Vous êtes sur la page 1sur 6

26.06.

2014

maxon motor control:


Focus on a product line
ESCON:
A close look
at some details
2014 maxon motor ag, V1.01

ESCON EC-S: Minimum speed


Minimum speed of sensorless control
Any sensorless control requires a minimum speed to evaluate
the motor speed properly based on the Back-EMF signals.
The minimum speed has to be configured in ESCON Studio.
The motor accelerates to the
configured minimum speed,
if the ESCON EC-S is enabled
and a set value > 50% of the
minimum speed is applied.

26.06.2014

ESCON EC-S: Minimum speed


Minimum speed in practice
Acceleration phase:
Set Value < 50% of configured min. speed:
=> Speed = 0 rpm
Set value equals 50 100% of configured min. speed:
=> Speed = configured min. speed
Set value > Min. speed:
=> Speed = set value
Deceleration phase:
Changeover points are linked to 25%
of configured min. speed.

ESCON EC-S: Minimum speed


Estimation of the "Minimum speed"
Rule of thumb:
Minimum Speed = (Supply Voltage * Speed constant) / 7
Example:
24V supply, EC45-flat 30W (#200189)
Minimum speed = (24V * 374 rpm/V) / 7 = approx. 1200 rpm
Keep in mind:
It is just a rule of thumb!
The actual minimum speed has to be checked by manual tests
and can even 20-50% below the "calculated" result depending on
some influecing factors.

26.06.2014

ESCON EC-S: Minimum speed


Influencing factors of the minimum speed
Supply voltage
Choose the lowest supply voltage, that fulfills the
maximum speed requirements of the application.
(12V supply is better than 24V and 24V is better than 48V)

LR of the motor, i.e. inductance and resistance of the windings


Prefer windings with a low inductance and resistance.
(Take the minimum required inductance into account:
Check chapter "Motor chokes" of EC-S Hardware reference).

Control parameters
Start tests and tuning in "Speed Control (Open Loop)" mode
to evaluate the lowest minimum speed.
(The required minimum speed of "Closed Loop Control" might be higher.)

ESCON EC-S: Manual Tuning (Overview)


If the automatic tuning does not work properly:
Make sure, that all motor parameters are configured properly!
Configure a minimum speed!
(according to the given rule of thumb)
Start tuning with "Speed Controller (Open Loop)"
and try to manually tune this configuration first of all.
Check Knowledge Document "ESCON Module 50/4 EC-S: Settings"
(DOC ID: 400917) for good hints about parameter optimization.
Adapt "Expert" parameter "Commutation Phase Adjustment"
in case of high-inductance motors.

26.06.2014

ESCON EC-S: Manual Tuning

Click
"Show parameters"

Mark
"Manual dimensioning"

Modify
"Startup Current",
"Alignment Time",
"Sync. Startup "
according to the
hints given in the
Knowledge Document
(DOC ID 400917).

ESCON EC-S: Optimization of Startup


Some hints, if the motor already shows problems at startup:
(see also Knowledge Document "ESCON Module 50/4 EC-S: Settings)
Check, if "Minimum speed" is configured.
Typically a good starting point is the
"Min. speed = 1/7 of max. speed" rule of thumb.
It is even possible to decrease this value in 10% increments until the
startup phase is not "smooth" anymore. Increase the "Minimum speed"
then in 20% increments until the startup behaviour is fine again.
"Startup Current"
has to be high enough to overcome the breakaway torque.
Set startup current to the motor's nominal current and increase the
value in 20% increments, if the torque is too low to start the movement
of the motor. If the starting jerk is too high, decrease the value.

26.06.2014

ESCON EC-S: Optimization of Startup


Some hints, if the motor already shows problems at startup:
(see also Knowledge Document "ESCON Module 50/4 EC-S: Settings)
"Alignment Time"
is the time in which the motor moves to the rotor start position and
stabilizes there before the actual start of movement.
Typical values are in the range of 200 1000 ms. Large inertia or low
friction require a longer "Alignment Time".
"Synchronous Startup Acceleration"
depends on the dynamics, load and inertia of the motor.
Typically start with a value of 2000 Hz/s for standard or no load
conditions. Try 500 Hz/s in case of a high inertia.
If the motor stalls during acceleration or overshoots strongly, decrease
the value in 20% increments. If decreasing does not solve the problem,
try to increase the value.

ESCON EC-S: Optimization for high-inductance


If a motor with a high winding inductance and resistance is in use,
the power supply voltage should be reduced as far as possible
taking acount of the required maximum speed.
the "Expert" parameter "Commutation Phase Adjustment"
has to be reduced. The default value is in the range of 20 - 30 and
defines the measuring point of the Back-EMF. If a high inductance
motor is in use, this value can even be reduced to a minimum of 15.
This value can just be accessed,
if the User Level is set to "Expert".
This has to be done by
"File -> Options -> Advanced".

26.06.2014

ESCON EC-S: Parameters for sensorless control

ESCON EC-S: Just Ask!


Please take profit of the Service & Support Desk
and put your request and all your information into an issue:
ESCON *.edc data file !!!!
Motor in use (part number)?
ESCON product type and part number?
Motherboard (or additional chokes) in use?
Supply voltage(s) in use (or available, e.g. 12V, 24V, 48V)?
Type of application (or short description)
Required speed range by the application: Min. and max. speed?
We are pleased to share your experience
and help you to get one step ahead!

Vous aimerez peut-être aussi