Vous êtes sur la page 1sur 1

Number

SafetySystem.1
SafetySystem.2
SafetySystem.3
SafetySystem.4
SafetySystem.5
SafetySystem.6
SafetySystem.7

ControlSystem.1

Requirements

Properties

Requested Value

N/A

Compliance

R,I

min 12 Inputs, min 12 Outputs

Compliance

R,I

N/A
N/A
N/A
N/A

Compliance
Compliance
Compliance
Compliance

R,T
R
R,T
R,I

N/A

Compliance

R,I

TANGO Control system,


Windows 7 based,
My SQL database,
C++ language

Compliance

R, I

N/A

Compliance

R, T

N/A
minimum 3 modes of operation,
e.g. Alignment, Maintenance, Running mode
N/A
remote control in experimental areas,
remote control in the control room of the HPLS

Compliance

R, T

Compliance

R, T

Compliance

R, T

Compliance

R, T

position feedback for translation stage, rotation stages and tip/tilt

Compliance

R,T

N/A

Compliance

R,T

N/A

Compliance

R,T

N/A

Compliance

R,T

Gate valve protection, mirrors motion protection, vacuum protection

Compliance

R, T

Compliance

R,T

Compliance

R, T

Able to record 100k HPLS shots

Compliance

R,T

NTP server with GPS unit

Compliance

R,T

TANGO interface

Compliance

R,T

N/A

Compliance

R,T

N/A

Compliance

R, T

Communication technologies shall be a widely used standard


Hardware signals shall follow applicable standards
In situ operation maintenance and service access space secured for all the HW
Alignment and motion related HMI clients shall be able to be accessed from portable
devices, in the experimental areas

e.g. Modbus, RS232, RS485, GigE, Ethernet, USB


N/A
N/A

Compliance
Compliance
Compliance

R,I
R,I
R,I

N/A

Compliance

R,T

The supplier shall provide a certificate of conformance for the safety system
The supplier shall provide operation manuals and mainteinance manuals with detailed
description of the devices used in the system
All drivers, programming applications and souce codes shall be made available to the
Purchaser.
The supplier shall provide detailed documentation for all software programs.

N/A

Compliance

R,I

N/A

Compliance

R,I

N/A

Compliance

R,I

N/A

Compliance

R,I

The Safety system shall be designed in acordance with the EU Safety regulations and
shall use hardware compliant with the EU Safety regulations
The Safety system shall have I/O hardware digital signals to interlock the operation of
the LBTS with external signals from other systems like HPLS, ELI General Safety system,
etc.
The Safety system shall have password access to the Safety system application
The LBTS Safety system shall protect the LBTS from accidental reconfiguration.
The LBTS Safety system shall output the status of the system
The LBTS Safety system shall be interfaced with the LBTS Control System
The LBTS Safety system shall use redundant safety limit switches placed on the mirror
motion stages.

The Control System application shall be build using open source software

ControlSystem.3

The computer system that stores the database shall have redundant hardware so that
a particular computer failure does not affect the LBTS operation.
The Control System database shall be redundant.

ControlSystem.4

The Control System application shall have multiple modes of operation.

ControlSystem.5

The Control System of the LBTS shall have multiple level access.

ControlSystem.6

The Control System of the LBTS shall have remote control of the parameters.

ControlSystem.2

The LBTS Control System shall provide independent monitoring and control of the
position of each mirror in the system.
The LBTS Control System shall provide automatic routing of the mirrors in the 7
ControlSystem.8
predefined configurations correlated with the gate valves position in any of the 7
predefined output configurations (according to Annex E - Mirrors position matrix).
The control System of LBTS shall control and monitor the vacuum level and gate valves
ControlSystem.9
status and positions.
The Control System of LBTS shall monitor and control the alignment of the entire beam
ControlSystem.10
transport
ControlSystem.7

ControlSystem.11

The Control System of LBTS shall provide machine protection features for the LBTS

ControlSystem.12

The LBTS Control System shall have a Supervision application

ControlSystem.13

The LBTS control system shall provide visual feedback through triggered cameras
facing the mirrors reflective surface

ControlSystem.14
ControlSystem.15
ControlSystem.16
ControlSystem.17
ControlSystem.18

Additional.1
Additional.2
Additional.3
Additional.4

Commisioning.1
Commisioning.2
Commisioning.3
Commisioning.4

Verification method
R= Revision ,
I= Inspection,
T= Test

The Control System shall provide alarms, logging and history of the configurations,
cameras image storage, functioning time of the system/pumps/etc for a predefined
period
The entire Control System and Safety System of LBTS shall be syncronized with a
dedicated NTP server with GPS unit to provide a unitary time of the system
The vacuum control system shall be developed using dedicated hardware and
interfaced with the Control System software application
The vacuum control system shall provide automatic venting procedures for the LBTS
vacuum system
The LBTS control system shall provide automatic alignment monitoring of the LBTS
during HPLS operation

Human Machine Interface,


Synoptic Display,
Alarm management,
history of configurations,
logging management,
User profile configurations,
dedicated HMI for each subsystem,
triggerable cameras,
TANGO compatible, video network traffic not to burden Control
System network