USERS MANUAL
Content
I. Product Advantage--------------------------------------------------.1
II .Technical parameters-----------------------------------------------2
III. Attentions-----------------------------------------------------------4
IV. Instrument structure ---------------------------------------------- 4
V.Wiring methods------------------------------------------------------9
VI. How to test cables-------------------------------------------------12
VII. How to test generator--------------------------------------------14
VIII. Operation procedure--------------------------------------------17
IX. Operating Instructions of Discharge Rod----------------------26
X. Printer Instruction--------------------------------------------------27
XI. Accompanied accessories----------------------------------------29
I. Product Advantage
1. VLF means Very Low Frequency and 0.1Hz to 0.02Hz
is considered to be very low frequency.
2. VLF HV Generator is suitable for testing cables,
transformers, switchgear,rotating machinery,and other
electrical apparatus.
3. The product combines modern advanced digital variable
frequency technology and micro computer control together,
therefore, it can realize the full automatic voltage boost,
stepdown, measurement and protection as well as the manual
intervention in the process of automatic voltage boost. The
full electronic design ensures the small size and light weight.
The big LCD screen ensures the clear and visual display, and
can display the output wave form. The printer outputs test
reports. In addition, the product has features as follows:
Data of current, voltage, wave form can be directly
sampled at high voltage side, so the data is real and
accurate.
Overvoltage protection: If the output exceeds the set limit
of voltage, the instrument will shut-down to protect itself,
the actuation time is less than 20ms.
Overcurrent protection: it is high-low voltage dual
protection in the design, the accurate shut-down
protection can be made according to the set value at high
voltage side; If the current on low voltage side exceeds
VLF30/1.1
VLF40/1.1
VLF50/1.1
VLF60/0.5
Output
Voltage/
Current
(Peak)
Load Capacity
Control Unit
Frequency/
Capacitance
Booster
Fuse
Tube
Dim.
(cm)
Wt
(kg)
Dim.
(cm)
Wt
(kg)
0.1Hz 1.1uF
0.05Hz 2.2uF
0.02Hz 5.5uF
283722
331834
25
8A
40KV/29mA
0.1Hz 1.1uF
0.05Hz 2.2uF
0.02Hz 5.5uF
283722
352036
45
50KV/59mA
0.1Hz 1.1uF
0.05Hz 2.2uF
0.02Hz 5.5uF
283722
372439
45
10A
60KV/59mA
0.1Hz 0.5uF
0.05Hz 1.0uF
0.02Hz 2.5uF
283722
331834
331834
25+45
20A
25+45
20A
25+45
20A
25+48
20A
30KV/29mA
VLF70/0.5
70KV/59mA
VLF80/0.5
80KV/59mA
VLF90/0.5
90KV/59mA
0.05Hz, 1.0F
0.02Hz, 2.5F
283722
283722
331834
352036
331834
372439
283722
331834
392639
III. Attentions
1. Power supply requirement: AC 220V 50/60Hz or AC
110V 50/60Hz (as per buyers requirement before booking),
stability of frequency: fluctuation less than 0.5%
2. When using it, it is prohibited to boost voltage without
load, or to connect with resistive load.
3. When using it, the capacitance of the DUT should not
exceed the rated capacity of the instrument. The overlow
capacitance of the DUT will affect the output wave form. If
the capacitance is less than 0.04F, the instrument cannot
output normally, at this time, please paralleling connection
with a 0.04F compensating capacitor supplied by us (Free),
then the equipment can output normally.
4. Before testing, please pour a litte dielectric oil
(transformer oil) into the tube (see below picture) , making
the tube almost overfill oil when insert the white input
connector. May demage the equipment if it is dry in tube.
White Connector
Figure 1
Figure 2
Figure 4
Figure 5
V. Wiring method
Wiring Method of Single booster:
The method of wiring shall be according to figure 6-1 &
figure 6-2 if the rated Voltage is less than or equal to 50kV.
When only 1 booster of the instrument will be used in the
method of series, it especially needs to click"Single
connection" or "Single" selection at Column of Parameter
Setting after the equipment is power on (as shown in figure
below).
25
35
50
70
95
120
150
185
240
270
10
0.15
0.17
0.18
0.19
0.21
0.24
0.26
0.28
0.32
0.38
35
0.11
0.12
0.13
0.14
0.15
0.16
0.17
0.19
Class(KV)
synchronously taken after paralleling cable cores of 3phases if Cable capacitance doesn't exceed the rated
capacitance of VLF Tester.
6. Cable test connection according to the method shown in
Figure 6-3. supplying the power, setting the test frequency,
time and voltage and high side over-current protection value,
over-voltage protection value, and then start to boosting test.
During boosting,high-voltage loop should be closely
monitored, meanwhile, surveying whether cable has
abnormal noise or not. The equipment will begin to record
test time and test voltage reading value when it goes to the
test voltage.
7. When test time is up, the instrument will automatically be
shutdown. It is considered to be passed the test if there is no
damaging discharging.
8. Please stop the equipment immediately if finding the
following things during boosting: output waveform distortion
abnormally, abnormal increasing strong current, voltage
instability, cable peculiar smell/smoke/abnormal
noise/flashover.
If these phenomena are caused by poor cable insulation, it is
considered that the withstand test failed; should be clean and
dry handling test materials cable, then testing if determining
test cable caused by air humidity or surface dirt and others.
200
0.20.25
Generator
of Hydropower
300
600
85
125150
300
400
0.180.26
0.310.34
0.69
1.8-1.9
1.72.5
2.02.5
Figure 8
Figure 9
(C) Click Return key, the instrument will enter into voltage
boost standby interface as shown in figure 10.
(3) Standby interface
(B) Click Setting key, the instrument will return to set limit
sub-interface as shown in
figure 7 to re-modify parameter.
(C) Click Check key to check the test data in the last nine
times.
(4) Automatic boost
Click Boost key as shown in Figure 10, the instrument will
enter into boost test under microcomputer control according
to the procedures as follows:
Self checkboostuniform amplitude outputshutdown
(A) Self check
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
(6) Print
Click Print key according to tips as shown in Figure 14,
the user can print the data shown on the display as test report.
On historical data checking status, click Print key, the user
can print the historical data as shown on the screen.
(7) Historical data check
Data displayed on condition of timing shut-down, click key
Stop, overvoltage and overcurrent protective shut-down
will be stored by the instrument as historical data. Data of
last nine times will be stored, and previous data will be
automatically eleminated. Click the Check key as shown in
Figure 10, the user can check the historical data of tests in the
last nine times.
X. Printer Instruction
1.Features
Open Button
SEL (Red Indicator)
LF (Green Indicator)
Figure 16
Panel of Printer
2. Loading paper :
Operation of loading paper for printer is very easy. It is not
necessary to take off the printer from the panel. Open the
front cover simply ,take out the paper just as Fig 17-1 shows
and then load the paper as Fig 17-2 shows, close the front
cover as Fig 17-3 shows.
Notice : Let the paper spread out of the paper exit or else
it can not print.
Before loading the paper, must make sure the thermal coat
of the paper is on the top, then put the paper into the paper
depot. If the thermal coat is not on the top, the printer can
not print out. If the paper has departed from the correct way,
please open front cover again, then adjusting the position of
paper.
Description
Quantity
Control unit
unit
unit
Discharging rod
unit
Capacitor, 0.05F
unit
Test/Connection Cables
set
Earth cable
unit
Fuse
unit
Maunal
unit
Print paper
unit
Calibration report
unit
10