Vous êtes sur la page 1sur 10

IPASJ International Journal of Electrical Engineering (IIJEE)

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Modelling, Simulation and Control of Utility


Grid Integrated Solar Photovoltaic System Using
Matlab
Kiran R Patil1, Shiddalingesh Akki2, Gaurav Nayak3, Ashok Muvva4 ,Basavaraj Totad 5
1

Asst. Professor, BVB college of Engg. & Tech, Hubli


2

Student, BVB college of Engg. & Tech, Hubli

ABSTRACT
In this paper we are modelling a solar based non-conventional energy generation system using MATLAB software. A 500-KW
grid connected PV system in a radial 2-bus test system is modeled and simulated using Matlab/Simulink software to study the
effects of this technology on the system under different levels of solar irradiation. PV module with a central three level inverter
is developed in the thesis, which is more suitable for medium power applications. However, the output of solar arrays varies
due to change of solar irradiation and weather conditions. Therefore, the maximum power point tracking algorithm is
implemented in DC/DC converter (Boost converter) to enable PV arrays to operate at maximum power point. The widely used
MPPT technique, incremental conductance algorithm is employed to control the boost converter. Then the central three level
inverter is controlled by decoupled current (Id, Iq) control algorithm and interfaced with the utility grid via the distribution
network. Besides, the current control of the inverter is independent of maximum power point control of the DC/DC converter.
Finally, system performance and transient responses are analyzed. And system stability is evaluated when solar irradiation
change or system fault happens. The system is simulated in MATLAB.

Keywords: MPPT, voltage source converter, Boost converter, Inverter, utility grid.

1. INTRODUCTION
The need for renewable energy sources is on the rise because of the acute energy crisis in the world today. At present,
solar cell (PV) generation is assuming increased importance as a renewable energy sources application because of
distinctive advantages such as simplicity of allocation, high dependability, absence of fuel cost, low maintenance and
lack of noise and wear due to the absence of moving parts. Many research institutions have dedicated their time to
harness the optimum power from it[1]. India plans to produce 20 Gigawatts Solar power by the year 2020, whereas we
have only realized less than half a Gigawatt of our potential as of March 2010. Solar energy is a vital untapped resource
in a tropical country like ours. The main hindrance for the penetration and reach of solar PV systems is their low
efficiency and high capital cost. In case of PV plant, the optimum efficiency is affected mainly by three factors: the
efficiency of the PV panel (in commercial PV panels it is between 8-15%[2]), the efficiency of the inverter (95-98%[3])
and the efficiency of the maximum power point tracking (MPPT) algorithm (which is over 98%[4]).Improving the
efficiency of panels and inverter is not easy as it depends on the technology availability and expenses, however
improving the MPPT algorithm is an inexpensive way. The VSC controller is also used to reduce the Total Harmonic
Distortions (THD) and synchronize the inverter output current with the grid voltage, in order to obtain a unitary power
factor.

2.THE PHOTOVOLTAIC CELL


A simple solar cell consist of solid state p-n junction fabricated from a semiconductor material (usually silicon), when it
is exposed to sunlight the photons are absorbed and hole-electron pairs may be formed as shown in figure 1. If these
mobile charge carriers reach the vicinity of the junction, the electric field in the depletion region will push the holes
into the p-side and push the electrons into the n-side. The p-side accumulates holes and the n-side accumulates
electrons, which creates a voltage that can be used to deliver current to a load[5]. If electrical contacts are attached to
the top and bottom of the cell, electrons will flow out of the n-side into the connecting wire, through the load and back
to the p-side. Since wire cannot conduct holes, it is only the electrons that actually move around the circuit. When they
reach the p-side, they recombine with holes completing the circuit. By convention, positive current flows in the
direction opposite to electron flow.

Volume 3, Issue 5, May 2015

Page 1

IPASJ International Journal of Electrical Engineering (IIJEE)


Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm
Email: editoriijee@ipasj.org
ISSN 2321-600X

A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Figure 1 Generic PV cell

3.THE PV CELL MODEL


A simple equivalent circuit model for a photovoltaic cell consists of a real diode in parallel with an ideal current source
as shown in Figure 2. The ideal current source delivers current in proportion to the solar flux to which it is exposed.

Figure 2 A simple ideal equivalent circuit for a PV cell


The practical model is obtained after considering the following parameters:

Temperature dependence of the diode reserved saturation current Is.


Temperature dependence of the photo current Iph.
Shunt resistance Rsh, in parallel with the diode, this corresponds to the leakage current to the ground.
Series resistance Rs [6](internal losses due to the current flow) which gives a more accurate shape between the
maximum power point and the open circuit voltage.

Figure 3 Practical equivalent circuit of a PV cell


The load current is given by
(1)
Where,
The photo current is given by,
(2)
The diode current is given by,

(3)
The current flowing through the parallel resistance is given
by,

Volume 3, Issue 5, May 2015

Page 2

IPASJ International Journal of Electrical Engineering (IIJEE)


Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm
Email: editoriijee@ipasj.org
ISSN 2321-600X

A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

(4)
The saturation current is given by,

(5)
The reverse saturation current is given by,

(6)
-23

Where k is the Boltzmann constant (1.38 x 10 JK-1), q is the electronic charge (1.602 x 10-19 C), T is the cell temperature (K),
n is the diode ideality factor, RS the series resistance () and RSh is the shunt resistance (). GK is the solar irradiance ratio. Eg
is the Band-gap energy of the cell, 1.12eV. NS is the number of cells connected in series. Np is the number of cells connected in
parallel. TOP is cell operating temperature, Tref is the cell temperature at 250 c, IS is Diode reversed saturation current, Irs is
Diode reversed saturation current at operating temperature.

Figure 4 Simplified diagram of the grid-connected PV system


To provide proper interface between grid-connected PV systems and the utility grid (Figure 4), some conditions must be
satisfied, such as phase sequence, frequency and voltage level matching. Providing these conditions strongly depends
on the applied power electronics technology of PV inverters. The electric characteristics of a PV unit can generally be
expressed in terms of the current-voltage or the power voltage relationships of the cell. The variations in these
characteristics directly depend on the irradiance received by the cell and the cell temperature. Therefore, to analyze the
dynamic performance of PV systems under different weather conditions, a proper model is required to convert the effect
of irradiance and temperature on produced current and voltage of the PV arrays.

4.THE BOOST CONVERTER


A boost converter is a dc to dc voltage converter with an output dc voltage greater than input dc voltage. Filters made
of capacitor and inductor is used to reduce the ripple in voltage and current respectively, is used at the output stage of
the converter[7]. The basic operating principle of the converter consists of the two distinct states.
In on state, switch is closed, resulting in an increase in the inductor current.
In off state, switch is open, resulting in decrease in the inductor current.

Figure 5 DC-DC Boost Converter

Volume 3, Issue 5, May 2015

Page 3

IPASJ International Journal of Electrical Engineering (IIJEE)


Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm
Email: editoriijee@ipasj.org
ISSN 2321-600X

A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

(7)
Where, V0= Boost converter output voltage, VS= Boost converter input voltage, D= Duty cycle of boost converter
switch
So, with variable Duty cycle we can extract constant voltage with maximum power with the help of maximum power
point tracking(MPPT).

5.INCREMENTAL CONDUCTANCE MPPT TECHNIQUE


The disadvantage of the perturb and observe method to track the peak power under fast varying atmospheric condition
is overcome by IC method . The IC can determine that the MPPT has reached the MPP and stop perturbing the
operating point. If this condition is not met, the direction in which the MPPT operating point must be perturbed can be
calculated using the relationship between dl/dV and I/V This relationship is derived from the fact that dP/dV is
negative when the MPPT is to the right of the MPP and positive when it is to the left of the MPP. This algorithm has
advantages over P&O in that it can determine when the MPPT has reached the MPP, where P&O oscillates around the
MPP. Also, incremental conductance can track rapidly increasing and decreasing irradiance conditions with higher
accuracy than P and O.

Figure 6 Graph Power versus Voltage for IC Algorithm


Fig-6 shows that the slope of the P-V array power curve is zero at The MPP, increasing on the left of the MPP and
decreasing on the Right hand side of the MPP. The basic equations of this method are as follows[8].
(8)
(9)
(10)
This method exploits the assumption of the ratio of change in output conductance is equal to the negative output
Conductance Instantaneous conductance. We have,
P=VI
Applying the chain rule for the derivative of products yields to
P/V = [(VI)]/ V

At MPP, as P/V=0
The above equation could be written in terms of array voltage V and array current I as
I/V = - I/V

Volume 3, Issue 5, May 2015

Page 4

IPASJ International Journal of Electrical Engineering (IIJEE)


Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm
Email: editoriijee@ipasj.org
ISSN 2321-600X

A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

The MPPT regulates the PWM control signal of the DC-DC boost converter until the condition: (I/V) + (I/V) = 0 is
satisfied. In this method the peak power of the module lies at above 98% of its incremental conductance. The Flow
chart of incremental conductance MPPT is shown below [9].

Figure 7 IC MPPT algorithm

6.POWER CONTROLLER
The controller sense the grid voltage and grid current and give the corresponding grid active and reactive power. And
also the power controller sense the inverter output voltage and current and give the corresponding active, reactive
power. After that through PI controller we get the direct axis reference current (Idref) which is the one input of another
controller which is current controller. Here we also sense the load voltage and load current and determine the RMS
value of the load. By using PI controller we can get quadrature axis reference current which is another input of current
controller.

7.CURRENT CONTROLLER
The current controller mainly used for getting triggering pulse as per the reference value. Here we take the inverter
output current and using by MATLAB software converts the current into direct axis and quadrature axis current. This
two currents and current given by power controller outputs compared and using PI controller we get the pulse.

8.MATLAB / SIMULINK SIMULATIONS

Figure 8 grid connected PV farm

Volume 3, Issue 5, May 2015

Page 5

IPASJ International Journal of Electrical Engineering (IIJEE)


A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

Figure 9 Output current from PV panel

Figure 10 Photocurrent, Iph

Figure 11 Shunt current, Ish

Figure 12 Diode current, Id

Volume 3, Issue 5, May 2015

Page 6

IPASJ International Journal of Electrical Engineering (IIJEE)


A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

Figure 13 Reverse saturation current, Is

Figure 14 Reverse saturation current at Top, Irs

Figure 15 IC MPPT method

Figure 16 VSC Controller

Volume 3, Issue 5, May 2015

Page 7

IPASJ International Journal of Electrical Engineering (IIJEE)


A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

9.RESULTS

Figure 17 Grid power

Figure 18 Grid voltage

Figure 19 Grid current

Figure 19 Error value produced in IC MPPT

Volume 3, Issue 5, May 2015

Page 8

IPASJ International Journal of Electrical Engineering (IIJEE)


A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

10.CONCLUSION
A MATLAB/SIMULINK model for the 500 KW, 2 radial grid connected PV farm was developed and presented in this
paper. This model is based on the fundamental circuit equations of a solar PV cell taking into account the effects of
physical and environmental parameters such as the solar radiation and cell temperature. We can use VSC controller to
synchronize PV system with grid. As a result of the study, one can from this model as a photovoltaic generator in the
framework of the Sim-Power-System MATLAB/SIMULINK toolbox in the field of solar PV power conversion systems.
In addition, such a model would provide a tool to predict the behaviour of grid connected PV farm under climate and
physical parameters changes.

11.ACKNOWLEDGMENT
On the submission of the paper report of MODELLING, SIMULATION AND CONTROL OF UTILITY GRID
INTEGRATED SOLAR PHOTOVOLTAIC SYSTEM USING MATLAB We would like to extend our gratitude and
sincere thanks to our mentor Professor H.N.Siddrameshwar and supervisor Asst. Professor Kiran.R.Patil, for their
constant motivation and support during the course of our paper. We truly appreciate and value their esteemed guidance
and encouragement from the beginning to the end of this paper.

References
[1] Sustainable Energy for All http://www.sustainableenergyforall.org
[2] Trends in photovoltaic applications. Survey report of selected IEA countries between 1992 and 2009,
International Energy Agency, Report IEA-PVPS Task 1 T1-19:2010, 2010.
[3] Sunny Family 2010/2011 - the Future of Solar Technology,SMA product catalogue,2010.
[4] L. Piegari, R. Rizzo, "Adaptive perturb and observe algorithm for photovoltaic maximum power point tracking,"
Renewable Power Generation, IET, vol. 4, no. 4, pp. 317-328, July 2010.
[5] Gilbert M. Masters, Renewable and Efficient Electric Power Systems.
[6] Francisco M. Gonzlez-Longat - 2do congreso iberoamericano de estudiantes de ingeniera elctrica, electrnica y
computacin, Model of Photovoltaic Module in Matlab (II CIBELEC 2005).
[7] Daniel.W.Hart, Power electronics.
[8] Azadeh Safari and Saad Mekhilef, Member, IEEE , Simulation and Hardware Implementation of Incremental
Conductance MPPT With DirectControl Method Using Cuk Converter.
[9] M.Lokanadham,PG Student, K.Vijaya Bhaskar,Asst. Professor, Incremental Conductance Based Maximum Power
Point Tracking (MPPT) for Photovoltaic System M.Lokanadham, K.Vijaya Bhaskar / International Journal of
Engineering Research and Applications (IJERA) ISSN:2248-96.
AUTHORS
Kiran R Patil received the B.E. degree in Electrical and Electronics Engineering from The
National Institute of Engineering, Mysore and M.Tech. degree in Energy Systems & Management
from Sri Jayachamarajendra College of Engineering, Mysore, Karnataka. He is currently perceiving
Ph.D in BVBCET affiliated to VTU, Belgaum. His areas of interest are Distributed Generations,
Non-conventional energy systems and Energy Auditing.. He is currently working as Asst. professor
in BVB College of Engineering & Technology, Hubli, Karnataka.
Shiddalingesh Akki is perceiving B.E. degree in Electrical and Electronics Engineering in BVB
College of Engineering & Technology, Hubli, Karnataka and his areas of interests are Nonconventional energy systems and power Electronics.
Gaurav Nayak is perceiving B.E. degree in Electrical and Electronics Engineering in BVB
College of Engineering & Technology, Hubli, Karnataka.

Ashok Muvva is perceiving B.E. degree in Electrical and Electronics Engineering in BVB
College of Engineering & Technology, Hubli, Karnataka.

Volume 3, Issue 5, May 2015

Page 9

IPASJ International Journal of Electrical Engineering (IIJEE)


A Publisher for Research Motivation........

Volume 3, Issue 5, May 2015

Web Site: http://www.ipasj.org/IIJEE/IIJEE.htm


Email: editoriijee@ipasj.org
ISSN 2321-600X

Basavaraj Totad is perceiving B.E. degree in Electrical and Electronics Engineering in BVB
College of Engineering & Technology, Hubli, Karnataka.

Volume 3, Issue 5, May 2015

Page 10

Vous aimerez peut-être aussi