Mounting flange
4-5# angle steel L=0.6mm
Front view
Top view
be on the narrow side of the channel), for which intermittent welding should be used
to reduce the effect of stress concentration. Carbon steel electrode E4300 (GB5117-85)
is recommended;
8. After completion of welding and cooling of the steel rack structure, perform the
anti-rust and anti-corrosion treatment on the surface.
The relationship between the spacing D of the two base racks and the beam L is
as follows:
When L=2200mm, D=1150mm;
When L2800mm, D=1750mm.
The parallelism of the centerline of the two base racks and the reference wall
surface should be noted during mounting.
(live, zero and grounding wires) and equal-potential grounding wires with core size
no less than 6mm2 (PE). The wires should be laid to within 15cm of the mounting
rack lower plate A, with reserved wire no less than 1.5m, for connection with pendant
when the pendant is mounted.