1 Board Layout
amps2404pcboard.CDR
Slider Switch
SW3
Rotary Switch
SW2
Battery Fuse
F2
5
9 8 7 6
ACCESSORIES
2 4V
GND
485
485
GND
2 4V
5V
1AMP
GND
T B3
24VPANEL
1 2
3
SW2
LED8
24V
1AMP
TB8
CAUTION !
GNDFAULT
TB2
HIGH VOLTAGE
14 15
13
12
11
10
+
TB4
LED9
TB6
GND
5 6
ACCESSORIES
SLCB
+
SLC B
Panel Output
TB2
See Figure 2.9
SLCA
+
Accessories Output
TB6
See Figure 2.11
HOT
10 AMP
NEUT
EARTH
GROUND
EARTH NEUTRAL
F2
HOT
LED10
24VPANEL
JP2
AC
LED1
BCHG
LED2
MON
LED3
TB5
SW 4
TXA
LED7
RXA
TRBL
LED4
SW1
DIP Switch
See Figure 3.1 and
Table 3.1
LED5
FAIL
+
BAT OUT +
BAT IN
IN + B ATT O UT +
BAT IN
BAT OUT
LED6
HI
LO
Charger
Selection Switch
SW4
Snap-on cover
for terminals
SLC A
www.PDF-Zoo.com
Supplement to the AMPS-24 Manual P/N 51907SUP:A
11/03/2003
COM Black
24V Red Wire
24V
GND
485
485
GND
24V
24VPANEL
TB2
www.PDF-Zoo.com
4
TB2*
1
1
[ ]
[ ]
[ ]
N/A
N/A
N/A
N/A
N/A
Calculation Column 1
Primary, Non-Fire Alarm
Current (amps)
Total on:
X [current draw]=
TB2
TB6
x [0.120]=
0.12
0
x [0.220]=
0.22
0
x [0.130]=
0
x [0.100]=
0
x [0.200]=
0
[
[
[
[
]
]
]
]
[
[
[
[
x [0.400]=
x [0.200]=
x [0.110]=
x[
]
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
[ ]
[ ]
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[
[
[
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
[
[
[
[
[
[
[
[
[
[
[
[
[
FZM-1, MMX-2
XPIQ (Refer to Doc. 51013)
RPT-W, RPT-WF, RPT-F
RPT-485W, RPT-485WF
RFX
UDACT Communicator
VEC-25/50
with optional FC-AAM25
Four-Wire Smoke Detectors
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
N/A
N/A
[ ]
[ ]
Quantities
AMPS-24 Terminal Blocks:
CPU-3030
Keyboard/Display Option
LCM-320 (refer to Doc. 51330)
LEM-320 (refer to Doc. 51330)
SLC Loop
NCA (Backlight ON)
NCA (Backlight OFF)
NCM-W, NCM-F
DPI-232
APS-6R
ACPS-2406
ICM-4RK, CRM-4RK
ICE-4
CRE-4
DCM-4RK
VCE-4
VCM-4RK
IZM-8RK
IZE-A
ARM-4 Auxiliary Relay
AA-30
AA-100, AA-120
DHX-501(Duct Detector)
ACM-24AT
ACM-48A
AEM-24AT
AEM-48A
Maximum number of LEDs
illuminated on these
annunciators during non-fire
conditions:
AFM-16AT, AFM-32A
ACM-16AT, ACM-32A
AEM-16AT, AEM-32A
TM-4
SCS-8 (refer to Doc. 15712)
AFM-16A
LCD-80
ACM-8R (refer to Doc. 15342)
LDM (refer to Doc. 15885)
UZC-256
AMG-1, AMG-E, ATG-2
FFT-7, FFT-7S
RM-1
[
[
]
]
TB6
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
x [0.007]=
x [0.001]=
N/A
x [0.008]=
x [0.001]=
x [0.007]=
x [0.047]=
x [0.004]=
0
0
0
0
0
0
0
0
Calculation Column 2
Primary, Fire Alarm
Current (amps)
x [0.400]=
x [0.200]=
x [0.110]=
x[
]=
X [current draw]=
x [0.120]=
x [0.220]=
x [0.130]=
x [0.100]=
x [0.200]=
Total on:
TB2
TB6
0.12
0
0.22
0
0
0
0
Calculation Column 3
Secondary, Non-Fire Alarm
Current (amps)
Total on:
X [current draw]=
TB2
TB6
x [0.120]=
0.12
0
x [0.220]=
0
0
x [0.130]=
0
x [0.100]=
0
x [0.200]=
0
x [0.400]=
x [0.200]=
x [0.110]=
x[
]=
x [0.072]=
x [0.065]=
x [0.065]=
x [0.080]=
x [0.040]=
x [0.040]=
x [0.047]=
x [0.003]=
x [0.146]=
0
0
0
0
0
0
0
0
x [0.025]=
x [0.0013]=
x [0.007]=
x [0.001]=
N/A
x [0.008]=
x [0.001]=
x [0.007]=
x [0.047]=
x [0.004]=
x [0.045]=
x [0.050]=
x [0.025]=
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
x [0.0054]=
x [0.025]=
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
x [0.0054]=
x [0.087]=
x [0.070]=
x [0.070]=
x [0.056]=
x [0.056]=
x [0.040]=
x [0.040]=
x [0.002]=
x [0.110]=
x[
]=
x [0.025]=
x [0.100]=
x[
]=
x[
]=
x [0.035]=
x [0.056]=
x [0.056]=
x [0.018]=
x [0.175]=
x[
]=
x [0.065]=
x [0.100]=
x[
]=
x[
]=
x [0.085]=
x [0.040]=
x [0.040]=
x [0.002]=
x [0.110]=
x[
]=
x [0.025]=
x [0.050]=
x[
]=
x[
]=
x [0.035]=
x [0.060]=
x [0.060]=
x [0.020]=
x [0.0094]=
x[
]=
x [0.017]=
x [0.049]=
x[
]=
x [0.040]=
x [0.215]=
x [0.245]=
x [0.060]=
x [0.120]=
x [0.020]=
x [0.090]=
x[
]=
x [0.017]=
x [0.049]=
x[
]=
x [0.100]=
x [1.215]=
x [2.215]=
x [0.060]=
x [0.060]=
x [0.020]=
x [0.0094]=
x[
]=
x [0.017]=
x [0.049]=
x[
]=
x [0.040]=
x [0.215]=
x [0.245]=
0
0
0
0
x[
]=
x[
]=
x [0.020]=
x[
]=
x[
]=
x [0.020]=
x[
]=
x[
]=
x [0.020]=
x[
x[
x[
x[
x[
x[
]=
]=
]=
]=
Primary,
non-alarm:
Primary,
alarm:
Secondary,
non-alarm:
Primary,
non-alarm:
Primary,
alarm:
Secondary,
non-alarm:
[
[
[
Primary,
non-alarm:
]x [
Primary,
alarm:
0
0
]=
]=
AMPS-24
CHG-120 Battery Charger
Local Energy Municipal Box
0
0
0
0
0
0
0
0
] x [0.052]=
] x [0.060]=
]=
Secondary,
non-alarm:
* Devices powered by the Panel Output (TB2) draw current through the fire panels connection to the power supply.
Value represents an SLCs maximum current draw. Refer to device datasheets for individual current draws. Total device current cannot exceed 200mA.
Current consumption of the DPI-232 is dependent upon the baud rate selection (via slide switch on the DPI-232). See DPI-232 manual for details.
** Refer to manual and/or Device Compatibility Document.
Maximum output: 4.2 A when 5V output (TB6) is used.
3.5 A when 24V output (TB6) is used.
3.2 A when both outputs on TB6 are used.
www.PDF-Zoo.com
Supplement to the AMPS-24 Manual P/N 51907SUP:A
11/03/2003