2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Contents
Important Abbreviations and Terms .................................................... 2
Safety Instructions ................................................................................ 3
Designated use .................................................................................. 3
Personnel ............................................................................................ 3
Modifications, spare parts, accessories ............................................ 3
General instructions .......................................................................... 3
Marking of safety instructions ........................................................ 3
Further symbols.................................................................................. 3
Transport and Storage .......................................................................... 4
Designated Use .................................................................................... 4
Function .................................................................................................. 4
Interface module 24 V DC ................................................................ 5
Adaptor module DeviceNet .............................................................. 6
Adaptor module AS Interface .......................................................... 7
Adaptor module AC-Interface .......................................................... 7
Design .................................................................................................... 9
Mounting.............................................................................................. 10
Mounting on to VARIVENT valve .................................................. 10
Pneumatic Connections ...................................................................... 11
Installing the air hose...................................................................... 11
Control air connections .................................................................. 11
Electrical Connections.......................................................................... 12
Commissioning .................................................................................... 13
Step 1 Control air .......................................................................... 13
Step 2 Valve actuation .................................................................. 13
Step 3 Voltage .............................................................................. 13
Step 4 Feed back of the valve activation .................................... 14
Step 4.1 Adjusting the sensors in the control module ................ 15
Step 4.2 Adjust external proximity switch
in the lantern for balanced double-disk ........................................ 16
Test procedure for PMO valve Type M_O (step 5 of commissioning) 17
Maintenance ........................................................................................ 18
Inspections........................................................................................ 18
Dismantling ...................................................................................... 18
Wiring diagram T.VIS M-1.................................................................... 23
Wiring diagram
for control systems with N-Logic .................................................... 24
for control systems with P-Logic .................................................... 25
Technical Data ...................................................................................... 26
General ............................................................................................ 26
List of Tools / Lubricant .................................................................... 26
Equipment ........................................................................................ 26
Specification interface module 24 V DC .......................................... 27
Specification Adaptor module AC interface .................................. 27
Specification Adaptor module DeviceNet ...................................... 28
Specification Adaptor module AS interface.................................... 29
Annex
Spare parts lists ................................................................................ 30
Dimension sheet .............................................................................. 35
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Output
PLC
T.VIS
T.VIS E
CAN_H
Communication DeviceNet
CAN_L
Communication DeviceNet
Input
ext.
external
V+
Supply+ DeviceNet
GEA
Supply DeviceNet
IP
Protection class
V DC
LED
Light-emitting diode
V AC
L+
Positive conductor
L-
Negative conductor
mA
mm
metric
Nm
NOT-Element
Logic element
NPN
PA
Polyamide
PE-LD
PNP
Prox.
Proximity switch
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Safety Instructions
Designated Use
The Control Module T.VIS is designed exclusively for
the purposes described below. Using the control module
for purposes other than those mentioned is considered
contrary to its designated use. Tuchenhagen cannot be
held liable for any damage resulting from such use; the
risk of such misuse lies entirely with the user.
The prerequisite for the reliable and safe operation of
the control module is proper transportation and storage
as well as competent assembly.
Operating the control module within the limits of its
designated use also involves observing the operating,
inspection and maintenance instructions.
Marking of Safety
Instructions in the
Operating Manual
Special safety instructions are given directly before the
operating instructions. They are marked by the following symbols and associated signal words.
It is essential that you read and observe the texts belonging to these symbols before you continue reading the
instructions and handling the control module.
Symbol
Signal word
Meaning
DANGER
CAUTION
Dangerous situation,
which may cause slight
injury or damage to
material.
ATTENTION
Personnel
Personnel entrusted with the operation and maintenance of the control module must have the suitable
qualification to carry out their tasks. They must be
informed about possible dangers and must understand
and observe the safety instructions given in the relevant
manual. Only allow qualified personnel to make
electrical connections.
General Instructions
The user is obliged to operate the control module only
when it is in good working order.
In addition to the instructions given in the operating
manual, please observe the following:
relevant accident prevention regulations
generally accepted safety regulations
regulations effective in the country of installation
working and safety instructions effective in the user's
plant.
Further symbols
Symbol
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Meaning
Process / operating steps which
must be performed in the specified
order.
General enumeration
Transport and
Storage
Function
DANGER
The synthetic materials of the control modules are
fragile.
In the case that during transport or storage the control
module was exposed to temperatures 0C, it must be
stored in a dry place against damage.
We recommend, prior to any handling an intermediate
storage of 24 h at a temperature of 5 C so that any ice
crystals formed by condensation water may melt.
Designated Use
The Control Module T.VIS M1 (Tuchenhagen Valve
Information System) is used for the pneumatic and
electrical connection of VARIVENT and ECOVENT
process valves.
Control Module T.VIS M-1 consists of
a 24 V DC interface module with 1 or 2 sensors for the
detection of the two actuated valve positions
an additional Adaptor module for the interface
modules AS-Interface, DeviceNet and 20130 V AC
(optional).
at least three solenoid valves maximum for the actuation of the main stroke and the lift strokes,
a logic element NOT (optional) for backup of the
valve`s main spring or for the actuation of indifferent
actuators (air/air) and
a connection for an external proximity switch for monitoring the non-actuated position of the double-disk
(optional).
an exhaust air throttle (optional) for variable setting of
the closing velocity of the main stroke.
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Statement of Equivalency
All Control Module options as described in this T.VIS
M-1 Operating Instructions as well as all Control Module options as described in the VARIVENT Control
Module Type S for PMO Valve Type M_O (06) and
M_OB (06) operating manual can be considered as
equivalent to the T.VIS M-1 Control Module with 24
V DC Interface for use with the PMO valve Type M_O
(06) and M_OB (06) as far as meeting the application
conditions of FDA Memorandum M-b-353.
Specifically these alternative Control Module options
are as follows:
1. T.VIS M-1 Control Module with DeviceNet Adapter
Module (described here on pages 7 and 28)
2. T.VIS M-1 Control Module with AS-Interface Adapter
Module (described here on pages 8 and 29)
3. T.VIS M-1 Control Module with AC-Interface Adapter
Module (described here on pages 8 and 27)
4. Control Module Type S with AS-Interface Module
(described Control Module Type S Operating manual
on page 19)
5. Control Module Type S with DeviceNet Module
(described Control Module Type S Operating Manual
on page 20)
6. Control Module Type S with 3-wire 24 V DC Interface
Module (described Control Module Type S Operating
Manual on pages 17)
7. Control Module Type S with AC voltage Interface
Module (described Control Module Type S Operating
Manual on page 18)
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Interface Module 24 V DC
LED A
LED B
Contact Designation
1*
Seat lift Prox+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CAUTION
Avoid direct looking at the LED A and B, because they
emit a very bright light that might blind the eyes!
green
Permanent light
Valve in start position (non-actuated)
yellow
Permanent light
actuated valve position
Flashing
Valve deviated from the set positions
Functional description
Connection of ext. prox.
L+ (brown lead)
2*
Seat lift Prox
Connection of ext. prox.
L (blue lead)
3
Y1.1
Connection solenoid
valve 1+
4
Y1.2
Connection solenoid
valve 1
5
Y2.1
Connection solenoid
valve 2+
6
Y2.2
Connection solenoid
valve 2
7
Y3.1
Connection solenoid
valve 3+
8
Y3.2
Connection solenoid
valve 3
9/10
PNP/NPN
With contact bridge:
Common
corresponds to PNP control
system; without contact
bridge: corresponds to
NPN control system
see Chapt. Commissioning, Step 3
11
Start
Feedback for the valve disk
in non-actuated position
12*
End
Feedback for the valve disk
in actuated position
(main stroke).
13*
Seatlift Y3
Feedback for the double-disk
in non-actuated position
PLC-information only
with ext. prox.
14
PV Y1
Actuation of solenoid
valve Y1 (main stroke)
15
PV Y2
Actuation of solenoid
valve Y2 (valve disk lift
stroke)
16
PV Y3
Actuation of solenoid
valve Y3 (double-disk lift
stroke)
17/18
Y-Common
L(+/)
18/19
19/20
24 V DC
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
DC
DC
24 VDC
10
20
19
18
17
16
15
14
13
12
24 VDC
L(-)
Y-Common
PV Y3
PV Y2
PV Y1
Seatlift
End
Start 11
Common
PNP/NPN
Y3.2
Y3.1
Y2.2
Y2.1
Y1.2
Y1.1
Seatlift prox -
Seatlift prox+
*
*
Y3
Y2
Y1
NAMUR
F2
L-
L-
supply
24 V DC
L+Power
L-
L-
L+
A 1.2
A 1.1
A 1.0
E 0.3
E 0.2
E 0.1
L-
LL+
Master PLC
I/O level 24 V DC (PNP)
If electrically isolated circuits are used for valve actuation and feedback are used, the
jumper between terminal 17 and 18 must be removed.
Notice: * only for interface module with 2 sensors, part no. 221-589.20
Type: 24 V DC
Part. no.221-589.19;20
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
DC
DC
24 VDC
13
12
11
20
19
18
17
16
15
14
24 VDC
L(+)
Y-Common
PV Y3
PV Y2
PV Y1
Seatlift
End
Start
Common 10
PNP/NPN
Y3.2
Y3.1
Y2.2
Y2.1
Y1.2
Y1.1
Seatlift prox -
Seatlift prox +
*
*
Y3
Y2
Y1
NAMUR
common L+ selected!
F1
Earthing
F2
L-
L+
L+
L-
L-
L-
L-
Power supply
24 V DC
A 1.2
A 1.1
A 1.0
E 0.3
E 0.2
E 0.1
L+
Master PLC
I/O level 24 V DC (NPN)
If electrically isolated circuits are used for valve actuation and feedback are used, the jumper between terminal 17 and 18 must be removed. The isolated reference potential is then assigned to terminal 17
Notice: * only for interface module with 2 sensors,part no. 221-589.20
Type: 24 V DC
Part. no. 221-589.19;20
L-
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Start
L(+/-)
Type: 24 V DC
Part no.: 221-589.19 + 221-589.20
Type: 20-130 V AC
Part No.: 221-589.21
DC
24 VDC
20
DC
Y-Common
PV Y3
PV Y2
24VDC
19
18
17
16
15
14
PV Y1
*Seatlift
13
12
*End
11
Common
PNP/NPN
Y3.2
Y3.1
Y2.2
Y2.1
Y1.2
Y1.1
*Seatlift prox -
*Seatlift prox +
10
Type: AS-Interface
Part No.: 221-589.24
PE
PE
~PV Y3
~PV Y2
~PV Y1
* ~Seatlift
* ~End
~Start
Internal wiring
Type: DeviceNet
Part No.: 221-589.22
- AS-i
V-
brown
V+
CAN_L
CAN_H
blue
white
red
black
32 5 4
Adaptor module
DeviceNet
LED
Terminal
1
Designation
CAN_H
Functional description
Communication
CAN_L
Communication
V+
Supply+
Supply
Colour:
Indication:
green
Permanent light
working properly
Flashing
On line not connected
Colour:
Indication:
red
Permanent light
connection not possible
Flashing
Time out or I/O failure
Colour:
Indication:
green/red
Flashing
Power up test
Colour:
Indication:
amber
Flashing
Autobaud detect
Baudrate
MAC ID
32 16 8
ON
DIP Switch
1 2 3 4 5 6 7 8
DIP 1
OFF
ON
OFF
ON
DIP 3
OFF
ON
OFF
...
OFF
*ON
DIP 2
OFF
OFF
ON
ON
Baudrate
125 kBaud
250 kBaud
500 kBaud
selectable via software
DIP 4
OFF
OFF
ON
...
ON
ON
DIP 5
OFF
OFF
OFF
...
ON
ON
DIP 6
OFF
OFF
OFF
...
ON
ON
DIP 7
OFF
OFF
OFF
...
ON
ON
DIP 8
OFF
OFF
OFF
...
ON
ON
MAC ID
0
1
2
...
62
63
*Factory setting
10
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Adaptor module
AS-Interface
AC-Interface AC Voltage
LED
LED
1
2
~Start
~End
~Seatlift
~PV Y1
~PV Y2
~PV Y3
PE
PE
N
L
1
2
3
4
5
6
7
8
9
10
+ASI
-ASI
Terminal
1
Designation
+ ASI
Contact Designation
1
Start
ASI
Functional description
Communication and
Supply+
Communication and
Supply
2*
End
3*
Seat lift
PV Y1
PV Y2
PV Y3
7
8
9
10
PE
PE
N
L
green
Permanent light
Data exchange active
red
Permanent light
no data exchange
Address 0
Flashing
Error peripheral equipment
Functional description
Feedback for the valve disk
in non-actuated position
Feedback for the valve disk
in actuated position
(main stroke)
Feedback of the double disk
in non-actuated position
PLC signal evaluation with
ext. proximity switch only
Actuation solenoid valve Y1
main stroke
Actuation solenoid valve Y2
lift stroke valve disk
Actuation solenoid valve Y3
lift stroke double disk
Protective conductor
Protective conductor
Neutral conductor
Live wire
green
Permanent light
Power supply ON
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
11
Design
1 Switch bar
5 Base plate
7 Hood
8 Pneumatic block
15 Clamps
43
47
21 Sound absorber
64
21.1 Exhaust air throttle
optional for 21
63
24.4
24 Cable glands
24.2 Plug M 12/4-poles
for ASI
24.3 Plug M 12/5-poles
for DeviceNet
24.4 Terminal box ASI
65
170
50
5
15
24
26 Sound absorber
26.1 Reflux valve
(optional)
43 Interface module
26
21
21.1
26.1
24.2/
24.3
47 Adaptor module
50 Cable gland for
external prox.
63 Solenoid valves
64 Logic element NOT
65 Steering/Blind plate
170 External proximity
switch (optional)
CAUTION
The permanent magnet on the switch bar (1) is fragile and
must therefore be protected against mechanical impact
stress.
The magnetic fields can delete data carriers and affect or
destroy mechanical components.
Avoid influence of external magnetic fields on the
sensor system!
CAUTION
Do not perform weldings in vicinity of the control module,
as otherwise this could cause data losses.
12
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Mounting
the Control Module on to a
VARIVENT valve
CAUTION
When mounting the control module, make sure that the
air hoses do not get kinked.
CAUTION
The permanent magnet on the switch bar (1) is fragile
and must therefore be protected against mechanical
impact stress.
The magnetic fields can delete data carriers and affect
or destroy mechanical components.
B
39
1.1
1.2
15
1
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
A.1
13
Pneumatic
Connections
CAUTION
The safety vent E1 and E2 must not be closed!
Y2 Y3
S1
S2
Y1
E1
Y2 Y3
E2
23
CAUTION
Control air pressure may build up at closing plugs of
the air connections! Before removal of a closing plug
(23) make sure that the specific air connection is free of
pressure.
Y1 Air connection for external main stroke
connection (with closing plug (23)
14
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Electrical Connection
DANGER
Only allow qualified personnel to make electrical
connections.
Prior to making electrical connections check the maximum permissible operating voltage.
Undo cylinder screws (25) and remove hood (7).
Insert the cable into the cable gland (24.1) and connect
it in the control module to the terminals (K) according
to the wiring diagram.
7
25
K
24.1
170
50
Connections ASI
Terminal Box ASI (24.4)
thus excluded.
24.43
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
15
24.2 /24.3
K1
K2
0
1
Insert the cable into the cable gland (50) and connect
it in the control module to the terminals K1 and K2
according to the wiring diagram.
CAUTION
Use only proximity switches that are specified in Chapt.
Technical Data, Equipment.
Commissioning
Commissioning can take place if the control module has
been mounted correctly on the valve and if the electrical
and pneumatic connections have been attached properly.
Step 3 Voltage
16
CAUTION
Firmly tighten terminals for jumper.
Switch on operating voltage.
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Sensor S1
Ill.:
S1
Module input
S2
Module output
End
Valve main stroke actuated
Start
Valve not actuated
Valve opened
Valve closed
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
17
CAUTION
When actuating the valve for adjusting the sensor or for
checking the switching function, make sure that no
media are inside the valve.
3
S1
CAUTION
There is a risk of overwinding the setting screw (1)!
Therefore turn the setting screw (1) with a torque of
0.3 Nm max. up to the upper or down to the lower limit
stop of the sensor.
Presetting
Slacken the locking screw (2).
Turn setting screw (1) of the sensor S1, until light emitting diode A at the interface module shines green
Move sensor using the setting screw (1) in the direction of the lower switching edge (4) of the switching
range (3) until the diode goes out.
S2
Presetting
Slacken the locking screw (2).
Turn setting screw (1) of the sensor S2, until light emitting diode B at the interface module shines yellow.
Move sensor using the setting screw (1) in the direction of the upper switching edge (4) of the switching
range (3) until the diode goes out.
18
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
4
2
1,1
CAUTION
1
7
8
Insert the hex. screw from the inside into the corresponding bore and tighten from the outside with the cap nut (8)
Thread seal wire (9) through the bore and seal.
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
19
Hardware Description :
1. The (blue-colored) T.VIS M1 Control Module on the
top of the valve will house 3 solenoid valves (see page
10):
a. Solenoid Y1 Main Valve Activation
b.Solenoid Y2 Lower Seat Lift Activation
c. Solenoid Y3 Upper Seat Lift Activation
These valves can be activated using a small screwdriver
to move the screw at the top of each solenoid valve from
the 0 position to the 1 position.
2. The lower seat closed position is detected by proximity switch S1 inside the control module as shown on
page 14 of the Operating instructions. The correct
adjustment of this switch to detect the closed position
of the lower seat is given in detail on page 14 of the
Operating instructions.
a. The sensitivity of the proximity switch is 0.1 mm.
3. The upper seat closed position is detected by the
externally-mounted lantern proximity switch S3 as
shown on page 15 of the Operating instructions. The
correct adjustment of this switch to detect the closed
position of the upper seat is given in detail on page 15
of the Operating instructions.
a. The sensitivity of this proximity switch is also 0.1 mm.
Step 2
Activate the lower seat lift operation by turning the
screw position at the top of solenoid Y2 from the 0
position to the 1 position.
When the seat moves downwards (approx. 6 mm), the
GREEN LED on the top of the control module will turn
off to indicate that the proximity switch S1 no longer
sees the lower seat in its closed position.
If the GREEN LED does not turn off, the lower seat
proximity switch S1 is NOT adjusted correctly and the
adjustment procedure described on Page 14 of the Operating instructions should be repeated.
Step 3
Activate the upper seat lift operation by turning the
screw position at the top of solenoid Y3 from the 0
position to the 1 position.
When the seat moves upwards (approx. 2 mm), the
YELLOW LED on the externally-mounted lantern proximity switch will turn off to indicate that the proximity
switch S3 no longer sees the upper seat in its closed
position. If the YELLOW LED does not turn off, the
upper seat proximity switch S3 is NOT adjusted correctly and the adjustment procedure described on page 15
of the Operating instructions should be repeated.
Test procedure 2
The methology behind test procedure 2 is to allow the
Regulatory Inspector to manually force open the seat
opposite to the valve housing which is part of an active
CIP circuit to ensure that proper control system interlocking is in place. In this case, the CIP supply pump or
the source of the CIP solution pressure should be deactivated.
CAUTION
Please note that great care should be taken with test procedure 2 as there is danger of CIP mixing with product
if the proper control system interlocks are not in place.
Ensure that product is NOT present in the valve housing opposite to the housing which is part of the active
CIP circuit for the duration of this test!
Step 1
Ensure that the valve being tested is part of an active
CIP circuit program and determine which housing
(upper or lower) of the valve is part of that active CIP
circuit.
Step 2
Remove the control module cap with a screw driver and
manual activate either the lower seat lift ( by turning the
screw position at the top of solenoid Y2 from the 0
position to the 1 position) if the upper housing is part
of the active CIP circuit OR the upper seat lift (by turning the screw position at the top of solenoid Y3 from the
0 position to the 1 position) if the lower housing is
part of the active CIP circuit.
Step 3
Test procedure 1
Step 1
The valve should be in the closed position. This can be
seen by the GREEN LED on the top of the control module. In this case, the lid of the control module should be
removed with a screwdriver
20
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Maintenance
Inspections
Check cap nut of the cable gland (24.1) for firm seat.
Check air hose connection for firm seat.
7
43.1
43
47
64
63
170
50
15
24.1
Dismantling
Separate control module from
the valve
7
25
5
CAUTION
Take care that no solenoid valve is actuated electrically
or manually.
15
39
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
21
DANGER
Switch off electrical current and control air before taking
apart the control module.
7
25
8
63
63.1
65.1
65
43
CAUTION
Risk of burns from the solenoid valve as a result of long
switch-on time and high ambient temperature.
Allow to cool before dismantling.
Disconnect cable of the solenoid valve from the terminals of the interface module (43).
53
54
CAUTION
Adhere to the assignment of the cable between the solenoid valve and the interface module Solenoid valve
Y1 to be connected to terminal Y1.1/Y1.2.
CAUTION
Use only solenoid valves which are specified in the
Chapt. Technical Data, Equipment.
22
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
65.12
65
65.11
65.22
65.21
65
CAUTION
Logic element NOT is provided in connection with the
pneumatic block T.VIS/NOT!
Undo screws (64.2) and remove logic element NOT
(64) complete with flat gasket (64.1).
If needed, change the gasket package only (64.1), consisting of screws and gasket.
64.2
64
64.1
8.2
CAUTION
Faulty assembly may cause failures, as the spring force
backup is then not given.
8.1
8
23
43
K
Slacken screws K (11-16 + 19-20) of the connection terminals of the interface module (43) and pull adaptor
module (47) in direction of the arrow by approx. 7 mm
out of the interface module for removing it from the
base plate (5).
Assemble the adaptor module in reverse order.
Observe the wiring diagrams. (see Chapt. Wiring diagram)
57.2
5
solenoid valves (63) /control plate and the logic element NOT (64) on the pneumatic block (8) can remain
screwed in place.
43
63
64
24
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
CAUTION
Lubricate the O-rings (42) slightly before installing
them, to prevent them from falling out.
8.1
Prior to installation, slightly lubricate the seals to prevent them from falling out!
42
42
55
57.2
57.2
57.2
42
42
55
CAUTION
On VARIVENT actuators with a vent hole in the actuator cover the control module may only be fitted without
O-ring (54)!
CAUTION
Use no other reflux valve (26.1) and sound absorber (21,
26) or exhaust air throttle (21.1) than the ones specified
in the Chapt. Technical Data, Equipment.
21.1
21
26
26.1
31
54
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
25
Technical Data
Equipment
General
Type
Proximity switch
M12x1
part no. 505-095
in the lantern
Material
Noryl
Ambient temperature
20 up to +50 C
Control air
acc. to ISO 8573-1:2001
Solid particle content: quality class 6
particle size max. 5 m
part. density max. 5 mg/m3
Water content:
quality class 4
max. dew point +3 C
If the valve is used at
higher altitudes or at low
ambient temperatures,
the dew point must be
adapted accordingly.
Oil content:
quality class 3,
preferably oil free
max. 1 mg oil in 1m3 air
Air hose
metric
Inch
Protection class
material PE-LD
outside dia. 6 mm
inside dia. 4 mm
material PA
outside dia. 6.35 mm
inside dia. 4.3 mm
IP 66, IP 67 on option
Technical Data
as per NAMUR
normally closed contact
4,5...30 V DC
Ambient temperature: 25...+85 C
Protection class IP 67
non-metal contact switching
Logic element NOT pressure range: 2,0...8,0 bar
part no. 512-137
Ambient temperature:
20...+70 C,
Solenoid valve
24 V DC+20%/-12,5%, 0,85 W
part no. 512-151
Ambient temperature: 20...+60 C
Protection class IP 51
pressure range: 2,0...8,0 bar
Sound absorber
Filter material: stainless steel wool
6 mm
Ambient temperature:
part no. 933-981
20...+70 C
Temperature of the medium: +70 C
max. pressure 10 bar
Sound absorber
Filter material: stainless steel wool
G 1/2"
Ambient temperature:
part no. 933-967
20...+70 C
Temperature of the medium: +70 C
max. pressure 10 bar
Check valve
pressure range: 0 up to 10 bar
part no. 602-060
opening pressure: 0,15 bar
flowrate at p 6 bar:
600 dm3n/min +/-5%
Exhaust air throttle Filter material: sintered s/s
6 mm
Pressure range 0 to10 bar
part no. 933-976
variable flow rate setting,
at p 6 bar: 200 dm3n/min
temperature of the medium
+70 C
ambient temperature:
20...+70 C
flow rate setting at 0...+70 C
Lists of Tools/Lubricant
Tool
Hose cutter
Allen key, size 3 and 8
Open spanner, size 12x13
Open spanner, size 14x17
Open spanner, size 20
Open spanner, size 22
Open spanner, size 24x27
Open spanner, size 25
Face wrench, pin 4
Screw driver Torx 10 IP
Screw driver Torx 20 IP Plus
Phillips head screw driver size 2
Slotted screw driver A 0.4 x 2.5
Flat-nosed pliers
Lubricant
Rivolta F.L.G. MD-2
PARALIQ GTE 703
26
Part no.
407-065
408-112
408-034
408-045
408-039
408-040
9065837
413-071
413-064
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
221-589.19 / 221-589.20
24 V DC (+20%, 15%)
40mA (with ext. Initiator 50mA)
No-load current + Current consumption
solenoid valve + Current load feedback output
No-load current interface module+ No-load
current adaptor module + Current consumption
solenoid valve
< 5%
Outputs
Maximum power rating per feedback output
Voltage drop at the outputs
Short ciruit and overload protection
50mA
3V
24 V DC (+20% 12,5%)
35 mA
Ambient conditions
Ambient temperature
Connection terminals for conductor cross section
20 ... +70C
up to 1,5mm2
1,5 kV
yes
Inputs
Actuation voltage
Actuation current
Outputs
Power rating IAx
Signal voltage ULx
Design
Dimensions
Housing material
Connection
Pin strip
Vibration proof
Shock proof
Protection class
Temperature range
221-589.21 AC-MODUL
48...130 VAC
11 mA*
100 mA
Uv 5 V)
E/A-module fr/I/O Module for T.VIS
85 x 61 x 32 mm
PA6-GF30-V0
10-polig/poles, 0,5...1,5 mm 2
10-polig/poles (ohne /w.o. 7 + 8),
Raster/grid 3,5 mm
55 Hz (1 mm)
15 x g
IP 20
25...+70 C
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
27
Inputs
- Input 1 Start
- Input 2 End
- Input 3 Seatlift Y3
Databit DI 0
Databit DI 1
Databit DI 2
Outputs
Output 1 PV Y1
Output 2 PV Y2
Output 3 PV Y3
Databit DO 0
Databit DO 1
Databit DO 2
Design
Dimensions
Housing material
Connections
Pin strip
Vibration proof
Shock proof
Protection class
Temperature range
* Note operating current for interface module!
28
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Inputs
Input (E/A ACTIVE HIGH)
Feedbeck
Input 1 Start
Input 2 End
Input 3 Seatlift Y3
Input 4
Datenbit DI 0
Datenbit DI 1
Datenbit DI 2
(not used)
Outputs
Output (I/O ACTIVE HIGH)
Actuation of solenoid
Output 1 PV Y1
Output 2 PV Y2
Output 3 PV Y3
Output 4
Datenbit DO 0
Datenbit DO 1
Datenbit DO 2
(reserved for A/B identification)
Design
Dimensions
Housing material
Connections
Pin strip
Vibration proof
Shock proof
Protection class
Temperature range
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
29
Date: 2011-11-07
Page 1 of 4
30
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Date: 2011-11-07
Page 2 of 4
221ELI008999EN_0.DOC
Control module T.VIS M-1;24VDC/PNP/NPN with cable connections in metric and air connections in inch
Item
Designation
Base PZM-T.VIS
5
Base PNZM-T.VIS
5.1
Filter
5.2
8
Pneumatic block without NOT
TM1L..A.
TM1Y..A.
221-589.13
--
--
221-589.14
221-003869
221-003869
933-144
933-144
221-589.02
221-589.02
--
221-589.04
221-589.05
--
GRIVORY
221-320.93
221-320.93
Ms/vern.
933-958
933-958
Material
Noryl/
GFN2
Noryl/
GFN2
PE
gesintert
Ms/vern.
Noryl/
GFN2
Noryl/
GFN2
Noryl/
GFN2
15
21
SRXQGDEVRUEHU
22
Round plug
HD-PE
922-284
--
23
Locking plug
PP
922-280
922-280
24
Cable gland
PA
508-995
508-995
26
Ms/vern.
933-967
933-967
31
O-ring
NBR
930-041
930-041
42
O-ring
NBR
930-436
930-436
--
221-589.20
221-589.20
PA
508-914
508-914
Interface module
Cable gland
52
O-ring
EPDM
930-148
930-148
53
O-ring
NBR
930-833
930-833
54
O-ring
NBR
930-093
930-093
55
O-ring
NBR
930-038
930-038
56
A2
514-749
514-749
57
A2
514-750
514-750
63
PPS
512-151
512-151
--
221-589.15
221-589.15
--
--
512-137
--
--
221-589.16
63.1
64
Thread-cutting screw
A2
514-751
514-751
67
Thread-cutting screw
A2
--
514-758
31
Date: 2011-11-07
Page 3 of 4
Control module T.VIS M-1;24VDC/PNP/NPN with cable connections and air connections in inch
Item
Designation
Base PZ-T.VIS
5
Base PNZ-T.VIS
5.1
Filter
5.2
8
Pneumatic block without NOT
TM1L..AZ
TM1Y..AZ
221-589.11
--
--
221-589.12
221-003869
221-003869
933-144
933-144
221-589.02
221-589.02
--
221-589.04
221-589.05
--
GRIVORY
221-320.93
221-320.93
Ms/vern.
933-958
933-958
Material
Noryl/
GFN2
Noryl/
GFN2
PE
gesintert
Ms/vern.
Noryl/
GFN2
Noryl/
GFN2
Noryl/
GFN2
15
21
6RXQGDEVRUEHU
22
Round plug
HD-PE
922-284
--
23
Locking plug
PP
922-280
922-280
24
Cable gland
PA
508-299
508-299
26
Ms/vern.
933-967
933-967
31
O-ring
NBR
930-041
930-041
42
O-ring
NBR
930-436
930-436
--
221-589.20
221-589.20
PA
508-913
508-913
Interface module
Cable gland
52
O-ring
EPDM
930-148
930-148
53
O-ring
NBR
930-833
930-833
54
O-ring
NBR
930-093
930-093
55
O-ring
NBR
930-038
930-038
56
A2
514-749
514-749
57
A2
514-750
514-750
63
PPS
512-151
512-151
--
221-589.15
221-589.15
--
--
512-137
--
--
221-589.16
63.1
64
Thread-cutting screw
A2
514-751
514-751
67
Thread-cutting screw
A2
--
514-758
32
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Date: 2011-11-07
Page 4 of 4
Item Designation
Material
part no.
21.1* &KRNHYDOYH*
Ms/vern.
603-042
21.2* &KRNHYDOYH*
Ms/vern.
603-042
Ms/vern.
933-976
Ms/vern.
508-060
Ms/vern.
508-981
Ms/vern.
508-996
Ms/vern.
221-359.65
24.4.1
reducer
PA
508-980
24.4.2
PA
508-914
24.4.3
PA
508-019
Application
for reduced closing speed of the main stroke
(Exhaust air outlet with silencer, item 21)
To reduce the opening speed during the main stroke
(cunnection with plug-in screw connector, item 5.2)
for reduced closing speed of the main stroke
(only for exhaust outflow with inserted air connection)
24VDC cable connection with cable socket, M12/8-pole/A-coded
DeviceNet cable connection with cable socket, M12/5-pole/A-coded
(Option for cable gland 508-995)
ASI cable connection with cable socket, M12/4-pole/A-coded
(Option for cable gland 508-995)
Cable connection ASI with cable and connecting box
(Option for cable gland 508-995)
171*
1.4404
) 172*
Hex. screw
A2-70
) 173*
Cap nut
Hex. Nut
1.4301
A2
) 175*
Nut Ni / M / 06
1.4305
Ms/vern
PVC
--
--
--
A2
1*
602-060
Please see more detail in the spare parts list of the valves typ M.
Accessoirs (please order separately)
Angular cable socket, M12/5-pole/A-coded / 24 V DC / Device Net
508-963
508-061
514-161
Straight cable socket M12 with 1.0m cable and ASi insulation
displacement connector
508-027
Straight cable socket M12 with 2.0m cable and ASi insulation
508-028
quick air vent valve D6 (double -sided with connection for hose 6mm)
603-039
33
TUCHENHAGEN
Datum/date: 2006-03-23
Process Equipment
Division
221MBL000380G_2.DOC
22
20
21
46
44
164
146
97
196
Anschluss Elektrik
Y3
Y2
Electrical connection
P
E2
Y1
N
E1
Externer Initiator
external proximity switch
Zuordnung N, Y1, Y2, Y3, E1, E2 und P siehe Betriebsanleitung 430-232 und 430-398
Allocation for N, Y1, Y2, Y3, E1, E2 and P see operating instruction 430-232 and 430398
34
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
Datum/date: 2011-05-26
Seite / Page 1 von / of 1
221ELI008224G_0.DOC
* Gesichert mit UHU Endfest 300 / Secured with UHU Endfest 300
Schaltstange LFT-R T.VIS A-8 /
switch bar LFT-R T.VIS A-8
Typ / type
Pos.
item
1
2
3
4
5
6
Benennung /
Designation
Schaltstange kpl. /
switch bar kpl.
Schaltstange /
switch bar LFT-RM7
Schaltstange LFT-R /
125
200
205
166
125
200
205
166
256
221-618.08
221-618.09
221-618.10
221-618.11
221-618.02
221-618.03
221-618.04
221-618.06
221-618.05
--
--
--
--
--
221-618.01
221-618.01
221-618.01
221-618.01
221-618.01
221-615.06
221-615.08
221-615.09
221-615.07
221-615.10
221-615.01
221-615.02
221-615.03
221-615.05
221-615.04
221-619.02
221-619.02
221-619.02
221-619.02
221-619.02
221-619.01
221-619.01
221-619.01
221-619.01
221-619.01
--
--
--
--
935-085
935-085
935-085
935-085
935-085
--
--
--
--
--
910-018
910-018
910-018
910-018
910-018
221-589.41
221-589.41
221-589.41
221-589.41
221-589.41
--
--
--
--
--
2012-06 Control Module T.VIS M-1 for Valve M_O (06), Valve M_OB(06), MT/T_R 08 (PMO)
35