Académique Documents
Professionnel Documents
Culture Documents
TR-CS91
Note: This file was revised in 91. This is not it, it is the original from PageMaker 2. Check over the illustrations
carefully to find which Fig was revised. DL 6-26-95.
List of Tables
Table
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Page
2.
3.
4.
Item Contained In
Required Devices
Disconnecting Means to disconnect motor and controller
from the circuit. It must either open all ungrounded conductors
and be in sight from* controller or it must lock in the open
position. This design must indicate whether switch is open or
closed. The disconnect must be a switch rated in horsepower
or a circuit breaker of the inverse time or instantaneous trip
type. The disconnect, either switch or breaker, for 600 volts or
less motor circuits must be ampere rated for at least 115% of
full load current. It must also be capable of interrupting stalledrotor current.
Motor Feeder Short-Circuit Protection to protect the
motor-branch-circuit conductors, the motor control apparatus,
and the motors against overcurrent due to short circuits or
grounds. There must be one in each ungrounded conductor. It
must carry motor starting current, but not over 400% of full load
current. See Tables 4 and 5 for sizing.
Motor Controller to start and stop the motor. Select the
controller for motor basic HP and voltage. See Tables 10, 11,
14 and 15.
Overload Protection to protect the motor, control apparatus
and the branch-circuit conductors against excessive heating
due to motor overloads, stalled rotor and excessive cycling.
Select overloads sized at 125% or less of motor full load current
for motors with service factor of at least 1.15. Overload size
must not exceed 115% of full load current for all other motors.
in sight from must be visible and not more than 50 feet distant.
3
Electrical
Supply
Fusible
Safety Switch
or
Circuit Breaker
Manual or
Magnetic
Starter
Conductors
Non-Fused
Disconnect Switch
In Sight from Motor
Motor
Wiring Diagrams
There are two common types of wiring diagrams. The
control equipment supplier provides the standard
Wiring Diagram, showing the physical layout of
components and wiring. These diagrams depict the
exact connections required. Each manufacturer uses
unique connection points and physical layout, so each
drawing applies only to one manufacturer.
in the simplest manner with no attempt to show physical layout. This requires separation of the coils from
their contacts. A letter designation ties coil S and
contact S. Only Elementary Diagrams appear in this
manual. All cooling tower motors and control enclosures must be grounded, even though grounding
connections do not appear in this manual. The diagram symbols are shown below:
Selector Switch
2 Position
3 Position
A1
A2
X
X
Low High
Push Buttons
Single Circuit
Double Circuit
NO
NC
NO
NC
A1 X
A2
X
Hand Off Auto
A1
A1
A2
A2
Contacts
Timed Contacts - Contact Action
Retarded When Coil is
Energized
De-Energized
NO
NC
NO
NC
Instant Operating
NO
NC
Coil
Overload Relay
Thermal
A.C. Motor
Single
Three
Phase
Phase
*NO - normally open, NC - normally closed - contact position when not energized, pushed, etc.
F - Forward
LF - Low Forward
CR - Control Relay
OL - Overload
R - Reverse
LR - Low Reverse
M
- Program Timer
LOL - Low Overload
H - High
HF - High Forward
TR - Time Relay
HOL - High Overload
L - Low
T1,T2 - Motor Terminal
L1,L2 - Line Terminals
By far, the largest percentage of cooling tower motors
are three phase squirrel cage induction type. Only
these motors appear in the diagrams. For reference,
the three phase motor winding connections most often
T3
T6
T9
T1
T4
T7
T4
T8
T5 T2
High Voltage
Connection
T1
Low Voltage
Connection
T3
L1
L2
L3
L1
L2
L3
Low Speed
Connection
T1
T2
T3
T1
T2
T3
L1
L2
L3
T1
T2
T3
T7
T8
T9
T7
T8
T9
T1
T2
T3
T6
T4
T5
T4
T5
T6
T4
T5
T6
T6
T4
T5
L1
L2
L3
T2
T5
T6
High Speed
Connection
Control Enclosures
of a rod larger than .250" diameter. Live
parts must be at least 4" from the nearest
drain hole.
Type 3
Type 4
Type 7
Type 9
*The Code defines hazardous locations in Division 1 and Division 2. In general, starters for either location division must be in
explosion-proof enclosures. Motors for Division 1 locations must also be explosion-proof. Motors for Division 2 locations can
be any enclosure, so long as motor does not employ sliding contacts, centrifugal switches or other types of switching mechanisms, or integral resistance devices.
Point of Utilization
(Motor Design) Voltage
115
200
230
460
575
2300
4000
4600
6600
KVA per HP
0-3.14
3.15-3.54
3.55-3.99
4.0-4.49
4.5-4.99
5.0-5.59
5.6-6.29
6.3-7.09
7.1-7.99
8.0-8.99
Code Letter
L
M
N
P
R
S
T
U
V
KVA per HP
9.0-9.99
10.0-11.19
11.2-12.49
12.5-13.99
14.0-15.99
16.0-17.99
18.0-19.99
20.0-22.39
22.4-and up
Type of Motor
Nontime
Delay
Fuse
Max.
300
300
250
150
400% not
exceeding
600 amps
175
175
175
175
225%
125
125
125
125
Inverse
Time
Breaker
Max.
Recommended
700
700
700
700
1300%
250
150-225%
250
150-225%
200
150-200%
150
150%
400% (with full
load current less
than 100 amps)
300% (with full
load current
greater than 100
amps)
HP
1/2
3/4
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
250
Full
Load
Amps
2.3
3.2
4.1
6.0
7.8
11.0
17.5
25.3
32.2
48.3
62.1
78.2
92.0
119.6
149.5
177.1
220.8
285.2
358.8
414.0
552.0
Fuse Size
Overload
Short*
& Short
Circuit
Circuit
Protection
Protection
Only
2.8
4
4
5.6
5
8
7
12
9
15
12
20
20
30
30
45
40
60
60
80
70
100
90
110
110
150
125
175
175
200
200
250
250
300
350
400
400
500
500
600
230 Volts
Full
Load
Amps
2.0
2.8
3.6
5.2
6.8
9.6
15.2
22
22
42
54
68
80
104
130
154
192
248
312
360
480
460 Volts
Fuse Size
Overload
Short*
& Short
Circuit
Circuit
Protection
Protection
Only
2.5
3.5
3.5
5
4.5
6.25
6.25
9
8
12
12
15
17.5
30
25
40
35
50
50
70
60
90
80
110
100
125
125
150
150
200
175
200
200
300
300
350
350
450
405
500
600
Full
Load
Amps
1.0
1.4
1.8
2.6
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
180
240
Fuse Size
Overload
Short*
& Short
Circuit
Circuit
Protection
Protection
Only
1.25
1.8
1.6
2.5
2.25
3.2
3.2
4.5
4
6
5.6
9
9
15
12
20
17.5
25
25
40
30
50
40
50
50
70
60
80
80
110
90
125
110
150
150
175
175
200
200
250
300
350
300
350
* Based on wire size in Tables 14 and 15 for RH, RHW, RVH, THW, THWN, & XHHW wire.
Thermal Magnetic
90
450
100
500
125
600
150
700
175
800
200
900
225
1000
250
1200
300
1400
350
400
Amp
Rating
3
7
15
30
50
100
150
Instantaneous Trip
Trip
Amp
Range
Rating
8-28
225
18-70
400
50-180
600
100-350
800
150-580
300-1100
750-1500
Trip
Range
300-2250
500-4000
625-9000
625-9000
500
Standard
Fuse
3
7.5
15
25
50
75
Dual
Fuse
7.5
15
30
50
125
200
480V - 3 Phase
Non
Fuse
7.5
15
30
50
125
Standard
Fuse
5
15
25
50
100
150
Dual
Fuse
15
30
60
125
250
400
600V - 3 Phase
Non
Fuse
20
50
75
125
250
400
Standard
Fuse
7.5
15
30
60
125
200
Dual
Fuse
20
50
75
150
350
500
Non
Fuse
20
60
100
150
350
500
elements.
Good practice dictates using dual-element fuses rather
than one-time fuses. Dual-element fuses interrupt
higher fault currents, generate less heat in the control
box, and permit use of smaller fuses for better protection. In addition, if a fuse clip is loose on a one-time
fuse, the case can carbonize and fail when the fuse
blows. A loose clip on a dual-element fuse will cause
the fuse to blow before the case can carbonize.
Single Element
35
100
40
110
45
125
50
150
60
175
70
200
80
225
90
250
300
350
400
450
500
600
0.1
0.15
0.2
0.3
0.4
0.5
0.6
0.8
1.0
1.125
1.25
1.4
1.6
1.8
2.0
2.25
Dual Element
2.5
6.25
2.8
7
3.2
8
3.5
9
4.0
10
4.5
12
5.0
15
5.6
17.5
20
25
30
35
40
45
50
60
70
80
90
100
110
125
150
175
200
250
300
350
400
450
500
600
Circuit Breaker
Circuit breakers used for motor protection usually have
both thermal and magnetic trip elements. The thermal
elements protect on overloads where inverse time
tripping is desired. The magnetic trip elements instantly operate the breaker in case of dangerous
overload or short-circuit faults. Usually circuit breakers
do not operate as fast as fuses at high overcurrents,
but operate faster on normal overloads.
Combination Starter
A combination starter includes circuit breakers and
disconnect switches as part of the motor controller.
Lightning Arrester
Motor Controller
Manual Controller
Manual Controllers consist of snap-action switch(es)
and overload(s). They are available in NEMA 1, 4, 7,
9, and 12 enclosures. Standard sizes appear in Table
10.
Manual controllers are available for reversing or twospeed two-winding motor control. Single phase
controllers are available with selector switch and pilot
light.
60 Hz
200 or
230 V
3
7.5
Horsepower at:
Three Phase
50 Hz
60 Hz
380 V
480 or 575 V
5
5
15
10
Single Phase
50 or 60 Hz
50 or 60 Hz
115 V
230 V
1
2
2
3
3
5
Magnetic Controller
Types of Magnetic Starters
The motor controller normally used on cooling towers is
a magnetic starter. The standard magnetic starter uses
a magnetic coil to close contacts and springs and/or
gravity to open them. Some type of pilot device, such
as a push button or float switch, actuates the magnetic
coil. The main types of magnetic starters are acrossthe-line, reduced voltage, and reconnectable.
Connection
Phase Voltage
Starting Current (phase)
Starting Current (line)
Starting Torque
Approx. Cost Comparison
Primary
AutoPart
Resistance Transformers
Winding
Y
Y
Y
KV*
KV
V
KIS
KIS
.6 TO .8 iS
KIS
K2IS
.6 TO .8 iS
K2TS
K2TS
.4 TO .48 TX
4.2
4.3
3.0 (2 steps)
(closed
transition)
Star Delta
Y
.58V
.333 IS
.333 IS
.333 TS
5.2
(closed
transition)
*K is a constant equal to the reduced voltage over the full line voltage.
B1 STOP
START
OL
F
L1
F
B2
L2
L3
F
F
FUNCTION at 60F
B2
B1
X
X
Hand
Off Auto
Continuous
Current Rating
Amperes
9
18
27
36
45
90
135
570
540
810
1215
2250
200 V
60 Hz
1.5
3
7.5
10
25
40
75
150
Three Phase
230 V
380 V
60 Hz
50 Hz
1.5
1.5
3
5
7.5
10
15
25
30
50
50
75
100
150
200
300
300
450
800
Single Phase
460 or 575 V 50 or 60 Hz 50 or 60 Hz
60 Hz
115 V
230 V
2
1/3
1
5
1
2
10
2
3
3
5
25
3
7.5
50
100
200
400
600
900
1600
Continuous
Current Ratings
Amperes
180
360
11
2 Wire Control
STOP
1
L1
START
2
F
L2
OL
3
L3
TR
TR
F
RES
RES
RES
OL
Motor
Reconnectable Starters
12
Stop
Start
L1
TR
TR TR
4
TR
L2
L3
F S
F
OL
S S
OL
OL
T2
T1
OL
T3
Motor
2 Wire Control
Stop
Start
L1
L2
TR1
TR1
TR1
L3
TR1
S
T
F
F
OL
OL
OL
T2
T1
Motor
OL
T3
2 Wire Control
Stop
TR
Start
OL
S
L1
L2
TR
L3
Fuse
S
OL OL OL
OL OL OL
T1 T2 T3
T7 T8 T9
Motor
running delta, with enough leads brought out to connect the motor for a star (or wye) start. In the first step
of starting with open transition, the motor is connected
wye and the timer energized. At a predetermined time
interval, the motor is disconnected and reconnected to
the line wired delta. Locked rotor amperage on the star
2 Wire Control
L1
Stop
Start
3
TR
S
S
F
L2
TR
L3
F
F
S
OL
OL OL OL
T1 T2 T3
T6 T4 T5
Motor
In the closed transition type, the motor remains connected to the line through resistors during the connection change from star to delta.
Special Features
Single-Speed Motor Starters
Auxiliary Contacts: Auxiliary contacts, sometimes
called interlocks, are mechanically connected to the
starter so that energizing the starter coil opens the
contacts (N.C.) or closes the contacts (N.O.). Most
starters come with one auxiliary contact. This contact
appears in the holding circuit with three-wire control or
it can control operation of other equipment with twowire control. Additional contacts (1 to 4, depending on
starter) are available factory installed or for field
installation.
the starter coil and does not require a coil of its own
(see page 24). Other manufacturers use a timer with
its own coil. On page 24, these timer coils must be in
parallel with the proper starter coil (forward timer coil in
parallel with forward starter coil, etc.). Timers are
available with two different types of contact operation:
16
STOP
L1
START
OL
L2
L3
F
OL OL OL
Motor
Space Heater
STOP
START
CR1
L1
F
L2
L3
F
G
CR1
TR
CR1
OL OL OL
CR2
TR
CR2
CR2
Heating Transformer
CR2
CR2
OL
Motor
17
19
Table 14 - Average Motor Full Load Amps and Minimum Conductor and Conduit Size
(1984 N.E.C.) for 60 Cycle Induction Type A.C. Motor Circuits 200 V & 230 V
200 V
230 V
1/2
3/4
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
2.3
3.2
4.1
6.0
7.8
11.0
17.5
25.3
32.2
48.3
62.1
78.2
92.0
119.6
149.5
177.1
220.8
285.2
358.8
414
552
2.0
2.8
3.6
5.2
6.8
9.6
15.2
22
28
42
54
68
80
104
130
154
192
248
312
360
480
200 V
230 V
200 V
230 V
Wire
Conduit
Wire
Conduit
Wire
Conduit
Conduit
Wire
Conduit
Conduit
AWG or
AWG or
AWG or RH, RHW, THWN AWG or RH, RHW, THWN
MGM
MGM
MGM RUH, THW XHHW
MGM RUH, THW XHHW
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
12
1/2
14
1/2
12
1/2
1/2
14
1/2
1/2
10
1/2
10
1/2
10
3/4 *
1/2
10
3/4 *
1/2
8
1/2
8
1/2
8
1 *
1/2
8
1 *
1/2
6
1
6
1
6
1 1/4 *
3/4
8
1 *
1/2
3
1 1/4
4
1
4
1 1/4 *
1
6
1 1/4 *
3/4
2
1 1/4
2
1 1/4
3
1 1/4
1
4
1 1/4 *
1
0
1 1/2
1
1 1/4
2
1 1/4
1 1/4
3
1 1/4
1
00
1 1/2
0
1 1/2
0
2
1 1/4
2
1 1/4
1 1/4
0000
2
000
2
00
2
1 1/2
0
2 *
1 1/4
300
2 1/2
250
2 1/2
0000
2 1/2 *
2
000
2
1 1/2
400
3
300
2 1/2
250
2 1/2
2
0000
2 1/2 *
2
600
3
500
3
400
3
2 1/2
300
2 1/2
2 1/2
900
4
700
3 1/2
600
3 1/2 *
3
500
3
3
2000
1250
4 1/2
900
4
3 1/2
700
3 1/2 *
3 1/2
2000
1250
5 *
4
900
4
3 1/2
Table 15 - Average Motor Full Load Amps and Minimum Conductor and Conduit Size
(1984 N.E.C.) for 60 Cycle Induction Type A.C. Motor Circuits 460 V & 575 V
460 V
575 V
1/2
3/4
1
1 1/2
2
3
5
7 1/2
10
15
20
25
30
40
50
60
75
100
125
150
200
1.0
1.4
1.8
2.6
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
180
240
0.8
1.1
1.4
2.1
2.7
3.9
6.1
9
11
17
22
27
32
41
52
62
77
99
125
144
192
460 V
575 V
460 V
575 V
Wire
Conduit
Wire
Conduit
Wire
Conduit
Conduit
Wire
Conduit
Conduit
AWG or
AWG or
AWG or RH, RHW, THWN AWG or RH, RHW, THWN
MGM
MGM
MGM RUH, THW XHHW
MGM RUH, THW XHHW
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
14
1/2
14
1/2
14
1/2
1/2
14
1/2
1/2
12
1/2
14
1/2
12
1/2
1/2
14
1/2
1/2
10
1/2
12
1/2
10
3/4 *
1/2
12
1/2
1/2
8
1/2
10
1/2
10
3/4 *
1/2
10
3/4
1/2
6
1
8
1/2
8
1 *
1/2
8
1
1/2
6
1
6
1
6
1 1/4 *
3/4
8
1
1/2
4
1
6
1
6
1 1/4 *
3/4
6
1 1/4
3/4
3
1 1/4
4
1
4
1 1/4 *
1
6
1 1/4
3/4
1
1 1/4
3
1 1/4
3
1 1/4
1
4
1 1/4
1
0
1 1/2
2
1 1/4
2
1 1/4
1 1/4
3
1 1/4
1
000
2
0
1 1/2
0
2 *
1 1/4
2
1 1/4
1 1/4
0000
2
000
2
000
2
1 1/2
0
2
1 1/4
300
2 1/2
0000
2
0000
2 1/2 *
2
000
2
1 1/2
400
3
300
2 1/2
300
2 1/2
2 1/2
0000
2 1/2
2
700
3 1/2
500
3
500
3
3
300
2 1/2
2 1/2
20
The device that changes d.c. back to variable frequency a.c. is called an inverter. Three basic inverter
designs are common:
(1) Six steps voltage inverter (VSI).
(2) Six steps current inverter (CSI).
(3) Pulse width modulating inverter (PWM). This
inverter uses constant voltage d.c.
Programmable Controllers
It has always been possible to reduce the cooling effect
on a multi-fan tower by turning off fans or reducing fan
speed with a multi-speed motor. Either an operator
changed speeds manually or automatic controls with
thermostats changed the speed using relays and
timers.
A thermostat normally controlled each speed change
on each motor. The thermostats were all set at different temperatures to prevent changing speed on more
than one fan at a time. By adding timers or a multicircuit timer, it was possible to use one thermostat
(temperature) to increase speed and another thermostat (temperature) to decrease speed of all fans as
required.
Programmable controllers are now available to increase or decrease fan speed; wait for the water
22
9.
10.
11.
12.
13.
Single or multi-speed.
Motor horsepower (each speed).
Line voltage.
Frequency (cycles).
Number of phases. (Number of wires if twophase.)
Full load motor current (at each speed if more
than one speed).
Enclosure type by NEMA type number and size
number.
Desired control type on cover: start-stop
buttons, plain cover, or selector switch marked
Hand, Off, and Automatic.
On multi-speed motor starters, state if consequent pole or separate winding. State if motor
is constant torque, variable torque, or constant horsepower.
On Multi-speed and single-phase motor starters,
send terminal diagram of motor.
State whether pilot control device is two or
three-wire. Three-wire is for push button
control. If two-wire, describe pilot device. State
voltage if different from line voltage.
State if compelling relay, accelerating relay,
decelerating relay, or extra interlocks are
desired on starter.
State if motor will be reversed. If two-speed
motor, will motor be reversed one-speed or twospeed. If reverse one-speed, which speed.
1.
2.
3.
4.
Safety Switch
1.
2.
3.
4.
5.
6.
7.
8.
Float Switch
1.
2.
3.
4.
5.
6.
7.
Timing Relay
1.
2.
3.
4.
Voltage.
Horsepower rating.
Whether a.c. or d.c.
If a.c., state phases.
Chain or rod operated.
Length of chain or rod.
Enclosure type by NEMA number.
23
FWD
R
OL
L1
F
CR1
CR1
L2
L3
R R R
REV
F F F
CR2
G
F
R
CR2
OL
T1 T2
T3
Fan
Motor
Item
Starter
Push Button
Allen Bradley
Bulletin 505
Bulletin 800T
Cutler Hammer
File A50
File E20
General Electric
CR 309 Form
CR 104P Form
24
Square D
Class 8736
Class 9001
Westinghouse
Class A-211
Type PB2
Low
A1
Stop
OL
L1
CR1
L2
A2
CR1
L3
High
H
L
LOL
H
HOL
A1
A2
T1 T2 T3
T6 T4 T5
X
X
Safe
Run
Fan
Motor
Item
Starter
Push Button
Allen Bradley
Bulletin 520
Bulletin 800T
Cutler Hammer
File A700
File E20
General Electric
CR 309 Form
CR 104P Form
Square D
Class 8810
Class 9001
Westinghouse
Class A-900
Type PB2
L1
L2
L3
L
Note:
L
LOL
T1 T2 T3
Fan
Motor
25
H
HOL
A1
Stop
L1
L3
20 Sec
HF
LF
A2
L2
LF
CR1
LR 2 Min TR1
LR
CR3 CR2 CR1
LF LF LF LR LR LR HF HF HF
CR2
HF
HF
2 Min LR
LF
TR1
HF
HF HF
T3
T1 T2
T6 T4
T5
OL
Fan
Motor
A1
A2
X
Run
X
Safe
L1
L2
L3
LF LF LF LR LR LR HF HF HF
Note:
T3
T1 T2
T11 T12
T13
Fan
Motor
Item
Starter
Push Button
Selector
Switch
Allen Bradley
Bulletin 520
Bulletin 800T
Bulletin 800T
Cutler Hammer
File A700
File E20
File E20
General Electric
CR 309 Form
CR 104P Form
CR 104P Form
26
Square D
Class 8810
Class 9001
Class 9001
Westinghouse
Class A-900
Type PB2
Type PB2
A1
Stop
Low
CR1
High
L3
F
CR1
A2
OL
L1
L2
L
H
R
H
L
LOL
H
C1
C2
HOL
T1 T2 T3
T6 T4 T5
A1
A2
X
Run
C1
C2
X
Safe
X
Fwd
X
Rev
Fan
Motor
Item
Starter
Push Button
Selector
Switch
Allen Bradley
Bulletin 520
Bulletin 800T
Bulletin 800T
Cutler Hammer
File A700
File E20
File E20
General Electric
CR 309 Form
CR 104P Form
CR 104P Form
Square D
Class 8810
Class 9001
Class 9001
Westinghouse
Class A-900
Type PB2
Type PB2
L1
L2
Note:
L3
F
LOL
T1 T2 T3
Fan
Motor
27
HOL
A1
Functions
@ 60F
Vib
Switch
Functions
@ 40F
B1
L1
A2
L2
L3
B2 Stop
L
L
LOL
CR1
Low
CR1
CR1
HOL
High
H
H
T1 T2 T3
OL
T6 T4 T5
Fan
Motor
A1
A2
X
Run
B1
B2
X
Safe
X
X
Hand
Item
Allen Bradley
Cutler Hammer General Electric
Square D
Starter
Bulletin 520
File A700
CR 309 Form
Class 8810
Push Button Bulletin 800T
File E20
CR 104P Form
Class 9001
Temperature
See Minneapolis Honeywell, Penn or Barber Coleman
Switch
Off
Auto
Westinghouse
Class A-900
Type PB2
L1
L2
Note:
L3
L
L
LOL
T1 T2 T3
Fan
Motor
28
H
HOL
29
Run
X
Safe
L3
L2
L1
L3
L2
L1
B1
B2
X
Hand
Fan
Motor
T11 T12
LR LR LR LF LF LF HF HF HF
T3
T1 T2
Off
Auto
C1
C2
T13
T5
For
A2
A1
X
Rev
VIB
SW
B2
B1
Stop
T1
Low
LF
HF
CR2
High
CR1
T2
C2
C1
LF
Note:
T1 Functions at 60F
T2 Functions at 40F
2 Min
TR1
20 Sec
TR3
2 Min
TR2
Type PB2
Class A-900
Westinghouse
OL
TR1
TR3
HF
CR2
TR2
LR
LF
CR1
Item
Allen Bradley
Cutler Hammer General Electric
Square D
Starter
Bulletin 520
File A700
CR 309 Form
Class 8810
Push Button Bulletin 800T
File E20
CR 104P Form
Class 9001
Temperature
See Minneapolis Honeywell, Penn or Barber Coleman
Switch
T6 T4
Fan
Motor
HF HF
T3
T1 T2
LF LF LF LR LR LR HF HF HF
A1
A2
Vib
Switch
L1
Functions
@ 60F
Functions
@ 40F
H
B1
A2
L2
L
H
L3
F
B2 Stop
CR1
Low
CR1
CR1
High
L
L
L
LOL
HOL
C1
C2
T1 T2 T3
Fan
Motor
F
R
OL
T6 T4 T5
A1
A2
X
Run
X
Safe
B1
B2
X
X
Hand
Off
C1
C2
X
For
Auto
Item
Allen Bradley
Cutler Hammer General Electric
Square D
Starter
Bulletin 520
File A700
CR 309 Form
Class 8810
Push Button Bulletin 800T
File E20
CR 104P Form
Class 9001
Temperature
See Minneapolis Honeywell, Penn or Barber Coleman
Switch
Westinghouse
Class A-900
Type PB2
L1
L2
L3
R
Note:
LOL
T1 T2 T3
Fan
Motor
30
X
Rev
HOL
31
L3
L2
L1
Fan
Motor
T11 T12
T13
T3
T1 T2
HF HF
LF LF LF LR LR LR HF HF HF
T3
T1 T2
A1
A2
Run
Fan
Motor
T4 T6
A2
X
Safe
A1
VIB
SW
C2
C1
Stop
C1
C2
CR2
X
Hand Auto
TM2
TM1
CR2
LF
HF
CR1
CR2
CR2
Low
HF
High
2 Min
LR
Westinghouse
Class A-900
Type PB2
Type PB2
Program
Timer
CR2
TM
LR
TR1
CR1
LF
HF
Square D
Class 8810
Class 9001
Class 9001
OL
2 Min
TR1
20 Sec
HF
LF
Item
Allen Bradley
Cutler Hammer General Electric
Starter
Bulletin 520
File A700
CR 309 Form
Push Button Bulletin 800T
File E20
CR 104P Form
Selector
Bulletin 800T
File E20
CR 104P Form
Switch
Program
See Zenith or Automatic Timing & Controls
Timer
T5
LF LF LF LR LR LR HF HF HF
L3
L2
L1
32
Time
Fwd
Run
X
Off
X
Rev
X
Safe
L3
L2
L1
L3
L2
L1
B1
B2
X
Hand
Off
Auto
T3
T1 T2
Fan
Motor
T6 T4
Fan
Motor
T2 T3
T11 T12
T13
LR LR LR LF LF LF HF HF HF
T1
HF HF
T5
LR LR LR LF LF LF HF HF HF
D1
D2
C1
C2
A1
A2
VIB
SW B1
B2
Functions
@ 32F
Stop
CR2
CR1
D2
D1
HF
LF
CR2
CR1
Functions
@ 40F
C2
C1
CR2
High CR1
CR1
CR2
Low
LF
2 Min
TM2
TR1
Functions 20 Sec
@ 60F
HF
TM1
OL
CR2
CR1
TR1
HF
LF
TM
Westinghouse
Class A-900
Type PB2
2 Min
LR
LR
Item
Allen Bradley
Cutler Hammer General Electric
Square D
Starter
Bulletin 520
File A700
CR 309 Form
Class 8810
Push Button Bulletin 800T
File E20
CR 104P Form
Class 9001
Selector
See Minneapolis Honeywell, Penn, or Barber Coleman
Switch
Program
See Zenith or Automatic Timing & Controls
Timer
A2
A1
Cooling Technologies