Access Scaffolding Structural Design Criteria
October 1, 2011
Basic Structural Criteria: Saudi Arameo’s Construction Safety Manual (CSM), Chapter II-2,
Section 2.5.1(A).
Dead (D) Loads + 4 x Live (L) Loads < Failure
Failure: defined in CSM.
Materials
Cold-formed steel may exhibit average yield strength in excess of the specified minimum,
Therefore, for scaffolding materials, Strength Increase Factor (SIF) is as follows:
Normal Case SIF = 1.0
Maximum SIF=1.10 (Requires vendor verification by yield strength test data)
Flexural Elements (ie., Runners & Bearers)
Mi (D+4L) Ce:
Fa=0E / (Kl
AISC ASD Eqn. E2-2 wio Safety Factor
Where:
C.= SQRT ((20°E) / (Fy * SIF)
K=10
However, K = 0.85 (min.) may be permitted if justified by system scaffolding mfg. test data
and agreed to by LPD-TSU & CSD-CEU.Access Scaffolding Structural Design Criteria (page 2 of 2)
Wind Loading
For individual scaffolds, the following loading combinations shall also be checked and shalll not exceed
AISC ASD allowable stresses for any scaffold clement
i, Dead Load + Live Load + Wind Load
ii, Dead Load + Wind Load (max. uplift case)
All wind load calculations, including shape factors for round and flat surfaces, shall be in accordance
with ASCE 7 for wind loads on “Other Structures.” An Importance Factor of 1.0 and Di
Factor of 0.95 shall be used. Foree Coefficient, Cf, shall be taken as 1.2 for round cross-s
tubes) and 2.0 for rectangular cross-sections (i.e., tocboards). Exposure Factor is specified in SA\
112 for the location.
Wind Loads for scaffolds shall be determined using a wind speed with a mean recurrence interval (MRI)
of ten (10) years. Per ASCE 7 Commentary, the 10-year MRI wind speed is 0.84 times the 3-second
gust Basic Wind Speed as specified in SAES-A-112 for the appropriate location
Wind forces shall be calculated at various heights for tall scaffolds, including the highest point, to
enable the wind load to be more accurately assessed.
For all types of scaffolds, tributary wind areas shall be increased an additional 5% to allow for fittings,
overlaps, etc.
Wind shielding is not allowed anywhere on the scaffold
6. General Requirements
a)
b
°
¢
°)
8)
h)
All design calculations shall be fully documented as required by SAES-A-204, inclu
analysis results extracted from the computer output,
1 a summary of
Per GI 8.001, the proponent is responsible for ensuring that structures supporting scaffolds are capable
of safely resisting all imposed loads from the scaffold, Therefore, resultant vertical and/or horizontal
reactions imposed on existing structures from Load Combinations (i) and (ji) above, and their locations,
shall be shown on the scaffold drawing(s).
Scaffolds tied to stacks or circular vessels should be tied with at least eight (8) horizontal ties, Total
resultant wind reaction at each level of ties shall be shown on the scaffold drawings.
Couplers shall be checked in accordance with CSM Chapter II-2, Section 2.4.2(0). Couplers shall be
capable of transferring D+L gravity loads with a safety factor of 4 (multiply the rated Safe Working
Loads [SWL] listed in CSM Table 2.1 by 0.4). However, for couplers resisting wind loads in braces,
the rated Safe Working Loads (SWL) listed in CSM Table 2.1 may be used (it’s nor required to multiply
the rated SWL by 0.4 for wind load combinations).
‘The EN 74 standard that will cover girder couplers is still under development. Therefore, girder
couplers marked as conforming to AS 1576.2 are acceptable. Since a safety factor of 4 is required when
girder couplers are supporting gravity loads, the usual downward (Y-axis) Safe Working Load of 30 kN
per pair of girder couplers (based on a safety factor of 2) must be reduced to 5 KN per pair to ensure a
safety factor of 4, The usual SWLs in the other two directions must also be reduced accordingly
‘The most critical posts (standards), bearers (transoms), and runners (ledgers) shall be checked manually
for gravity loads, including manual compilation of all gravity loads.
Ladder beams, including splices, shall be manually checked for the criteria: D+4LFailure. Failure
may be taken as the ladder beam manufacturer's SWL multiplied by the safety factor used by the
manufacturer to obtain their SWL. Ladder beam splice details and locations shall be shown on the
scaffold drawings.
Freestanding scaffolds shall have a safety factor of 1.5 against overturning and 1.2 against sliding,
Gravity loads shall be excluded from wind braces when performing a 3D computer analysis and butt-
tube ties shall be modeled to no! take tension loads.