GTP of 245 kV Circuit Breakers

Sr. No.

Particulars

Guaranteed Values
245kV,50kA(3s),3150A
Siemens Ltd
SF6 Gas, outdoor type
3AP1FI
IEC 62271-100, IS 13118 (1991)
245 kV
50 Hz

a
b

Name of manufacturer
Type of Circuit Breaker
Manufacturer's type and designation
Standard applicable
Rated voltage
Rated frequency
Normal current rating under site conditions of 50 deg. C ambient
air temperature
Under standard conditions
Under site conditions.
Derating factor, if any, for site conditions
Altitude of installation above sea level
Seismic withstand
No. of poles of circuit breaker
Temperature rise in current carrying parts at rated current and the
maximum temperature attained by any part over an ambient of 40
deg. C
Breaking capacity
Symmetrical
Asymmetrical
Percentage D.C. component
Rated short-circuit making current
Rated small inductive breaking current
Rated transient recovery voltage for short line faults kVp
Rate of rise of recovery voltage for short line faults (kV/microsec)

a
b

Rated transient recovery voltage for terminal faults kVp


Rate of rise of recovery voltage for terminal faults (kV/microsec)

c
a
b

First pole to clear factor


1.3
Rated out of phase (asynchronus) breaking current
12.5 kA
Rated transient recovery voltage for out of phase kVp
500 kVp
Type of devices, if any, used to limit the RRRV
Not required
Maximum over voltage on switching transformer on no load and Test not specified as per IEC 61233 clause 2.2, However, breaker
corresponding charging current.
is suitable for this application (value 0-25 A, 2.5 pu)

1
2
3
4
5
6
7
a
b
c
8
9
10
11

12
a
b
13
14
15
16

17

18
19
20

21
22
23
24

25

26

a
b
a
b
c
a
b
c

27
28
29
30
31
32
a
b
c
d
33
a
b
c
34

3150 A
3150 A
No
Max 1000 m
As per IEC 62271-100
Three
Within limits specified by IEC 62271-100

50 kA
Not specified in IEC-62271-100
As per IEC 62271-100
125 kAp
Not specified in IEC-62271-100
280 kVp
2.00
364 kVp
2.00

Reactor
loaded
transformer
interrupting
capacity
and
>=30 A/<=2.0 p.u. ; >=100 A/<=1.5 p.u.
corresponding surge OV
Number of breaks in series per pole.
One
Rated operating sequence
O-0.3 sec-CO-3 min-CO
Short time current rating for following duration :
For one sec.
50 kA
For three sec.
50 kA
Opening time
37+/-4 ms
Normal voltage of opening
110 or 220V DC
Voltage range (%)
70 - 110%
Closing or make time
62 +/- 6 m sec
Normal voltage of closing
110 or 220V DC
Voltage range (%)
85 - 110%
Difference in the instant of closing of contacts between poles
<=3 ms
Difference in the instant of opening of contacts between poles
<=2 ms
Total break time in milli second :
Max. 60 msec
Maximum arcing time in any test duties
25 m sec
Is the breaker suitable for single phase / 3 phase reclosing
1 Phase and 3 Phase auto reclosing, Electrically Gang operated
Minimum dead time for :
3 phase reclosing
Single phase reclosing
Limits of adjustment of dead time for 3 phase closing
Limits of adjustment of dead time for 1 phase closing
CAPACITY
Data on transient recovery voltage :
Amplitude factor
First pole to clear factor
Rate of rise of recovery voltage kV/micro sec.
Maximum line charging breaking current

100%
1.4
1.3
2.0

300 m sec
300 m sec
Not applicable
Not applicable
CAPACITY
60%
30%
1.5
1.5

10%
1.53

1.3
3.0

1.5
7.0

1.5
5.0
125A

1/4

GTP of 245 kV Circuit Breakers


Sr. No.
35
36
37

a
b

38
39
a
b
40
a
b
41
a
b
c
42
43

a
b

44
45

a
b

46
47

48
49
50
51

Guaranteed Values
245kV,50kA(3s),3150A

Maximum Cable charging breaking current


Maximum single Capacitor bank charging breaking current
Rated back to back capacitor bank breaking current
Rated capacitor bank inrush making current
Maximum breaking capacity under Kilometric faults & rated TRV
Characteristic
Dry one minute power frequency withstand test voltage for
complete circuit breaker :
Between terminals with circuit breaker contacts open (kVrms)
Phase to earth & between phases (kVrms)
1.2/50 full wave impulse withstand voltage for complete circuit
breaker
Between terminals with circuit breaker contacts open.(kVp)
Phase to earth & between phases (kVp)
250/2500 micro second switching surge withstand test voltage
Between phase to earth (KVp)
Between phases (KVp)
Across isolating distance (kVp)
Radio Interference Voltage (Micro-Volts)
Total length of break per phase / arc length (Distance between pin
and tube contact)
Total length of contact travel

250A
400A
Not applicable
Not applicable
As per IEC 62271-100

53
a
b
c

a
b

57
a
b
c
58
59

General
Minimum clearances in air
Between phases
Live part and earth
Lowest line terminal to ground
Normal pressure of SF6 gas inside circuit breaker
Minimum operating pressure of SF6 gas
Density monitor Settings (Adjustable / Non adjustable)
Voltage and power supply system for which the temp.
compensating gas pressure switch (density monitor) and other
pressure switches are suitable
Pressure at which gas pressure will give :
Alarm
Tripping impulse
Lockout
Minimum time interval between each make/break operation (ms)

66
67

Maximum pressure of SF6 gas developed in the arcing chamber at


rated breaking capacity (kg/sq.cm)
Chemical composition of the absorbent
Recommended interval for renewal of absorbent for circuit
breakers operating in tropical condition.
No. of operations breaker is capable of performing without
inspection, replacement of contacts and other main parts with
normal current breaking
No. of operations breaker is capable of performing without
inspection, replacement of fault current breaking capacity
No. of operation at rated current after which routine inspection of
breaker is necessary contacts and other main parts at 100% rated
Guaranteed no. of opening operation,the Breaker is capable of
performing
At full rupturing capacity
At 50% rated rupturing capacity
At 100% rated current
At 50% rated current
Weight of complete breakers
Weight of heaviest part of breaker (kg)
Static loading of the circuit breaker
Shipping dimension of the largest package in mm

68
69
70
71

Breaker Contacts :
Type of main contacts
Type of arcing contacts
Whether main contacts silver plated
Thickness of silver plating

60
61
62

63
64

65

a
b
c
d
a
b

460 kV
460 kV

+/- 1050kVp
+/- 1050kVp
Not applicable
Not applicable
Not applicable
<= 2500
140.5 mm
150 mm

SF6 gas and related devices details :


Standard to which SF6 gas complies.
IEC 60376
Quantity of SF6 gas per breaker
18 kg
Quantity of SF6 gas per cylinder (Kg.)
20 kg
Quantity of SF6 per pole (m3) at rated pressure.
6.0 kg
Whether breakers are dispatched filled with SF6 or required to be CB Poles pre filled with 0.5 Bar pressure at 20 Deg C , topping up
filled at site.
to required pressure at site
Guaranteed maximum leakage rate per year.
Rated pressure of SF6 in operating chamber
Rated alarm pressure of SF6
Limits of pressure at which breaker operate correctly or Lockout
pressure
Whether 20% spare SF6 gas. Stored in unused gas cylinders,
included in proposal.

52

54
55
56

Particulars

< 1% pa
6.0 Bar @ 20 Deg C
5.2 Bar @ 20 Deg C
5.0 Bar @ 20 Deg C
Yes

min 2800 mm (ph-ph)


1900 mm
As per customer requirement
6.0 bar at 20 deg c
above 5.0 bar at 20 degc
Non adjustable
As per control supply voltage

5.2 bar at 20 deg C


At 5.0 bar at 20 degC if specified by the client
5.0 bar at 20 deg C
As per operating sequence O-0.3 Sec.-CO-3 min.-CO
Within safe limits
MOS 13X
upto 6000
upto 6000

18 operations
50 kA

18
90
6000
6000
3500 kg approx, Without support structure
1000 Kg approx
As per IEC 62271-100, table-14
H - 2000, W - 1550, L - 5550

Contact fingers, Multilam, Heat Cylinder


Pin, Finger contact
Yes
Adequate

2/4

GTP of 245 kV Circuit Breakers


Sr. No.

Particulars

72

Material of contact

73
74

Contact pressure
Auxiliary contact :
Type of auxiliary contact
Material of auxiliary contact
Contact silver plated or not
Thickness of silver plating
No. of auxiliary switch / multiplied contacts, operating with all
individual poles of a breaker

a
b
c
d
75
a
b
a
b
c

which are closed when breaker is closed


which are open when breaker is closed
No. of spare auxiliary contacts wired up to the terminals
Opening
Closing
Those adjustable with respect to position of main contact

d
e

Continuous rating of contacts


Breaking capacity of contacts

76

77

Type of operating mechanism


Opening
Closing
Numbers of drive mechanisms
Whether the circuit breaker is trip free of fixed trip and whether it is
with lockout preventing closing
e Tripping and closing control circuit voltage
f No. of trip coils
g No. of close coils
h Power required for trip coil at 110/220V DC
i Power required for closing coil at 110/220V DC
For stored energy mechanism
Spring charging motor:
a Manufacturer's name & address
b Equipment driven by the motor
c Motor type
d Type of duty
e Applicable standard
f Power required for motor
g Rated voltage
h Motor current
i) Starting current
ii) Continuous current
i Time required for the motor to charge the spring fully (sec.)
a
b
c
d

78

Guaranteed Values
245kV,50kA(3s),3150A
Main contact Multilam- St. strip with Cu louvers, Heat cylinder
Al silver plated, Contact fingers Cu Cr Zr silver plated
Arcing contact - Pin Copper with Cu Tungsten, Finger contact
Cu Cr Zr plated

As per Design requirement


Rotary
Silver Plated Brass
Yes
Sufficient

20
19
6
6
Auxiliary switch is rotary type and all above contacts are preadjusted in the factory.
10A
220V DC -2.0 A (Resistive-Inductive load); 110V DC - 4.0A
(Resistive-Inductive load)

Spring
Spring
Three
Trip free
110V DC or 220V DC
Two nos. per pole
One no. per pole
300 W
300 W

KPT / FAL / Equivalent


Closing spring
Universal
Short time duty
IS 996
550 Watts
220V DC / 240V AC
220V DC
110V DC
9+/-1.5
16+/-3
2.5+/-1
4+/-1
15 sec. Max

3/4

GTP of 245 kV Circuit Breakers


Sr. No.

79
a
b
c
d
e
80

Particulars

Circuit Breaker - Control cabinate


Manufacturer's Name
Indoor/Outdoor application
Ambient air temperature (oC)
Thickness of sheet steel (mm)
Degree of protection provided

Bushing or insulator :
Make of insulator
Type
Applicable standards
Dimension
Numbers of support insulators
Creepage distance
-Interrupter Chamber
-Support Insulator
g Rated voltage (kV)
h Power frequency withstand voltage for 1 minute (kVrms) dry and
wet
i 1.2/50 micro sec. impulse withstand voltage (kVp)
j 250/2500 micro sec. switching impulse withstand voltage (kV p)
dry and wet
k Corona Extinction voltage (kV)
m OGA drawing enclosed.
n Insulation class
a
b
c
d
e
f

Guaranteed Values
245kV,50kA(3s),3150A
Siemens Ltd
Outdoor
As per IEC 62271-100
CR 2.0
IP 55

Aditya Birla / Modern / IEC / Equivalent


Hollow porcelain
IEC 60233
Chamber - 2122mm; Support - 2120mm
One
6125 mm
6125 mm
245 kV
In line with breaker value
In line with breaker value
Not applicable
Not specified in IEC 62271-100
GA enclosed
C - 120

4/4