Standard Features
Heavy Duty Engine Cooling System
Heavy duty, 4-cycle, diesel engine; naturally aspirated, overhead Closed circuit, pressurized system with ambient temperature rating
valves, indirect injection, water cooled. of 40°C (104°F).
Manual speed control governor. Generator Control Panel
Meets EPA Tier 2 emissions standards. MEC 20TM microprocessor-based, digital control panel; vibration
Alternator isolated and NFPA 110 compliant.
Brushless, 4-pole, synchronous, 12 lead design. Liquid crystal display screen with alphanumeric readout for display
Class H insulation system conforms to NEMA MG1-22, BS5000, and programming.
CSA-C22-2, IEC-34-1 standards for temperature rise. Self-diagnostic feature continuously verifies processing, memory
Sustained short-circuit capability allowing downstream coordination circuits and input/output.
breakers to trip without collapsing the generator field. Skid and Housing
Drip-proof, self-venting, amortisseur windings. Generator available as skid-mount or sub-base tank mount design.
Epoxy impregnated windings with tropical insulation for increased Integral vibration isolators.
environmental protection and long life. Outdoor weather-protective or sound-attenuated housings.
Exceptional waveshape and voltage balance; 2/3 pitch winding to Steel battery rack and battery cables.
minimize harmonic distortion. Warranty
Electronic Voltage Regulator
Engine-generator sets are covered by an express written 2-year/
2000 hour (whichever occurs first) limited warranty.
■ Encapsulated electronic voltage regulator precisely regulates the Optional extended warranties available.
current into the exciter field.
Voltage regulation of 1% no load to full load. Agency Approval
UL 2200 certification.
Full Load Acceptance
CSA standard C22.2 No. 100-04
Accepts 100% of standby nameplate rating in one step, in compliance
with NFPA, para 5-13.2.6.
MQP20IZ Rev 1
20kW Diesel On-Site
Power Industrial Generator
Lubrication System
Type Gear Driven
System Capacity - Less Filter 1.5 gallons (5.6 liters)
System Capacity - With Filter 2.1 gallons (8.1 liters)
Oil Filter Full flow disposable spin-on
Oil Pressure at Rated Speed 35 psi (241.3 kPa)
Maximum Oil Temperature 230oF (110oC)
GENERATOR CONTROLLER
MEC 20TM microprocessor-based digital generator controller.
Cooling System 12 or 24 Volt DC compatible.
Exhaust Manifold Type Dry Meets all NFPA 110 requirements for emergency power systems
Radiator Design Horizontal Discharge Level I installations.
Ambient Temperature Rating 104oF (40oC) Backlit LCD display screen with alphanumeric readout.
Coolant Capacity - Engine Only 0.7 gal (2.8 L) Front panel keypad provides password protected programming.
Water Pump Design/Type Belt driven, Centrifugal Self diagnostic features continuously verify processing, input/output and
memory circuits.
Coolant Flow 54 gal/min (205L/min)
Metering accurate to +1% within temperature range of 0oC to +50oC.
Radiator Cooling Air 3810 cfm (108m3/min)
EMI/RFI noise immunity and surge performance per IEEE C62.41.
Heat Rejection From Engine 222.0 Btu/min (3.9 kW)
Certified to UL508 and CSA 22.2 #14 Industrial Control Equipment
Heat Rejection To Coolant 1309.2 Btu/min (23 kW) Standards.
Fan Diameter 15.0 in. (380 mm)
Standard Controller Features
Fan Horsepower 0.8 hp (0.6 kW)
High Water Temperature Indication 221.0oF (105oC) AC Metering Display: Switches And Operating Controls:
Voltage/Amperage/ Frequency Run / Off / Auto / Load Test Buttons
Pressure Cap Setting 14 psi (97 kPa) Generator Phase Voltage / Current Decrement / Increment / Previous
Generator Frequency (Exit) /Next (Enter) Program Buttons
Engine Information Display: Emergency Stop Button
Engine Temperature / Audible Alarm Horn – 80 dB(A) at 2 ft.
Oil Pressure (psi) Alarm Horn Silence Button
Battery Voltage (DC) / Tachometer Lamp Test Button
Hourmeter Fault Reset Function
Engine Electrical System Minor Fault Warning Display: RJ45 Remote Communications,
Battery Charging Alternator - Make Kokusan Denki Switch Not In Auto External Expansion Module Ports
Low Fuel Level Timer Countdown Display:
Ground Type Negative
Low Oil Pressure Alarm Engine Start Delay
Volts (DC) 12VDC Low Engine Temperature Oil Bypass
Ampere Rating 20A High Engine Temperature Alarm Overcrank
Low Battery Voltage Cycle Crank
Starter Motor Make/Model Denso
High Battery Voltage Starter Re-engage Delay
Starter Motor Rated Voltage 12VDC Weak Battery Condition Bypass Delay
Starter Motor Battery Capacity 580 Ah Battery Charger Input Fail Control LED Indicators:
Undervoltage Switch Position (Run,Off,Auto,Test)
Over / Underfrequency Common Alarm (Minor Fault)
Overcurrent Common Shutdown (Major Fault)
Major Fault Shutdown Display: Generator Ready (When in Auto)
Overvoltage Speed Signal
Emergency Stop Emergency Stop
Ambient Loss Of Speed Diagnostic LED Indicators:
Derating Factors Altitude
Temperature Overcrank Run Output Energized
Overspeed Crank Output Energized
The engine may be operated up to 500 ft.
and up to 25°C without derating. For Low Oil Pressure Remote Start Signal Initiated
operation at higher altitudes and ambient 3% / 1000 ft. 0.4% / °C High Engine Temperature Common Fail Output Energized
temperatures, the power should be derated Low Coolant Level Watchdog - CPU Running
according to the following factors: Spare Programmable Digital Faults Programmable Output Contacts
MQP20IZ Rev 1
20kW Diesel On-Site
Power Industrial Generator
Generator Set Options
Alternator Open Unit Automatic Transfer Switch
❑ Full output 1 Phase Alternator ❑ Critical Exhaust Silencer ❑ Amperage ______________________
❑ Generator Strip Heater ❑ Exhaust Mounting Package ❑ No. Poles _______________________
❑ Permanent Magnet Generator (PMG) Electrical System ❑ Type Enclosure __________________
Control Panel ❑ Battery ❑ Options
❑ Remote Monitoring and Generator ❑ Environmental Plastic Battery Box with Lid Miscellaneous
Network Communications Link ®
❑ Battery Tender Charger, Float Type, ❑ Main Line Circuit Breaker
❑ Voltage Adjusting Rheostat 5 Amperes @ 12VDC / (2.5A@24 VAC) ❑ 120/208 Volt, 3 Phase, 3 Pole
❑ Frequency Adjusting Potentiometer ❑ Battery Charger, Equalize/Float Type ❑ 120/240 Volt, 3 Phase, Delta, 3 Pole
(Requires Electronic Governor Option) 3.5 Amperes / 20 VAC ❑ 139/240 Volt, 3 Phase, 3 Pole
Engine ❑ Battery Charger w/Alarms, Equalize/Float ❑ 277/480 Volt, 3 Phase, 3 Pole
❑ Electronic Governor Type, 10 Amperes / 20 VAC ❑ 120/240 Volt, 1 Phase, 2 Pole
❑ Engine Crankcase Ventilation Filter Fuel System ❑ Main Line Circuit Breaker Options
❑ Engine Block Heater ❑ Sub-base Fuel Tank (12-hr / 50 gal), ❑ Auxiliary Contacts
Enclosed Unit Double Wall, UL142 ❑ DC Shunt Trip
❑ Outdoor Weather-protective Housing ❑ Sub-base Fuel Tank (24-hr / 100 gal), ❑ Remote Annunciator Panel
❑ Outdoor Sound-Attenuated Housing Double Wall, UL142 ❑ Remote Emergency Stop Kit
❑ Critical Grade Exhaust Silencer Cooling System ❑ Vibration Isolators, Spring Type
❑ Exhaust Mounting Package ❑ Coolant Heater
❑ Rain Cap ❑ Low Coolant Shutdown Safety
❑ Radiator Duct Flange