V
Rated current
UC 5 A
Break capacity AC 230 V, p.f. = 0.4
AC 2 A
DC 220 V, L/R = 0.04s
DC 0.2 A
Operating mode
Normally Energized / De-energized
Testing
Dielectric test: Test voltage
3 kV
Impulse voltage test acc. to IEC255-5
class III
Elec. disturbance test acc. to IEC255-5
class III
Elec. fast transient burst acc. to IEC801-4
severity degree 2
Shock resistance acc. to IEC68-2-27
15g / 11sec
Vibration strength acc. to IEC68-2-6 10...15kHz / 0.15mm - 2g
Bumping acc. to IEC 68-2-29
40g / 11msec
Environmental conditions
Operating temperature
Storage temperature
Climatic class acc. to DIN 40040
General Data
Type of connection
screw terminals
Wire size, solid
14 AWG
Wire size, stranded with end sleeve
16 AWG
Mounting
DIN rail or screw (#990 056)
Weight
2 lbs
= 180k / 40k
Operating mode
= Normally De-energized
(MENU: 11-12 14 / 21-22 24)
Time delay
Measuring mode
= AMP
Ordering Guide
Model
Supply Voltage US
Ordering #
AC 230 V
91068001
IRDH265-413
AC 90 ... 132 V
91068004
IRDH265-421
DC 10.5...80 V
91068002
IRDH265-431
AC/DC 93...132 V
91068003
IRDH265-432
AC/DC 187..264 V
91068005
IRDH265-4
Accessories
High-voltage Coupling Devices
Model
System voltage
Ordering #
AGH204S
AC 0...1500V
914013
AGH520S
AC 0...6000V
913033
AGH150W
DC 0 ... 1000V
915576
Dimensions
Ordering #
7204S-1421
72x72mm
986804
9604S-1421
96x96mm
986774
Page 2 of 4
1.5 - 10.2A / Jan 1997
Bender Inc. - 700 Fox Chase - Coatesville, PA 19320 - Toll Free: (800) 356-4266 - Fax: (610)383-7100
IRDH265-4..
Wiring Diagram
UN
11
alarm LED yellow, illuminates
when the insulation level falls
below the preset response value
RALARM1
Supply Voltage
US
(see on
nameplate)
(depends
unit ordered)
12
Fuse 6 A
L1
L2
L3
14
L1
+/
3 AC - System
Alarmrelay
RALARM1
21
L1
L2
L3
N
24
L1
A2(-)
L1 (L/+) L2 (L/-) L3
A-ISOMETER
Serie 260
1 ALARM
TEST
RESET
Combined TEST/RESET-button
short-time pressing (<1s) = Reset
long-time pressing (>2s) = Test
AK
L2
AC - System
L2
k
MONITOR
(L/+)
(L/-)
DC - System
11 12 14 21 22 24
L+
L-
Insula
tion
(L/+)
M+ M-
KE
<LT>
(L/-)
B A
<PT>
RS485
Fuse 6 A
3 AC >690 V /
DC >500 V with
coupling device
external k-measuring
instrument (analog)
PE
10
A1(+)
A2(-)
L1
A-ISOMETER
Serie 260
(L/-)
L3
TEST
1 ALARM
RESET
M+
M-
<LT>
<PT>
B A
12
14
21
22
24
L1 (L/+) L2 (L/-) L3
AK
R=193k
7
KE
Ankopplungsgert
Typ AGH520S
AK
Monitor
AL1=250k
2
Achtung Hochspannung
Danger High Voltage
Serial Interface
(L/+) L2
L3
L1
operator buttons
KE M+ M <LT> <PT> B A
L3
Alarmrelay
RALARM2
22
A1(+)
L2
3N AC - System
After each measurement update the following data block will be sent.
The data transmission is carried out continuously and cannot be
interrupted or influenced in some other way by any other bus member.
fault location
"+"
= insulation fault at L+
"-"
= insulation fault at L"s"
= new measuring value is being calculated
measuring value
6, 7, 8
operator buttons
TEST/RESET-button
10
02H 0H
US
US
30H 30H 30H 31H 32H 38H 0FH 30H 30H 30H 30H 30H 36H 30H 0FH
Ansprechwert
response value
Alarm 1 z.B. 60k
Mewert
measuring value
z.B. 128k
US
US
US
US End
30H 30H 30H 31H 32H 30H 0FH 30H 0FH 30H 0FH 30H 0FH 03H
Ansprechwert
response value
Alarm 2 z.B. 120k
30H = Kein/no
No AlarmAlarm
31H = Alarm 1
32H = Alarm 2
33H = Alarm 1/2
30H = K1 off, K2 off
30H = AC Fault
Fehler/fault
31H = K1 on, K2 off
Fehler/fault
31H = DC- Fault
32H = K1 off, K2 on
32H = DC+
DC+ Fault
Fehler/fault
33H = K1 on, K2 on
Page 3 of 4
1.5 - 10.3A / Jan 1997
Response Time
Setup 1
SETUP1
t (s)
35
PASSWORD: X X
ALARM1=990k
ALARM2=10k
ALARM2=990k
K1: 12 11 - 14
K1: 12 - 11 14
K2: 12 11 - 14
K2: 12 - 11 14
RF = 100k
SETUP2[Y/N]
10
15
ALARM1=10k
20
25
RF = 1M
30
RF = 0...10k
3
10
CE (F)
SETUP2[Y/N]
540
t (s)
480
RF = 1M
420
AL1=180k
R= 150k
SETUP2
360
300
RF = 100k
240
180
Setup 2
RF = 0...10k
60
30
60
90
120
SETUP 2
150
CE (F)
ALARM1: AC OR DC
120
ALARM1: ONLY AC
ALARM1: ONLY DC
ALARM1: ONLY DC+
ALARM1: ONLY DC-
ALARM1: SYST-TEST
ALARM2: ONLY AC
COUPLING TEST : ON
FLASH:
FLASH:
*)
ALARM2: AC OR DC
U (V)
10000
IRDH265+AGH520
OFF
K1
IRDH265+AGH204S
1000
IRDH265
K2
K1/K2
FLASH:
FLASH:
RELAYTEST: OFF
TIME DELAY: ON
TIME: t = 1s
TIME: t = 10s
CE MAX: 150F
CE MAX: 500F
PASSWORD: OFF
PASSWORD: ON
NEW WORD: XX
RESET [Y/N] N
RESET [Y/N] Y
SETUP3[Y/N]
RELAYTEST: ON
100
10
0,2
10
50
100
f (Hz)
0,1
R= 150k
AL2=040k
R= 150k
AL1=180k
SOFTWARE V XXXX
SETUP3[Y/N]
SETUP1[Y/N]
SETUP1[Y/N]
AL1=180k
R= 150k
SETUP3
SETUP1
Page 4 of 4
1.5 - 10.4A / Jan 1997