Vous êtes sur la page 1sur 24

Extra

High Voltage
(EHV) Cables

Technical Catalogue

Company
Profile

Silvassa Plant

Mysore Plant

Thane Plant

RPG Cables, a division of KEC International Limited has established


itself as one of the leading manufacturers of Power, Control
& Telecommunication cables in India. One of the oldest cable
manufacturing company (1958), we have been serving the
industries with quality cables for over 5 decades. The state-of-the
art manufacturing plants are located at Thane for HT cables upto
33 kV and EHV cables upto 132 kV and Silvassa for LT cables upto
1.1 kV (power and control). The manufacturing facility at Mysore
manufactures LT Power and Control Cables, apart from Telecom Cables
(Fiber Optic & Jelly Filled), Instrumentation, Fire Survival and Signaling
Cables. RPG Cables also offers expertise in Turnkey contracts involving
cable laying, jointing, testing and commissioning. To keep pace with
the changing needs of the customers and requirement of cables for
voltage grades above 132 kV, the company is coming up with a new
manufacturing unit near Halol, Gujarat with capability to manufacture
cables up to 400 kV. The brand name Asian is synonymous with
stringent norms in quality, environment and safety management. The
plants have been ISO 9000 and ISO 14000 certified.
RPG cables has been making major export thrust in keeping with its
global aspirations. We match international quality standards and cables
can be designed to comply with required international standards. The
division has also been given recognition by the Govt. of Maharashtra
for achieving excellence in Exports.

Technical Catalogue

Manufacture
of EHV Cables
RPG Cables commenced the manufacture of
XLPE cables at its Thane Plant in 1978. The
division has already supplied more than 150 Kms
of cables (EHV) with various combinations of
construction ranging from 66 kV to 132 kV and
sizes with both Aluminum and Copper conductors.
The cables can be manufactured according to
most international specifications and designs.

SPECIAL FEATURES OF EHV


XLPE MANUFACTURING LINE
AT RPG CABLES :

Highly sophisticated Dry Cure Line using superclean XLPE compound .


Computerised vulcanizing & cooling systems as well as extruder heating control system.
In line metal detectors for semicon & XLPE materials which ensure removal of ferrous & non ferrous metallic
impurities from compound before extrusion.
In line dust & fine separator for XLPE insulation to have homogenous & extra clean insulation.
Separate pressurized rooms for semicon shielding & XLPE insulation compound to avoid contamination.
Automatic material handling by vacuum loaders.
Pressurised air system with air showers on doors to eliminate dust entry.

Technical Catalogue

ADAVNTAGES OF LEAD SHEATH :


Lead has superior corrosion resistant properties in any environment than that of Aluminium .
Lead sheathed cables can follow bending in contours with ease.
W
 ith Aluminium corrugated cable, longitudinal water tightness is lost, eventually increasing
the size ofthe cable due to high temperature developed during sheath extrusion.
Lead sheath is easily solderable.
Minimum life of lead sheath is 40 45 years.
Lead is very dense & easily fusible . It has got very good corrosion resistant property in
all kinds of environment.

SPECIALISED CONTINUOUS LEAD EXTRUDER :


Continuous extrusion free from external impurities which eliminates stop marks
Microprocessor based temperature controller for precise temperature profile
Microprocessor based DC drive system gives uniform Lead thickness, better concentricity.
Electrical system based on programmable logic controllers for reliability.

Elements in
EHV Cables
Typical Cross-Sectional Sketches
Conductor

Aluminium/Copper

Conductor Shielding
INSULATION
INSULATION SHIELDING
COPPER WIRE SHIELD
WATER SWELLABLE TAPE
METAL TAPE MOISTURE BARRIER
OUTER JACKET

Constructional features: EHV CABLES :


Conductor

Insulation

The conductor shall be formed from plain copper or aluminium


complying to IS: 8130 or IEC 228 Publication.The conductor
shall be compacted circular, or segmental compacted circular.

The insulation shall be of dry cured XLPE compound with


a thickness to meet dimensional, electrical and physical
requirements specified . The insulation shall be suitable for
operation in wet or dry locations at conductor temperature not
exceeding 900C for normal condition, 1300C for emergency
overload conditions and 2500C for short circuit conditions.

Conductor Shielding
Conductor Shielding of an extruded semiconducting XLPE
compound shall be applied over the conductor. One or two
layers of semiconducting tape(s) may be applied with an
proper lapping between the conductor and the extruded
semiconducting layer.

Technical Catalogue

Insulation Shielding

Water Swellable Tape

The insulation shielding shall be applied direct upon


the insulation and shall consist of a layer of extruded
semiconducting compound. The extruded semiconducting
compound shall be a thermoset type and firmly and totally
bonded to the insulation.

Water swellable tapes are used in cables to prevent longitudinal


water penetration along the cable. These tapes are used below
and above copper wire screen and below lead sheath. These
tapes are normally semiconducting tapes. However on some
special occasions these are used below outer sheath as well in
which case these are of insulating type.

Copper Wire Shield


When a layer of copper wire shield is required, it shall be applied
over the insulation shielding. One or more layers of suitable
seperator or tape may be applied helically over a layer of this
shield.

Lead Alloy
When the lead alloy sheath is required, it shall be applied by
a continuous screw extrusion in high quality, smooth surface
and free from pinholes and any other imperfections including
one associated with oxide inclusions. When the lead sheath
is applied directly over the extruded semi-conducting layer or
inner plastic bedding, suitable non magnetic tape(s) can be
applied under the lead sheath to prevent heat transfer onto
the plastic material during the manufacturing.The lead sheath
can act as screen, moisture barrier and armour.

Corrugated Aluminium Sheath/Metal Tape


Moisture Barrier
When the moisture barrier other than lead is required,
corrugated aluminium sheath or a layer of aluminium
tape laminated on outer side with copolymer is used. It
shall be applied longitudinally over the cable core with an
overlap.

Outer Jacket
The outer jacket shall consist of thermoplastic compound (PVC,
PE or similar materials) extruded continuously over the metallic
layer or moisture barrier. A bitumeneous compound primer shall
be applied under the outer jacket to protect the sheath against
local corrosion when corrugated aluminium sheath or lead alloy
sheath is adopted.

CABLE DESIGN
REQUIREment
CURRENT RATING DETERMINATION
Current rating depends upon :
Installation conditions (ground, air, ducts, depth of burial, etc.)
Environmental effects soil temp, soil thermal resistivity, depth of burial, spacing.
Mutual heating derates cable.
Laying Method Flat Formation, Close Touching Trefoil formation.
Type of Bonding Both End Bonding, Single Point Bonding, Mid Point Bonding, Cross bonding.

Information required for cable design


System Voltage

Route Length requirements

Maximum Air Temperature

Type of Earthing

Site Limitations &


Installation conditions

Ground Thermal resistivity

Impulse Level

Frequency

Termination

Cyclic Load

Fault level & Duration

Max. ground Temperature

Normal Load

D.C. RESISTANCE OF CONDUCTOR


NOMINAL CROSS-SECTIONAL AREA

MAXIMUM RESISTANCE OF CONDUCTOR AT 200C

Sq.mm

Copper Conductor (ohm/km)

Aluminium Conductor (ohm/km)

185

0.0991

0.164

240

0.0754

0.125

300

0.0601

0.100

400

0.0470

0.0778

500

0.0366

0.0605

630

0.0283

0.0469

800

0.0221

0.0367

1000

0.0176

0.0291

1200

0.0151

0.0247

Technical Catalogue

Short Circuit Rating For One Second In Ka.


NOMINAL SIZE OF CONDUCTOR (MM2)

COPPER

ALUMINIUM

150

21.450

14.100

185

26.455

17.390

240

34.320

22.560

300

42.900

28.200

400

57.200

37.600

500

71.500

47.000

630

90.090

59.220

800

114.400

75.200

1000

143.000

94.000

1200

171.600

112.800

TESting of EHV Cables


IS: 7098 / PART 3

IEC 60840

Routine Tests

Acceptance Tests

ROUTINE TESTS

ACCEPTANCE TESTS

Conductor Resistance

Conductor Resistance

High Voltage

Conductor Examination

High Voltage

Annealing test (where applicable)

Partial Discahrge

Conductor resistance and Metallic


screen resistance

Partial Discahrge

Tests for dimensions of insulation

Electrical test on
oversheath

Thickness of insulation and


oversheath

Hot set test for insulation

Thickness of metallic sheath

Voids and Contaminant

Hot set test for insulation

Thickness of metallic sheath

Measurement of capacitance

Thickness of outer sheath

Water penetration test


( if applicable)

Partial Discharge
High Voltage
Measurement of capacitance

Technical particulars Cables with Aluminium Conductors


VOLTAGE GRADE
NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

185

240

300

400

A2XLyCY

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

(a) In air......(A) at 40C

391

401

412

455

469

483

514

533

550

592

621

642

(b) In ground(A) at 30C Thermal


Resistivity 1.5 K.m/W
Depth : 1500mm

267

276

294

304

318

339

338

357

381

380

407

435

Approx. Overall Dia. of cable (mm)

61

64

66

69

Approx. Weight of cable (kg / km)

7780

8220

8600

9410

Max. DC Resistance of conductor


at 20C (ohm / km)

0.164

0.125

0.100

0.0778

Max.AC Resistance at 90C (ohm / km)

0.2108

0.2107

0.1610

0.1608

0.1291

0.1289

0.1010

0.1007

Reactance at 50 Hz (ohm / km)

0.1443

0.1925

0.1390

0.1858

0.1349

0.1808

0.1288

0.1729

Approx. Capacitance (microFarad / km)

0.179

0.193

0.205

0.225

Max. Length

1000

950

900

825

TOTAL WT

8109

8570

8962

9802

TOTAL kA for 1 Sec

31.95

31.79

32.05

31.97

Technical particulars Cables with Copper Conductors


VOLTAGE GRADE
NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

185

240

300

2XLyCY

2XLyCY

2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

(a) In air......(A) at 40C

496

515

531

573

602

622

646

685

710

(b) In ground(A) at 30C Thermal Resistivity 1.5 K.m/W


Depth : 1500mm

335

354

378

379

407

435

418

455

489

Approx. Overall Dia. of cable (mm)

61

64

66

Approx. Weight of cable (kg / km)

8930

9690

10490

0.0991

0.0754

0.0601

Max. DC Resistance of conductor at 20C (ohm / km)


Max.AC Resistance at 90C (ohm / km)

0.1272

0.1270

0.0973

0.0971

0.0781

0.0778

Reactance at 50 Hz (ohm / km)

0.1438

0.1918

0.1385

0.1852

0.1338

0.1794

Approx. Capacitance (microFarad / km)

0.181

0.195

0.208

Max. Length

875

800

725

TOTAL WT

9312

10101

10937

Max. Length

875

800

725

31.98

31.82

31.64

TOTAL kA for 1 Sec

Technical Catalogue

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

500

630

800

1000

1200

A2XLyCY

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

A2XLyCY
(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

A2XLyCY
(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

682

723

750

774

832

867

876

955

1001

976

1079

1139

1056

1180

1254

427

462

496

473

523

563

521

587

634

567

649

706

600

695

760

73

76

81

85

90

10250

11060

12330

13580

14850

0.0605

0.0469

0.0367

0.0291

0.0247

0.0792

0.0788

0.0623

0.0617

0.0499

0.0491

0.0409

0.0399

0.0360

0.0399

0.1231

0.1656

0.1193

0.1603

0.1148

0.1540

0.1111

0.1489

0.1074

0.1436

0.248

0.267

0.294

0.319

0.348

750

700

625

575

525

10684

11526

12846

14154

15478

31.52

31.53

31.76

31.98

31.84

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

38/66(72.5kV)

400

500

630

800

1000

2XLyCY

2XLyCY

2XLyCY

2XLyCY

2XLyCY

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

734

790

822

831

907

950

931

1036

1093

1035

1171

1247

1135

1302

1399

464

514

554

512

578

627

560

646

706

605

714

786

647

776

860

70

73

77

82

86

11810

13310

15080

17150

19640

0.0470

0.0366

0.0283

0.0221

0.0176

0.0619

0.0614

0.0493

0.0486

0.0395

0.0386

0.0324

0.0313

0.0276

0.0262

0.1281

0.1720

0.1231

0.1656

0.1188

0.1597

0.1143

0.1534

0.1103

0.1479

0.228

0.248

0.270

0.297

0.324

650

575

500

450

400

12303

13871

15709

17872

20463

650

575

500

450

400

31.55

31.52

31.59

31.83

31.64

Technical particulars Cables with Aluminium Conductors


VOLTAGE GRADE
NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

240

300

400

500

A2XLyCY
(In Flat
(In Trefoil
Formation)
Formation)
(D+70)
BEB SEB
SEB

A2XLyCY
(In Flat
(In Trefoil
Formation)
Formation)
(D+70)
BEB SEB
SEB

A2XLyCY
(In Flat
(In Trefoil
Formation)
Formation)
(D+70)
BEB
SEB
SEB

A2XLyCY
(In Flat
(In Trefoil
Formation)
Formation)
(D+70)
BEB SEB
SEB

(a) In air......(A) at 40C

454

465

477

513

529

543

592

615

633

683

716

738

(b) In ground(A) at 30C


Thermal Resistivity
1.5 K.m/W
Depth : 1500mm

306

319

337

341

358

379

384

408

432

431

464

493

Approx. Overall Dia. of cable (mm)

76

78

82

86

Approx. Weight of cable (kg/km)

10460

10850

11780

12760

Max. DC Resistance of
conductor
at 20C (ohm / km)

0.1250

0.1000

0.0778

0.0605

Max.AC Resistance at 90C


(ohm / km)

0.1609

0.1608

0.1290

0.1289

0.1008

0.1007

0.0790

0.0788

Reactance at 50 Hz (ohm / km)

0.1503

0.1914

0.1460

0.1864

0.1393

0.1783

0.1332

0.1709

Approx. Capacitance
(microFarad / km)

0.152

0.160

0.174

0.190

750

725

650

600

TOTAL WT

10903

11303

12279

13293

TOTAL kA for 1 Sec

31.78

31.81

31.86

31.55

Max. Length

Technical particulars Cables with Copper Conductors


VOLTAGE GRADE
NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

240

300

400

2XLyCY

2XLyCY

BEB

SEB

575

597

614

648

680

700

738

784

810

383

408

433

423

457

486

470

516

551

(In Trefoil
Formation)

(a) In air......(A) at 40C

2XLyCY
(In Flat
Formation)
(D+70)
SEB

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

(In Trefoil
Formation)
BEB

(In Trefoil
Formation)

(b) In ground(A) at 30C Thermal


Resistivity 1.5 K.m/W
Depth : 1500mm
Approx. Overall Dia. of cable (mm)

77

79

82

Approx. Weight of cable (kg / km)

11940

12790

14230

0.0754

0.0601

0.0470

Max. DC Resistance of conductor


at 20C (ohm / km)
Max.AC Resistance at 90C (ohm / km)

0.0972

0.0970

0.0780

0.0778

0.0617

0.0614

Reactance at 50 Hz (ohm / km)

0.1498

0.1908

0.1448

0.1850

0.1385

0.1774

Approx. Capacitance (microFarad / km)


Max. Length

0.153

0.162

0.176

650

600

550

TOTAL WT

12439

13329

14827

TOTAL kA for 1 Sec

32.04

31.89

31.93

Technical Catalogue

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

630

800

1000

1200

A2XLyCY

A2XLyCY

A2XLyCY

A2XLyCY

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

777

824

852

882

946

984

983

1067

1116

1069

1170

1230

480

525

560

531

590

632

579

653

703

615

701

758

(In Trefoil
Formation)

(In Trefoil
Formation)

(In Trefoil
Formation)

(In Trefoil
Formation)

89

93

97

102

13650

14960

16410

17710

0.0469

0.0367

0.0291

0.0247

0.0621

0.0617

0.0496

0.0490

0.0406

0.0398

0.0356

0.0399

0.1289

0.1655

0.1233

0.1587

0.1192

0.1535

0.1149

0.1479

0.204

0.222

0.239

0.260

575

475

450

425

14225

15591

17097

18449

31.61

31.77

31.78

31.70

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

64/110(123 kV)

500

630

800

1000

2XLyCY

2XLyCY

2XLyCY

BEB

SEB

838

901

935

942

1030

1075

1053

1166

1226

1153

1294

1371

521

581

623

571

651

702

620

720

782

664

783

856

(In Trefoil
Formation)

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

2XLyCY

(In Flat
Formation)
(D+70)
SEB

(In Trefoil
Formation)
BEB

SEB

(In Flat
Formation)
(D+70)
SEB

BEB

SEB

(In Flat
Formation)
(D+70)
SEB

(In Trefoil
Formation)

(In Trefoil
Formation)

86

89

93

98

15820

17680

19800

22520

0.0366

0.0283

0.0221

0.0176

0.0490

0.0486

0.0391

0.0385

0.0321

0.0313

0.0271

0.0262

0.1332

0.1709

0.1283

0.1648

0.1228

0.1581

0.1184

0.1525

0.190

0.205

0.224

0.243

475

425

375

325

16480

18418

20626

23464

31.55

31.68

31.84

31.94

Technical particulars Cables with Aluminium Conductors


VOLTAGE GRADE

76/132(145kV)

76/132(145kV)

76/132(145kV)

300

400

500

A2XLyCY

A2XLyCY

A2XLyCY

NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(a) In air......(A) at 40C

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

513

527

540

592

613

629

681

712

733

342

358

378

385

408

432

433

464

492

(b) In ground(A) at 30C Thermal Resistivity


1.5 K.m/W
Depth : 1500mm
Approx. Overall Dia. of cable (mm)

83

87

90

Approx. Weight of cable (kg / km)

11830

12820

13650

0.1000

0.0778

0.0605

Max. DC Resistance of conductor


at 20C (ohm / km)
Max.AC Resistance at 90C (ohm / km)

0.1290

0.1289

0.1008

0.1007

0.0790

0.0787

Reactance at 50 Hz (ohm / km)

0.1497

0.1884

0.1429

0.1803

0.1365

0.1728

Approx. Capacitance (microFarad / km)


Max. Length

0.148

0.161

0.175

650

600

575

TOTAL WT

12329

13358

14221

TOTAL kA for 1 Sec

31.57

31.68

31.83

Technical particulars Cables with Copper Conductors


VOLTAGE GRADE

76/132(145kV)

76/132(145kV)

300

400

2XLyCY

2XLyCY

NO OF CORES
NOMINAL AREA sqmm
TYPE OF CABLE

(In Trefoil
Formation)

(a) In air......(A) at 40C

(In Flat
Formation)
(D+70)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

648

678

697

739

781

806

425

457

485

473

517

550

(b) In ground(A) at 30C Thermal


Resistivity 1.5 K.m/W
Depth : 1500mm
Approx. Overall Dia. of cable (mm)

83

87

Approx. Weight of cable (kg / km)

13780

15270

Max. DC Resistance of conductor at 20C (ohm / km)

0.0601

0.0470

Max.AC Resistance at 90C (ohm / km)

0.0780

0.0778

0.0617

0.0614

Reactance at 50 Hz (ohm / km)

0.1486

0.1870

0.1421

0.1794

Approx. Capacitance (microFarad / km)


Max. Length

0.150

0.162

550

500

TOTAL WT

14359

15910

TOTAL kA for 1 Sec

31.65

31.75

Technical Catalogue

76/132(145kV)

76/132(145kV)

76/132(145kV)

76/132(145kV)

630

800

1000

1200

A2XLyCY

A2XLyCY

A2XLyCY

A2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

776

819

846

882

942

977

986

1065

1110

1074

1167

1222

482

526

559

534

591

631

583

655

702

621

703

757

93

97

101

106

14790

16140

17280

18870

0.0469

0.0367

0.0291

0.0247

0.0620

0.0617

0.0495

0.0490

0.0405

0.0398

0.0354

0.0346

0.1320

0.1673

0.1262

0.1604

0.1219

0.1551

0.1173

0.1494

0.187

0.204

0.219

0.237

475

450

450

400

15406

16823

18004

19664

31.77

31.86

31.63

31.62

76/132(145kV)

76/132(145kV)

76/132(145kV)

76/132(145kV)

500

630

800

1000

2XLyCY

2XLyCY

2XLyCY

2XLyCY

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

(In Trefoil
Formation)

(In Trefoil
Formation)

(In Flat
Formation)
(D+70)

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

838

897

929

944

1025

1067

1056

1162

1217

1160

1293

1363

523

582

622

574

652

700

625

722

781

670

786

855

90

94

98

102

16710

18810

20980

23400

0.0366

0.0283

0.0221

0.0176

0.0490

0.0486

0.0391

0.0385

0.0320

0.0312

0.0270

0.0261

0.1365

0.1728

0.1314

0.1666

0.1257

0.1598

0.1211

0.1540

0.175

0.189

0.206

0.222

450

400

375

325

17408

19604

21862

24375

31.83

31.84

31.94

31.78

VOLTAGE GRADE : 38/66(72.5kV) & TYPE : A2XLyCY


Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/ Lead Sheath / Semico Tape /
Copper Wire Screen / PVC Sheath / Graphite Coating
Aluminium Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

185

240
In Flat
Form
D+70

In Trefoil
Form

300
In Flat
Form
D+70

In Trefoil
Form

In Trefoil
Form

400
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

391

401

412

455

469

483

514

533

550

592

621

642

Ground (30C)(A)
TRS-1.5 K.m/W
Depth-1500mm

267

276

294

304

318

339

338

357

381

380

407

435

Approx. Overall Dia.(mm)

61

64

66

69

Approx. Weight (kg / km)

7780

8220

8600

9410

Max. DC Resistance at
20C (ohm / km)

0.164

0.125

0.100

0.0778

Max.AC Resistance at
90C(ohm / km)

0.2108

0.2107

0.1610

0.1608

0.1291

0.1289

0.1010

0.1007

Reactance at
50 Hz (ohm / km)

0.1443

0.1925

0.1390

0.1858

0.1349

0.1808

0.1288

0.1729

Approx. Capacitance
(mFarad / km)

0.179

0.193

0.205

0.225

Max. Length

1000

950

900

825

VOLTAGE GRADE : 38/66(72.5kV) & TYPE : 2XLyCY

Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/Lead Sheath / Semico Tape /


Copper Wire Screen / PVC Sheath / Graphite Coating
Copper Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

185

240
In Flat
Form
D+70

In Trefoil
Form

300
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

In Trefoil
Form

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

496

515

531

573

602

622

646

685

710

Ground (30C)(A)
TRS-1.5 K.m/W
Depth-1500mm

335

354

378

379

407

435

418

455

489

Approx. Overall Dia.(mm)

61

64

66

Approx. Weight (kg / km)

8930

9690

10490

0.0991

0.0754

0.0601

Max. DC Resistance at
20C (ohm / km)
Max.AC Resistance at
90C(ohm / km)

0.1272

0.1270

0.0973

0.0971

0.0781

0.0778

Reactance at 50 Hz (ohm / km)

0.1438

0.1918

0.1385

0.1852

0.1338

0.1794

Approx. Capacitance (mFarad / km)


Max. Length

0.181

0.195

0.208

875

800

725

Technical Catalogue

500
In Trefoil
Form

630
In Flat
Form
D+70

In Trefoil
Form

800
In Flat
Form
D+70

In Trefoil
Form

1000
In Flat
Form
D+70

In Trefoil
Form

1200
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

682

723

750

774

832

867

876

955

1001

976

1079

1139

1056

1180

1254

427

462

496

473

523

563

521

587

634

567

649

706

600

695

760

73

76

81

85

90

10250

11060

12330

13580

14850

0.0605

0.0469

0.0367

0.0291

0.0247

0.0792

0.0788

0.0623

0.0617

0.0499

0.0491

0.0409

0.0399

0.0360

0.0399

0.1231

0.1656

0.1193

0.1603

0.1148

0.1540

0.1111

0.1489

0.1074

0.1436

0.248

0.267

0.294

0.319

0.348

750

700

625

575

525

400
In Trefoil
Form

500
In Flat
Form
D+70

In Trefoil
Form

630
In Flat
Form
D+70

In Trefoil
Form

800
In Flat
Form
D+70

In Trefoil
Form

1000
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

734

790

822

831

907

950

931

1036

1093

1035

1171

1247

1135

1302

1399

464

514

554

512

578

627

560

646

706

605

714

786

647

776

860

70

73

77

82

86

11810

13310

15080

17150

19640

0.0470

0.0366

0.0283

0.0221

0.0176

0.0619

0.0614

0.0493

0.0486

0.0395

0.0386

0.0324

0.0313

0.0276

0.0262

0.1281

0.1720

0.1231

0.1656

0.1188

0.1597

0.1143

0.1534

0.1103

0.1479

0.228

0.248

0.270

0.297

0.324

650

575

500

450

400

VOLTAGE GRADE : 64/110 (123 kV) & TYPE : A2XLyCY

Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/Lead Sheath / Semico Tape /


Copper Wire Screen / PVC Sheath / Graphite Coating
Aluminium Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

240
In Trefoil
Form

300
In Flat
Form
D+70

In Trefoil
Form

400
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

454

465

477

513

529

543

592

615

633

Ground (30C)(A) TRS-1.5 K.m/W


Depth-1500mm

306

319

337

341

358

379

384

408

432

Approx. Overall Dia.(mm)

76

78

82

Approx. Weight (kg / km)

10460

10850

11780

Max. DC Resistance at 20C (ohm / km)

0.1250

0.1000

0.0778

Max.AC Resistance at 90C(ohm / km)

0.1609

0.1608

0.1290

0.1289

0.1008

0.1007

Reactance at 50 Hz(ohm / km)

0.1503

0.1914

0.1460

0.1864

0.1393

0.1783

Approx. Capacitance (mFarad / km)

0.152

0.160

0.174

750

725

650

Max. Length

VOLTAGE GRADE : 64/110(123 kV) & TYPE : 2XLyCY


Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/Lead Sheath / Semico Tape /
Copper Wire Screen / PVC Sheath / Graphite Coating
Copper Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

240
In Trefoil
Form

300
In Flat
Form
D+70

In Trefoil
Form

400
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

575

597

614

648

680

700

738

784

810

Ground (30C)(A) TRS-1.5 K.m/W


Depth-1500mm

383

408

433

423

457

486

470

516

551

Approx. Overall Dia.(mm)

77

79

82

Approx. Weight (kg / km)

11940

12790

14230

Max. DC Resistance at 20C (ohm / km)

0.0754

0.0601

0.0470

Max.AC Resistance at 90C(ohm / km)

0.0972

0.0970

0.0780

0.0778

0.0617

0.0614

Reactance at 50 Hz(ohm / km)

0.1498

0.1908

0.1448

0.1850

0.1385

0.1774

Approx. Capacitance (mFarad / km)


Max. Length

0.153

0.162

0.176

650

600

550

Technical Catalogue

500

630
In Flat
Form
D+70

In Trefoil
Form

800
In Flat
Form
D+70

In Trefoil
Form

1000
In Flat
Form
D+70

In Trefoil
Form

In Trefoil
Form

1200
In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

683

716

738

777

824

852

882

946

984

983

1067

1116

1069

1170

1230

431

464

493

480

525

560

531

590

632

579

653

703

615

701

758

86

89

93

97

102

12760

13650

14960

16410

17710

0.0605

0.0469

0.0367

0.0291

0.0247

0.0790

0.0788

0.0621

0.0617

0.0496

0.0490

0.0406

0.0398

0.0356

0.0399

0.1332

0.1709

0.1289

0.1655

0.1233

0.1587

0.1192

0.1535

0.1149

0.1479

0.190

0.204

0.222

0.239

0.260

600

575

475

450

425

500
In Trefoil
Form

630
In Flat
Form
D+70

In Trefoil
Form

800
In Flat
Form
D+70

In Trefoil
Form

1000
In Flat
Form
D+70

In Trefoil
Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

838

901

935

942

1030

1075

1053

1166

1226

1153

1294

1371

521

581

623

571

651

702

620

720

782

664

783

856

86

89

93

98

15820

17680

19800

22520

0.0366

0.0283

0.0221

0.0176

0.0490

0.0486

0.0391

0.0385

0.0321

0.0313

0.0271

0.0262

0.1332

0.1709

0.1283

0.1648

0.1228

0.1581

0.1184

0.1525

0.190

0.205

0.224

0.243

475

425

375

325

VOLTAGE GRADE : 76/132(145kV) & TYPE : A2XLyCY

Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/Lead Sheath / Semico Tape /


Copper Wire Screen / PVC Sheath / Graphite Coating
Aluminium Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

300
In Trefoil Form

400
In Flat
Form
D+70

500
In Flat
Form
D+70

In Trefoil
Form

In Trefoil Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

513

527

540

592

613

629

681

712

733

Ground (30C)(A) TRS-1.5 K.m/W


Depth-1500mm

342

358

378

385

408

432

433

464

492

Approx. Overall Dia.(mm)

83

87

90

Approx. Weight (kg / km)

11830

12820

13650

Max. DC Resistance at 20C (ohm / km)

0.1000

0.0778

0.0605

Max.AC Resistance at 90C(ohm / km)

0.1290

0.1289

0.1008

0.1007

0.0790

0.0787

Reactance at 50 Hz(ohm / km)

0.1497

0.1884

0.1429

0.1803

0.1365

0.1728

Approx. Capacitance (mFarad / km)


Max. Length

0.148

0.161

0.175

650

600

575

VOLTAGE GRADE : 76/132(145kV) & TYPE : 2XLyCY

Conductor / Conductor-Screen/XLPE Insulation/Insulation-Screen / Semicon WS Tape/Lead Sheath / Semico Tape /


Copper Wire Screen / PVC Sheath / Graphite Coating
Aluminium Conductor & Combined Screen(Lead+Copper Wire) fault Level 31.5kA for One Second
NOMINAL AREA sqmm

300
In Trefoil Form

400
In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

Air (40C)(A)

648

678

697

739

781

806

Ground (30C)(A) TRS-1.5 K.m/W Depth-1500mm

425

457

485

473

517

550

Approx. Overall Dia.(mm)

83

87

Approx. Weight (kg / km)

13780

15270

Max. DC Resistance at 20C (ohm / km)

0.0601

0.0470

Max.AC Resistance at 90C(ohm / km)

0.0780

0.0778

0.0617

0.0614

Reactance at 50 Hz(ohm / km)

0.1486

0.1870

0.1421

0.1794

Approx. Capacitance (mFarad / km)


Max. Length

0.150

0.162

550

500

Technical Catalogue

630
In Trefoil Form

800
In Flat
Form
D+70

In Trefoil Form

1000
In Flat
Form
D+70

In Trefoil Form

1200
In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

776

819

846

882

942

977

986

1065

1110

1074

1167

1222

482

526

559

534

591

631

583

655

702

621

703

757

93

97

101

106

14790

16140

17280

18870

0.0469

0.0367

0.0291

0.0247

0.0620

0.0617

0.0495

0.0490

0.0405

0.0398

0.0354

0.0346

0.1320

0.1673

0.1262

0.1604

0.1219

0.1551

0.1173

0.1494

0.187

0.204

0.219

0.237

475

450

450

400

630

800

1000

500
In Trefoil Form

In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

In Trefoil Form

In Flat
Form
D+70

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

BEB

SEB

SEB

838

897

929

944

1025

1067

1056

1162

1217

1160

1293

1363

523

582

622

574

652

700

625

722

781

670

786

855

90

94

98

102

16710

18810

20980

23400

0.0366

0.0283

0.0221

0.0176

0.0490

0.0486

0.0391

0.0385

0.0320

0.0312

0.0270

0.0261

0.1365

0.1728

0.1314

0.1666

0.1257

0.1598

0.1211

0.1540

0.175

0.189

0.206

0.222

450

400

375

325

Process Flow
Chart
MATERIAL
COPPER

SEMICONDUCTING CROSS - LINKED POLYETHYLENE

CROSS LINKED POLYETHYLENE

SEMICONDUCTING CROSS - LINKED POLYETHYLENE

WIRE DRAWING

CONDUCTOR DRAWING

CONDUCTOR SHIELDING (EXTRUSION AND VULCANISING)

CROSS LINKED POLYETHYLENE INSULATION (EXTRUSION AND VULCANISING)

INSULATION SHIELDING (EXTRUSION AND VULCANISING)

SEMI CONDUCTING WATER SWELLABLE TAPE

ANNEALED COPPER TAPE

TAPING
INSULATION METALLIC SHIELDING

TAPING

SEMI CONDUCTING WATER SWELLABLE TAPE

LEAD ALLOY SHEATHING / COPPER SCREENING

PVC TYPE ST - 2

METALLIC SHIELDING

PVC SHEATHING (EXTRUSION)


WITH GRAPHITE COATING

TESTING FINISHED CABLE

PACKING

Technical Catalogue

Laying
Methods
Both End Bonding Method
Cable Termination

typical trench cross section


Cables in Trefoil Formation

G.L.

Conductor

Excavated earth
Backfill

Bonding
Cable

R.C.C.
Protection Tile

EHV Cable in
close touching
trefoil formation
50

single point bonding method

300

Link Box

Pre-warning
Tape

Link Box

1500

Screen

Cable Termination
Cable sheath
insulated at
termination

600

Conductor
Bonding
Cable

Screen

Link Box with


SVL Unit
Link Box

typical trench cross section


road crossing
Cables in Flat Formation

G.L.

Excavated earth
Backfill

cross-bonding method
Cable terminations
Conductor

Pre-warning Tape
1500

Screen separation

R.C.C. Protection Tile


Screen

SVL

Cross-bonding
of screens

Sieved compacted
Earth

765

Direct earthing

PVC / HDPE Pipe

EVH Cable in
flat formation

KEC
International
Ltd.

KEC is one of the oldest players in the industry and global leader in the Infrastructure Engineering, Procurement and
Construction space. Established in 1945, KEC has a significant presence in the segments of Power Transmission & Distribution,
Cabling, Railway, Telecom and Water Resource management. KECs strengths lie in Engineering, Design, Manufacture and
Testing, supply of transmission towers, telecom towers, cables and Construction of turnkey infrastructure projects. KECs
focused approach towards project management enables the creation of world class products, innovative solutions, customized
to overcome extreme terrain and climate. With proven technical prowess in handling mega projects and superior project
management expertise, KEC has made an indelible mark on the world map by constantly and consistently reengineering itself
to retain its position of leadership in the areas of quality, technology, capacity and capability.

rpg
Enterprises

RPG Enterprises is one of Indias largest business conglomerates. Since its inception in 1979, RPG Enterprises has been one
of the fastest growing business houses in India. RPG Enterprises has diverse businesses under its fold ranging from Power,
Tyres, Infrastructure, IT to Pharma. The Groups management comprises individuals extensively qualified and experienced in
their domain areas. RPGs wide ranging business invite growing returns and high esteem in the eyes of all its stakeholders.
The Group lives by values of keen entrepreneurial skills, performance and excellence.
Corporate office
6th Floor, RPG House, 463. Dr. Annie Besant Road, Worli, Mumbai - 400 030. India
Tel. +91-22-66670300, 24937244 | Fax No. +91-22-24930206
email: powercables@kecrpg.com | telecomcables@kecrpg.com | exportcables@kecrpg.com

Sales Offices
Delhi

Mumbai

Pune

Chennai

N-83,1st Floor,(Above PNB )


Pratap Building, Cannaught Place,
New Delhi - 110 001. India

6th Floor, RPG House, 463.


Dr. Annie Besant Road, Worli,
Mumbai - 400 030. India

Flat No.9, KSHITIJ ,1st Floor, 769/6,


Lane No.7, Prabhat Road, Deccan
Gymkhana, Pune - 411 004. India

Bhavani Mansion No.3, 4th Lane,


Nungambakkam High Road,
Chennai - 600 034. India

Tel. +91-11-66098598, 599


Fax No. +91-11-66098597

Tel. +91-22-66670300, 24937244


Fax No. +91-22-24930206

Tel. +91-20-64706061, 6065


Fax No. +91-20-2436178

Tel. +91-44-28332920, 28332918


Fax No. +91-44-28224917

Kolkata

Vadodara

Hyderabad

Bangalore

Halwasiya Mansion, Ground Floor,


6/2, Moira Street,
Kolkata - 700 017. India

421, Center Point,


R.C.Dutta Road, Alkapuri,
Vadodara - 390 007. India

406 & 407, Maheshwari Chambers,


Erramanzil, Somajiguda,
Hyderabad - 500 082. India

C/o. CEAT Limited, Jasmine Mansion,


4th Floor, 19, J. C. Road,
Bangalore - 560 002. India

Tel. +91-33-64590654
Fax No. +91-33-22906720

Tel. Tel. +91-265-3015454


Fax No. +91-265-3015454

Tel. +91-40-30901642
Fax No. +91-40-30901642

Tel. +91-80-22124444
Fax No. +91-80-22124444

April 2011