3.4.2 All such deviations shall be clearly mentioned on the Deviation sheet,
with reference to the respective clause of the specification.
3.5 DRAWING APPROVAL
Before starting manufacture of any equipment, the contractor shall have to take
approval of relevant drawings and data from purchaser in writing.
3.6 RECORD OF PAST EXPERIENCE
3.6.1 The Bidder shall submit along with his bid a list of major contracts of
supply and erection of similar equipment already executed or under execution,
giving detailed particulars such as equipment rating, contract value, name of
the owner, year of commissioning etc.
3.7 QUALITY ASSURANCE
3.7.1 Contractor shall follow his standard procedures for quality assurance and
control. The procedures shall be in such a form as to clearly delineate the
manufacturing sequence & major inspection point.
3.7.2 Manufacturing and quality control procedures shall be available for audit
to the Owner and/or its representative at the place of manufacture.
4.0 SITE CONDITIONS
4.2 The site is also connected to National Highway by an all weather metal road.
4.3 Equipment shall be packaged for transportation so as to meet the space and
weight limitation of transport facilities, especially along the railroad rightof-way.
4.4 For the purpose of equipment design, the following data shall be taken into
consideration:
a) Average Grade
:
173 M above MSL
b) Ambient Air Temperature (mean)
:
31.6oC(max.), 18.9oC(min.)
c) Relative Humidity
:
69% Maximum
d) Wind Velocity
:
162 Km/Hr
e) Isoceraunic Level
:
29.4
f) Seismic Zone
:
Zone-III
5.7
MECHANICAL DATA
Pressure of SF6 gas
Temperature Class
Degree of Protection
:
SF6 Tank
Fuse Canisters
Front Cover
Cable Cover
:
Busbars
Earth Bar (external)
Thickness of Stainless Steel Tank
1.4 bar at 20 0C
(-) 25 0 C indoor
:
:
:
:
:
:
5.8
ELECTRICAL DATA
Rated Voltage
:
Rated Current for busbars
Rated Current for Cable switch disconnector
Short time with stand current (3 sec)
Rated Current for transformer T-off
:
Impulse withstand voltage
(To earth and between phases)
Insulation Level
:
(Power frequency 1 min.)
IP67
:
IP67
IP2X
IP3X
240 mm2
Cu
120mm2
3.0 mm
:
:
:
:
12 kV
630 A
Cu
630 A
630 A
21 kA RMS
95 kV
28kV
6.2
APPLICABLE STANDARDS
Metal Enclosed Switchgear
General Purpose Switches
Disconnectors and Earthing Switches
Circuit Breakers
:
Common Clauses
:
Cable Bushings
:
:
:
:
IEC 60298
IEC 60265
IEC 60129
IEC 60056
IEC 60694
DIN 47636
6.3
CABLE SWITCH MODULE
Each Cable Switch Module with a three position load break switch and earthing
switch, busbars, interlocking and earthbar shall have a minimum of following:
(i)
Cable switch 12Kv, 630 A, 21 kA for 3 sec.
(ii) Snap action mech. for manual operation
(iii) Cable bushings, 630 A suitable for 11KV, XLPE, Aluminium cable of size
3Cx300 Sq. mm.
(iv) Arc proof cable cover including Interlocking
(v) Capacitive voltage indication (fixed type)
6.4
VACUUM CIRCUIT BREAKER MODULE
Vacuum circuit Breaker module with vacuum circuit breaker, three-position
isolator/ earthing switch, busbars, interlocking, earthbar and stored spring
energy mechanism shall have following:
(i) Vacuum circuit breaker 12kV, 630A, 21kA for 3 sec.
(ii) Stored energy mechanism for manual operation
(iii) Protection relay for Over Current & Earth Fault of Transformer
(iv) Ring Core current transformer suitable for 250KVA Distribution Transformer
(v) Cable bushings, 630 A suitable for 11KV, XLPE, Aluminium cable of size
3Cx300 Sq. mm.
(vi) Arc proof cable cover including Interlocking
(vii) Capacitive voltage indication (fixed type)
6.5
CABLE TERMINATION
6.5.1 The Ring Main Unit Modules shall be designed for cable entry from the
bottom. Sufficient space shall be provided for ease of termination and
connection.
6.5.2 Power Cable shall be XLPE insulated, 11kV grade, armoured, overall PVC
sheathed with stranded Aluminum conductor of size not less than 3Cx300 Sq. mm.
6.5.3 All provision and accessories shall be furnished for termination and
connection of cables, including removable gland plates, cable supports etc.
6.5.4 The gland plates shall be minimum 4 mm thick. The gland plate and
supporting arrangement for I/C Power cables shall be such as to minimize flow of
eddy current.
6.6 GROUND BUS
A ground bus rated to carry maximum fault current shall extend full length of
the switchgear.
6.7 NAMEPLATES
6.7.1 Nameplates of approved design shall be furnished at each module and at
each instruments and device mounted on or inside the RMU.
6.7.2 The material shall be lamicoid or approved equal, 3 mm thick with white
letter on black background.
6.10 TROPICAL PROTECTION & PAINTING
6.10.1 All equipments, accessories and wiring shall have fungus protection,
involving special treatment of insulation and metal against fungus, insects &
corrosion.
6.10.2 Screens of corrosion resistant material shall be furnished on all
ventilating louvers to prevent the entrance of insects.
6.10.3 All surfaces shall be sand blasted, pickled and grounded as required to
produce a smooth, clean surface free of scale, grease and rust.
7.0 TESTS
7.1
The Ring Main Unit shall be completely assembled, wired, adjusted and
tested at the factory as per the relevant standards.
7.2
Routine Test
The tests shall include but not necessarily limited to the following:
ANNEXURE-I
TECHNICAL SPECIFICATIONS OF SF6 INSULATED RING MAIN UNIT
1.0 CABLE SWITCH MODULE
1.1 It shall consist of an SF6 cubicle housing a switch disconnector and an
earthing switch. The switch disconnector, earthing switch shall be interlocked
to each other for safety of the operator.
1.2 Busbars and all electrical connections shall be located inside the tank. The
operating shafts for switches shall have rotary seals where they enter the SF6
cubicle. The operating mechanism shall be located outside on the front of the
SF6 tank.
1.3 Cable bushings shall be located on the front of the SF6 cubicle in a
separate cable compartment. Front covers containing the mimic diagram and having
a degree of protection IP2X close the fronts.
1.4 The switch disconnector and earthing switch shall have padlocking facility
from maintenance point of view.
2.0 CIRCUIT BREAKER MODULE (630 A)
2.1
The circuit breaker module shall consist of an SF6 cubicle housing a
circuit breaker unit and a disconnector-earthing switch. For isolation of the
circuit breaker and safety of the operator, a disconnector switch shall be
provided in line with the breaker.
2.2
The Vacuum breaker, disconnector switch, earthing switch and its cable
covers shall be operated in the sequence and interlocked with each other. It
shall not be possible to open the cable cover when earthing switch is not in
earth position. Similarly the earthing switch shall not be closed when the
disconnector switch is in ON position. The circuit breaker shall be closed only
when the disconnector switch is in ON position.
2.4 Busbars and all electrical connections shall be located inside the tank. The
operating shaft for the switches shall have rotary seals where they enter the
SF6 cubicle. The operating mechanisms shall be located outside on the front of
the SF6 tank. Cable bushings shall be located on the front of the SF6 cubicle in
a separate cable compartment. Front covers containing the mimic diagram and
having a degree of protection IP2XC seal off the fronts.
2.5 An integrated relay and related CTs are used for tripping of the circuit
breaker.
2.6 The switch disconnector and earthing switch shall have padlocking facility
from maintenance point of view.
2.7 Circuit Breakers shall use vacuum bottles as interrupters of the currents.
The circuit breaker main circuit should be connected in series with a
disconnector switch for isolation purpose.
5.0
EARTHING SWITCH
Earthing switches shall be rated equal to the switchgear rating. Earthing
switches shall be quick make type capable of making full Rated Fault Current.
Earthing switch shall be operated from the front of the cubicle by means of a
removable handle. The earthing Switch shall be interlocked with the isolator and
cable cover for the safety of the operator.
6.0
BUSBARS
Comprising the 3 single phases copper busbars and the connections to the switch
or circuit breaker. The busbar shall be integrated in the cubicle. Busbars shall
be rated to withstand all dynamic and thermal stresses for the full length of
the switchgear. The busbars shall be inside the SF6 gas chamber made of 3-mm
stainless steel sheet.
7.0
CABLE COMPARTMENT
It shall be possible to terminate 11kV, armoured, aluminium conductor, 3Cx300
sq. mm. HV cables.
The access to the compartment shall be possible by removing the arc proof cable
cover, bolted to the main frame.
Each module shall have a separate cable compartment that is segregated from each
other by means of a partition wall. A partition wall shall be fitted to divide
the cable compartment from the rear side of the switchgear. In case of an arc
inside the tank, followed by the opening of the pressure relief, the partition
wall prevents the hot gases flowing out from the pressure relief to enter the
cable compartments.
The ground continuity shall be achieved when the covers are in place by means of
bolted connections.
The cable covers shall be interlocked to the corresponding earthing switch of
the module.
8.0 ACCESSORIES:
All the required accessories in the each module shall be provided.
Accessories are list as below:
(i) Cable Support Bars
(ii) Short Circuit Indicator
(iii) Cable boots
(iv) Manometer for SF6 pressure/density monitoring
(v) Emergency trip push button
(vi) Lifting Lugs
(vii) Aux. Switch for circuit breaker Position
(viii) Aux. Switch for disconnector position
(ix) Aux. Switch for Earth switch position
ANNEXURE - II
RATINGS AND REQUIREMENTS
1.0
RING MAIN UNIT SWITCHGEAR 11KV
1.1 General
Type
:
SF6 Insulated Ring Main Units
Service
, Enclosure
:
Out door, IP-52
1.2 System
Voltage
:
11kv 10%
Phase, Frequency
:
3, 50 Hz 5%
System ground
:
Non-effectively earthed through
resistance
1.3 Rated Current
Cable Switch Module
:
630 Amp
Vacuum Circuit Breaker Module :
630 Amp
1.4 Short Circuit Rating (for 3 Sec.)
Cable Switch Module
:
21 KA for 3 sec.
Vacuum Circuit Breaker Module :
21 KA for 3 sec.
1.5
Insulation Level
95/28 kV (peak/r.m.s.)
1.8
1.9
Breaking Current
Making Current
:
:
To be indicated at 11KV
To be indicated at 11KV
ANNEXURE-III
SF6 RMU HAVING 1 NO. CABLE SWITCH & 1 NO. VCB MODULE