SD200
HYDROPOWER STATION
AUTOMATION SYSTEM
OPERATION MANUAL
SD 200
Hydropower Station Automation System
Operation Manual
2005
Contents
1.
Summary..........................................................................................................1
1.1.
Installation introduction......................................................................................1
1.2.
1.3.
1.4.
1.5.
1.6.
1.7.
2.
Communication server.........................................................................................3
2.2.
Function introduction.........................................................................................25
3.2.
Running program................................................................................................25
3.3.
Usage method.......................................................................................................25
3.4.
Operating illustration.........................................................................................32
4.
Introduction..........................................................................................................33
4.2.
Basic usage............................................................................................................37
4.3.
File management.................................................................................................46
4.4.
5.
Picture display.....................................................................................................51
5.2.
Picture print.........................................................................................................51
5.3.
Alarm.....................................................................................................................51
5.4.
Remote Control....................................................................................................52
5.5.
Events record.......................................................................................................52
5.6.
Events print..........................................................................................................53
5.7.
5.8.
5.9.
5.10.
5.11.
Mutual-check....................................................................................................53
5.12.
Option................................................................................................................54
6.
6.2.
6.3.
Report design.......................................................................................................55
6.4.
Report display......................................................................................................57
7.
7.2.
7.3.
7.4.
7.5.
1 Summary
SD200
1. Summary
1 Summary
SD200
SD 200
Figure 2-1
In Figure 2-2, there are Port information box, Send and receive data box, Save data box,
Message stop roll select box and Port select pull-down list box in the window of program.
Figure 2-2
In Port information box, it can display some basic information of Ethernet and serial port. Select
the port in Port select, which basic information can display in Port information. Send and
3
SD 200
receive data box can display the data of sending and receiving, it can analyze the information of
communication protocol according to these data. If the different port corresponds to the different
protocol, it can separate to display the sending data and receiving data when select the port in
Port select.
Save data button is for saving the data in Send and receive data box, as Figure 2-3 shows,
clients can select a file name or input a file name by self, the data in Send and receive data box
can save to the file. We suggest saving as the text file type .text.
Figure 2-3
Message stop roll select box is for clients to select the roll message or not, stop the roll message
can observe the message better. The quit password of communication server is xxxx.
Figure 2-4
SD 200
Figure 2-5
SD 200
Figure 2-6
SD 200
Figure 2-7
Figure 2-8
Range of complication: MOBBUS TCP protocol applies to the PLC Ethernet module of
MODICON serial, the PLC Ethernet module of GEPLC serial (mantissa number is GH and
anon). Others apply to this protocol of PLC network module. Only apply to the network port
ENET.
Setting method and parameter illustration as Figure 2-9 shows.
IsOnlan: it indicates whether PLC Ethernet module connect to the network, and configure the IP
address. If match two criteria, then select it. If do not select it, all uplink machines cannot collect
the data in PLC.
Double network: the uplink machine whether communicates to PLC through the double network
and process as the backup for each other.
PLC number: PLC number such as LCU1 numbers 1, LCU2 numbers 2.
PLC type: PLC type, it is GEPLC or MODICONPLC, etc. Because different PLC of
MODBUSTCP protocol has the different access, it keeps these options.
PLC IP address 1: the first IP address of Ethernet module in PLC. Caution this IP address must
configure in the same network field with the downlink machine of Host.
PLC IP address 2: the second IP address of Ethernet module in PLC. Caution this IP address must
configure in the same network field with the downlink machine of Host.
7
SD 200
Timing configuration: timing configuration between the uplink machine and PLC, include two
timing approaches: Up timing PLC is timing to uplink machine; down timing uplink machine
is timing to PLC. Time can store in the register cell of PLC as timing.
PLC memory address distribution: Start address is start address of all contents store in R register
in PLC. Length is the length of different board. Different boards contain different quantity of
contents.
Telesignal content: each board contains 24 telesignal contents;
Communication content: each board contains 24 telemetry contents;
Simulation content: each board contains 16 telemetry contents;
Temperature content: each board contains 16 telemetry contents;
Synthesis switch content: each board contains 24 telesignal contents;.
SOE content: each board contains 5 words;
Control record: each board contains 5 words;
Other telemetry content: each board contains 24 telemetry contents;
Other telesignal content: each board contains 24 telesignal contents;
Telecontrol content: each board contains 32 telecontrol contents;
Teleadjust content: each board contains 32 teleadjust contents.
Figure 2-9
SD 200
Range of complication: apply to PLC Ethernet of GE PLC serial; only apply on the network
port ENET.
Setting method and parameter illustration as Figure 2-10 shows.
Figure 2-10
This configuration of protocol is same as MODBUS TCP protocol; the difference is the Title of
PLC, because adopting GE HCT protocol need to HCT drivers, in HCT configuration need to
configure PLC1, PLC2, etc. Here the title should accord to the title of HCT. Material
configurations are: No.1 LCU configure to PLC1, No.2 LCU configure to PLC2, by analogy.
Range of complication: monitoring system receive the data that the sending device adopting
the CDT protocol send to (Host); monitoring system sends data to the control terminal (slave
machine). Only apply on the serial ports COM1 COM10.
Setting method and parameter illustration as Figure 2-11 shows (Host), as Figure 2-12 shows
(slave machine).
Adopting CDT protocol coding data usually include: main telemetry, minor telemetry, general
telemetry, telesignal, electric energy. In Figure 2-11 and Figure 2-12, it needs to configure the
number of these contents. Other devices send the number of data to monitoring system as Host;
Monitoring system send the number of data to other devices (such as control terminal) as the slave
9
SD 200
machine.
Local address and Opposite terminal address: they configure by monitoring system when
monitoring system as Host; they configure by the control terminal then monitoring system as the
slave machine.
A: Monitoring system receive the data other devices sending as Host
After receiving these data store to the database of monitoring system, so it needs to configure the
start address in the database. For example, if SD200 monitoring system receives 124 main
telemetry variables, the start address in database is 10120011, and then these variables occupy the
database from 10120011 to 10125041. Other telemetry variables cannot occupy these cells in the
database.
As Host mentions whether it needs to run the command such as timing, reset, setup, etc. from
clients. If select the corresponding check box it can run such commands on the slave machine.
Figure 2-11
B: Monitoring system sends the data to other devices as the slave machine.
What the data sending need to confirm by the control terminal, the data usually is discontinuous in
monitoring system, so it needs to set up the address for each telemetry and telesignal variable. And
because each telemetry variable transfer by 12 bit in CDT, the transferring maximum of each
telemetry variable cannot more than 0x07FF, so it needs to process the proportional action
10
SD 200
coefficient product for each telemetry variable without being out of limit. Different telemetry
variable adopt different coefficient, if adopt too small coefficient, then the precision of transferring
data would decline at last.
Figure 2-12
Range of complication: apply to the electric meter adopting DL/T 645 protocol, such as
WeiSheng electric meter; this protocol only applies on the serial ports COM1 COM10.
Setting method and parameter illustration as Figure 2-13 shows.
Electric meter address: because monitoring system and electric meter usually adopt No. 485
communication method, it needs to set the address to each table. The setting method of each
electric meter refer to their instruction, therefore special write the electric setting program
DianDuAddressSet.exe to work in.
Monitoring system collect the data from each electric meter as Table 2-1 shows. The data from
each table in monitoring database occupy 20 telemetry cells. The start address in database can
configure in the dialog box of DLT645 protocol configuration.
11
SD 200
If it needs to time the electric meter, then select the timing check box.
Figure 2-13
NOO
NAME
NOO
NAME
10220011
10220111
10220021
Positive peak-peak
power of Generator 3#
active
10220121
Positive peak-peak
power of Generator 3#
10220031
10220131
10220041
10220141
10220051
10220151
10220061
10220161
10220071
Reverse peak-peak
power of Generator 3#
active
10220171
Reverse peak-peak
power of Generator 3#
10220081
10220181
10220091
10220191
10220101
10220201
reactive
reactive
Table 2-1
Range of complication: WeiSheng electric meter, only apply on the serial ports COM1
COM10.
Setting method and parameter illustration as Figure 2-14 shows.
Electric meter address: because monitoring system and electric meter usually adopt No. 485
12
SD 200
communication method, it needs to set the address to each table. The setting method of each
electric meter refer to their instruction, therefore special write the electric setting program
DianDuAddressSet.exe to work in.
Monitoring system collect the data from each electric meter as Table 2-2 shows. The data from
each table in monitoring database occupy 64 telemetry cells. The start address in database can
configure in the dialog box of V41 protocol configuration.
Figure 2-14
NOO
10220011
NAME
Active power of Generator 3#
10221091
10220021
10221101
10220031
Voltage of Generator 3#
10221111
10220041
Current of Generator 3#
10221121
10220051
10221131
10220061
10221141
10220071
10221151
10220081
10221161
10221191
10220091
10220101
10220111
NOO
10221171
10221181
NAME
Valley of reverse reactive
power of Generator 3# in this
month
Peak-peak of reverse reactive
power of Generator 3# in this
month
Total capacitive reactive
power of Generator 3# in this
month
Peak of capacitive reactive
power of Generator 3# in this
month
Off-peak of capacitive reactive
power of Generator 3# in this
month
Valley of capacitive reactive
power of Generator 3# in this
month
Peak-peak of capacitive
reactive power of Generator
3# in this month
Total reverse active power of
Generator 3# in this month
Peak of reverse active power
of Generator 3# in this month
Off-peak of reverse active
power of Generator 3# in this
month
Valley of reverse active power
13
10220121
10220131
10220141
10220151
Generator 3#
Off-peak of reactive power of
Generator 3#
Valley of reactive power of
Generator 3#
Peak-peak of total reactive
power of Generator 3#
Total capacitive reactive
power of Generator 3#
SD 200
10221201
10221211
10221221
10221231
10221241
10222021
10221011
10222091
10221021
10222101
10221031
10222111
10220161
10220171
10220181
10220191
10220201
10220211
10220221
10220231
10220241
10221041
10221051
10221061
10221071
10222011
10222031
10222041
10222051
10222061
10222071
10222081
10222121
10222131
10222141
10222151
of Generator
Peak-peak of reverse active
power of Generator 3# in this
month
Total positive active power of
Generator 3# in last month
Peak of positive active power
of Generator 3# in last month
Off-peak of positive active
power of Generator 3# in last
month
Valley of positive active power
of Generator 3# in last month
Peak-peak of positive active
power of Generator 3# in last
month
Total reactive power of
Generator 3# in last month
Peak of reactive power of
Generator 3# in last month
Off-peak of reactive power of
Generator 3# in last month
Valley of reactive power of
Generator 3# in last month
Peak-peak of reactive power
of Generator 3# in last month
Capacitive reactive power of
Generator 3# in last month
Peak of capacitive reactive
power of Generator 3# in last
month
Off-peak of capacitive reactive
power of Generator 3# in last
month
Valley of capacitive reactive
power of Generator 3# in last
month
Peak-peak of capacitive
reactive power of Generator
3# in last month
Reverse active power of
Generator 3# in last month
Peak of reverse active power
of Generator 3# in last month
Off-peak of reverse active
power of Generator 3# in last
month
Valley of reverse active power
14
10221081
SD 200
10222161
Table 2-2
Range of complication: double mimic screen, only apply on the serial ports COM1
COM10.
Setting method and parameter illustration as Figure 2-15 shows.
Double mimic screen communication method is: each telesignal box drives 16 telesignal statuses;
each telemetry box drives 1 telemetry status. Each telesignal box address is different to each
telemetry box address. So it needs to evaluate for each telesignal and telemetry address from 1 to
255. It can configure the color of combination and discerption for the telesignal display.
According to Figure 2-15, for example: if it needs to display 75 telesignal statuses (The telesignal
status is green as discerption with 0; is red as combination with -1), and 12 telemetry statuses.
First select 0 is green; 1 is red. Number of the telesignal box is 5 (75/16=5), number of telemetry
is 12; configure address for each telesignal and telemetry box; set 16 telesignal addresses in the
database, such as 10101012, 10101052, etc. total is 75; set 1 telemetry database address for each
telemetry box, such as 10135018, etc.
Figure 2-15
15
SD 200
Range of complication: No. 94 agreement applies to exchange the information between the
protector and the background monitor, which usually adopt serial port. It only applies on the
serial ports COM1 COM10. The monitoring system collects the data of No. 94 agreement
device when the monitoring system as the mainframe. For requirement of update, it keeps the
port for No. 94 agreement as the slave machine.
Setting method and parameter illustration as Figure 2-16 shows.
The data adopting No. 94 agreement commonly involve: telemeter, telesignal, Event telesignal,
Fixed Value and Time. It configures for these data as below:
16
SD 200
Figure 2-16
Notice: each CPU needs to configure options as above.
CPU serial number: select corresponding CPU serial number to configure, begin at 1.
Main parameter setting of the typical device adopting No. 94 protocol as below:
A. NanZi WMZ-41A differential protector TongZiHAo project
Baud rate: 9600; 8 bit as data bit; 1 bit as stop bit; unverity; WMZ-41A setting as the slave
machine; CPU number: 2; each Fixed value number is: 11, 11; telesignal variable number is:
15, 15.
B. NanZi WPD243 line protector JiaoJiaoHe project
Baud rate: 9600; 8 bit as data bit; 1 bit as stop bit; unverity; WPD243 setting as the slave
machine; CPU number: 1; Fixed value number is: 31; telemeter variable number is: 12;
telesignal variable number is 16.
The table of measuring point of typical device adopting No. 94 protocol is as annexed Table 1,
2.
17
SD 200
Figure 2-17
B. Parameter illustration
As the mainframe in communication: if the circulation collect the data from devices, must
select this option. And as the mainframe or the slave machine arrange by both parts.
Demand time: when need to time devices, must select this option.
Demand telemeter: when need to attain telemeter from the device, must select this option.
When need other traffic, select corresponding check box.
Setting address: corresponding setting address is from 1 to 255.
Telemeter number: read telemeter number is from 0 to 125.
Telemeter protocol address: read the start address of telemeter data in MODBUS agreement.
Telemeter data type: select telemeter data type for transferring, usually it is HEX, but CD194E
adopt floating point numbers to transfer.
Telemeter serial number: select corresponding telemeter serial number to configure.
Telemeter proportion coefficient: infill corresponding serial number to telemeter proportion
coefficient. The infilling is 1 without any explanation.
18
SD 200
Telemeter database address: the start address in telemeter database. Occupy telemeter address
of LCU.
Telemeter request frame data length type: default is the number of R occupied. But some
factories do not adopt canonical protocol; date length is the number of byte.
telesignal request frame data length type: default is the number of R occupied. But the data
length of some factories is the number of byte or the number of telesignal from 0 to 250.
telesignal data denotation format: default 1 byte = 8 telesignal, sometime 1 byte = 1 telesignal.
In a similar way configure the database address for Fixed value, telesignal, etc. telemeter is
same as Fixed value, telesignal is similar to Fixed value, only the unit of telesignal occupying
the database address is 1 byte, for example 7 telesignal occupy 1 byte, and 9 telesignal occupy
2 byte. telesignal occupy the telesignal address of LCU.
Confirm: confirm modification, close dialog box.
Cancel: cancel modification.
Notice: read means that read the data from devices or system as the slave machine to devices
or system as the mainframe.
The setting of typical devices adopting the standard MODBUS protocol is as below:
A. NanZi nep988/nep983 device
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; nep988/nep983 device as the slave
machine.
B. KeYuan DCS system
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; monitoring system as the slave
machine.
Telesignal number: 8; telesignal protocol address: 0; telesignal function code: 3; remote
control number: 8; remote control protocol address: 0; remote control function code: 16.
Notice: unconfiguration option default 0.
Yangtse River SiFeiEr plating meter.
ChangKongSuo speed regulator.
19
SD 200
Parameter setting dialog box is as below figure shows. ( such as NARI speed regulator
communication)
B. Parameter illustration:
Setting address: corresponding setting address is from 1 to 254.
Telemeter number: the number of telemeter variable need to collect. Because different options
are for the different device, this option setting is from 0 to 125.
telesignal number: the number of telesignal variable need to collect. Because different options
are for the different device, this option setting is from 0 to 250.
Standby byte number: the number of standby byte need to collect. Because different options
are for the different device, this option setting is from 0 to 125.
Reading data protocol address: the start address of reading date in MODBUS agreement.
Because different options are for the different factory, this option setting is for it.
Reading data function code: the function code of reading data in MODBUS agreement.
Because different options are for the different factory, this option setting is for it.
Modify telemeter protocol address: write the start address of telemeter data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
Modify telemeter function code: write the function code of telemeter data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
Figure 2-18
Modify telesignal protocol address: write the start address of telesignal data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
Modify telesignal function code: write the function code of telesignal data in MODBUS
agreement. Because different options are for the different factory, this option setting is for it.
20
SD 200
Telemeter database start address: the start address of telemeter in database. Occupy the
telemeter address of LCU. Because different options are for the different project, this option
setting is for it.
Telesignal database start address: the start address of telesignal in database. Occupy the
telesignal address of LCU. The unit of telesignal occupying the database address is 1 byte, for
example 7 telesignal occupy 1 byte, and 9 telesignal occupy 2 byte. telesignal occupy the
telesignal address of LCU.
Confirm: confirm modification, close dialog box
Cancel: cancel modification.
Notice: The setting of typical devices adopting the NARI MODBUS protocol is as below:
A. NARI speed regulator:
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; speed regulating as the slave machine.
Name
Value
Name
Value
Address of the
device
2(Given by the
supplier )
Address of setting
telemeter protocol
10
Quantity of
telemeter
Code of writing
telemeter data function
16
Quantity of
telesignal
32
Address of writing
telesignal protocol
Quantity of standby
word
Code of writing
telesignal function
Address pf reading
data protocol
Starting address of
telemeter database
Undetermined
Code of reading
data function
Starting address of
telesignal database
Undetermined
B. GuangKongSuo excitation
Baud rate: 9600; 8 bit data bit; 1 bit stop bit; unverity; excitation as the slave machine.
Name
Value
Name
Value
Address of the
device
2(Given by the
supplier)
Address of setting
telemeter protocol
Quantity of
telemeter
Code of writing
telemeter function
Quantity of
telesignal
4*16
Address of writing
telesignal protocol
Quantity of standby
word
Code of writing
telesignal function
Address of reading
data protocol
Starting address of
telemeter database
telemeter
Undetermined
Code of reading
function
Starting address of
telesignal database
Undetermined
21
SD 200
22
SD 200
Figure 2-19
Notice: it needs to configure each above option for each CPU.
CPU serial number: select corresponding CPU serial number to configure, begin at 1.
23
SD 200
Figure 2-20
B. Parameter illustration:
Terminal number: order by dispatching terminals.
telemeter number: the number of telemeter needs to collect. Because different options are for
the different project, this option setting is from 0 to 180.
telesignal number: the number of telesignal needs to collect. Because different options are for
the different project, this option setting is from 1 to 240.
telemeter serial number: select corresponding telemeter serial number to configure.
telemeter maximum: the corresponding maximum of telemeter.
telemeter minimum: the corresponding minimum of telemeter. Usually with the maximum to
buildup the range of telemeter, and according to the actual range of telemeter. Modify with
dispatching terminals.
telemeter database address: the telemeter need to communicate in database is uncontinuous, so
need address of each telemetry variable in database. Because different options are for the
different project, this option setting is for it.
telesignal database address: the telesignal need to communicate in database is uncontinuous, so
need address of each telesignal variable in database. Because different options are for the
different project, this option setting is for it.
24
SD 200
25
SD 200
SD 200
SD 200
J. Transformation
The measuring point whether transform to other systems, such as dispatching, SYMIMIC, etc.
K. Teleadjust serial number
If need teleadjust for the measuring point by right button, input the corresponding serial number in
the teleadjust list.
SD 200
SD 200
For example, to No. 1 machine opening, its return telesignal is No. 1 machine incorporate in
network. After sending out the command, monitoring program will judge the current value of
No. 1 machine incorporate in network, if the telesignal to telecontrol is positive correlation
blockage, the value of telesignal variable is 1, means the telecontrol operating succeed, contrarily
the value is 0, means the operating cannot succeed; if the telesignal to telecontrol is negative
correlation blockage, the value of telecontrol variable is 0, means the telecontrol operating
succeed, contrarily the value is 1, means the operating cannot succeed.
C. Telecontrol flow picture
When the telecontrol operating condition is satisfied, and the command succeeds in sending to
LCU, open the telecontrol flow picture. The flow picture indicates whether succeed in the
telecontrol operating.
D. Waiting time
It is the time of waiting complete operating by monitoring program. If pass the waiting time, the
return telesignal still unchanged, means fail to regulate.
E. Protocol type
It includes MODBUSTCP protocol, GEHCT protocol, TCP103 protocol, MODBUS protocol, and
CDT protocol.
F. Operating type, operating object, device number
Operating type means the number of telecontrol, device number means the number of LCU, and
operating object means that as using CDT protocol, 0 means disport, 1 means joint.
G. Channel number
When using Ethernet communication, serial ports are COM1 COM10.
H. Password
It whether need confirm the password as the telecontrol.
SD 200
B. Waiting time
It is the time of waiting complete operating by monitoring program. If pass the waiting time, the
return teleadjust still cannot achieve the target value, means fail to regulate.
C. Protocol type
They include MODBUSTCP protocol, GEHCT protocol, TCP103 protocol, MODBUS protocol
and CDT protocol.
D. Operating type, operating object, device number
Operating type means the number of teleadjust, device number means the number of LCU, and
operating object means that as using CDT protocol, 0 means disport, 1 means joint.
E. Channel number
When using Ethernet communication, serial ports are COM1 COM10.
F. Password
It whether need confirm the password as the teleadjust.
SD 200
Uplink machine IP address it is the IP address of network card communicating among several
uplink machines.
Downlink machine IP address it is the IP address of network card communicating between the
uplink machine and PLC.
B. Running position
Running position the running position of SD200 software, include all-in-one machine, master
machine, communication machine, information center/master terminal.
C. Host/reserve machine
It is the running method as master machine start up, select host machine or reserve machine, if do
not master machine, then unnecessary select.
D. Using network, quit password
Using network it is whether the computer using network.
Quit password it whether need password when quit from SD 200 software running on the
computer.
32
4.
4.1.
Introduction
SD200
Graphics software (interface design program) GE, may redesign the monitoring picture
according to the different requirement of clients. It can add various lines, paints, time for the
beautified picture, add the telemetry and telesignal variable for monitoring the operating
information of power plant, the telecontrol and teleadjust variable for controlling the operating
condition of power plant, and add Picture Index for fast searching the picture.
4.1.1.
Summarize
4.1.2.
User interface
UI is the important component in the whole monitoring system, through the graphics it indicates
the condition of real-time devices and parameters, User can inspect the spot operating
information. UI produces by the graphics software GE, through using the standard object and the
denotation by some objects, user can build the UI indicates the collect data.
4.1.3.
Startup
User can click Start Program SD 200 automatic software Graphics software GE to
open in WINDOWS NT/95/98/2000, also double click c:\nr-1001\bin\ge.exe to open the graphics
software GE.
4.1.4.
Interface illustration
The interface produced by the graphics software GE adopts many file operating method provided
by Windows. The frame includes title bar, menu bar, standard tool bar, SD 200 tool bar, drawing
area, status bar and so on.
33
4.1.5.
4.1.5.1.
SD200
Menu introduction
Main menu
Main menu is that user performs their operation through the mouse and keyboard selection. The
main menu of graphics software GE includes file, edit, view, insert, rank, option, data definition
and help. Some operations carry out through the menu item in main menu, also through the
button in tool bar.
34
4.1.5.2.
SD200
Submenu
File menu includes new, open, save, save as, print, print preview, print setting, latest
opened 1.4. file and quit.
Edit menu
Edit menu include cut, copy, paste, delete object, cancel link, graphics edit, form edit, and
all select.
View menu
View menu include standard tool bar, SD 200 tool bar, status bar, roam, regulate screen and
zoom.
Insert menu
Insert menu include mark object, line, rectangle, ellipse, polygon, polyline, camber line, text,
time, telemetry, pulse, telesignal statistic, control, bar graph, strobe, curve, meter graph, standard
graphics, bitmap, animation, retrospect, protect value and setting value.
35
SD200
Rank menu include flush left, flush top, flush right and flush bottom.
Option menu include gridding, Terminal, background, line color, infill color, font, line width
and color configuration.
Data definition menu include definition formula and definition counting formula.
36
SD200
4.2.
Basic usage
Graphics software (interface design program) GE, may redesign the monitoring picture
according to the different requirement of clients. It can add various lines, paints, time for
beautifying picture, add the telemetry and telesignal variable for monitoring the operating
information of power plant, the telecontrol and teleadjust variable for controlling the operating
condition of power plant, and add Picture Index for fast searching the picture.
The method of adding various lines, paints, time for beautifying picture is similar to the general
graphics edit software. Here mostly introduce telemetry (include curve, bar graph and meter),
pulse, telemcommand variable, telecontrol variable, teleadjust variable and adding picture
quoting method.
4.2.1.
Window management
Window management includes the management of display status of graph edit window, standard
tool bar, SD200 tool bar and status bar. It can display or hide the standard tool bar through
clicking the option in standard tool bar under the view menu; It can display or hide SD 200 tool
bar through clicking the option in SD 200 tool bar under the view menu; it can display or hide
the status bar through clicking the option in status bar under the view menu.
Drawing area can set or cancel the gridding, click the gridding option under option menu by
mouse, or use Alt + O to open the option menu, and then use Crtl + G to set or cancel the
gridding; the aim of using gridding can easily regular the drawing. When user wish to see the
part effect of drawing, click the roam option under the view menu, press left button in the red
line box in the ejecting roam window, then put the red line box to daggle the appoint position.
Because fresh the screen by WINDOWS, it will leave some tracks on the screen, for example
drawing a rectangle on the screen, latter move the rectangle, but leave some lines on the original
position, it can clear by regulating the screen. In addition, this software provides the function of
screen zooming display, click the zoom option under the view menu, it ejects a zoom dialog box,
it can select eight display proportions of system provided, and input the arbitrary display
proportion in the percent box.
4.2.1.1.
Before drawing user needs to confirm some necessary parameters: screen background color, line
color, infill color, font, line width and color setting. After confirm the parameter of background
37
SD200
color, line color, infill color, font, and line width, it will display the current color, line width and
font on the graphics of user drawing.
When user needs to amend the property of the graphic primitive, first select one or more graphic
primitive, through the parameter under the selection option, it can change the property of the
graphic primitive. The method of selecting some graphic primitives: first click the graphic
primitive by mouse, when press the Ctrl button, click the other selection graphic primitive by
mouse.
4.2.1.2.
Through clicking the Terminal option under the option menu, it can display or hide
Terminal as drawing.
4.2.1.3.
Select the background option under option menu, system eject the dialog box of color selection,
in the basic color and self-defined color, after select the color, press Confirm. The defined
screen background of system is dark green. RGB (61.4.,128,128)
38
4.2.1.4.
SD200
Select color
When user select the line color, can click line option under the selection option to select the
color. In the basic color or self-defined color of ejecting color selection dialog box, select the
color, press Confirm. To the finished graphic primitive, if change the color, first select the
graphic primitive, and change the line color; if select some graphic primitives, and involve multicolor, here need to all selected line color of the graphic primitive turn to the current line color.
4.2.1.5.
When draw infill circularity and infill rectangle, need select the infill color, click the infill color
option under the selection menu to select infill color. In the basic color or self-defined color of
ejecting color selection dialog box, select the color, press Confirm. To the finished graphic
primitive, if change the color, first select the graphic primitive, and change the infill color; if
select some graphic primitives, and involve multi-color, here need to all selected infill color of
the graphic primitive turn to the current infill color.
4.2.1.6.
Font
Click the font option under the option menu to eject the dialog box for selection font, select the
proper font, font type and size. When user needs to amend the existent literal font, font type and
size, select these characters, then select font, it can amend the font, font type and size as need.
4.2.1.7.
The line width submenu in option menu provides 5 kinds of line width to select: single line
width, double line width, triple line width, quadruple line width, and quintuple line width. When
draw the line, circularity, rectangle and polygon, confirm the size of line and frame, select the
proper line width. System default is single line width.
Click the option under the line width submenu of option menu to select the corresponding line
width. Once select the type, users beeline, rectangle and circularity drew will display as the
current line width type. When user needs to amend the existent line width of beeline, rectangle
and circularity, first select these graphic primitive, then select the line width, it can turn the line
width type of beeline, rectangle and circularity as need.
4.2.1.8.
Click the color setting option under the option menu to display the user self-defined color for
error and exceeding telemetry and telesignal. These items include: telemetry blockage,
temecommand blockage, telemetry exceeding upper limit, telemetry exceeding more upper limit,
telemetry exceeding lower limit, telemetry exceeding more lower limit and error data.
39
4.2.2.
SD200
Graphics edit software GE provides several basic elements for user selection as below:
Line: include horizontal line, vertical line, polyline, camber line and random beeline
between two points.
Rectangle: include infill and uninfill rectangle.
Ellipse: include infill and uninfill ellipse
Polygon: include infill and uninfill polygon
Text: the character string consist of Chinese and English
Time: system time
Standard graphic primitive: the graphic primitive editor produces the graphic primitive.
Telemetry
Telesignal
Telecontrol
Control
User needs to select the drawing properties such as color, line width, font and infill color before
drawing. These realize through clicking the submenu option under the option menu. If amend
existent the property of the graphic primitive, first select these graphic primitives, control the
operating to amend the property of the graphic primitive.
4.2.2.1.
Line
Beeline
Before user draw the beeline, first select line color and width to select the color and width of the
beeline. Then click one of general line, horizontal line and vertical line in the submenu under the
eject menu (according to the different beeline select different choice), here cursor change to +,
in the drawing area, press the left mouse button, confirm the start point, loose the mouse after
dragging mouse to another end point.
Polyline
Before user draw the polyline, first select line color and width to select the color and width of the
polyline. Then click polyline option under the eject menu or select the button of SD 200 tool bar,
here cursor change to +, in the drawing area, press the left mouse button, confirm the start
point, loose the mouse after dragging mouse to another end point, and press the mouse button
until to the last end point, click the fight mouse button to complete in the drawing area.
Camber line
Before user draw the camber line, first select line color and width to select the color and width of
the camber line. Then click camber line option under the eject menu or select the button of SD
200 tool bar, here cursor change to +, in the drawing area, press the left mouse button, confirm
the start point, loose the mouse after dragging mouse to another end point.
40
4.2.2.2.
SD200
Before user draw the rectangle, first select line color and width to select the color and width of
the rectangle; if drawing infill rectangle, may select the infill color of infill rectangle.
Click uninfill or infill option under the eject menu or select the button of SD 200 tool bar, here
cursor change to +, in the drawing area, press the left mouse button, confirm the start point,
drag the mouse, there is a dummy box follow the mouse, loose the mouse at another end point.
4.2.2.3.
4.2.2.4.
Before user draw the polygon, first select line color and width to select the color and width of the
polygon; if drawing infill polygon, may select the infill color of infill rectangle.
Click uninfill or infill option under the eject menu or select the button of SD 200 tool bar, here
cursor change to +, in the drawing area, press the left mouse button, confirm the start point,
drag the mouse to the next point, and press the left mouse button to the next point until to the end
point, loose the right mouse button to complete.
4.2.2.5.
Text
User can input characters, add character string (Chinese or English) in the current display
drawing. The size, font and color of character string can select in the tool bar or menu option.
Select the existent character string to amend the property.
Click the text option under eject menu or the button of selecting under SD 200 tool bar, then the
cursor turn to +, input the character position in drawing area, press the left mouse button,
confirm the start position, there is a vertical line display in the drawing area, then input the
character.
4.2.2.6.
Time
Click the time option under eject menu, the cursor turn to +, display the time position in the
drawing area, press the mouse left button, drag the mouse, there is the simulating box follow the
mouse, loose the mouse at another point, system eject a time setting dialog box, select the
specific format for time display, then press confirm button to complete.
4.2.2.7.
Telemetry
Select Telemetry option under Insert menu, the cursor turn to +, press the left mouse
41
SD200
button where you need to display position, drag the mouse to draw a proper rectangle, loose the
mouse, select the proper integer and decimal fraction to add a telemetry variable. In this
telemetry drawing rectangle, press the right mouse button to amend the color, font of the
telemetry, and can cut and copy to the telemetry.
4.2.2.8.
Histogram
From Histogram submenu in Insert menu, insert the group histogram and single histogram.
Group histogram
Select Group histogram in Histogram submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper group count, each histogram, variable, maximum
and minimum to add a group histogram. Press the right mouse button in rectangle range of each
histogram to amend the line color, infill color of the histogram, and can cut or copy to whole
histogram.
Single histogram
Single histogram includes two kinds: coordinate and uncoordinated, insert method is same as
group histogram.
4.2.2.9.
Curve
From Curve submenu in Insert menu, insert general curve, real-time curve and group curve.
General curve
General curve can display the telemetry for yesterday 21.4. hours curve, today 21.4. hours plan
curve and today changeable curve until current time.
Select General curve option in Curve submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper display property, variable, maximum and minimum
to add a general curve. Press the right mouse button in a general curve to amend the line color of
the curve, and can cut or copy to whole curve.
Group curve
The group curve can display today changeable curve of some telemetry until current time. The
minimum time definition of the curve is 5 minutes.
Select Group curve option in Curve submenu under Insert menu, the cursor turn to +,
press the left mouse button where you need to display position, drag the mouse to draw a proper
rectangle, loose the mouse, select the proper curve number, variable, maximum and minimum to
add a group curve. Press the right mouse button in a group curve to amend the line color of the
curve, and can cut or copy to whole curve.
Real-time curve
Real-time curve can display the changeable curve of some telemetry in 300 seconds. The time
definition of the curve is 6 seconds.
42
SD200
4.2.2.10. Meter
Select Meter graphics submenu under Insert menu, the cursor turn to +, press the left
mouse button where you need to display position, drag the mouse to draw a proper rectangle,
loose the mouse, select the variable, maximum and minimum to add a meter graphics. Press the
right mouse button to amend the color of dial and line, and can cut or copy to whole meter
graphics.
4.2.2.11.
Strobe
4.2.2.12.
Pulse
The insert method of pulse is similar to the telemetry. And it can select apex, vale, calm and
different times as formula definition.
4.2.2.13. Telesignal
Insert-Standard graphical primitive, eject NR-1001 standard graphical primitive dialog
box, select Switch or Strobe, press Confirm, in the eject window, press left button to put
the graphical primitive selected to drag into design picture. Press the right mouse button to define
the formula for the telesignal, and can cut and copy for it.
Telesignal statistic
Insert-Telesignal, it can define the telesignal statistic information.
4.2.2.14.
Telecontrol
Insert-Telecontrol, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse to add a telecontrol
variable. Press the right mouse button to amend the color infill color and font of the telecontrol,
define the formula for it, and can cut or copy.
4.2.2.15.
Teleadjust
Insert-Teleadjust, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse to add a teleadjust
variable. Press the right mouse button to amend the color infill color and font of the teleadjust,
define the formula for it, and can cut or copy.
43
4.2.2.16.
SD200
Picture index
Insert-Picture index, the cursor turn to +, press the left mouse button where you need to
display position, drag the mouse to draw a proper rectangle, loose the mouse, infill the proper
title and hit to add a picture index. Press the right mouse button to amend the color infill color
and font of the picture index, and can cut or copy for it.
4.2.2.17.
Color configuration
Option-Color configuration, it can define the exceed telemetry variable display in the
graphic display program and the measuring point color being blanked.
4.2.2.18.
Definition formula
Date definition-Definition formula, it can define the formula of the telemetry variable and
telesignal variable.
4.2.3.
Click standard graphical primitive under the eject menu, system will eject the nr-1001 standard
graphical primitive dialog box, select needed single or double graphical primitive and click
confirm button, system will eject another dialog box, it can select more specific graphical
primitive in it. Click the graphical primitive by the left mouse button to select, if it is double
graphical primitive, press F8 to preview the difference as different value for the graphical
primitive. After click the graphical primitive by left mouse button, press the left mouse button to
drag to the drawing area.
4.2.3.1.
Bitmap
Click the bitmap option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject a open
(file) dialog box, select the bitmap need to add into the drawing area (suffix is bmp) and press
confirm button to complete. The bitmap file is built by users who use the bitmap editor Paint
provided by Windows.
4.2.3.2.
Animation
It applies to display the revving graphical interface, select three pictures and define the formula
as ejecting, the graphic display program will alternate display pictures with 3 different speeds
according to the definitional revving signal. Notice the definitional revving signal must define
44
SD200
the limit.
Click the bitmap option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject first
selection dialog box, select a bitmap which suffix is bmp, press the confirm button, system eject
second selection dialog box, reselect a bitmap which suffix is bmp, press the confirm button,
system eject third selection dialog box, reselect a bitmap which suffix is bmp, press the confirm
button to complete.
4.2.3.3.
Setting value
Click the setting value option under eject menu, the cursor turn to +, at the position of display
bitmap in the drawing area, press the mouse left button, drag the mouse, there is the simulating
box follow the mouse, loose the mouse at another point of the rectangle, system eject first setting
value dialog box to select the integer digits and decimal digits of display the telemetry variable,
press the confirm button to complete.
4.2.4.
4.2.4.1.
Graphics edit
The processing of graphics edit, first must select the object, the method is:
1. Click the button on SD200 tool bar, and then click the left mouse button to select the object
needed.
2. Move the mouse to the left top of the object, press the left mouse button, pull a simulating box
involve the object, all objects in the box will be selected.
3. If it needs to add objects out of the selection, move the mouse to new object, press CTRL
button and left mouse button.
4. Click all select option under edit menu to select all graphical primitives in the selection
picture.
If it needs to cancel the selection object, move the mouse out of the object, press the left mouse
button, all selection object boxes will disappear, indicates selection is cancelled.
4.2.4.2.
Change size
When it needs to change the size of a graphical primitive, select the graphical primitive, move
the mouse to the four squares of box, the cursor turn to double arrowheads, press the left mouse
button, drag the mouse, loose the mouse as adjusting the proper size, press left mouse button out
of the graphical primitive to complete.
Notice: when change the size, it can cause the bitmap distortion because of the operation error.
So the bitmap size cannot change too much, and reduce the changeable times.
45
4.2.4.3.
SD200
Move
When it needs to move the position of a graphical primitive, select the graphical primitive, when
press the CRTL, press the direction button on the keyboard, the object will move; or move the
mouse to the graphical primitive, press the left mouse button to drag the mouse to the new
position, the object will move.
4.2.4.4.
Cut
If it needs to copy the graphical primitive, must put the object copy to the cutting board, Cut is to
delete the selection graphical primitive, and copy it to the cutting board. The method of Cut is
same as WORD.
4.2.4.5.
Copy
Copy is to copy the selection graphical primitive to the cutting board. The method of Copy is
same as WORD.
4.2.4.6.
Paste
Paste is to copy the content in cutting board to the picture. The content in cutting board can copy
from the graphics software GE, also from other graphics software. The method of Paste is same
as WORD.
4.2.4.7.
Delete
Delete object is to delete the graphical primitive from the picture. The method of Delete is same
as WORD.
4.2.4.8.
Picture regulation
It is to regulate the relation between graphical primitives. The method of Delete is same as
WORD.
4.3.
File management
The graphics file built by the graphical software GE can provide the real-time monitoring
software to display the graphics. The graphical file save as directory c:\nr-1001\pic, the suffix
is .ng. The system has a graphical file for main graphics main graphics.ng, when the system
startup, it automatic transfer the graphical file for main graphics display the main picture. When
the system display any picture, it can return to the main graphics by the graphics tool bar.
46
4.3.1.
SD200
This menu is to build new graphical file. Select the new option under the file menu, or press new
file button on the standard tool bar, or press Alt+F, Ctrl+N to build a new graphics window.
4.3.2.
Open file
When user needs to amend current graphics, select the open option under file menu, or press
open file button on the standard tool bar, or press Alt+F, Ctrl+O, system will eject a graphical
dialog box, according to the title to select the file needed to open a current graphics.
4.3.3.
Save file
After finish graphics edit, it can save the result, click the save option or save as option under file
menu, or click the save button under standard tool bar, or press Alt+F, Ctrl+S, system will eject
save file dialog box, it can input the new file name, also select existent file names. When select
the existent file name, the current graphic will cover the old one.
47
4.3.4.
SD200
Click the printer option under file menu or the print button under standard tool bar, or press
Alt+F, Ctrl+P, system will eject the print dialog box; user can select the printer, set the property
of print, select print range and copy.
4.3.5.
Print preview
After set the material and medium of printer, it can click the print preview option under file
menu, or press Alt+F, Ctrl+V, to preview the printing effect, it can to preview the printing effect,
it can forward turn or back turn preview for some pages.
4.3.6.
Print setting
Click the print setting option under file menu, or press Alt+F, Ctrl+R, system will eject the print
setting dialog box, user can select the printer, according to the selection printer to select the size,
source of paper and the print direction.
4.3.7.
Quit
Click the quit option under file menu, or press Alt+F, Ctrl+X, it can close all opened files, quit
48
SD200
the graphical software GE. For the unsave file, it will eject a dialog box for user selection or not.
4.4.
The graphical primitive editor nb.exe applies to edit the graphical primitives album. The
system default provides a set of graphical primitives, such as the transformer, switch, strobe, tide,
etc. The system can use editor self-define the graphical primitive and add it to the graphical
primitives album.
4.4.1.
Click the graphical primitive editor option under edit menu, or press Alt+E, Ctrl+F to open the
graphical primitive editor.
4.4.2.
Produce a new graphical primitive, first click the new option under editor file menu, then select
the proper parameter of view, proportion, line width menu, it can use every option under picture
menu and left shortcut tool bar to complete the new graphical primitive. After drawing click save
or save as to save the graphical primitive. It will eject the dialog box as saving, if drawing is
single graphical primitive, select single value in the sort and select the transformer, input the file
49
SD200
name. (The suffix of file is 0); if drawing is double graphical primitive, select double value in the
sort and select the corresponding kind, input the file name. Notice: if the double graphical
primitive of drawing is 1, the suffix of file name is .1, if the double graphical primitive of
drawing is .0, the suffix of file name is .0. So a graphical primitive respond to two file names, .0
and .1, which delegate the display this double graphical primitive as 0 and 1.
4.4.3.
The graphical primitive after editing provides for drawing. Click the standard graphical primitive
option under eject menu, the system eject nr-1001 standard dialog box, select needed single
value or double value and press confirm button, the system will eject another dialog box, it can
select specific graphical primitive in there. Click the left mouse button to select the graphical
primitive, if it is the double value, press F8 to preview the display difference as the different
value. Click the left mouse button to select the graphical primitive, press the left mouse button to
drag to the drawing area.
4.4.4.
The link and cancel the graphical primitive is build the connection between the dynamic
graphical primitive and the measuring point in database, after that, the dynamic graphical
primitive can indicate the spot actual operating information, it changes as the actual operating
information.
To build the connection of the graphical primitive, select the graphical primitive, click the
definition formula option under data definition dialog box ejecting, select the measuring point in
the database, press confirm button to complete the connection. To cancel the connection, first
select the graphical primitive, and then click the cancel option under edit menu to complete.
50
SD200
5.3. Alarm
Click the alarm button on the left of screen to open the alter widow. Alarm information divides
three sorts: alarm for simulation exceeds the limit, alarm for changeable switch (include
information, trouble and accident) and alarm for self-check.
The downlink machine program information is on the right screen of bottom status bar, display
newest alarm information.
51
SD200
52
SD200
5.5.3. Record
1998/01.4./02 12:21.4.:11.4. line 110 , close 1001 switching-out operation
It is denotes closing command 1001 at the line 110 sent to CB by the PLC in 1998/01.4./02
12:21.4.:11.4.
5.11. Mutual-check
In the double systems, the master machine will automatic checkout the operating condition termly.
When the master machine cannot work or quit with the accident, the slave machine automatic
updates to the master machine, ensure the system not to break.
53
SD200
5.12. Option
Press Option on Switch to select the monitoring program to work.
54
6.
6.1.
SD200
Report system program includes report design, display, and print program. SD200 software
report system is base on EXCEL.
6.2.
REPORT
BUTTON
Startup SD200 interface display software package, the left picture will display the tool bar, the
report button as shown as above. Press the report button, appear Use macro, click yes, then
access the report design interface based on EXCEL. And appear the report tool bar as below
figure shows.
There are five buttons on the report tool bar; they are Access report design status, Report data
inquire, Events inquire, Report management, and Hide display EXCEL menu from left to
right.
6.3.
6.3.1.
Report design
Access report design status
Click Access report design status button, appear password input dialog box as below shows,
input password sd200, then access report design status.
55
6.3.2.
SD200
Report management
Access report design status, click Report management button, appear the report management
dialog box as below shows. User can do several things as below through the report management
dialog box:
1. Create a new report: input the repot name as wanted in new report name:, such as 3# unit
report, set the property of report such as height of row, col width, whether automatic draw form
and so on, click new button, the new report has built. EXCEL will display the name of new
report.
2. Delete a report: select the name of report in the report list, click Delete button to complete.
3. Amend the report: if user wants to amend the property of report such as height of row, col
width, select the name of report in the report list, set the property of report such as height of row,
col width, whether automatic draw form and so on, click Amend button
56
6.3.3.
SD200
Data definition
Access the report design status, double click any grid in the form, appear data definition dialog
box as below shows. User can do several things as below through the report management dialog
box:
1. Define a data point: if want to start to display any point history data report in the grid, it can
select the measuring point, select the measuring point in the selection box, define the display
property of measuring point, such as Start point, Continuous point, Time interval, Up or
down, press Confirm button to complete.
2. Amend the point property: if user wants to amend the point or the property of point, such as
Start point, Continuous point, Time interval, Up or down, etc. Then click the defined
grid, re-select the point or re-amend the property, press Amend button to complete.
3. Delete the defined point: if user wants to delete the defined point, then click the defined grid,
press Delete button to complete.
6.4.
Report display
After defining the report, if want to view the content of history data report, then click report
data search button, and appear the dialog box as below figure shows.
57
SD200
Press the confirm button, and then can appear the history data of defined point, as below figure
shows.
Remark: (1). If user needs to do some data statistic, account, please refer to some high level
function of Microsoft EXCEL. (2). The report date display fixup at First row, second row,
please do not define data in these grids for users.
58
7.
SD 200
The history data online search program is the part of SD200 software package for searching
history data. It completes the curve search and data form search, also switch between the curve
interface and the form interface, and display the two interfaces in the same interface. The
program interface is as Figure 7-1 shows.
Figure 7-1
7.1.
7.1.1.
Before introducing the program usage, introduce the interface composing factors for data online
search program:
Menu bar ----- below the title bar, display by the character.
Tool bar ----- below the menu bar, display by the graphic and character, can display or hide.
Float tool bar ----- below the tool bar
Selection area ----- the left window below the float tool bar, can select display or undisplay.
Display area ----- the right window below the float tool bar, locate the right of selection
59
SD 200
area.
Status bar ----- the bottom of the whole program, can display or hide.
7.1.2.
The complex tool operating steps in the menu bar, tool bar and float tool bar.
7.1.2.1.
Time search
Step: 1. Click the calendar display on the float tool bar for searching the date, display as Figure
7-2 shows.
2. Select the search date, then calendar automatic close to complete the time setting.
Figure 7-2
7.1.2.2.
Color setting
Method: 1. Click Color on the tool bar, appear the dialog box as Figure 7-3 shows. Otherwise,
Menu ----- Setting ----- Set color also appears the dialog box as Figure 7-3 shows.
2. Click the list bar on the dialog box for data information, select the option of setting color,
then the button under colors will display the selection current color.
3. Click the button under colors, push the color box as Figure 7-4 shows, select the needed
color to confirm, close the color box, back to the dialog box for the curve color setting, the
button under colors display the wanted color, click to confirm to complete the setting.
Figure 7-3
60
SD 200
Figure 7-4
7.1.2.3.
Step: 1. Menu ----- Setting ----- Subsection display, can push the dialog as Figure 7-5
shows.
2. Infill the start time and end time of search, click the confirm button to compete the time
setting.
Figure 7-5
7.1.2.4.
Menu ----- View ----- Selection area, click the selection area with V to hide; click the
selection area without V to display.
61
7.1.2.5.
SD 200
1. Single curve: click the left mouse button to select the title of needed searching telemeter.
2. Multi curve: click the left mouse button to select the title of needed searching telemeter or the
icon ahead of title telemeter.
7.1.2.6.
Forbid to modify the inputting number for direct searching period by the keyboard, only through
add or reduce mode to modify the number of searching period.
7.1.2.7.
It may direct modify the inputting number of maximum (minimum) by the keyboard, then
through add or reduce mode to be available for inputting number.
7.2.
The curve for daily history can display any daily changeable curve of telemetry until the current
day in a year. It can contrast display any changeable curve of telemetry for any nine days in an
interface, or contrast display any changeable curve of nine telemetries for any day in an
interface. The minimum time definition of curve display is 5 minutes.
7.2.1.
Select Single curve on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the searching date on the float tool bar, it can draw
the selection telemeter history curve in display area.
As drawing curves it can use different color to draw curve of upper limit and lower limit for
telemeter; above the curve it may display the telemeter title and searching date, below the curve
it may display the maximum, minimum, average and happen time.
It can set the display color for the curve, upper limit, lower limit and background through the
color setting.
The mouse move to the curve area, display the current cursor position in the status bar.
7.2.2.
Select Single curve on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the searching date on the float tool bar and the
time quantum needed, it can draw the selection telemeter history curve in the time quantum in
display area.
The display sorts of curve, display mode of relating information and color setting are similar to
62
SD 200
7.2.1.
7.2.3.
Select Time-sharing on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the 9 days different searching dates on the float
tool bar, it can draw the 9 days contrast history curves of telemeter in display area.
If want to cancel the curve display of any day, select the time of day again, the original selection
curve will be cancelled.
The sort of curve display is similar to 7.2.1. The curve of different date displays in different
color. The display mode of relating information as below: the top of curve display the title of
telemeter, the bottom display different date in different color. The color setting except unsetting
the color of curve, others is similar to 7.2.1.
7.2.4.
Select Time-sharing on the tool bar, select Day on the float tool bar, select the telemeter title
needed searching in selection area, then select the 9 days different searching dates on the float
tool bar, then select the time quantum of needed searching, it can draw the 9 days contrast history
curves of telemeter in the time quantum selected in display area.
If want to cancel the curve display of any day, it is similar to 7.2.3.
The display sorts of curve, display mode of relating information and color setting are similar to
7.2.3.
7.2.5.
Select Multi-curve on the tool bar, select Day on the float tool bar, select the searching date
on the float tool bar, select the several telemeter titles needed searching in selection area, it can
draw the contrast history curves of several telemeter of one day in display area.
If want to cancel the curve display of telemeter, select telemeter in the selection area again, the
original selection curve will be cancelled.
The sort of curve display is similar to 7.2.1. The curve of different telemeter displays in different
color. The display mode of relating information as below: the top of curve display the searching
date, the bottom display different telemeter in different color. The color setting except unsetting
the color of curve, others are similar to 7.2.1.
7.2.6.
Select Multi-curve on the tool bar, select Day on the float tool bar, select the searching date
on the float tool bar, select the several telemeter titles needed searching in selection area, then
select the time quantum, it can draw the contrast history curves of several telemeter in the time
63
SD 200
7.3.
The curve for monthly history can display any monthly changeable curve of telemetry until the
current time in two years. It can contrast display any changeable curve of any nine telemetries of
any one month in an interface
7.3.1.
Make Day change to Month on the float tool bar in 7.2.1, select Average, Maximum,
Minimum on the float tool bar, others are same.
7.3.2.
Make Day change to Month on the float tool bar in 7.2.2, select Average, Maximum,
Minimum on the float tool bar, others are same.
7.3.3.
Make Day change to Month on the float tool bar in 7.2.5, select Average, Maximum,
Minimum on the float tool bar, others are same.
7.3.4.
Make Day change to Month on the float tool bar in 7.2.6, select Average, Maximum,
Minimum on the float tool bar, others are same.
7.4.
Select Day on the float tool bar, select LCU title on the selection area, select the searching date
on the float tool bar, then select the searching period on the float tool bar, in the display area it
may display the data which LCU stores all telemeter variables of one day in the history database
in the form.
7.5.
Select Month on the float tool bar, select any option of Average, Maximum, Minimum
on the float tool bar, select the LCU title on the selection area, then select searching date on the
64
SD 200
float tool bar, in the display area it may display the data of Average, Maximum,or
Minimum, which LCU stores all telemeter variables of onemonth in the history database in the
form.
65