DC Inverter VRF Air Conditioning Systems

VRF

C A T A L O G U E

2 0 1 2

YOUR CONDITIONS!
Since 1916,

pioneers in the US market, by designing and manufacturing innovative air conditioning and

heat pump units. The companys primary competitive advantage is the use of its know-how expertise gained in the past,
to build air conditioning systems of the future.
The key to

units' success is that they are specifically designed to enable the modern individual invent his

own custom made living and working conditions. Regulating effectively the natural environment,
units can create silently the perfect indoor conditions; your conditions!

All
units carry a
2-year Warranty for the compressor and for all parts of the unit.

units can be found all across Europe in a


continuously growing selected network of air conditioning
professionals!
Their excellent quality and operational efficiency has been
awarded by the European Union with the highest standard
certificates.
Furthermore, the use of the environmental friendly refrigerants
(freon) do not contribute to the increase of the global warming
environment.

index
INV
Features

Pages

Higher Efficiency
Better Comfort
Higher Reliability
Better Versatility
Easy Installation & Maintenance
INV Mini

4-5
6-7
8-9
10-11
12-13
14-15

Outdoor Units

Pages

Line up
Specifications

16-17
18-21

Indoor Units

Pages

Line up
Duct Type
Slim Duct Type
Four-way Cassette Type
One-way Cassette Type
Floor Standing Type
Wall Mounted Type
Floor Ceiling Type
Concole Type
Treated Fresh Air Duct Type

22-23
24-27
28-29
30-33
34
35
36-37
38-40
41
42-43

Control System

Pages

Control Network Sketch


Controllers Comparison
Comments of Control Functions
Wired Remote Controller
Wireless Remote Controller
Group Controller
Smart Zone Controller
Centralized Controller
IR Receiver & Key-card Control Board
Communication Module
Commissioning Program
RS-422/485 Repeater
RS-232 to RS-422/485 Converter
INVENTOR Eudemon 2009 PC SUIT
Piping Design Program

44-45
46
47
48-49
50-51
52
53
54
55
56
57
58
59
60-61
62-63

Energy Recovery Ventilation


Connection Branches

64-66
67
3

HIGHER EFFICIENCY
) Significantly improved EER/COP
Significantly greater efficiency is realized by the use of DC Inverter
Hermetic Scroll Compressors with high-pressure chamber
design, improved DC inverter driving technology and large heat
exchanger.

27%

18%

increase of EER

increase of COP
4.37

4.07
4.0

4.0
3.7

3.5

3.5
3.2

3.0

3.0

2.5

2.5

Former
model

INV

Former
model

INV

Heat Exchanger

Fan Motor

EER is the efficiency rate= cooling capacity (kW) cooling power input (kW)
COP is the coefficient of performance = heating capacity (kW) heating power input.

Compressor

EER/COP values are based on INVENTOR laboratory testing method


The data refers to a 8HP outdoor unit

) High efficiency compressor


High pressure chamber design
Whats high pressure chamber?
The compressed gas that is discharged from the fix scroll, fulfills the whole hermetic chamber of the compressor.
Then, when the whole compressor shell has high temperature and there is high pressure inside the compressor, the gas goes
out from the exhaust.
Whats the Benefit of High Pressure Chamber?
Direct suction in high pressure chamber compressor. No loss from overheat suction. Increased compressor efficiency
up to 3-5%.
Suction
High
Pressure
Fixed
Scroll

Orbiting
Scroll

Discharge

Intermediate
Pressure
Low
Pressure
Intermediate
Pressure
Chamber
Motor in
high Pressure

HP chamber
structure can
raise the high
and middle
frequency
performance
New DC motor
(concentrated winding)
raises the low frequency
performance

) DC Fan motor

Air flow volume

Compared with the former model, airflow volume is increased 3% with the same single fan and 7% with the new
dual fan, but the power consumption is decreased by 5% with the DC inverter motor.
8HP/10HP Models

INV

Former model

3%
Former
model

INV

Air flow volume

12HP/14HP Models

Former model

INV

7%
Former
model

INV

) Heat Exchanger
The bigger condenser increases
the heat-exchange area, improving
the efficiency.

Compared with the normal fin,


the heat exchange efficiency of the
louver is increased by 5%.

Former model:
2098x38.1x1156

Former model:
Normal flat fin

INV:

INV:

2248x38.1x1190

Louver fin with


golden coated

Comparing with normal compressor, the DC Inverter


Scroll compressor can save up to 40% of energy
consumption in a year.

Special thickened inner groove


copper tube enhances heat
exchanging performance.

With stepless power regulating technology, the DC


inverter compressor achieves stepless output regulation
between 20Hz-120Hz

Improved DC inverter motor


Low frequency performance is highly raised thanks to the concentrated winding.

Compressor efficiency

Distributed winding

Concentrated winding

7%
0

20

Rotating speed (/rps)

BETTER COMFORT
) Quiet Operation
Quiet operation during night time
The Intelligent adjustment of the outdoor
fan control can minimize the operation
noise during night time.
It can be reduced up to 8dB(A).
So the operating noise at night is lower,
at 50dB(A).

58dB(A)

Capacity Operating
sound

50dB(A)

Capacity Operating
sound

Heat load

Low noise design


OUTDOOR UNIT
HP chamber compressor has lower exhaust
pressure fluctuation, so the noise is lower.

The optimized design of the condensing fan blade reduces


the air flow turbulence among blades. So, the noise is lower.

Quiet compressor

Average
2dB(A) down

Optimized

Original design

INDOOR UNIT

New design with


higher performance
&lower noise
4dB(A) less!

Low noise indoor unit

37dB(A)
Office
Duct Type with High ESP

37dB(A)
Hotel
Slim Duct Type

37dB(A)
Reception
Four-way Cassette Type

28dB(A)
Bedroom
Wall Mounted Type

) Comfortable
Temperature

fluctuation of

the room

Less Cool

Uncomfortable
Comfortable

Cooler

Uncomfortable

INV

Defrosting

Heating

Defrosting

Heat Loss

Intelligent defrost technology


Traditional defrost program
Simply executes defrosting according to a
certain time.
The defrost function may still start even if there
is no such (defrosting) demand.

Non VRF

Heating Capacity

Precise temperature control


The EXV (Electronic Expansion Valve) of each
Indoor unit responds to the loading changes of
indoor environment, so it continually adjusts the
flow rate of refrigerant.
Meanwhile, the outdoor unit with DC inverter
compressor provides the capacity with certain
amount of refrigerant exactly according to the total
demands of the indoor units.
With this Variable Refrigerant Flow (VRF) technology, we can quickly get a nearly constant room
temperature. The typical temperature fluctuation
that occurs with a conventional ON/OFF control
system is eliminated.

Time
10mins

50mins

10mins

50mins

10mins

Defrosting

Heating Capacity

Intelligent defrost program


Humanized technology which considers the maximization of energy saving.
Defrosting program that is designed under the
consideration of heating efficiency and operation
reliability.
Precise defrosting timing, which is intelligent
indeed.
Its an optimized defrosting program, which will
be performed only when the systems pressure
is too low. This can obviously lengthen the time
gap between two defrost operations and reduce
the times of defrosting.
Heating capacity loss has been decreased by
75% with highly comfortable heating operation.

Heating

Time
Defrosting starts if the unit detects frost

Defrosting stops
after completion

Individual control
The set temperature of each room may vary by the individual thermostat control of each indoor unit.

OFF
260C
220C

200C
240C

270C

HIGHER RELIABILITY
) Modular operating
The operating priority sequence of the outdoor unit
modules will be changed without restart when the
system accumulatively operates for 12 hours. This
can maximize the service life of the system.

12hours
Rotation

Emergency operation
Each module is an independent sub-system. The whole
system wont fail down even if partial malfunction occurs.
If a malfunction occurs at any module, there can be performed
an emergency operation. This can simply be achieved
by setting up manually the outdoor PCB switches.

12hours
Rotation

Operating

Malfunction
12hours
Rotation

Emergency
Operation

12hours
Rotation

) Continuous operation of indoor units


Each indoor unit is controlled individually on the system network. This allows all indoor units to continue operating even if an error
occurs at any indoor unit on the VRF system.

Failure

) Wide voltage range operation

) Power supply security

The unit can safely operate within 342V-456V

With power supply security, the outdoor unit will start autoprotection if the power voltage or the current is out of the
normal range. Protection will be relived automatically if the
power condition resumes normal.

342V

456V
Safe operation range

) PCB protection design

) Anti-corrosion

With unique high efficiency radiating air-dust


design, the outdoor electric box is designed
as water-proof, dust-proof, damp-proof and
well ventilated. This can ensure the required
condition for the electric elements even in tropical conditions. Also, it improves the systems
reliability and service life.

The primary material of Golden Fin is Al-Mn (Aluminum-Manganese) anti-rust alloy, which is coated with the Golden Protection
Layer (Components: Epoxy Resin & Modified Acrylic, Silicon
free). The anti-corrosive performance in salt-spray testing is
200%-300% higher than normal Blue Fin*.
Hydrophilic Layer
Golden Protection Layer
(Epoxy resin & Modified Acrylic)

Al-Mn-corrosive alloy

*Salt-spary testing result is from INVENTOR materials chemistry testing


laboratory

Air outlet

) New generation of oil return control


The pressure control achieves an optimized oil return of the system.
As a result, the operating life of the compressor is greatly improved.

Negative pressure

Electric Box
Baffle
Electric Box Cover

Backflow

Guide louver
Positive pressure
Air inlet
Front pane

) High efficiency oil-balanced technology


High-pressure chamber
Suction pipe
compressor with oil-balanced pipe
can automatically drain
out the excess oil.
Discharge pipe
This can prevent an
oil-unbalance between
the compressors.
Auto-oil pipe

New patented oil separator allows the oil separating efficiency up to 99%.
Oil equalizing pipe connection designed at the outside of the module allows high reliability.
Before Oil Balanced

After Oil Balanced

Compressors
Oil storage
tank

Oil equalizing pipe

Oil equalizing pipe

BETTER VERSATILITY
) Long piping design
Maximum total piping length --- 500m
Maximum actual piping length --- 150m
Maximum equivalent piping length --- 175m
Maximum height difference between indoor units --- 15m
Maximum height difference between outdoor
and indoor units --- 50m*
Maximum piping length from first indoor branch to the
farthest indoor unit --- 40m

) Higher Static pressure


of outdoor unit
The maximum external static pressure (ESP) of the outdoor fan
can reach up to 75Pa*.
The outdoor unit can be installed in the equipments room of high
buildings.
* Default ESP of the product is 40Pa. If higher ESP is required, please contact us.

15m

40m

150m

50m

* This value is based on the case that the outdoor unit is located above the
indoor unit. If the outdoor unit is located underneath the indoor unit, the value
is 40m.

) Wide operation range


The unit can operates in wide range, greatly reducing the
ambient temperature limitation.

If the required capacity of indoor units is 50% higher than the outdoor unit,
the cooling range may be lower up to 150C
If the required capacity of indoor units is 50% lower than the outdoor unit, the
cooling range may be up to 50C.

10

Heating

Cooling

) Compact Design
Compact size has been achieved by significantly reducing the width of the outdoor units compared to previous models.
Former model (8HP)

INV (8HP)

1670mm

1772mm

17%
reduction

880mm

770mm
990mm
Floor area: 0,87m

930mm
2

Floor area: 0,72m2

INV (16HP)

41%

1670mm

1772mm

Former model (8HP + 8HP)

reduction

880mm
(990+990)mm
Floor area: 1,74m2

770mm

1340mm

Floor area: 1,03m2

) Modular outdoor unit design


Various combinations from 8HP to 64HP with 2HP increments.
Max capacity of outdoor unit is 180kW (4 x modules)

) Various combinations
Up to 110 sets of indoor units can be connected*
*For the standard model that 4 models connect in parallel, up to 64 indoor
units can be connected. If more indoor units are required to be connected
please contact us.

12 types and 69 models.


Maximum diversity is 135%

11

EASY INSTALATION & MAINTENANCE


) Easier maintainability
Special-designed elecric box.
The electric box can be opened by inverting downwards, for easy maintenance.

Error display & Self-diagnostics system.


Any malfunction can be judged by the LED display that is on the main board (different combinations of ON/OFF or BLINK).
Self diagnostics
system display

12

LED display on the


connection board

LED display on the


connection board

) Easier transportation & installations


Light weight
Former model (8HP+8HP):
240x2=480kg

Transportation by forklift

INV (16HP):
370kg

Optimized base frame


Optimized base frame. The locating and fixing of the
outdoor unit during installation is more convenient and
reliable.

Five-Way piping connection


Piping and wiring are available to the front and back,
left and right, bottom.
The five-way piping connection reduces installation
difficulty and cost. Improves the installation efficiently.

Compact design
With compact design, the outdoor unit can be carried to the roof of a building through elevator. No crane is needed.
Traditional Central Air Conditioner

INV

13

INV MINI
70m

Long piping design


Maximum total piping length --- 150m
Maximum actual piping length --- 70m
Maximum equivalent piping length --- 80m
Maximum height difference between
indoor units --- 10m
Maximum height difference between outdoor
and indoor units --- 30m*
Maximum piping length from first indoor branch and
the farthest indoor unit --- 25m

30m

) Flexible Design

25m

10m

* This value is based on the outdoor unit to be located above


the indoor unit. If the outdoor unit is located underneath
the indoor unit, the value is 25m.

Compact Design
Compact size has been achieved by significantly reducing the width
of the outdoor units compared to previous models.
INV

1100mm

14%

1250mm

1250mm

Former Model

reduction

340mm

340mm
mm

Floor area: 0,374m2

) Wide voltage range operation


The unit can safely operate within the power supply voltage
of 185V to 264V.

14

950mm

Floor area: 0,323m2

185V

264V
Safe operation range

) High efficiency

) Comfort

DC inverter rotary compressor

Auto quiet operation


The unit is ensured to operate with the lowest noise due
to the ultra-low fan speed and auto adjustment according
to system parameters. The operation noise of the unit is
reduced by 3dB(A) at lower loading.

Operation noise

3dB(A)

) Easy Installation
When total piping length is less than 50m
[(A+B+C+D+a+b+c+d) 50m],
no additional refrigerant is required.

) Powerful heating in low temperature


When outdoor ambient temperature is low, the system can automatically increase the heating effect according to its judgment
on parameters. Heating performance is improved by 15%, which brings great comfort.

) Capacity
MODEL
Capacity
Power Supply

HP
kW

INV-Pd100W/NaB-K

INV-Pd120W/NaB-K

INV-Pd140W/NaB-K

INV-Pd160W/NaB-K

3.5
10

4.0
12

5.0
14

6.0
16

1Phase, 220-240V, 50Hz

15

OUTDOOR UNITS LINEUP


INV-Pdm224W/
NaB-M (8HP)

MODEL
INV-Pdm224W/
NaB-M (8HP)

INV-Pdm228W/
NaB-M (10HP)

INV-Pdm335W/
NaB-M (12HP)

INV-Pdm400W/
NaB-M (14HP)

INV-Pdm450W/
NaB-M (16HP)

INV-Pdm504W2/
NaB-M (18HP)

INV-Pdm560W2/
NaB-M (20HP)

INV-Pdm615W2/
NaB-M (22HP)

INV-Pdm670W2/
NaB-M (24HP)

INV-Pdm730W2/
NaB-M (26HP)

INV-Pdm785W2/
NaB-M (28HP)

INV-Pdm850W2/
NaB-M (30HP)

INV-Pdm900W2/
NaB-M (32HP)

16

INV-Pdm280W/
NaB-M (10HP)

INV-Pdm335W/
NaB-M (12HP)

INV-Pdm400W/
NaB-M (14HP)

INV-Pdm450W/
NaB-M (16HP)

INV-Pdm224W/
NaB-M (8HP)

MODEL

INV-Pdm280W/
NaB-M (10HP)

INV-Pdm335W/
NaB-M (12HP)

INV-Pdm400W/
NaB-M (14HP)

INV-Pdm450W/
NaB-M (16HP)

INV-Pdm950W3/
NaB-M (34HP)

INV-Pdm1008W3/
NaB-M (36HP)

INV-Pdm1605W3/
NaB-M (38HP)

INV-Pdm1130W3/
NaB-M (40HP)

INV-Pdm1180W3/
NaB-M (42HP)
INV-Pdm11253W3/NaBM (44HP)
INV-Pdm1300W3/
NaB-M (46HP)
INV-Pdm11350W3/NaBM (48HP)
INV-Pdm1405W4/
NaB-M (50HP)

INV-Pdm1456W4/
NaB-M (52HP)

INV-Pdm1512W4/
NaB-M (54HP)

INV-Pdm1570W4/
NaB-M (56HP)

INV-Pdm1650W4/
NaB-M (58HP)

INV-Pdm1700W4/
NaB-M (60HP)

INV-Pdm1750W4/
NaB-M (62HP)

INV-Pdm1800W4/
NaB-M (64HP)

17

SPECIFICATIONS
INV Mini
RATING CAPACITY

HP

MODEL
Combination units
Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power consumption
Heating (kW)
Compressor
Type
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions WxDxH (mm)
Net weight
Refrigerant charge

INV-Pd 100W/NaB-K

INV-Pd 120W/NaB-K

INV-Pd 140W/NaB-K

INV-Pd 160W/NaB-K

6
5.0-13.5

7
8
6.0-16.2
7.0-18.9
1-Phase, 220-240V, 50Hz
12.0
14.0
14.0
15.4
3.50
4.36
3.40
4.05
DC inverter dual-rotor type compressor x 1
6200
6000
3642
3525
58
58
950x340x1250
950x340x1250
111
111
7.5
7.5
Cooling: 10 to 48, Heating: -20 to 27
Cooling: 18 to 118.4, Heating: -4 to 81
5/8
5/8
3/8
3/8

10.0
11.0
2.86
2.60

Capacity

kg

6200
3642
58
950x340x1250
111
7.5

C
F

Operation range
Connection pipe
diameter

3.5

Gas
Liquid

inch

5/8
3/8

9
8.0-21.6
16.0
17.6
4.98
4.85
6400
3759
58
950x340x1250
115
7.5

3/4
3/8

Basic Module
RATING CAPACITY

HP

MODEL
Combination units
Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power consumption
Heating (kW)
Compressor
Configration*
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions
WxDxH
Net weight
Operating range
Refrigerant charge
Capacity

Gas
Liquid

*DC: DC inverter scroll compressor

18

kg
C
F

Operation range
Connection pipe
diameter

mm

inch

8
INV-Pdm 224W/
NaB-M

10
INV-Pdm 280W/
NaB-M

12
INV-Pdm 335W/
NaB-M

14
16
14.0 - 37.8
16.8 - 45.2
3-Phase, 380-415V, 50Hz
22.4
28.0
33.5
25.0
31.5
37.5
5.52
7.52
9.23
5.82
7.70
9.38
DCx1+Cx1
10000
10000
13000
5874
5874
7636
58
58
60
930x770x1670
255
255
350
275
275
380
12
13
15
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
7/8
7/8
9/8
3/8
3/8
1/2

14
11.2 - 30.2

C: Constant speed scroll compressor

14
INV-Pdm 400W/
NaB-M

16
INV-Pdm 450W/
NaB-M

16
20.0 - 54.0

16
22.5 - 60.8

40.0
45.0
12.45
11.2
DCx1+Cx2
13000
7636
61
1340x770x1670
350
380
16

45.0
50.0
14.32
13.90

9/8
1/2

13000
7636
61
370
400
17

9/8
1/2

Combination Modules
RATING CAPACITY

HP

MODEL

Combination units
Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power consumption
Heating (kW)
Compressor
Configration*
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions
WxDxH
Net weight
Refrigerant charge
Capacity

kg
C
F

Operation range
Connection pipe
diameter

mm

Gas
Liquid

RATING CAPACITY

Inch
HP

MODEL

Combination units

Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power consumption
Heating (kW)
Compressor
Configration*
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions
WxDxH
Net weight
Refrigerant charge
Capacity

kg
C
F

Operation range
Connection pipe
diameter

mm

Gas
Liquid

*DC: DC inverter scroll compressor

Inch

18
INV-Pdm 504W2/
NaB-M

20
INV-Pdm 560W2/
NaB-M

22
INV-Pdm 615W2/
NaB-M

24
INV-Pdm 670W2/
NaB-M

26
INV-Pdm 730W2/
NaB-M

INV-Pdm 224W/
NaB-M
INV-Pdm 280W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 280W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 335W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 400W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 450W/
NaB-M

30
25.2-68

32
32
32
32
28.0-75.6
30.8-83.0
33.5-90.5
36.5-98.6
3-Phase, 380-415V, 50Hz
50.4
56.0
61.5
68.0
73.0
56.5
63.0
69.0
76.5
81.5
13.04
15.04
16.75
19.97
21.84
13.52
15.40
17.08
18.90
21.60
(DCx1+Cx1)x2
(DCx1+Cx1)+(DCx1+Cx2)
10000x2
10000+13000
5874x2
5874+7636
62
62
62
62
63
(930x770x1670)+(930x770x1670)
(930x770x1670)+(1340x770x1670)
255+255
255+255
255+350
255+350
255+370
13+13
13+15
13+15
13+16
13+17
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
9/8
9/8
9/8
9/8
11/8
5/8
5/8
5/8
3/4
3/4

28
INV-Pdm 785W2/
NaB-M

30
INV-Pdm 850W2/
NaB-M

32
INV-Pdm 900W2/
NaB-M

34
INV-Pdm 950W3/
NaB-M

36
INV-Pdm 1008W3/
NaB-M

INV-Pdm 335W/
NaB-M
INV-Pdm 450W/
NaB-M

INV-Pdm 400W/
NaB-M
INV-Pdm 450W/
NaB-M

INV-Pdm 450W/
NaB-M
INV-Pdm 450W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 280W/
NaB-M
INV-Pdm 400W/
NaB-M

INV-Pdm 280W/
NaB-M
INV-Pdm 280W/
NaB-M
INV-Pdm 450W/
NaB-M

32
39.3-106.0

32
32
48
48
42.5-114.8
45.0-121.5
47.5-128.3
50.4-136.1
3-Phase, 380-415V, 50Hz
78.5
85.0
90.0
96.0
101.0
87.5
95.0
100.0
108.0
113.0
23.55
26.77
28.64
27.49
29.36
23.28
25.10
27.8
26.60
29.30
(DCx1+Cx2)x2
[(DCx1+Cx1)x2]+(DCx1+Cx2)
13000x2
10000x2+13000
7636x2
5874x2+7636
63
63
63
64
64
(1340X770X1670)+(1340X770X1670)
(930x770x1670)+(930x770x1670)+(1340x770x1670)
350+370
350+370
370+370
255+255+350
255+255+370
15+16
18+17
17+17
13+13+16
13+13+17
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
11/8
11/8
11/8
11/8
11/8
3/4
3/4
3/4
3/4
3/4

C: Constant speed scroll compressor

19

Combination Modules
RATING CAPACITY

HP

MODEL

Combination
units

Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power
consumption Heating (kW)
Compressor
Configration*
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions
WxDxH
Net weight
Refrigerant charge
Capacity

kg
C
F

Operation range
Connection
pipe diameter

mm

Gas
Liquid

RATING CAPACITY

Inch

HP

MODEL

Combination units

Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power
consumption Heating (kW)
Compressor
Configration*
m/h
Airflow rate
CFM
Sound pressure level (dB(A))
Capacity

Dimensions

WxDxH

Net weight
Refrigerant charge

kg

Operation range

C
F

Connection
pipe diameter

Gas
Liquid

*DC: DC inverter scroll compressor

20

mm

Inch

38

40

42

44

46

48

INV-Pdm
1065W3/NaB-M

INV-Pdm
1130W3/NaB-M

INV-Pdm
1180W3/NaB-M

INV-Pdm
1235W3/NaB-M

INV-Pdm
1300W3/NaB-M

INV-Pdm
1350W3/NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm335W/
NaB-M

INV-Pdm400W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm335W/
NaB-M

INV-Pdm400W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

48
53.3-143.8

48
48
48
48
48
56.5-152.6
59.0-159.3
61.81-166.7
65.0-175.5
67.5-182.3
3-Phase, 380-415V, 50Hz
106.5
113.0
118.0
123.5
130.0
135.0
119.0
126.5
131.5
137.5
145.0
150.0
31.07
34.29
36.16
37.87
41.09
42.96
30.98
32.80
35.50
37.18
39.00
41.70
(DCx1+Cx1)+[(DCX1+Cx2)x2]
(DCx1+Cx2)x3
10000+13000x2
13000X3
5874+7636x2
7636x3
64
64
64
65
65
65
(930x770x1670)+(1340x770x1670)+(1340x770x1670)
(1340x770x1670)+(1340x770x1670)+(1340x770x1670)
255+350+370
350+370+370
350+370+370
370+370+370
13+15+17
13+16+17
13+17+17
15+17+17
16+17+17
17+17+17
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
3/4
3/4
3/4
3/4
3/4
3/4

50
INV-Pdm1405W4/
NaB-M

52
INV-Pdm1456W4/
NaB-M

54
INV-Pdm1512W4/
NaB-M

56
INV-Pdm1570W4/
NaB-M

58
INV-Pdm1650W4/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm280W/
NaB-M

INV-Pdm335W/
NaB-M

INV-Pdm400W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm400W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

64
78.5-212.0

64
82.5-222.8

155.0
176.5
48.61
46.70
(DCx1+Cx1)+[(DCx1+Cx2) x3]
10.000+13.000x3
5.874+7.636x3
65

163.0
181.5
50.48
49.90

64
70.3-189.7

64
64
72.8-196.6
75.6-204.1
3-Phase, 380-415V, 50Hz
141.0
146.0
151.5
158.0
163.0
169.0
41.84
43.68
45.39
40.05
43.20
44.88
[(DCx1+Cx1) x2]+[(DCx1+Cx2)x2]
10.000x2+13.000x2
5.874x2+7.636x2
65
65
65

(930x770x1.670)+(930x770x1.670)+
+(1.340X770X1670)+(1.340X770X1.670)
255+255+350+370
13+13+16+17

1 3/4
7/8

255+255+350+370 255+350+370+370 255+350+370+370


13+13+17+17
13+15+17+17
13+16+17+17
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
1 3/4
7/4
2 1/8
7/8
7/8
1

C: Constant speed scroll compressor

65

(930x770x1.670)+(1.340x770x1.670)+
+(1.340x770x1670)+(1.340x770x1.670)
255+370+370+370
13+17+17+17

2 1/8
1

Combination Modules
RATING CAPACITY
MODEL

HP

Combination
units

Connectable
indoor unit
Power supply

Maximum
Cooling Capacity (kW)

Cooling (kW)
Heating (kW)
Cooling (kW)
Power
consumption Heating (kW)
Compressor
Configration*
m3/h
Airflow rate
CFM
Sound pressure level (dB(A))
Dimensions
WxDxH
Net weight
Refrigerant charge
Capacity

kg
C
F

Operation range
Connection
pipe diameter

mm

Gas
Liquid

*DC: DC inverter scroll compressor

Inch

60
INV-Pdm1700W4/NaB-M

62
INV-Pdm1750W4/NaB-M

64
INV-Pdm1800W4/NaB-M

INV-Pdm335W/
NaB-M

INV-Pdm400W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

INV-Pdm450W/
NaB-M

64
85.0-230.0

64
64
87.5-236.3
80.0-243.0
3-Phase, 380-415V, 50Hz
168.0
175.0
180.0
187.5
195.0
200.0
52.19
55.41
57.21
51.80
52.90
55.60
(DCx1+Cx2) x4
13000x4
7636x4
66
66
66
(1340x770x1670)+(1340x770x1670)+(1340x770x1670)+(1340x770x1670)
350+370+370+370
15+17+17+17
16+17+17+17
17+17+17+17
Cooling: -5 to 48, Heating: -20 to 27
Cooling: 23 to 118.4, Heating: -4 to 81
2 1/8
2 1/8
2 1/8
1
1
1
C: Constant speed scroll compressor

21

INDOOR UNITS LINEUP


CAPACITY INDEX (kW)

Duct Type
(EXV Integrated)

Slim Duct Type


(EXV Integrated)
Four-way Cassette Type
(EXV Integrated)
Compact Four-way
Cassette Type
(EXV Separated)
One-way Cassette Type
(EXV Separated)

Floor Standing Type

Concole Type

Floor Ceiling Type


(EXV Integrated)
Wall Mounted Type
(EXV Separated)
Wall Mounted Type
(EXV Integrated)
Treated Fresh Air
Duct Type

22

2.2

2.8

3.6

4.5

5.0

5.6

6.3

7.1

8.0

9.0

10.0

11.2

12.5

14.0

22.4

28.0

23

DUCT TYPE
) Highly flexible installation
Highly flexible installation is possible to satisfy various needs
eeds
Installation examples

Return air inlet


Supply air duct

Indoor unit
Supply air duct
Canvas air duct
Indoor unit
Long life filter

Maintenance access

Flexible and easy to install in type-L, type-U and in large rooms

) Fresh air function option for 5.6kW and above units

24

Long life filter

) Drain pump lift reaches 1000mm


Only available for INV(L)-R*PS/NaB-K

) Easy maintenance
Long life and washable filter with buckles can be easily disassembled from each direction.
Compact size has been achieved by significantly reducing the width of the outdoor units compared
to previous models.

Former structure: push pull type


The former structure is not easy to disassembly.

New structure: with buckles


The new structure makes the disassembly convenient.

) HIGHER ESP & lower noise


The ESP is obviously upgraded while the noise is almost at the same level as before.
Low ESP of new model

Former model

New model (In low ESP)

ESP (Pa)

Sound level (dB(A))

Former model
High ESP of new model

Model (kW)

Model (kW)

) Key-card control

25

Duct Type (With drain water pump)


MODEL

INV-R22PS/NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Airflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Standard Esp (H/L) (Pa)
Dimensions (WxDxH) (mm)
Net weight (Kg)
Inch
Gas (Flare)
mm
Connection
pipe
Inch
Liquid (Flare)
mm
External dia. mm
Drain Pipe
Thickness
mm

MODEL

2.2
2.5
75
450
265
37/35/33
50/20
28.5
3/8
9.52
1/4
6.35
20
1.5

INV-R56PS/
NaB-K

INV-R28PS/NaB-K

1-Phase, 220-240V, 50Hz


2.8
3.6
3.2
4.0
80
80
570
570
335
336
39/37/35
39/37/35
50/20
50/20
880x665x250
30.5
30.5
3/8
1/2
9.52
12.7
1/4
1/4
6.35
6.35
20
20
1.5
1.5

INV-R71PS/
NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Airflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Standard Esp (H/L) (Pa)
Dimensions (WxDxH) (mm)
Net weight (Kg)
Inch
Gas (Flare)
mm
Connection
pipe
Inch
Liquid (Flare)
mm
External dia. mm
Drain Pipe
Thickness
mm

26

INV-R36PS/NaB-K

5.6
7.1
6.3
8.0
240
240
1.000
1.100
589
647
44/42/40
45/43/41
60/30
60/30
1155x756x300
51
51
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
30
30
1.5
1.5

INV-R90PS/
NaB-K
1-Phase, 220-240V, 50Hz
9.0
10.0
360
1.700
1.000
48/46/44
80/40
64
5/8
15.9
3/8
9.52
30
1.5

INV-R45PS/NaB-K
4.5
5.0
140
700
412
40/38/36
50/20
980x721x266
36
1/2
12.7
1/4
6.35
30
1.5

INV-R112PS/
NaB-K

INV-R140PS/
NaB-K

11.2
12.5
360
1.700
1.000
48/46/44
80/40
1425x736x300
64
5/8
15.9
3/8
9.52
30
1.5

14.0
15.0
500
2.000
1.177
50/48/46
100/50
65.5
5/8
15.9
3/8
9.52
30
1.5

Duct Type (Without drain water pump)


MODEL

IN-R22P/
NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Airflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Standard Esp (H/L) (Pa)
Dimensions (WxDxH) (mm)
Net weight (Kg)
Inch
Gas (Flare)
mm
Connection
pipe
Inch
Liquid (Flare)
mm
External dia. mm
Drain Pipe
Thickness
mm

MODEL

2.2
2.5
75
450
265
37/35/33
50/20
27
3/8
9.52
1/4
6.35
20
1.5

INV-R90P/
NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Airflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Standard Esp (H/L) (Pa)
Dimensions (WxDxH) (mm)
Net weight (Kg)
Inch
Gas (Flare)
mm
Connection
pipe
Inch
Liquid (Flare)
mm
External dia. mm
Drain Pipe
Thickness
mm

9.0
10.0
360
1.700
1.000
48/46/44
80/40
62
5/8
15.9
3/8
9.52
30
1.5

INV-R28P/
NaB-K

INV-R36PS/
NaB-K

INV-R45P/
NaB-K

1-Phase, 220-240V, 50Hz


2.8
3.6
3.2
4.0
80
80
570
570
335
336
39/37/35
39/37/35
50/20
50/20
880x665x250
28.5
28.5
3/8
1/2
9.52
12.7
1/4
1/4
6.35
6.35
20
20
1.5
1.5

INV-R112P/
NaB-K
1-Phase, 220-240V, 50Hz
11.2
12.5
360
1.700
1.000
48/46/44
80/40
1425x736x300
62
5/8
15.9
3/8
9.52
30
1.5

INV-R56P/
NaB-K

4.5
5.0
140
700
412
40/38/36
50/20
980x721x266
34
1/2
12.7
1/4
6.35
30
1.5

INV-R140P/
NaB-K
14.0
15.0
500
2.000
1177
50/48/46
100/50
63.5
5/8
15.9
3/8
9.52
30
1.5

INV-R71P/
NaB-K

5.6
7.1
6.3
8.0
240
240
1.000
1.100
589
647
44/42/40
45/43/41
60/30
60/30
1155x756x300
49
49
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
30
30
1.5
1.5

INV-R224P/
NaB-M

INV-R280P/
NaB-M

3-Phase, 380-450V, 50Hz


22.4
28.0
25.0
31.0
1.600
1.600
4.000
4.800
2.381
2.857
56(H)
57(H)
200
220
1463x799x389
1628x869x454
88
113
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
25.4
25.4
1.5
1.5

27

SLIM DUCT TYPE


) Compact Design
2.2kW, 2.8kW, 3.6Kw
Only 700mm in width, 200mm in height and 22kg in weight*, which is perfect to install in limited spaces like drop ceiling in
hotel.

Note: the weight is 23kg for the unit of 3.6kW.

200mm

700mm

4.5kW, 5.6kW
Only 200mm in height, which can be installed in rooms with little depth as 240mm depth between the drop ceiling and ceiling slab.
Suspension bolt

Suction duct*

200mm

AIR
900mm
Discharge grille

Air filter

Suction grille

AIR

Note: to be obtained locally

) Highly flexible installation


Highly flexible installation is possible to satisfy various needs.
Installation examples
Example 1

Example 2
Return air inlet

Supply air duct

Indoor unit

Supply air duct

Canvas air duct


Indoor unit
Long-life filter

28

Maintenance access

Long-life filter

) Lower noise
Plastic propeller housing, fan blade and intelligent-designed air-channel ensure air flow volume with lower operation noise.

For example the normal unit of 2.8kW has noise level up to 40dB(A), but the new unit of 2.8kW reduces the noise up to only
37dB(A).

) Drain pump lift reaches 1000mm

MODEL

INV-R22P/
NaE-K

INV-R28P/
NaE-K

2.2
2.5
64
450
265
37/35/33
20

2.8
3.2
64
450
265
37/35/33
20
700x615x200
21
3/8
9.52
1/4
6.35
20
1.5

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Airflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Standard Esp (Pa)
Dimensions (WxDxH) (mm)
Net weight (Kg)
Inch
Gas (Flare)
mm
Connection
pipe
Inch
Liquid (Flare)
mm
External dia. mm
Drain Pipe
Thickness
mm

21
3/8
9.52
1/4
6.35
20
1.5

INV-R36P/
NaE-K

INV-R45P/
NaE-K

INV-R56P/
NaE-K

1-Phase, 220-240V, 50HZ


3.6
4.5
5.6
4.0
5.0
6.3
70
91
91
550
700
700
324
412
412
39/37/35
40/38/36
41/39/37
20
20
20
900x615x200
21
26
26
1/2
1/2
5/8
12.7
12.7
15.9
1/4
1/4
3/8
6.35
6.35
9.52
20
30
30
1.5
1.5
1.5

INV-R71P/
NaE-K
7.1
8.0
100
1000
589
42/40/38
20
1100x615x200
30
5/8
15.9
3/8
9.52
30
1.5

29

FOUR WAY CASSETTE TYPE

) Four
Four-way
way Cassette Type
Compact, light weight and square panel in the same size for
easy installation.

Compact
act Four-way
Four way Cassette
Cassette
Type
Compact size of 650mm x 650mm for 2.8kW 5.6kW

650mm

960mm

960mm

30

650mm

A slim unit below 5.0kW is only 190mm in thickness. It can


be installed in a narrow ceiling space of at least 210mm.

Only 230mm in thickness that can be installed in a ceiling


space of at least 250mm.

Drain pump fitted as standard with increased lift of


1100mm.

Drain pump fitted as standard with increased lift of 500mm.

Common characteristics
Low noise with 3 dimensional blade.

Diffuser

3-dimensional blade

The full-automatic operation, the 4-way air supply, the 3-speed fan setting and the strong circulating air flow volume, make the
cooled or heated air to reach directly every corner of the room. This can be succeded even if the ceiling is higher than standard
height.
The units below 7.1kW are applicable to
height below 3m.

The units below 8kW are applicable to


height below 4.5m.

Air supply in different directions with 30-60 degree


sweep for even better temperature distribution*

Note: the guide louver defaults to min. position of 30 during cooling,


dry and fan operation, or maximum position of 60 during heating operation.

Designed with fresh air baffle for fresh air introduction.

Long life and washable filter.

31

Four-Way Cassette Type


MODEL
Power supply

INV-R28T/Na-K

Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
Aiflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Capacity

Connection
pipe
Drain Pipe
Main body
Panel

Gas (Flare)
Liquid (Flare)

Inch
mm
Inch
mm

External dia. (mm)


Thickness (mm)
Dimensons (WxDxH) (mm)
Net Weight (kg)
Dimensons (WxDxH) (mm)
Net Weight (kg)

MODEL
Power supply
Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
Aiflow rate
CFM
Sound pressure level (H/M/L) (dB(A))

Drain Pipe
Main body
Panel

32

25
6.5

INV-R56T/Na-K

Capacity

Connection
pipe

2.8
3.2
65
680
400
37/35/33
3/8
9.52
1/4
6.35
30
1.5

Gas (Flare)
Liquid (Flare)

Inch
mm
Inch
mm

External dia. (mm)


Thickness (mm)
Dimensons (WxDxH) (mm)
Net Weight (kg)
Dimensons (WxDxH) (mm)
Net Weight (kg)

5.6
6.3
83
1.180
694
39/37/35
5/8
15.9
3/8
9.52
30
1.5
30
6.5

INV-R36T/Na-K

INV-R45T/Na-K

1-Phase, 220-240V, 50HZ


3.6
4.5
4.0
5.0
65
65
680
680
400
400
37/35/33
37/35/33
1/2
1/2
12.7
12.7
1/4
1/4
6.35
6.35
30
30
1.5
1.5
840x840x190
25
25
950x950x60
6.5
6.5

INV-R63T/Na-K

INV-R80T/Na-K

1-Phase, 220-240V, 50HZ


6.3
8.0
7.1
8.8
83
83
1.180
1.180
694
694
39/37/35
39/37/35
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
30
30
1.5
2.5
840x840x240
30
30
950x950x60
6.5
6.5

INV-R50T/Na-K
5.0
5.8
65
680
400
37/35/33
1/2
12.7
1/4
6.35
30
1.5
25
6.5

INV-R90T/Na-K
9.0
10.0
133
1.860
1.095
40/38/36
5/8
15.9
3/8
9.52
30
3.5
840x840x320
38
6.5

Four-Way Cassette Type


MODEL
Power supply

INV-R100T/Na-K

Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
Aiflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Capacity

Connection
pipe
Drain Pipe
Main body
Panel

Gas (Flare)
Liquid (Flare)

Inch
mm
Inch
mm

External dia. (mm)


Thickness (mm)
Dimensons (WxDxH) (mm)
Net Weight (kg)
Dimensons (WxDxH) (mm)
Net Weight (kg)

10.0
11.0
133
1.860
1.095
40/38/36
5/8
15.9
3/8
9.53
30
1.5
38
6.5

INV-R112T/Na-K

INV-R125T/Na-K

1-Phase, 220-240V, 50HZ


11.2
12.5
12.5
13.5
133
133
1.860
1.860
1.095
1.095
40/38/36
40/38/36
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
30
30
1.5
1.5
840x840x320
38
38
950x950x60
6.5
6.5

INV-R140T/Na-K
14.0
14.5
133
1.860
1.095
40/38/36
5/8
15.9
3/8
9.52
30
1.5
38
6.5

Compact Four-Way Cassette Type


MODEL
Power supply

INV-R22T/NaA-K

Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
Aiflow rate
CFM
Sound pressure level (H/M/L) (dB(A))
Capacity

Connection
pipe
Drain Pipe
Main body
Panel

Gas (Flare)
Liquid (Flare)

Inch
mm
Inch
mm

External dia. (mm)


Thickness (mm)
Dimensons (WxDxH) (mm)
Net Weight (kg)
Dimensons (WxDxH) (mm)
Net Weight (kg)

2.2
2.5
12
600
353
47/44/41
3/8
9.52
1/4
6.35
30
1.5
20
2.5

INV-R28T/NaA-K

INV-R36T/NaA-K

1-Phase, 220-240V, 50HZ


2.8
3.6
3.2
4.0
12
12
600
600
353
353
47/44/41
47/44/41
3/8
1/2
9.52
12.7
1/4
1/4
6.35
6.35
30
30
1.5
1.5
570x570x230
20
20
650x650x50
2.5
2.5

INV-R45T/NaA-K
4.5
5.0
12
600
353
47/44/41
1/2
12.7
1/4
6.35
30
1.5
20
2.5

33

ONE-WAY
CASSETTE TYPE
) High flexible

D i pump lift
) Drain

Highly flexible installations for various needs.

Drain pump flitted as standard with


increased lift of 700mm.

) The unit is applicable to


height below 3.5m

) Detachable and washable grille

) Ultra quiet operation

) Comfortable

Low noise cross flow fan reduces vortex flow in the duct thus
reducing the noise.

The equal and gentle air supply design and the advanced air flow
controlling design make the room temperature equal and balanced. So, the people inside the room feel more comfortable.

) Long life and washable filter


MODEL
Power supply

INV-R22Td/NaA-K

Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
Aiflow rate
CFM
Sound pressure level (dB(A))
Capacity

Connection
pipe
Drain Pipe
Main body
Panel

34

Gas (Flare)
Liquid (Flare)

Inch
mm
Inch
mm

External dia. (mm)


Thickness (mm)
Dimensons (WxDxH) (mm)
Net Weight (kg)
Dimensons (WxDxH) (mm)
Net Weight (kg)

2.2
2.5
42
450
265
45/43/41
3/8
9.52
1/4
6.35
30
1.5
16
3

INV-R28Td/NaA-K
1-Phase, 220-240V, 50HZ
2.8
3.2
42
500
294
45/43/41
3/8
9.52
1/4
6.35
30
1.5
920x360x185
16
118043030
3

INV-R36Td/NaA-K
3.6
4.0
42
500
294
45/43/41
1/2
12.7
1/4
6.35
30
1.5
16
3

FLOOR STANDING
TYPE

Wireless
FCU Wired remote controller WK-010PA-K

Auto diagnosis
Fashionable and novel appearance
Quiet operation
Intelligent drainage device
Long life filter
Wider air supply and swing angle
Dynamic color display
Horizontal and vertical swing

Model / Heat pump


Capacity

Cooling
Heating

Power supply
Motor power input
Air flow volume
Sound pressure level
Connecting pipe
Drain pipe
Dimensions
Net Weight

Gas
Liquid
External dia.
Thickness
WxDxH
Body

kW
kW
V/Ph/Hz
W
m3/h
CFM
dB(A)
inch
inch
mm
mm
mm
kg

INV-R71L/Na-K

INV-R100L/Na-K

INV-R140L/Na-K

7.00
8.00
220-240/1/50
160
1100/1000/920
655/595/548
48/45/42
5/8
3/8
31
4.5
502x316x1756
39.0

10.00
11.00
220-240/1/50
185
1600/1500/1300
952/893/774
51/49/47
5/8
3/8
31
4.5
556x381x1896
53

14.00
15.00
220-240/1/50
200
1700/1600/1400
1012/952/833
52/50/48
5/8
3/8
31
4.5
556x381x1896
57

35

WALL MOUNTED TYPE

) Streamlined design for spaces without ceiling


) Anti cool air design

) Vertical auto swing

When heating in winter, intelligent anti cool air function


is started.The unit blows only when the unit is
pre-heated inside, to prevent it from blowing out cool air.

When cooling, the cool air is directed across the room


and then it sinks. When heating, the warm air is directed
across the floor and then it rises.
Cooling

Heating

) Auto clean (under COOL & DRY mode)

) Low noise design

After the unit is turned off, the indoor fan will still operate in low
speed in order to dry the inner components and parts. This way
mould and odor are prevented from growing.

The advanced irregular-distance mixed flow fan, the unique


duct design and the multi-grill auxiliary duct, make the operation
highly efficient and the noise lower.

) Ternary filters
Ternary air filters with anti-mildew, static electric dust capture and anti-bacterial function.
Ternary filter

) Washable grille
The front grille can be easily removed for washing.

36

MODEL

INV-R22G/
NaG-K

INV-R28G/
NaG-K

Cooling (kW)
Heating (kW)
Power consumption (W)
m3/h
CFM
Sound pressure level (H/M/L) (dB(A))
Dimensions (WxDxH)(mm)
Net weight (kg)
Inch
Gas (Flare)
mm
Connection pipe
Inch
Liquid (Flare)
mm
External dia. (mm)
Drain Pipe
Thickness (mm)
EXV Position
Aiflow rate

MODEL

2.2
2.5
50
500
294
38/36/34

m3/h
CFM
Sound pressure level (H/M/L) (dB(A))
Dimensions (WxDxH)(mm)
Net weight (kg)
Inch
Gas (Flare)
mm
Connection pipe
Inch
Liquid (Flare)
mm
External dia. (mm)
Drain Pipe
Thickness (mm)
EXV Position
Aiflow rate

2.8
3.2
50
500
294
38/36/34

3.6
4.0
60
630
371
44/41/38

10.5
3/8
9.52
1/4
6.35
28
4

13
1/2
12.7
1/4
6.35
28
4

843x180x275
10.5
3/8
9.52
1/4
6.35
28
4

4.5
5.0
60
630
371
44/41/38
940x200x298
13
1/2
12.7
1/4
6.35
28
4

Intergrated

INV-R50G/
NaG-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)

INV-R45G/
NaG-K

1-Phase, 220-240V, 50HZ

Power supply
Capacity

INV-R36G/
NaG-K

5.0
5.8
60
630
371
44/41/38
940x200x298
13
1/2
12.7
1/4
6.35
28
4

INV-R56G/
NaG-K

INV-R71G/
NaG-K

1-Phase, 220-240V, 50HZ


5.6
7.1
6.3
8.0
70
70
800
800
471
471
44/41/38
44/41/38
1008x221x319
15
15
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
28
28
4
4
Integrated

INV-R71G/
NaB-K

INV-R80G/
NaB-K

7.1
8.0
8.0
9.0
63
65
1.200
1.200
706
706
49/45/42
49/45/42
1178x227x326
17.5
17.5
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
30
30
1.5
1.5
External

37

FLOOR CEILING TYPE


) Compact and light weight
Only 238mm in height

) Ultra quiet operation

) Long life, detachable and washable grille

) Easy to install and good looking, satisfies more requirements

38

) Easy maintenance
Convenient disassembly and maintenance thanks to unique design.
Plastic filter with buckles
Grill buckle

Dismountable motor

) Wide discharge range


With cross-direction sweep. The air supply range is efficiently wider.

) Drain pump lift reaches 1100mm

39

Floor ceiling (EXV Integrated)


MODEL

INV-R28Zd/NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
CFM

Aiflow rate
Sound pressure level (dB(A))
Dimensions (WxDxH) (mm)
Net weight (kg)
Connection
pipe
Drain Pipe

Inch
Gas (Flare)
mm
Inch
Liquid (Flare)
mm
External dia. (mm)
Thickness (mm)

MODEL

2.8
3.2
55
650
383
40
40
3/8
9.52
1/4
6.35
17
1.75

INV-R90Zd/NaB-K

Power supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
CFM

Aiflow rate
Sound pressure level (dB(A))
Dimensions (WxDxH) (mm)
Net weight (kg)
Connection
pipe
Drain Pipe

40

Inch
Gas (Flare)
mm
Inch
Liquid (Flare)
mm
External dia. (mm)
Thickness (mm)

9.0
10.0
180
1.600
942
51
1420x245x700
54
5/8
15.9
3/8
9.52
17
1.75

INV-R36Zd/NaB-K

INV-R50Zd/NaB-K

1-Phase, 220-240V, 50HZ


3.6
5.0
4.0
5.8
55
110
650
950
383
559
40
45
1.220x225x700
40
40
1/2
1/2
12.7
12.7
1/4
1/4
6.35
6.35
17
17
1.75
1.75

INV-R112Zd/NaB-K

INV-R125Zd/NaB-K

1-Phase, 220-240V, 50HZ


11.2
12.5
12.5
13.5
250
250
2.000
2.000
1.777
1.777
55
55
1700x245x700
64
66
5/8
5/8
15.9
15.9
3/8
3/8
9.52
9.52
17
17
1.75
1.75

INV-R71Zd/NaB-K
7.1
8.0
140
1.400
824
49
1420x245x700
52
5/8
15.9
3/8
9.52
17
1.75

INV-R140Zd/NaB-K
14.0
16.0
250
2.000
1.777
55
66
5/8
15.9
3/8
9.52
17
1.75

CONCOLE TYPE

Vertical swing
Anti-cold function
Quiet operation
Comprehensive protection
Auto restart
Compact design
Easier maintainability

MODEL

INV-R28-C/Na-K

Power Supply
Cooling (kW)
Capacity
Heating (kW)
Power consumption (W)
m3/h
Air flow rate
CFM
Sound pressure level (H/M/L) (db(A))
Dimenions (WxDxH) (mm)
Net weight (kg)
inch
Gas
mm
Connection pipe
inch
Liquid
mm

2.8
3.2
60
500-430/370/280
294-253/218/165
38/33/26

3/8
9.52
1/4
6.35

INV-R36-C/Na-K
1-Phase, 220-240V,50Hz
3.6
4.0
60
600-520/440/360
353-306/259/212
40/37/32
700x215x600
16
3/8
9.52
1/4
6.35

INV-R28-C/Na-K
5.0
5.5
60
650-620/500/410
383-365/294/241
46/41/35

1/2
12.7
1/4
6.35

41

TREATED FRESH AIR DUCT TYPE


) Provide fresh air of temperature that is close to the indoor
ambient, ensures fresh and comfortable indoor air.

Note: The capacity of fresh air ducted unit should be less than 30% of the capacity of outdoor unit.

) Comfortable
Makes you feel comfortable, like in the nature. It is introducing
the outdoor fresh air, after treatment, in to the room.

42

Treated fresh air supplying temperature is close to


the indoor temperature (factory setting at 22 Celsius),
reducing the cooling load of other indoor units.

) Easy control
Wired remote control

Wireless remote control

Centralized control

Long-distance monitoring

Sub-room switch

Memory function

Auto restart after power recover

Weekly timer

) Flexible application
The indoor unit with high static pressure can realize long-distance fresh air supply to all corners of the room. So, it is greatly
applicable to places that there is high density of people.
The standard pressure is 200Pa and the optional range is 50-300Pa.

MODEL
Power supply
Capacity
(At rated ESP)
Power input1
Aiflow Volume

Cooling (kW)
Heating (kW)
Cooling (kW)
Heating (kW)
CFM
m3/h

Sound pressure level (H/M/L) (dB(A))


Rated (Pa)
External Static
Pressure
Range (Pa)
Dimensions (WxDxH) (mm)
Weight (kg)
Valve Connection Type
Length (m)
Connection pipe
Gas additional charge (g/m)
Liquid Pipe (Inch)
Gas pipe (Inch)

INV-R140P/
Na(X1.2)-K

INV-R224P/
Na(X2.0)-M

INV-R280P/
Na(X2.5)-M

INV-R280P/
Na(X3.0)-M

220V, 50Hz, 1 Phase


14
10
0.5
0.5
706
1200
42
150
50~150
1463x756x300
63.5
Flare Connection
7.5
54
3/8
5/8

380V, 50Hz, 3 Phase


22.4
16
1.1
1.1
1177
2000
47
200
50~200
1500x1000x500
130
Brazing Connection
7.5
54
3/8
7/8

380V, 50Hz, 3 Phase


28
20
1.1
1.1
1471
2500
48
200
50~200
1500x1000x500
150
Brazing Connection
7.5
54
3/8
7/8

380V, 50Hz, 3 Phase


28
20
1.1
1.1
1766
3000
51
200
50~200
1500x1000x500
150
Brazing Connection
7.5
54
3/8
7/8

43

CONTROL NETWORK SKETCH


Air Conditioning
Individual Control

System

Communication module
ME30-00/E2

Group Controller
ZJA011

Wired Remote Controller


Z63351F/Z63151F
Z60351F/Z60151F

Communication module
ME30-00/E2
Wired Remote Controller
ZX60451

Wireless Remote Controller


YB1FA
Y512
RS-422/485
Repeater

Key-card Control Board


MK03

Key-card

IR Receiver Unit
JS01
(Field supplied)

Note:
Control network sketch is for reference only,
please refer to the equipment manuals for actual cable connection method.

44

Air Conditioning
Central Control
RS-232 to RS-422/485
Converter

Building
Management

INVENTOR AC Eudemon 2009


(Monitoring Software)
Module link

FE30-00/A(M)

Transmission line (INV network)


Group controller line
Remote Controller line

RS-232 to RS-422/485
Converter

Modbus network

Web Monitoring Client

IR receiver line
Key-card control board line

Internet

Key-card signal line

Web Monitoring Client

Communication module
ME30-00/E2
Centralized Controller
CE51-24/E(M)

Smart Zone Controller


CE50-24/E

Building Management System

BMS Interface (Modbus)


ME30-00/E2

Commissioning Program (Software)


Text Parser

45

CONTROLLERS COMPARISON
ITEM

Connections

Control
functions

Wired
Smart Centralized
Wired
Wireless Wireless
INVENTOR
BMS
Group
Remote
Controller
Zone
Remote
remote
remote
AC Eude- Interface
Controller
Controller
Controller CE51-24/
Controller
Controller controller
mon 2009 (Modbus)
ZJA011
Z63351F/
CE50-24/E E(M)
XK02
YB1FA
Y512
Z60351*

Max Nos. of Outdoor Units

64

Max Nos. of Wired Controller

16

16

1024

n*255*16 n*255*16

Max Nos. of Indoor Units

16

16

1024

n*255*16 n*255*16

ON/OFF

Fan Speed

Vertical Swing

Energy Saving Mode

Turbo Mode

Light

Clock

Indoor unit Address

0.5h

1min

0.5h

0.5h

0.5h

0.5h

1min

1sec

Weekly Timer

Centralized Week Timer

Group Week Timer


Shielding
Centralized Shielding

Group Shielding
Centralized Control

Group Control

Note:
n: Nos. of serial port
Control functions availability is based on the indoor units. Please refer to the users manual of indoor unit for details.

46

Lock
ON/OFF Timer

Centralized
Control

Week

Minimum Timer Gap

Shielding

Room Temp.

Sleeping Mode
Errors

Timer

n*255

Mode Setting

Drying

Display

n*255

COMMENTS
OF CONTROL FUNCTIONS
) ON/OFF Timer Function

) Sleeping Function

Under ON/OFF state, set the unit to be automatically turned


on or turned off in 0.5h hours (1n<48).

Automatically corrects the set temperature in order to


prevent excessive cooling or heating during sleep. In cooling
or defrosting mode, the set temperature will automatically
increase 2C in 2 hours (1C per hour) and then the unit will
operate at such temperature. In heating mode, the set temperature will automatically decrease 2C in 2 hours (1C per
hour) and then the unit will operate at such temperature.

) Error Display
When the malfunction occurs during
the operation, the room temperature display area will show the error
code.
The picture here shows the code of
compressor high-pressure protection.

Timer setting

Timer setting

60min

60min
1 0C

2 0C

1 0C

) Energy Saving Function


By setting the minimum value of setting temperature in
cooling and defrosting mode as well as the maximum value
in heating mode, the unit can operate in smaller temperature
range so as to save energy.

) Switch between Fahrenheit


and Celsius Scale
Under OFF state, press MODE and buttons simultaneously
to switch between C and between F.

2C

Note: There is no SLEEP function in FAN mode.

) Memory Function
After power failure, if the unit is energized again, it will operate according to previous set, which includes setting temp,
fan speed, swing angle, energy-saving mode, blow function
etc.

) Blow Function
(Only for cooling and heating mode)

) Turbo Function
(In COOL or HEAT mode)
The unit operates at super-high fan speed so as to cool or
heat quickly so that the ambient temperature approaches
the set temperature as soon as possible
When the difference between the room temperature and the
set temperature is not more than 2C, this function will be
turned off automatically.

When the unit is turned off, the indoor fan will keep running at
low speed for 10min so as to dry the indoor evaporator,
in order to prevent mildew and keep users healthy.
This function can be memorized.

) Mute Function
(Only for cooling and heating mode)

) Shield Function
(Remote monitoring)
The indoor unit is operated by remote control. At the same
time the functions of the wired controller, such as ON/OFF,
temp., mode setting, energy saving function etc, are shield.

Common mute function: the unit automatically operates at


low speed and the fan speed cant be adjusted at that time.
Auto mute function: The unit will enter mute operation
according to discrepancy between room temperature and
setting temperature.
At that time, fan speed can be manually turned down.

47

WIRED REMOTE
CONTROLLER
Z60351F/Z63351F (Heat pump)

51
1F (H
Hea
at pu
pump
mp
p)
Z60351F/Z63351F
(Heat
pump)
51
1F (C
Coo
ooli
ling
li
ng
go
onl
nlly)
nl
y)
y)
Z60151F/Z63151F
(Cooling
only)

ON/OFF
Temperature setting
Fan speed setting
Energy-saving function
Room temperature display
Sleep function
Infrared remote control function is available
and the remote controller is optional

ON/OFF Timer
Operation mode setting
Vertical swing
Self-diagnosis function (Error code display)
Memory function
Child lock function

Operating Mode Display


(COOL, DRY, FAN, HEAT)

Mode Setting Button

Sleep Mode Display


Temperature Setting Button
Room Temperature Display
/Error Displa
Fan Speed Display
(HIGH, MID, LOW, AUTO)
Fan Speed Setting Button
Set Temperature Display
Sleep Mode Setting Button*
Defrosting Display
Timer Setting Button
Timer Display
Signal Receiver
(For Remote Controller)

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

ON/OFF button

Z63351F / Z60351F
DC12V (Supplied by the indoor unit)
85x85x20
94

* Z60351F is for duct type indoor unit, and swing function is unavailable;
Z63351F is for other types of indoor unit, button SLEEP changes to SWING, and sleep function is unavailable.

48

WIRED REMOTE
CONTROLLER
ZX60451

ON/OFF
Displayed as white characters on
black background
Fan speed setting
Self-diagnosis function (Error code
display)
Turbo cooling/heating function
Quiet function
Enquire and setting address of wired
controller

ON/OFF Timer
Temperature setting
Vertical swing
Environmental temperature display
Evaporation function
Shield function
Infrared remote control function is
available and the remote controller is
optional

Operating Mode Display


(COOL, DRY, FAN, HEAT)

Touchable wired controller


Operating mode setting
Energy saving function
Sleep function
Memory function
Child lock function

Defrosting Operation Display

Sleep Mode Display

Key- card Display

Swing Display

Lock Display
Timer Display

Fan Speed Display


(AUTO, TURBO, LOW, MID, HIGH)

Set / Room Temprature Display


Function Display Area

Temperature /Timer /
Quiet Mode Setting button

Fan Speed Setting Button


Operation Mode Setting Button

Enter / Cancel Button

On/Off Button

Functions Setting Button

Timer Setting Button

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

ZX60451
DC12V (Supplied by the indoor unit)
92x92x24
116

49

WIRELESS REMOTE
CONTROLLER
Y512

ON/OFF
Temperature setting
Fan speed setting
Child lock function

ON/OFF Timer
Operation mode setting
Vertical swing
Sleep function

Fan Speed setting button


Swing Button
Fan Speed Setting Display
(HIGH, MID, LOW, AUTO)
Operation Mode Display/
(AUTO, COOL, DRY, FAN, HEAT)
Room Temperature/
Malfunction Display

Sleep Mode Display


Timer Display
Sleep Button
Light ON/OFF Button
Temperature/Timer
Setting Button
Timer ON Setting Button
Timer OFF Setting Button
Mode Setting Button

ON/OFF Button

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

50

Y512
AAA 1.5Vx2
159x56x18
92

WIRELESS REMOTE
CONTROLLER
YB1FA

ON/OFF
Temperature setting
Fan speed setting
Energy-saving function
Room temperature display
Turbo cooling/heating function
Mute function
Child lock function

ON/OFF Timer
Operation mode setting
Vertical swing
Self-diagnosis function (Error code display)
Sleep function
Blow function
Memory function (Turbo, Energy save, Quiet,
Evaporation, etc. )
Clock display

Fan Speed
(HIGH, MID, LOW, AUTO)
Operating Mode Display
(AUTO, COOL, DRY, FAN, HEAT)

Room Temperature/Malfunction Display


Timer Display

Sleep Mode Display


Temperature Type Display
Swing Angle Display
ON/OFF Button

Child Lock Display


Light Displayer
Mode Setting Button

Temperature/
Timer Setting Button
Fan Speed Setting Button
Clock Setting Button

Swing Mode Setting Button


Timer Setting Button

Blow Function ON/OFF Button


Temperature Display Button
Turbo Mode Setting Button

Light ON/OFF Button


Sleep Mode Setting Button

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

YB1FA
AAA 1.5Vx2
122x44x21
70

51

GROUP CONTROLLER
ZJA011

) Group monitoring control and group wired control


t l are the
th
h two
t
main control functions for group Controller.
Group monitoring controller can monitor or control 16 indoor units of a group for inquiry and single or centralized
control.
Features:
For a region consisted of 1-16 indoor units both single and central control are available.
The wired controller buttons in a region of 16 indoor units can be shielded or locked.
It can time 16 indoor units in a region.
It has the function of power-off memory.

Note: Wired controller must be reserved with the indoor unit that has been matched.
Group wired controller could replace 1-16 selected wired controllers, in order to uniformly set or control the
indoor units.
Features:
It can uniform the time for the selected indoor units.
It can replace the wired controller, in order to control the selected indoor units in a region.
It has the function of power-off memory.

Note: The wired controller that is matched with the indoor unit must be removed and the indoor unit must be
re-energized after debugging.

No. Of indoor Unit


Inquiry/Single or Central Control Setting Button

Inquiry/Control Display

Operating Mode Setting Button


(COOL, DRY, FAN, HEAT)

Operating Mode Display/


(COOL, DRY, FAN, HEAT)
Error display for indoor
or outdoor unit

Long-Distance Shield Status Display


Value Setting Button for Temperature/
Timer/Indoor Unit Number Selecting
(Under INQUIRY Status)

Room temperature display/


Malfunction display
Fan Speed Display
(AUTO, HIGH, MID, LOW)

Forced Operation Display


Fan Speed/ Swing Setting Button

Lock Display

Defrosting Operating Display

Swing Display
Set Temperature/Timer
Time Display

Timer Button
(Under SINGLE / CENTRAL Status)
ON/OFF Timer Inquiring of On-line Indoor Uni
(Under INQUIRY Status)

ON/OFF Button

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

52

ZJA011
DC12V (Supplied by the indoor unit)
85x85x20
94

SMART ZONE
CONTROLLER
CE50-24/E
When the indoor units are connected to 3 sets of INV outdoor units, the air duct type
indoor unit can be also connected.
Directly controls 16 indoor units in the network without extra communication module.
played
If an indoor unit is being operated by its own control group, it can be inquired and displayed
on the operation status.
Remote shield function.
Timer function.
Weekly Timer Function.

Operating Mode Display


(AUTO, COOL, DRY, FAN, HEAT)
Current Day of Week
and Time Display

Fan Speed Display


(HIGH, MID, LOW, AUTO)

Shield Status Display


(From long distance)
Setting Temperature
/ NO. of Indoor Unit Display

Error/Child Lock/Lock Display


Environmental Temperature
/COM # Display
On-line or Selected Indoor
Unit No. Display

Timer Display

Operation Mode Setting Button


(COOL, DRY, FAN, HEAT)
Indoor Unit NO.
/ Week Selecting

Fan Speed/Swing Setting


Set Temperature/Timer Setting Button

Shield Setting Button

On/Off Button
Timer/Clock Setting Button

Central Control Setting

Max 16

Serial 1 (multirequency)

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

Serial 2 (multirequency)

Serial 3 (multirequency)

CE50-24/E
220V~240V, 50/60Hz
120x120x62
391

53

CENTRALIZED
CONTROLLER
CE51-24/E(M)

Clock setting.
Error alarm and error code display
Single/Group/Center Control
(including weekly timer setting, shield setting, etc)
64 communication modules can be connected and
1024 sets of indoor units can be controlled.

Inquire and control the ON/OFF, operation mode,


set temperature, fan speed, swing state, etc. of indoor unit.
Automatically detect and display the status of online region
and indoor unit (including operation mode, set temperature,
fan speed, swing, weekly timer, shield, etc).
Long distance shield function.
Up to 1km communication wires without repeaters.

Error Display

All Indoor Units ON/OFF Button

Current Region No. and Unit No.


Display (for indoor unit)

Operation Mode Display


Fan Speed Display
(HIGH, MID, LOW, AUTO)

Group No. Display


Online Region No. Display*

SWING Operation Display

Online Indoor Unit No. Display

Control Command Sending Display

CENTER/GROUP
Operating or Setting Display

Shield Status Display

Day of Week and Time Display

Weekly Timer Display


Set Temperature Display

Weekly Timer Display

Room Temperature Display

Direction Key (UP/DOWN/LEFT/RIGHT)

Swing Operation Setting Button


Temperature Setting Button

Function Setting Confirmation Button

Operation Mode Setting Button


Grouping Information Setting Button

Shield Setting Button

Back to Superior Menu Button

ON/OFF Button

Center Control Setting Button


Clock Setting Button

Timer Setting or Inquiring Button

Group Control/Setting Button

Fan Speed Setting Button

Cancel Button

Max 64
Communication
Module

Max 16

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

Communication
Module

Max 16

CE51-24/E(M)
220V~240V, 50/60Hz
185x131x68
557

* All indoor units connected by one communication module are automatically distributed in one region.

54

Communication
Module

Max 16

IR RECEIVER
& KEY-CARD CONTROL BOARD
JS01 / MK03

) IR receiver
JS01
It is applicable to INV duct type indoor unit
and equipped with LED lamp for status
indication and infrared remote control function.
LED Lamp

Signal Receiver: it is used for receiving


command sent from remote controller
Heating ON/OFF and Cooling ON/OFF

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

JS01
DC5V (Supplied by the indoor unit)
120x70x58.5
172

) Key-card Control Board


MK03
This direction control board is only suitable for INVENTOR multi-variable (INV) indoor
unit with gate-control function.
The AC will operate after plugging in the gate-control card and stop operating after
pulling out the card.
Upon pulling out the card in order to stop the unit, the running states of the unit will
be memorized.
After plugging in the card, the unit will be under standby state or resume running
according to settings.
The AC will operate when the customer plugs in the card and automatically stop
when he pulls out the card. This ensures that the unit will turn off after people leave
the room and that energy will be saved.

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

MK03
220V~240V, 50/60Hz or DC5V~24V (Supplied by the indoor unit)
73x73x36
65

55

COMMUNICATION
MODULE
ME30-00/E2

) Functions
The communication module (ME30-00/E2) is used for transforming and transmitting
signals of the computer and the air conditioning system. It acts as a communication
controller.
Modbus protocol and RS485 interface are adopted so that the unit can be connected to users BMS system and other networks.
Lots of monitoring nodes make possible to have as many as 255 units in the same network.
Control of setting parameter is available.
Monitoring of operation state is available.
Monitoring of malfunction state is available.

POWER

RS485 Interface

Power Indicator (Red)


Communication Indicator (Green)

PC or COM2 of Other Module

Unit
9~12V DC 800mA

Model Name
Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

56

ME30-00/E2
220V~240V, 50/60Hz
185x131x68
557

COMMISSIONING PROGRAM
Text Parser

) Brief introduction
This software receives data from the INV system through local COM port or network (both internet and LAN are suitable) and
then analyses these data according to communication protocol.
Running parameters of unit, after analysis, will be displayed and saved in real time. There are two kinds of displaying methods,
the text displaying and the curve displaying. The analytic data can be saved in database. Technician and service person can use
this software to do commissioning.

Real-time parameter display

Operating System

CPU
HDD
Memory

Curves Analysis

Microsoft Windows 2000 Professional (English version / Service pack 4 or later)


Microsoft Windows XP PROFESSIONAL (English version / Service pack 2 or later)
Microsoft Windows Vista Home premium / Business / Enterprise / Ultimate
Microsoft Windows 7 Home premium / Business / Enterprise / Ultimate
64-bit version of Windows are not supported
Intel Pentium / Celeron, AMD Athlon / Duron 1Ghz or higher
4 GB or more of free space
512MB or more

57

RS-422/485 R
REPEATER (ISOLATED)
) Functions
Rs-422/485 repeater (isolated) is used to amplify the communication signal when the
quantity of communication modules in the network is more than 30, or communication
distance is longer than 800m.

RS-422/485

Operation Indication LEDs

RS-422/585

Power

Maximum 30 Nos. of module


between two repeaters

Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

58

Maximum cable length


between two repeaters is 800m

Input AC 220V~50/60HZ Output 12~30 DC 800mA


96 x 100.6 x 25
277

RS-232 TO RS-422/485
CONVERTER (ISOLATED)
) Functions
RS232-RS485 opt electronic isolated converter is used for converting the signal between
computer / BMS System (RS232) and INVENTOR Air Conditioning Systems (RS485).

RS-422/485

Operation Indication LEDs

RS-232
Power

Power Supply
Dimensions (HxWxD) (mm)
Weight (g)

Input AC 220V~50/60HZ Output 12~30 DC 800mA


96 x 100.6 x 25
263

59

INVENTOR AC EUDEMON
2009 PC SUIT
) Brief introduction of INVENTOR AC Eudemon 2009
009
INVENTOR AC Eudemon 2009 is the latest solution for controlling, monitoring and management of INVENTOR central air conditioning systems with your PC.
Maximum Connectable Systems/ Outdoor Units: 255
Maximum Connectable Indoor Units (INV System): 4,000
Maximum Control Distance: 5,600m (Standard distance 800m & extendable to 5.6km)
Compatible Systems: INV System, Centrifugal Chiller, Water-cooled screw chiller, Air-Cooled screw chiller,
Air-cooled scroll chiller, etc.

) System schematic plan


INVENTOR AC Eudemon 2009 Management System/BMS Network Schematic Plan

Personal Computer

BMS System

INVENTOR AC Eudemon 2009

Serial Port
Max 255

More
AC Units

Convertor
RS485 Network
Protocol (Modbus)

Max 255
Communication
Module 1
Max 16

Communication
Module n
Max 16

Note:
In a RS485 Network, different type of systems cannot be connected.
User can only choose either INVENTOR AC Eudemon 2009 or BMS (Modbus) to manage the Air-conditioner system.

60

Communication
Module 255
Max 16

) Functions of INVENTOR AC Eudemon 2009


Air Conditioning System running status / error information checking.
Air Conditioning System Operation Parameter setting.
Multi User Management with different authorized levels.
Intelligent Timer with simplified schedule management.
Multi Serial port and Multithreading Monitoring.
Automatic Detection enables quick monitoring even if the user is not familiar with the concept of equipments, protocol and
models, etc.
Vivid network plan helps the easy understanding of the physical structure of the air conditioning system.
Vivid location plan helps easy management of the air conditioning system.

) Functions of INVENTOR AC Eudemon 2009


Model name

INVENTOR AC Eudemon 2009 FE30-00/A(M)

Content

INVENTOR AC Eudemon 2009 CD-ROM x 1 PCS


RS232-RS485 Opto electronic Isolated Convertor x 1 PCS

) Requirement of PC for INVENTOR AC Eudemon 2009


Operating System
CPU
HDD
Memory

Microsoft Windows XP PROFESSIONAL (English version / Service pack 2 or later)


Microsoft Windows Vista Home premium / Business / Enterprise / Ultimate
Microsoft Windows 7 Home premium / Business / Enterprise / Ultimate
64-bit version of Windows are not supported
Intel Pentium / Celeron, AMD Athlon / Duron 1Ghz or higher
10 GB or more of free space
1GB or more
Internet Explorer 6.0 SpP1 or later (.NET Framework supported)
Microsoft . NET framework 2.0

Software Environment

Microsoft SQL Server 2005 Express


Microsoft Data Access Components (MDAC) 2.8 SP1 or later.
Microsoft Visual C++ 2008 Redistributable SP1

61

PIPING DESIGN PROGRAM


INV SELECTOR
) BRIEF Introduction
INVENTOR INV Selector is a program for doing the piping design of INV VRF systems.

Interface of the main program.

62

) The software provides two ways to output the design


Excel summary files: it consists of
the equipment summary, design condition,
system details and remote monitor detail.

AutoCAD drawings: Electrical & Communication


wiring design of the system.

Download VRF Selection Software www.inventor.ac/tech_spec

Operating System

CPU
HDD
Memory

Microsoft Windows 2000 Professional (English version / Service pack 4 or later)


Microsoft Windows XP Professional (English version / Service pack 2 or later)
Microsoft Windows Vista Home premium / Business / Enterprise / Ultimate
Microsoft Windows 7 Home premium / Business / Enterprise / Ultimate
64-bit version of Windows are not supported
Intel Pentium / Celeron, AMD Athlon / Duron 1Ghz or higher
4 GB or more of free space
512MB or more
AutoDesk AutoCAD Excel 2004/2005/2008

Software Environment

Microsoft Office Excel 2000/2003/2007 Professional


Microsoft Visual C++ 2008 Redistributable SP1

63

ENERGY RECOVERY
VENTILATION
) Introducing outdoor fresh air and discharging
arging indoor air.
air
Makes you feel comfortable as in the nature.

Shell

Indoor air outlet


Fresh air outlet

Indoors air inlet

Electrical box
Heat exchanger
Fresh air outlet
Air filter

Lug

) Energy saving
Unique by-pass mode can reduce power consumption of fan
motor, in order to prolong lifetime of the heat exchanger core.
By the combination of heat exchange mode and by pass mode,
the unit load can be reduced about 26% in a year.

Power reduction ratio

Internal heat exchanger performs cooling and heating


exchange between the discharged air and fresh air.
Energy-recovery rate above 70%, high energy saving.

0%
Direct fresh
air introduction

Air Supply
Discharge air

20%

Independent heat
exchange process

Temp plate

Heat exchange mode


Air exchange fan

Heat exchange element

26%

Heat exchange
combined with
by-pass proccess

By-pass mode
Room temperature
sensor

Air exchange fan

Heat exchange element

Indoor air temperature


sensor

Exchange
air

Return
air

Exchange
air

Return
air

Outdoor
air intake

Supply
air

Outdoor
air intake

Supply
air

Outdoor air temperature sensor

64

Air supply fan

Outdoor air temperature sensor

Air supply fan

) High efficiency heat exchange


The ERV can exchange the latent heat and sensible heat simultaneously, which can adjust temperature and humidity at the
same time. It can be widely applied where there is big humidity difference between indoor and outdoor.
Heat exchange (sensible heat) inside the core
Heat is exchanged between discharged air and fresh
air, so that the fresh air temperature to come down
and be close to the indoor temperature. The feeling of
uncomfortable is avoided and meanwhile the load of air
conditioning is effectively decreased.

Exchanege of humidity (latent heat)


The vapour on the side with high humidity is absorbed by hygroscopic agent and discharged to the side with low humidity
through capillary action of the fibber.
Through heat exchange between the indoor air and fresh
air, the internal heat exchanger reduces the fluctuation of
indoor temperature. At the same time it prevents from high
temperature difference of the supply air, while reducing the
operation load of the unit.

Moisture absorption
Move through capillary
Moisture release

Air Filtration and purification Function


Internal air filter keeps the fresh air introduced into room pure and dustless.
The efficient isolation between fresh air duct and discharge air duct ensures pure air supply.
With antibacterial and anti-mildew materials, the heat exchange core is suiting for healthy.
Wide range of models
7 models in a range of 350~3000m3/h, which can fit
for different spaces and reduce the waste of power. Wide
range from 350 to 3000 m3/h, matching with
buildings of various structures.

Flexible control
LED display
Energy saving mode
24h timer
Centralized controller
Weekly timer
Long-distance Monitoring Control (optional)

Reliability and easy maintenance


The complete unit with non-moving parts except the
fan motor can reliably operate for a long period of time,
without frequent maintenance.
Filter and heat exchange core can be easily taken out
from the access door for cleaning.

Low-noise Design
Build-in low noise ventilation fan.

Compact design and easy installation


With a minimum height of 360mm, the unit is space
saving. It can be installed inside limited ceiling spaces.

) Installation example
Fresh air duct

Fresh air inlet


Fresh air Supply

Indoor air outlet


Discharge air duct
Insulation material

Indoor
air return

Fresh air outlet

Room air inlet

65

SPECIFICATIONS
) ERV

MODEL
Power supply
Power Input (W)
Airflow rate
Sound pressure level (dB(A))
External static pressure
Temperature exchange efficiently
Enthalpy exchange efficiency

HRVQ-D3.5-K

H/M/L
H/M/L
H/M/L
Heating (H/M/L)
Cooling (H/M/L)

m3/h
CFM
Pa
%

Dimension (WxDxH) (mm)


Net weight (Kg)

MODEL
Power supply
Power Input (W)
m3/h
CFM

Airflow rate
Sound pressure level (dB(A))
External static pressure
Temperature exchange efficiently
Enthalpy exchange efficiency
Dimension (WxDxH) (mm)
Net weight (Kg)

66

Pa
Heating
Cooling

165
360/260/210
212/153/124
37
100/80/60
71/73/75
65/67/68
61/63/65
800x879x306
45

HRVQ-D5-K

HRVQ-D8-K

220 240V, 1Ph, 50Hz


262
400
500/380/300
800/600/480
294/224/176
471/353/282
39
45
100/80/60
110/85/65
68/70/72
70/72/74
62/64/65
63/65/67
57/59/61
60/62/64
800x879x306
832x1016x380
45
57

HRVQ-D10-K
440
1000/750/600
588/441/353
46
110/85/65
75/77/79
66/68/70
62/64/65
832x1016x380
57

HRVQ-D15-M

HRVQ-D20-M

HRVQ-D30-M

600
1500
882
48
150
73
65
60
1210x1215x452
100

380~415V 3N~50Hz
950
2000
1176
50
150
71
62
58
1210x1215x452
100

2800
3000
1176
54
220
70
62
58
1340x1550x572
240

CONNECTION BRANCHES
) Modular Outdoor
Unit Branch Joint

) Indoor Unit Y-Type


Branch Joint

Gas Pipe

Gas Pipe

Liquid Pipe

Liquid Pipe

Modular Outdoor Unit Branch Joint


Model Name
ML01R
ML02R

Configuration
Configuration

22.4 X 96
96 < X

Indoor Unit Y-Type Branch Joint


Model Name
FQ01A/A
FQ01B/A
FQ02/A
FQ03/A
FQ04/A
FQ01Na/A
FQ02Na/A
FQ03Na/A
FQ04Na/A
FQ05Na/A
FQ06Na/A
FQ07Na/A

Configuration
X 20.0
20.0 < X 30.0
30.0 < X 70.0
70.0 < X 135.0
135.0 < X
X 5.6
5.6 < X 22
22 < X 30
30 < X 68
68 < X 96
96 < X 135
135 < X

67

ALL UNITS ARE AVAILABLE FROM OUR SELECTED NETWORK


OF
AIR CONDITIONING PROFESSIONALS

No1

for the compressor


and for all parts of the unit

For more technical


al information
inform
mati
ma
tion
on d
download
dow
ownl
nlo
nloa
nl
oa
ad the te
technical
ec
files

www.inventor.ac/tech_spec
.inventor.ac/tech_spe
ec

www.inventor.ac