Académique Documents
Professionnel Documents
Culture Documents
DIGITAL DC DRIVE
1.0 Introduction to system
Two (02) numbers 8kW rating DC motor is used for main travel of
reclaimer. Both motors accurate speed control is required for efficient
operation of reclaimer.
Motor Name plate details DC SHUNT MOTOR, KW-8 , ARMATURE
VOLTAGE- 440V DC, ARMATURE CURRENT-22AMP. BASE SPEED1500RPM,
SPEED
VARIATION-150/1500/1500,
EXCITATIONSEPARETELY SHUNT WOUND, EXCITATION VOLTAGE- 220V DC,
INSULATION CL-F, PERMISSIBLE OVER SPEED 1800RPM, IP55,
RATING-CMR,
2.0 Scope of work
Supply of required hardware (DC drive Panel) & software, Installation,
testing & commissioning of complete system, the drive panel should
houses all the required accessories & ready to terminate DC motor power
cable, aux relays, power contactor, digital display panel for current
voltage etc, bottom entry gland plate with suitable openings, On site
training for operation of above system to PURCHASER staff. Vendor
should get the drawing approval for proposed drive and power
distribution SLD for panel before supplying the material.
3.0 Commissioning --Vendor shall be handed over the existing DC motor control panel in
working condition. Vendor shall replace the new DIGITAL DC DRIVE
PANEL in place of existing DC control panel. After replacing new DC drive
panel vendor shall show the normal operation, control etc. of the
reclaimer main travel.
Any other item required for making the system work except those covered
in the order shall be the responsibility of the vendor unless until it is
specifically informed at the time of submission of the bid.
4.0 Job Completion Time
Four (07) days from handing over of the site. Exact date shall be
communicated later on.
5.0 Documentation
Six (06) hard copies of technical manual of DIGITAL DC DRIVE to be
submitted .
6.0 Warrantee 12 months from the date of commissioning.
7.0 Exclusions
The following items are excluded from scope of vendor
1.
Power cable for incoming supply
2.
Digging & reinforcement of cable trenches.
3.
Laying of control cables, terminations etc.
S.
Description
NO
PURCHASER Requirement
Offered
B
y
T
e
n
d
e
r
e
r
1.
2.
NAME
OF
EQUIPMENT
3.
4.
INPUT FREQUENCY
OUT
PUT
VOLTAGE
-ARMATURE
5.
OUT
PUT
VOLTAGE
-FIELD
6.
RATING
OF
DRIVEsuitable for 2x8kW DC
motor
7.
Model
no.
&
type
Offered
8.
OUTPUT
CURRENT
RANGE 0 to 100%
continuous,
-150%
overload for 25sec.
9.
CONTROL
CIRCUITSFully
isolated
from
power circuit
10. CONTROL
ACTIONFully digital, Advanced
PI with fully adaptive
current
loops
for
optimum
dynamic
performance.
Self
tuning
current loop
utilizing
Autotune
algorithm.
11. SPEED CONTROL- By
armature
voltage
/
Tacho / encoder or a
combination of encoder
feedback and analogue
tachogenerator.
Speed
range 100:1 typical with
tachogenerator
feedback.
50 +/- 5 % Hz
440VDC
220VDC
To be specified by the party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
12. STEADY
STATE
ACCURACY
1. with analog tacho To be specified by the party
feed back.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
Over
current
Instantaneous
Protection Features For
Field Failure
Protection Features For
Motor
Over
Temperature
Protection Features For
Thyristor
Trigger
Failure
Protection
against
stalling
during
the
normal running of the
equipment.
Protection
against
stalling
during
the
starting
of
the
equipment.
Protection Features For
tacho
failure
(AVF
backup)
Protection Features For
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
30. Specify
protection To be specified by the party
features provided for
Over load protection of
Motor
31. The following features To be specified by the party
are required1.field
weakening
sensing
2.Motorised
Pot
simulator
3.Connection
conflict
checker
36. Ambient
Temperature
for drive panel.
37. Safe
continuos
operating temperature of
the drive at full load.
38. Does the facility for the
remote operation exists
39. Kind of fault diagnostic
methods being offered.
40. Provision
for
drive
ON/OFF
from remote
control room
41. Provision
for
drive
ON/OFF/
REACCELERATION
from PLC
42. Panel
shall
have
independent alarm /
fault annunciation on
LCD Display window at
50
To be confirmed by the
party
Required
To be specified by the party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
To be confirmed by the
party
PURCHASER staff
programming
Operation.
for
&