FIRE PUMPS
N KS M O RSE P
1.
2.
3.
4.
5.
6.
Pump: Horizontal split case, double-suction, UL Listed, FM Approved, mounted on a common base with and flexibly
coupled to a diesel engine. Pump sized for rated capacity and head. Also must be capable of producing 150% rated flow
at not less than 65% rated head and not to exceed 140% rated head at a shutoff or no-flow condition.
Diesel Engine: UL Listed or FM Approved diesel engine adequately sized so as to not overload at any point on the pump
hydraulic curve. Consideration must be given and de-rates applied based on job site elevation and ambient temperature.
Engines must be specifically designed for fire protection service.
Coupling: Flexible type, sized to transmit the horsepower requirements of the pump. Coupling shall be furnished with an
OSHA-design coupling guard.
Base: Fabricated steel design base capable of adequately supporting the weight of the pump and driver. After pump has
been fully piped and accurately aligned with the engine, the base should be fully grouted into place.
Controller: Diesel engine controller starts the engine automatically on a loss of system pressure. System pressure is
monitored via a sensing line from the system side of the check valve. Controller can also be manually started. Controllers
are UL Listed and FM Approved specifically for fire pump service.
Standard Pump Accessories: Accessories furnished with the fire pump system include: suction and discharge gauges
and automatic air release valve. Other accessories commonly furnished as part of the fire pump package include: hose
valve manifold with hose valves, caps and chains, flowmeter, main relief valve and enclosed waste cone, ball drip valve,
eccentric suction reducer, concentric discharge increaser.
Standard Engine Accessories: Accessories furnished with the diesel engine include: engine starting batteries, battery
rack, battery cables, engine exhaust flexible connector and silencer.
Jockey Pump: Jockey pump keeps pressure in the system to prevent the main fire pump from operating to maintain
system pressure. Jockey pumps are generally a few gallons per minute sized to overcome small system leaks and
typically sized for 10 PSI greater than the rated pressure of the main fire pump. Jockey pumps are not required to be
UL Listed or FM Approved.
Jockey Pump Controller: Starts the jockey pump across the line by sensing the system pressure via a sensing line from
the system side of the check valve. This sensing line must be independent from the main fire pump controller sensing line.
Controller is sized per the jockey pump motor horsepower and voltage. Jockey pump controllers are UL Listed specifically
for this service.
Across-the-line
Wye-Delta
Open-Transition
STARTING
TORQUE
(% LOCKED
ROTOR
TORQUE)
TYPE
TRANSITION
600%
100%
Not applicable
300%
25%
Closed
390%
42%
Closed
200%
33%
Open
200%
33%
Closed
CHARACTERISTICS
Primary
When controller is actuated, a
Resistance
resistance is connected to each
Reduced Voltage phase. Resistors are by-passed after
a time delay and motor then runs at
full voltage.
Part Winding
STARTING
CURRENT
(% MOTOR
FULL LOAD
STARTING
CURRENT)
ADVANTAGES
*
*
*
*
*
*
*
*
*
*
*
Auto
Starters supply reduced voltage
*
Transformer
starting at motor terminals through use *
Reduced Voltage of tapped, 3-phase autotransformer.
*
A timing relay causes transfer of motor
w/50% tap
from reduced voltage start to line voltage *
w/65% tap
operation without disconnecting motor *
from power source.
w/80% tap
Soft Start/Stop
Least expensive
Highest starting torque
Low maintenance
Standard motor used
Smooth starting
Low shock to motor
Standard motor used
RESTRAINTS
Closed
150%
252%
384%
25%
42%
64%
Adjustable
50% - 500%
Varies
Closed
Long established as a leading fire pump manufacturer, Fairbanks Morse Pump offers a broad range of
horizontal split case, vertical in-line and vertical turbine designs over a wide range of rated capacities
and pressurespumps for every fire pump application. Split case and vertical turbine pumps have
the option of being driven via either an electric motor or diesel engine, and are furnished as a
complete package with controller, jockey pump and its controller, as well as standard fire pump system
accessories.
Units are Underwriters Laboratories Listed and Factory Mutual Approved specifically for fire pump
service continually meeting their stringent inspection, testing and record-keeping standards. Split case
rated capacities range from 250 GPM through 5000 GPM, vertical in-line rated capacities range from
50 GPM through 750 GPM, and vertical turbine fire pumps cover 250 GPM through 4500 GPM, all with
a wide range of rated pressures.
The Fairbanks Morse Pump sales family includes highly qualified distributors and representatives well
versed in fire pump systems, who provide prompt and accurate quotations, submittals and acceptance
testing as required. These sales professionals stand ready to address and meet your fire pump needs,
and are backed by many years of factory knowledge and experience.
RATED
HEAD
40 167 PSI
40 278 PSI
40 266 PSI
40 244 PSI
43 236 PSI
40 228 PSI
53 210 PSI
50 213 PSI
60 165 PSI
94 151 PSI
94 223 PSI
90 223 PSI
88 221 PSI
Pump Features:
VERTICAL IN-LINE
RATED
CAPACITY
50 GPM
75 GPM
100 GPM
150 GPM
200 GPM
250 GPM
300 GPM
400 GPM
450 GPM
500 GPM
750 GPM
RATED
HEAD
60 155 PSI
90 135 PSI
40 150 PSI
41 160 PSI
40 160 PSI
40 138 PSI
42 140 PSI
50 205 PSI
49 205 PSI
55 200 PSI
54 143 PSI
Pump Features:
VERTICAL TURBINE
RATED
CAPACITY
250 GPM
500 GPM
750 GPM
1000 GPM
1500 GPM
2000 GPM
2500 GPM
3000 GPM
3500 GPM
4000 GPM
4500 GPM
RATED
HEAD
PSI
100 370 PSI
99 361 PSI
96 316 PSI
98 320 PSI
98 198 PSI
100 187 PSI
100 189 PSI
101 180 PSI
120 189 PSI
120 181 PSI
Pump Features:
Bronze impellers
Cast iron bowl (multi-stage)
Stainless steel bowl shaft
Carbon steel open lineshaft
Steel column pipe
Cast iron or fabricated steel discharge heads
Brass suction strainer
Packed stuffing box
February 2009
1-1
Modbus
The Diesel Plus fire pump controllers
communicate to systems using the Regular
level of Modbus (includes both RTU and ASCII
transmission modes). Communication settings
are user configurable through the Diesel Plus
configuration menu.
Product Description
Field Connections
Inputs
Product Features
Communication
Embedded Web Page
The embedded web pages allow the user to
view the current status of the controller as
well as all amperage readings, set points,
diagnostics and history. An external computer
connected via the Ethernet port is used to
access the pages. The specific data required
can be downloaded for reference purposes.
Communication Types
Canbus
The controller can communicate with the
diesel engine electronic control module
(ECM) and log key engine data via the
Canbus (SAE J1939) engine port.
Standard Inputs
Deluge Valve
Low Suction
Interlock On
Pump Start
Low Fuel
Programmable Outputs
Up to 10 additional, programmable outputs (two
standard; eight via optional output boards) can be
programmed to indicate up to 45 output conditions.
They can be programmed for fail safe and latch
until reset by the user. All optional inputs, outputs
and LED's can be linked, as required. They can
also be programmed with time delay functions. As
well, six optional alarm LED's can be programmed
for up to 28 alarm conditions.
Programmable Inputs
Up to 10 additional, programmable inputs can
be programmed to indicate up to 13 different
types of inputs. They can be programmed to
energize the common alarm output, link to
relays and optional LED's and latch until reset
by the user.
All optional inputs, outputs and LED's can be
linked, as required. They can also be
programmed with time delay functions.
Outputs
Standard Output Relays
All standard output relays are 8 amp, DPDT.
Future # 1
Future # 2
Low Fuel
Auto Mode
Common Alarm
USB
The USB port is used to download the
controller message history, statistics,
diagnostics, status and configuration data to
a USB disk drive. The USB port can also be
used to upload custom messages, additional
languages, and update the microprocessor
firmware.
Power / Voltage
Universal Voltage Supply
The controller can be powered with supply voltages
from 90Vac to 240Vac by connecting to the three
input terminals L,N,G located on the bottom left of
the engine board.
Dual Output
12 or 24Vdc output is selectable via a DIP Switch
located on the battery chargers.
Note: Each controller is factory set for 12Vdc. If
24Vdc is required from the factory, it should be
noted on the ordering information.
Line Filter
A line filter incorporated onto the engine board, is
used to reduce/eliminate external incoming voltage
transients.
AC Power Disconnect
A breaker located inside the controller on the
Engine Board, is used to switch on and off AC
power to the unit. It will illuminate when energized.
DC Power Disconnect
The engine board houses two on-board circuit
breakers used to switch on or off DC power from
the batteries.
Each breaker has an LED mounted on the engine
board that illuminates when the breaker is
energized.
For more information visit: www.chfire.com
BR05805067K
1-2
February 2009
Diagnostics
Up to ten diagnostic points are recorded that
can be used to help in troubleshooting issues
with the controller. The diagnostics can be
viewed on the main display, saved to a USB
disk drive, or viewed on the embedded
webpage.
Message History
LCD Display
The Controller Display Board contains a 4
Line by 40 Characters wide, backlit, LCD
display which is capable of generating
multiple languages. The display will show the
current system pressure, time and date,
charger output voltage and any custom
messages, alarms or timer values.
DC Fail
A visual indication and audible alarm is provided
to indicate DC power loss due to one or both
batteries being disconnected from the controller.
This indication will also be provided if the
controller is not operating due to an electronic
board failure.
Technical Specifications
Supply Voltage: 90-240Vac
Output Voltage: 12-24Vdc
Hertz: 50/60 Hz
Enclosure: Standard NEMA 2
Optional NEMA 3R, 4, 4X, 12
Temperature: 4 to +40 deg. C; 39 to +104 deg. F
Alarm Relays: 24Vdc, DPDT 8amp
Engine Run Relay: 24Vdc, DPDT 10amp
Crank / Fuel Stop Relays: 24Vdc, SPDT
Pressure Transducer: 600psi
Immunity Compliance: Environment A
Emission Compliance: Environment B
Battery Chargers
Mode: Switching
Dual 10 Amp
Diagnostics Recording
Programmable Features
Alarm LED's
The controller is supplied with fourteen (14)
red alarm LED's for the following:
BATTERY #1 FAILURE
CHARGER # 1 FAILURE
BATTERY #2 FAILURE
CHARGER # 2 FAILURE
LOW PRESSURE
SYSTEM OVER PRESSURE
LOW SUCTION PRESSURE
LOW FUEL
FAIL TO START
HIGH ENGINE TEMP
LOW OIL PRESSURE
ENGINE OVER SPEED
ECM SELECTOR IN ALT POSITION
FUEL INJECTION MALFUNCTION
Statistics
Up to 27 of statistical points are recorded to
provide a quick review of how the system
has been operating. The statistics can be
viewed on the main display, saved to a USB
disk drive, or viewed on the embedded
webpage.
BR05805067K
Languages
(English, French, Spanish Standard.
Other languages are available. Consult
factory.)
Stop Mode
AC Failure Alarm
AC Fail to Start
Enclosures
Ratings
All FD120 controllers come standard with
NEMA 2 enclosures unless otherwise ordered.
Available options include: NEMA 3R, 4, 4X, 12.
Reduced Size
A streamlined internal design has allowed the
overall size of the DIESEL Plus controllers to be
reduced from previous models. See
dimensional drawings in this document.
N. Y. C.
APPROVED
February 2009
1-3
Dimensions
Standard Enclosure - Type NEMA 2, 3R, (*4, 4X), 12
19.17 [487]
15.00 [381]
26.72 [679]
7.00 [178]
2.00 [51]
13.11 [333]
34.98 [888]
32.98 [838]
18.00 [457]
10.56 [268]
3.46 [88]
5.31 [135]
1.23 [31]
7.20 [183]
3.85 [98]
1.37 [35]
1.13 [29]
10.29 [261]
3.32 [84]
Approx. Weight
Lbs. (Kg)
NOTES:
1. All enclosures finished in FirePump red.
2. Cable Entrance bottom only.
3. Standard Enclosure type NEMA 2, 12
4. Enclosure made from #14 Gauge (0.75) HR Steel.
5. Feet are removable.
105
(48)
N. Y. C.
APPROVED
BR05805067K
1-4
February 2009
INPUT #10
INPUT #9
INPUT #8
INPUT #7
INPUT #6
INPUT #5
INPUT #4
INPUT #3
INPUT #2
INPUT #1
INTERLOCK ON
LOW FUEL
LOW SUCTION
PUMP START
DELUGE VALVE (1)
REMOTE START
NOTES:
1. DELUGE VALVE INPUT NORMALLY CLOSED.
REMOVE JUMPER IF USED.
2. ALL RELAY CONTACTS ARE SHOWN IN NO POWER
CONDITION.
3. ALARM CONTACTS RATED FOR 8A/250VAC. ENGINE
RUN CONTACTS RATED 10A/250VAC.
CUSTOMER INPUTS
OPTION RELAY #1
(2 SETS FORM-C)
ENGINE RUN
OPTION RELAY #2
(2 SETS FORM-C)
ENGINE RUN
FUTURE #1
OPTION RELAY #3
(2 SETS FORM-C)
FUTURE #1
OPTION RELAY #4
(2 SETS FORM-C)
ALARM CONTACTS
FUTURE #2
FUTURE #2
LOW FUEL
LOW FUEL
OPTION RELAY #5
(2 SETS FORM-C)
OPTION RELAY #6
(2 SETS FORM-C)
OPTION RELAY #7
AUTO MODE
(2 SETS FORM-C)
AUTO MODE
OPTION RELAY #8
(2 SETS FORM-C)
COMMON ALARM
(NORMALLY ENERGIZED)
COMMON ALARM
(NORMALLY ENERGIZED)
90-240VAC
POWER
BATTERY #1 INPUT(+)
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
BATTERY #2 CRANK
BATTERIES (-)
BATTERIES (-)
ENGINE CONNECTIONS
FUEL SOLENOID
ECM IN ALTERNATE
FUEL INJECTOR FAIL
N. Y. C.
APPROVED
BR05805067K
February 2009
Field Connections
Inputs
Outputs
ENGINE RUN
LOW FUEL
ENGINE RUN
LOW FUEL
FUTURE #1
AUTO MODE
FUTURE #1
AUTO MODE
FUTURE #2
COMMON ALARM
(NORMALLY ENERGIZED)
FUTURE #2
COMMON ALARM
(NORMALLY ENERGIZED)
Terminal Number
Distance
I/O Board
Stranded # 14
(1.63 mm)
N. A.
Stranded # 14
(1.63 mm)
N. A.
N. A.
Engine Board
Stranded # 14
(1.63 mm)
Battery Wire
Stranded # 10
Stranded # 8
BR05805067K
(2.59 mm)
(3.26 mm)
6, 8, 11
6, 8, 11
1-5
MODELS
JX6H-UFADFO
JX6H-UFAD60
JX6H-UFADK0
JX6H-UFADN0
JX6H-UFADP0
JX6H-UFAD88
FM-UL-CUL APPROVED
RATINGS BHP/KW
JX6H
RATED SPEED
1760
2100
MODEL
UFADF0
460
343 488
364
UFAD60
510
380 525
392
UFADK0
517
385.5 526
392
UFADN0
542
404 575
429
UFADP0
575
429 600
447
UFAD88
617
460
SPECIFICATIONS
ITEM
UFADF0
JX6H MODELS
UFADK0
UFADN0
UFAD60
Number of Cylinders
UFAD88
Aspiration
TRWA
Rotation*
Clockwise (CW)
Weight - lb (kg)
3315 (1500)
Compression Ratio
16.0:1
824 (13.5)
Engine Type
Installation Drawing
D - 626
Wiring Diagram AC
Wiring Diagram DC
Engine Series
Speed Interpolation
UFADP0
Optional
N/A
Abbreviations: CW - Clockwise NA - Naturally Aspirated T - Turbocharged TRWA - Turbocharged Raw Water Aftercooled.
*Rotation viewed from Heat Exchanger/Front of engine Engine intended for indoor use or inside weatherproof enclosure only
Note: Engines are not to be used for continuous duty. Engines are to be used
only for stationary emergency standby fire pump service. According to NFPA 25
engines are to be tested 30 minutes per week at no pump flow and full pump flow
once per year.
MODELS
JX6H-UFADFO
JX6H-UFAD60
JX6H-UFADK0
JX6H-UFADN0
JX6H-UFADP0
JX6H-UFAD88
ENGINE EQUIPMENT
EQUIPMENT
STANDARD
OPTIONAL
Air Cleaner
Alternator
Exhaust Protection
Coupling
Bare Flywheel
Flywheel Housing
S.A.E. #2
Fuel Connections
Fuel Filter
Unit Injector
Engine Heater
Governor, Speed
Heat Exchanger
Instrument Panel
Overspeed Control
Run-Stop Control
Starters
Throttle Control
Junction Box
Water Pump
Non Listed Drive Shaft & Guard, JX6H-UFADF0 SC2140, UFAD60/K0/N0/P0 -SC2155, UFAD88 - SC2160
SS Flex, 150# Flange, 10
Note: Engine Controller needs 2 additional signals: Injector Failure, Alternate ECM Selected
* JX6H-UFADF0/60/K0/N0/P0/88 All provided with orifice plate mounted in flex exhaust.
JX 6 H - U FA D F 0
UK, Ltd.
Grange Works, Lomond Rd., Coatbridge, ML5-2NN
United Kingdom
Tel +44-1236-429946 Fax +44-1236-427274
www.clarkefire.com
Specifications and information contained in this brochure subject to change without notice.
Printed in U.S.A.
580
575
(429)
570
560
550
542
(404)
540
1700
1800
RESTRICTED:
1900
2000
ENGINE SPEED - RPM
2100
2200
ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77F (25C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
CREATED
DATE CREATED
08/14/08
C132690
REV
CLARKE
Fire Protection Products
JX6H-UFADN0
INSTALLATION & OPERATION DATA
Basic Engine Description
Engine Manufacturer...........John Deere Co.
Ignition Type..............
Compression (Diesel)
Number of Cylinders............6
Bore and Stroke - in.(mm)...........
5.20 (132) x 6.50 (165)
Displacement - cu.in.(L)............
824 (13.5)
Compression Ratio............ 16.0:1
Valves per cylinder - Intake...........
2
Exhaust...........2
Combustion System............Unit Injection
Engine Type.............In-Line, 4 Stroke Cycle
Aspiration.............Turbocharged
Firing Order (CW Rotation)...........1-5-3-6-2-4
Charge Air Cooling Type.......... Raw Water Cooled
Rotation (Viewed from Front) - Clockwise........
Standard
Counter-Clockwise...... Not Available
Engine Crankcase Vent System.......... Open
Installation Drawing........... D-626
Weight - lb (kg)............3315 (1500)
Cooling System
1760
Engine H2O Heat -Btu/sec.(kW)..........200 (211)
Engine Radiated Heat - Btu/sec.(kW)..... 123 (129)
Heat Exchanger Minimium Flow
60F (15C) Raw H2O - gal/min. (L/min.)...... 40(151)
95F (35C) Raw H2O - gal/min. (L/min.)......
60(227)
2100
212 (224)
130 (137)
40(151)
60(227)
CLARKE
Fire Protection Products
JX6H-UFADN0
INSTALLATION & OPERATION DATA (Continued)
Exhaust System
1760
Exhaust Flow - ft.3/min. (m3/min.)......... 2725 (77)
Exhaust Temperature - F (C).......... 843 (451)
Maximum Allowable Back Pressure - in. H20 (kPa).... 40 (10)
Minimum Exhaust Pipe Dia. - in. (mm)**........ 8 (203.2)
2100
2955 (84)
908 (486)
40 (10)
Fuel System
Fuel Consumption - gal./hr. (L/hr.)........ 25.6 (96.6) 29.2 (110.3)
Fuel Return - gal./hr. (L/hr.).........
Total Supply Fuel Flow - gal./hr. (L/hr.).........
Fuel Pressure - lb./in.2 (kPa)...........70-90 (483-620)
Minimum Line Size - Supply - (in.)...... .75 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... 1.05 (0.41)
Minimum Line Size - Return - (in.)........ .50 Schedule 40 Steel Pipe
Pipe Outer Diameter in. (mm).......... .848 (.033)
Maximum Allowable Fuel Pump Suction
With Clean Filter - in. H20 (mH20)......... 40 (1.02)
11.7 (3.6)
Maximum Allowable Fuel Head above Fuel pump, Supply or Retrun - ft.(m).....
Fuel Filter Micron Size........... 2 (Secondary)
Heater System
Jacket Water Heater............ Standard
Wattage (Nominal).............2500
230 (+5%, -10%)
Voltage - AC, 1P.............
Optional Voltage - AC, 1P.......... 115 (+5%, -10%)
Lube Oil Heater Wattage
(Required Option When Ambient is Below 40F (4C) 150
Induction Air System
Air Cleaner Type...........Indoors Service Only - Washable
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in. H20 (kPa).......... 25 (6.25)
Clean Air Cleaner - in. H20 (kPa)........
3
15 (3.75)
Engine Air Flow - ft. /min. (m /min.)......... 1122.9 (31.8) 1160.3 (32.9)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)***... 130 (54)
Lubrication System
Oil Pressure - normal - lb./in.2 (kPa)........ 42 (287)
In Pan Oil Temperature - F (C).......... 239 (115)
Total Oil Capacity with Filter - qt. (L)....... 44 (41.5)
Oil Capacity - High - qt. (L)..
42 (40)
- Low - qt. (L)
40 (38)
45 (310)
Performance
BMEP - lb./in.2 (kPa)........... 296(2040)
263 (1813)
Piston Speed - ft./min. (m/min.)........ 1907 (581)
2275 (693)
Mechanical Noise - dB(A) @ 1M.
Consult Clarke
Power Curve............
C132690
** Based On Nominal System. Flow Analysis Must Be Done To Assure Adherance To System Limitations.
(Minimum Exhaust pipe Diameter is based on 15 feet of pipe, one elbow, and a silencer
pressure drop no greter than one half the max. allowable back pressure.)
*** Review For Power Deration If Air Entering Engine Exceeds 77F (25C)
C132903 revB
DSP 08JUL09
CLARKE
Fire Protection Products
Cylinder Liners
Type.. Centrifugal Cast, Wet Liner
Material... Alloy Iron Plateau, Honed
Valves
Type.. Poppet
Material... Steel Alloy
Arrangement Overhead Valve
Number/Cylinder
2 intake
2 exhaust
Operating MechanismMechanical Rocker Arm
Type of Lifter.. Solid Roller
Valve Seat Insert Replaceable
Exhaust Manifold
MaterialIron Alloy
Fuel Pump
TypeGear
DriveCam Lobe
Heat Exchanger
TypeTube & Shell
Materials
Tube& Headers90/10 CU/NI
ShellCopper
ElectrodeZinc
Coolant Pump
Type.Centrifugal
Drive Gear
Injection Pump
Type.. Electronic Unit Injector
DriveCam Shaft
Coolant Thermostat
TypeFull Blocking
Qty2-12.5L / 3-13.5L
Lubrication Cooler
TypePlate
Connecting Rod
TypeI-Beam Taper
MaterialForged Steel Alloy
Crank Pin Bearings
TypePrecision Half Shell
Number1 Pair Per Cylinder
MaterialWear-Guard
Crankshaft
MaterialForged Steel
Type of BalanceDynamic
Cylinder Block
TypeOne Piece with
Non-Siamese Cylinders
MaterialCast Iron Alloy
Cylinder Head
Type.. Slab 4 Valve
Material. Cast Iron
C132893 rev C
Lubrication Pump
TypeG rotor
DriveGear
Main Bearings
TypePrecision Half Shells
Material Steel Backed-Aluminum Lined
Piston
Type and Material12.5L - 2 piece- Steel Crown, Al. skirt
13.5L Steel- Monolithic
Oil Jet Spray
Cooling
Piston Pin
TypeFull Floating - Offset
Piston Rings
Number/Piston 3
Top Keystone Barrel Faced Plasma Coated
Second
Tapered Cast Iron
ThirdChromium Faced