Government of India

Central Electricity Authority


Hydro Engg. & Technology Development Division
7th Floor, Sewa Bhawan
R.K Puram, New Delhi
ISO: 9001-2008
Dated: 23rd April, 2015

No.62 /24 /HE&TD-2015/


Shri O.P. Chibber
General Manager (E&M)
WAPCOS Ltd.,
Plot No. 76 C, Sector-18,
Gurgaon 122015(Haryana).
Sub:

Punatsangchhu-I HE Project (6X200MW), Bhutan Examination of Auto Transformer


Drawings regarding.

Sir,
Please refer your letter no. WAP/E&M/P-1/MEM-2/2015/369 dated 19.02.2015
enclosing therewith following drawing for Auto Transformer of our examination:
Sl.
no.
1.
2.
3.

Drawing/ Document
no.
3-459-62-00166
3-459-62-00168
3-459-62-00167

4.

3-459-64-00024

Title

Rev.

Diagram of Cooler Control Gear


Diagram of Common Kiosk
General Arrangement of Cooler Control
Cabinet
Schematic Diagram of non-Automatic Tap
Changer Control Equipment Simultaneous
Parallel

02
02
02
02

The above drawings have been examined and our comments/ observations on the
same are enclosed in Annexure-I.
Encl: As above

Yours faithfully

(Sanjay Srivastava)
Director-HE&TD
Annexure-I

A. Diagram of Cooler Control Gear, Drwg. no. 3-459-62-00166 (Rev.02)


General
1.

It is observed that the provision of 2 nos. running & 1no. standby fan motor and 1
no. running and 1 no. standby pump motor has been made. However, automatic
changeover from running to standby motor and vice versa is not clear from the
furnished drawing. This needs to be clarified/ explained.

2.

The proper identification of main & standby fan motor and pump motor has not
been provided. The same needs to be done & incorporated suitably in the control
circuitry.

3.

It may be confirmed that the fan motor & pump motor shall be capable to operate
for 10 min. at 75% of rated voltage (415V) and normal operation at 85%. Further,
the motor rating in the part list may also be modified accordingly.

4.

It may be confirmed that only two (2) fans and one pump will operate in auto mode
since it appears in the schematic /logic diagram that all the three fans will operate
simultaneously.

5.

The basis of considering the various temperature limits for very high tripping,
alarms, start & closing of cooling system may be explained.

Sheet 02 of 17
1.

The phase reference indicated for terminal F41-1 may be corrected as B instead
of Y.

2.

For input terminals to heater circuit i.e. terminal X1- 8&9 , the zone reference may
be corrected as 202 instead of 203.

Sheet 05 & 06 of 17
1.

It is observed that the logic condition to actuate time delay relay K53X & K54X
have not been indicated in the drawing. The same may be indicated.

Sheet 07 of 17
1.

It is understood that whenever any thermal/ overload relay (KM1 to KM6 or KM21
to KM24) is operating both the auxiliary contactors K49 & K50 picked up which in
turn close the contacts K49 & K50 indicated in zone A-705 and thus fan motor &
pump motor thermal/ overload trip indication & alarm will be initiated. As the same
is not desirable and therefore needs to be reviewed.

2.

The terminal no. of terminal board TB-X88 connecting with terminals of TB X2


may be indicated.

3.

The redundancy for 220 V DC supply has not been provided. The provision of same
may also be considered.
The terminals 1 to 6 of TB-X88(RTCC panel) have been used for Fan ON
indication as well as for selector switch S42 on sheet 05 & 06 of 17. This may be

4.

reviewed/ reconciled. Further, the terminal nos. TB X88-29 & 30 have been used for
supply system for RTCC under zone A-1101. This may also be corrected.
5.

The terminals for 220 V DC supply have been indicated as X81-5 & 7. However,
under reference zone 1101, the same have been indicated as X81-6 &8. This may be
reconciled/ corrected.

6.

The name & location of TB-X81 may be indicated on the relevant sheets.

Sheet 08 of 17
1.

The alarm signal to RTCC panel for Cooler Power Supply Fail and No flow or
reverse flow of oil in oil pump may also be included in the Alarms list.

Sheet 09 of 17
1.

The provision for Power Failure Alarm System may also be considered for DGA
system (F60).

2.

The temperature limit for Winding Temperature Indicator (WTI-IV High Alarm)
indicated has been indicated as 900 0C. The same may be reconciled/ corrected.

Sheet 10,11 of 17
1.

CT parameters like protection class, Burden, knee point voltages etc. may be
indicated in this drawing.

2.

The equipment represented by symbol in PT sensor unit R1, R2 & R3 may be


identified & may be included in legends/ graphics symbols table.

3.

The CT nomenclature indicated in various sheets and part list needs to be reconciled
and corrected.

Sheet 13 of 17
1.

The destination of signals from terminals 37 to 48 of TB- X2 has been shown as To


RTCC Panel. The same may be corrected as To SCADA.

2.

The sheet grid reference for wires terminated at various terminal block may be
indicated as agreed.

3.

The destination of signals from terminals 51 to 60 of TB-X2 has been shown as To


SCADA. The same may be corrected as To RTCC Panel.

4.

The terminal block TB XE (1-6) & phase bar TB X6 has not been indicated. The
same may be suitably shown in the drawing.

5.

Under zone C-1207, the source of DC power supply indicated as from P91 may be
corrected as from P90.

Sheet 15,16 &17 of 17


1.

Against item no. 14, the Cooler Control Switch (S41) has been indicated as 3
WAY. However, the same has been indicated as 4 WAY in sheet 05 & 06 of 17.
This needs to be reconciled.

2.

The symbol for space heater indicated in the graphic symbol table is not matching
with that shown in the drawing. The same may be corrected.

3.

Against item no. 15, the rating of Rotary Switch (S1 to S6 & S21 to S24) indicated
as 440 V may be reviewed/ corrected. Further, the indication 3 WAY may also be
reconciled.

4.

The quantities of item no. 59 & 60 indicated as 14 nos. may be reconciled with
drawing & corrected accordingly. Further, the signal lamp H1 to H15 may be
indicated separately for fan, motor & other indication.

5.

The item X7 indicated at sl. no. 28 has not been shown in the drawing. The same
may be reviewed/ reconciled.

6.

Against item no. 62, the rating of Pump Selector Switch (S42) indicated as
2WAY. However, the same has been indicated as 4 WAY in sheet 05 & 06 of 17.
This needs to be reconciled.

B. General Arrangement of Cooler Control Cabinet (Drawing no. 34596200167)(Rev02)


The comments have already been furnished vide our letter dated 27.03.2015. However, in
continuation to that we have following additional comments.
1.

The temperature indicators have been installed at height of 1415 mm. However, as
per the requirement of cl. 4.16.2 (iii), the same should not be more than 1200 mm.
This needs to be reviewed.

2.

As per the clause 4.16.2 (ii), the cooler control cabinet shall have two (2) sections.
One section for control equipment exclusively meant for cooler control and other
shall house temp. indicators, aux. CTs & TBs etc. However, as per OGA drawing all
the components is housed in single section. This may be reviewed.

C. Diagram of Common Kiosk , Drawing no. 34596200168 (Rev. 02)


General
The two incoming AC supply needs to be designated as Normal Source and
Standby Source. The normal operation shall be from Normal Source and if it fails
then automatic changeover to Standby Source shall take place. Further, indication
for failure to transfer needs to be provided. Also, automatic re-transfer to normal
source without any intentional time delay following re-energisation of the normal
source shall also be provided.
Sheet 02 of 06
1.

The provision of 220 V DC Supply System (as per the requirement of cl. 4.17.5 (a))
along with 415 V AC supply has not been considered. The same needs to be

reviewed.
Sheet 03 of 06
1.

The terminal no. TB-X10-40, 41,42 & 43 has been shown connected to terminal of
TB-X82-52, 53, 54 & 55. However, the same is not indicated on sheet 11 of 12 of
drawing for Schematic Diagram of Non Automatic Tap Changer Control. This may
be indicated.

Sheet 06 of 06
1.

The terminals for air break contactor K31 for zone A/203 indicated as A1 & A2
may be corrected as a & b respectively. Similarly contactor K32 may also be
corrected.

D. Schematic Diagram of non-Automatic Tap Changer Control Equipment


Simultaneous Parallel( Drawing no. 34596400024)(Rev-02)
General
1.

The drawing regarding general arrangement of RTCC panel & OLTC has not been
furnished. The same may be furnished for our examination.

2.

M/s BHEL may be asked to confirm that alarm for INCOMPLETE STEP shall not
operate during momentary loss of auxiliary power as per cl. 4.14.2.1 (j) of contract
document.

3.

It may be confirmed that the limit switches shall be provided to prevent overrunning
of the mechanism and shall be directly connected in the circuit of running motor.

Sheet 03 of 12
1.

In fuse table, the quantity of fuse F61 & F62 have been indicated as 2 nos. The same
may be corrected as 6 nos..

2.

The description under column Device No. indicated as F91 & F96 may be
corrected as F91 to F96.

Sheet 04 of 12
1.
2.
3.
4.
5.

The description, make & type and quantities of contactor K88 & Q31 has not been
included in the list of material. The same may be included suitably.
The calculation in support of selection of tap changer driving motor capacity as 1.1
kW may be furnished. Further, the duty class of motor may also be indicated.
The ampere rating of item F61 & F62 indicated as 4A may be corrected as 6A as
indicated in fuse table.
The voltage rating of voltmeter P181 & P182 has been indicated as 0-500V &
0-300V respectively. The same may be corrected s 0-500kV & 0-300kV.
The ampere rating of Q61 i.e. motor protective switch may be indicated.

Sheet 06 to 10 of 12

1.

The zone reference indicated for X85-17 & 18 under zone 801 may be corrected as
604 instead of 504. Further, zone reference for X86-17 & X86-18 may also be
indicated.

2.

Under zone 806-A, the zone reference for X86-17 & 18 has not been indicated. The
same may be indicated.

3.

The destination of signal X86-17& 18 under zone 904-D of sheet 09 of 11 indicated


as To K80 & K81 may be corrected as To K81 & K82 as agreed.

4.

Under zone 1002-A of sheet 10 of 11, the destination of signal from X81-42
indicated as To K84-34 may be corrected as K84-54.

5.

The source of 240 V, 50 Hz AC supply indicated under zone 1006-D on sheet 10 of


11 may be indicated.

6.

On sheet 08 of 12, the terminal X82-29 & X82-19 shown connected for Bank-1 &
Bank-2 respectively may be corrected.