Académique Documents
Professionnel Documents
Culture Documents
Module 3.20
Testing Requirements in
the Boiler House
3.20.1
Daily:
1. Blow through of the chambers is required, using the sequencing purge valves to remove
any accumulated sludge.
2. Separately, the first and second low alarms are tested.
Weekly:
1. Lower the actual boiler water level to the 1st low (by evaporation), and then blow down to
the 2nd low.
The main reason for this weekly test is to ensure that the alarm is given, and at the correct
level, when the level drops slowly in the boiler (because floats could stick).
2. A high alarm is usually tested weekly.
Position 1 - Normal working
Gauge glass connection
Handwheel
Boiler connection
Drain
Position 2 - Blow through water
Handwheel
Drain
Position 3 - Blow through chamber
Handwheel
Drain
Fig. 3.20.1 Operation of sequencing valves
3.20.2
A daily test is still required, but this means dropping the actual level, unless test facilities are
incorporated. The time involved and the loss of heat, water and treatment chemicals means that
this is only really practical in smaller boilers.
The UK regulations for supervision state that, for standard (for example, non-self-monitoring,
high integrity) controls there must be a trained boiler attendant on site at all times that the boiler
is operating.
In many countries and in all types of industries, there is a need or desire to run steam boiler plant
unattended. This has led to the development of special, high integrity self-monitoring level
alarms, and controls for increased safety in the event of low water conditions.
For externally mounted float controls, automatic sequencing valves are required, plus a control
system which will then carry out automatic sequenced blowdown of the external chambers and
electrical testing of the externally mounted boiler level controls (Figure 3.20.2).
Control box
Chamber connection
Blowdown valve
Boiler connection
Fig. 3.20.2 Automatic sequencing valves and control systems
for externally mounted float type level controls
Direct mounted float type level controls must be fitted with a test device, plus a control system
which will then automatically and electrically test the direct mounted level controls (Figure 3.20.3).
Steam
Signal to start
feedwater pump
Level controls
Flue
Burner
Solenoid valve
Non-return valve
3.20.3
Removable
probe head
Probe body
PTFE insualtion
Comparator tip
Probe connection
PTFE insualtion
The manual weekly test must still be carried out under UK regulations. In Germany, where
approved probe -type high integrity self-monitoring low water alarms are fitted, the interval
between manual tests is 6 months.
Under the UK regulations, if high integrity self-monitoring systems are fitted, supervision
requirements are reduced to the need to have someone available to respond to any alarm and
call for further assistance. An adequately trained security guard or porter could be considered
suitable.
Self-monitoring probes
Protection tubes
Control panel
3.20.4
Summary
When the low water level alarm systems are housed in external chambers they will require
manually blowing down and testing, and this must be carried out at least once per day. In these
cases a trained boiler attendant must be on site whenever the boiler is operating including during
silent hours (nights and weekends).
The trained boiler attendant need not be permanently situated in the boiler house but must be
able to respond immediately to the level alarms.
When high integrity self-monitoring low level alarms are mounted in the boiler shell, since they
are automatically self-testing, they only require a full operational test by a trained boiler attendant
once per week.
When standard low level alarms (floats or probes) are fitted in external chambers, automatic
sequencing valves have to be fitted in order for the alarm system to be deemed self-monitoring.
A trained boiler attendant need not be on site at all times and another person (watchman or
porter) can be put in charge of the boiler instead, as part of his duties during the silent hours.
This person should always be ready to respond correctly to the boiler alarms, shutting down the
boiler if necessary. Thus, depending on the type of installation there are two possible types of
supervision: A trained boiler attendant (or technician), who must be fully conversant with the
operation of the boiler and its controls; or an individual such as a watchman who, although not
a fully trained boiler attendant, must be familiar with the alarm protocol and know the procedure
for shutting down the boiler.
Table 3.20.1 Testing required by UK HSE (Health and Safety Executive)
Standard controls
In external chambers
In shell
High integrity,
self-monitoring controls
Weekly (true) test
Footnote: These basic notes are based on UK boiler house practice, rules, and regulations.
These regulations vary around the world, some examples follow:
Australia
Canada
Italy
Dynamic (float type) low water alarm systems are currently called for by boiler regulations.
A boiler plant engineer must always be present during boiler operation.
Boiler regulations state that the second low water alarm has to be of a mechanical type.
3.20.5
Questions
1. Which weekly tests of level controls should be conducted on a boiler with
external level chambers?
a| Evaporate to 1st low and then blowdown to 2nd low
2.
a| Hydraulic test
b| Electromagnetic test
3.
Which tests are required on high integrity self-monitoring direct mounted level
controls?
a| None
b| Daily functional test by evaporating to 1st low and then blowing down to 2nd low
d| Weekly functional test by evaporating to 1st low and then blowing down to 2nd low
6.
If boiler plant fitted with float level controls in external chambers is to be left unattended
a| The plant cannot be left unattended unless self-monitoring probe controls are fitted
b| There will be no need for daily lowering of the water in each chamber
Answers
1: a, 2: d, 3: d, 4: c, 5: d, 6: d
3.20.6