For the network shown in figure 1, find the subtransient current in per unit from
generator 1 and in line and the voltages at buses and for a three phase
fault on bus . Assume that no current is flowing prior to the fault and that the prefault
voltage at bus is 1.00 per unit.
(2)
(0)
Equipment
Machines M1 & M2
Transformer T1 & T2
Line
MVA
rating
100
100
100
Voltage
rating
11 KV
11 / 230 KV
220 KV
X1 (p.u)
X2 (p.u)
X0 (p.u)
0.25
0.25
0.05
0.06
0.06
0.06
0.1
0.1
0.3
8. Two synchronous machines are connected through three phase transformers to the
transmission line as shown in figure 5. The ratings and reactances of the machines and
transformers are
Machines 1 and 2: 100MVA, 20 kV;
Xd = X1= X2 = 20%, X0 = 4%, Xn = 5%
Transformers T1 and T2: 100MVA, 20Y/345Y kV;
X = 8%
On a chosen base of 100 MVA, 345 kV in the transmission-line circuit the line
reactances are X1= X2 = 15% and X0 = 50%. The system is operating at nominal voltage
without prefault currents when a bolted (Zf = 0) double line-to-ground fault occurs
between phases BC and ground at bus . Using the three sequence networks,
determine the subtransient fault current.