Vous êtes sur la page 1sur 306

Triconex General Purpose v2

Systems

Planning and
Installation Guide

Assembly Number 9700122-003


June 2011

Information in this document is subject to change without notice. Companies, names and data used in
examples herein are fictitious unless otherwise noted. No part of this document may be reproduced or
transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express
written permission of Invensys Systems, Inc.
2010-2011 by Invensys Systems, Inc. All rights reserved.
Invensys, the Invensys logo, Foxboro, I/A Series, Triconex, Tricon, Trident, and TriStation are trademarks
of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective
owners.

Document Number 9720122-003


Printed in the United States of America.

Contents

Preface

ix
Summary of Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Product and Training Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x
We Welcome Your Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi

Chapter 1

Introduction

Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fault Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TriStation 1131 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Main Processor Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Bus Systems and Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Logic Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Controller Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System Diagnostics and Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Analog Input/Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Analog Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pulse Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Solid-State Relay Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
International Certifications and Qualifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Canadian Standards Association. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Factory Mutual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TV Rheinland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
European Union CE Mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Chapter 2

System Description

23

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General Environmental and EMC Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Typical Weight of Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cable Flame Test Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Planning and Installation Guide for Triconex General Purpose v2 Systems

iv

Contents

Ground Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Standard Tri-GP Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Main Processor Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
MP Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
MP Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Communication Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Logic Power Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
CM Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
I/O Modules Common Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Wiring Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Logic Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Field Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Analog Input Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
AI Module 3351S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
AI Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
AI External Termination Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
RTD/TC/AI External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
AI Hazardous Location External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . . 65
AI HART Baseplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Analog Input/Digital Input Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
AI/DI Module 3361S2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
AI/DI Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
AI/DI External Termination Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
AI/DI Hazardous Location External Termination Panels . . . . . . . . . . . . . . . . . . . . . 81
Analog Output Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
AO Module 3481S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
AO Module 3482S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
AO Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
AO External Termination Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
AO HART Baseplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
AO Hazardous Location External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . 97
Digital Input Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
DI Module 3301S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
DI Module 3311S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
DI Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
DI External Termination Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Solid State Relay Input External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . 112
DI Hazardous Location External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . 115
Digital Output Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
DO Module 3401S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
DO Module 3411S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
DO Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
DO High-Current Baseplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
DO Low-Current Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Planning and Installation Guide for Triconex General Purpose v2 Systems

Contents

DO External Termination Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134


Relay Output External Termination Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
DO Hazardous Location External Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . 142
Pulse Input Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
PI Module 3382S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
PI Baseplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
PI Hazardous Location Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Solid-State Relay Output Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
SRO Module Schematic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
SRO Baseplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Interconnect Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
I/O Extender Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
I/O Bus Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
I/O Bus Terminators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
End Caps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
MP Baseplate End Caps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
I/O Baseplate and I/O Extender Module End Caps . . . . . . . . . . . . . . . . . . . . . . . . . 173
Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174

Chapter 3

Installation and Maintenance

175

System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176


System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Determining Logic Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
General Cooling Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Determining Cooling Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
General Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Plant Power and Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Tri-GP Field, Power, and Ground Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Application-Specific Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Component Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Mounting a Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Installing Baseplates on a Column . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Connecting Columns with I/O Extender Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Installing Modules on Baseplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Installing the Module Address Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Installing Other Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Enclosing the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Controller Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Grounding Baseplates to Protective Earth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Grounding Logic Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Grounding Field Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Connecting Shields to Earth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203

Planning and Installation Guide for Triconex General Purpose v2 Systems

vi

Contents

Implementation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204


Disabling Output Voter Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Checking Controller Power Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Enabling Disabled Output Voter Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Toggling Field I/O Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Verifying Spare Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Guidelines for Replacing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Replacing a Main Processor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Replacing a Communication Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Replacing an I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210

Chapter 4

Fault and Alarm Indicators

211

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Fault and Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Main Processor Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
MP Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
MP System Mode Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
MP Alarm Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
MP Communication Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Communication Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
CM Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
CM Communication Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Analog Input Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
AI Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
AI Field Power Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Analog Input/Digital Input Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
AI/DI Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
AI/DI Field Power Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Analog Output Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
AO Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
AO Field Alarm Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Digital Input Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
DI Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
DI Field Power Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
DI Point Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Digital Output Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Status Indicators on DO and SDO Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Power/Load Indicator on DO and SDO Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Point Indicators on DO and SDO Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Load Indicators on SDO Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Pulse Input Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
PI Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
PI Field Fault Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239

Planning and Installation Guide for Triconex General Purpose v2 Systems

Contents

vii

PI Point Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239


Solid-State Relay Output Module Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
SRO Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
SRO Point Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242

Appendix A Pin-Outs for Cables and Connectors

243

Ethernet Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244


10BaseT and 100BaseTX Ethernet Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
AUI 10 Megabit Ethernet MAU Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
MII Ethernet MAU Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Serial Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
RS232 Pin-Outs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
RS485 Pin-Outs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Ethernet Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Cross-Over Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Straight-Through Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Serial Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
RS-232 Serial Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
RS-485 Serial Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Diagread Cables and Debug Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Diagread Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Debug Connector for MP and Left-Position CMs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Debug Connector for I/O and Right-Position CMs . . . . . . . . . . . . . . . . . . . . . . . . . . 255

Appendix B Non-Incendive Circuit Parameters

257

MP and CM Non-Incendive Circuit Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258


Hazardous Location HART Baseplate Non-Incendive Circuit Parameters . . . . . . . . . . . 259

Appendix C HART Communication

261

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
Triconex 4850 Hart Multiplexer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Installing the Triconex 4850 HART Multiplexer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Triconex 4850 HART Multiplexer Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267

Appendix D Warning Labels

269

General Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269


Hazardous Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Hot Surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270

Appendix E Recommended Parts for Replacement

271

Appendix F Panel Labels

273

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
AI/DI Hazardous Location External Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . 275
RTD/TC/AI External Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Planning and Installation Guide for Triconex General Purpose v2 Systems

viii

Contents

SSR Input External Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277

Glossary

279

Index

287

Planning and Installation Guide for Triconex General Purpose v2 Systems

Preface

This guide includes information on planning and installing a version 2.x Triconex General
Purpose System.
Throughout the rest of this guide, the Triconex General Purpose System also may be referred to
as the Tri-GP.

Summary of Sections

Chapter 1, Introduction Describes the theory of operation supporting the controller.

Chapter 2, System Description Provides descriptions, illustrations, specifications,


and simplified schematics for components of the controller.

Chapter 3, Installation and Maintenance Provides guidelines for the person


responsible for installing and maintaining a controller.

Chapter 4, Fault and Alarm Indicators Provides information on responding to alarm


conditions.

Appendix A, Pin-Outs for Cables and Connectors Provides pin-out information for
standard cables and adapters used with the controller.

Appendix B, Non-Incendive Circuit Parameters Describes the parameters to be used


for non-incendive communication circuits in the field.

Appendix C, HART Communication Describes HART communication through


Tri-GP systems.

Appendix D, Warning Labels Provides a physical description of warning labels


required for systems in which certain hazards may occur.

Appendix E, Recommended Parts for Replacement Lists the parts recommended by


Invensys to replace existing parts and to customize your system.

Appendix F, Panel Labels Shows how to apply external termination panel (ETP)
labels.

Glossary Provides information for terms and topics used throughout the guide.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Preface

Related Documents

Communication Guide for Triconex General Purpose v2 Systems

Product Release Notice for Triconex General Purpose v2.x Systems

Safety Considerations Guide for Triconex General Purpose v2 Systems

TriStation 1131 Developers Guide

TriStation 1131 Libraries Reference

Product and Training Information


To obtain information about Invensys products and in-house and on-site training, see the
Invensys website or contact your regional customer center.
Web Site
http://www.iom.invensys.com

Technical Support
Customers in the U.S. and Canada can obtain technical support from the Invensys Global
Customer Support (GCS) center at the numbers below. International customers should contact
their regional Invensys support office.
Requests for support are prioritized as follows:

Emergency requests are given the highest priority

Requests from participants in the System Watch Agreement (SWA) and customers with
purchase order or charge card authorization are given next priority

All other requests are handled on a time-available basis

If you require emergency or immediate response and are not an SWA participant, you may
incur a charge. Please have a purchase order or credit card available for billing.
Telephone
Toll-free number 866-746-6477, or
Toll number
508-549-2424 (outside U.S.)
Fax
Toll number

508-549-4999

Web Site
http://support.ips.invensys.com (registration required)

Planning and Installation Guide for Triconex General Purpose v2 Systems

Preface

xi

We Welcome Your Comments


To help us improve future versions of Invensys documentation, we want to know about any
corrections, clarifications, or further information you would find useful. When you contact us,
please include the following information:

The title and version of the guide you are referring to

A brief description of the content you are referring to (for example, step-by-step
instructions that are incorrect, information that requires clarification or more details,
missing information that you would find helpful)

Your suggestions for correcting or improving the documentation

The version of the Triconex hardware or software you are using

Your name, company name, job title, phone number and e-mail address

Send e-mail to us at:


triconextechpubs@invensys.com
Please keep in mind that this e-mail address is only for documentation feedback. If you have a
technical problem or question, please contact the Invensys Global Customer Support (GCS)
center. See Technical Support on page x for contact information.
Or, you can write to us at:
Attn: Technical Publications - Triconex
Invensys
26561 Rancho Parkway South
Lake Forest, CA 92630
Thank you for your feedback.

Planning and Installation Guide for Triconex General Purpose v2 Systems

xii

Preface

Planning and Installation Guide for Triconex General Purpose v2 Systems

1
Introduction

Controller Features

Fault Tolerance

System Configuration

Theory of Operation

International Certifications and Qualifications

16

Planning and Installation Guide for Triconex General Purpose v2 Systems

Chapter 1

Introduction

Controller Features
The Tri-GP version 2.x controller is a state-of-the-art programmable logic and process controller
that provides a high level of system fault tolerance. To ensure the highest possible system
integrity at all times, the Tri-GP controller includes these features:

Provides Triple Modular Redundant (TMR) architecture whereby each of three


identical system channels independently executes the control program, and specialized
hardware/software mechanisms vote all inputs and outputs.

Withstands harsh industrial environments.

Enables field installation and repair to be done at the module level while the controller
remains online. Replacing an I/O module does not disturb field wiring.

Supports I/O modules (analog and digital) and an optional Communication Module
that interfaces with Modbus masters and slaves, other Triconex controllers in Peer-toPeer networks, and external host applications on Ethernet networks.

Support for:
25 I/O baseplates maximum
416 AI points maximum (13 AI baseplates, 13 AI/DI baseplates, or any combination
that does not exceed 416 total AI or AI/DI points)
20 AO points maximum (5 baseplates)
640 DI points maximum (20 DI baseplates, 13 AI/DI baseplates, or any combination
that does not exceed 640 total DI points)
320 DO points maximum (20 baseplates)
30 PI points maximum (5 baseplates)
640 SRO points maximum (20 baseplates)

Integrates the I/O module with the termination assembly.

Executes control programs developed and debugged with TriStation 1131 software.
(For software compatibility, see the Product Release Notice for Tri-GP v2.x, available on
the Invensys Global Customer Support (GCS) website.)

Allows normal maintenance while the Tri-GP controller is operating, without


disturbing the controlled process.

Provides TriStation 1131 and Modbus communication from the Main Processor (MP) or
from the Communication Module (CM).

Provides a dedicated co-processor which controls the input and output modules to
reduce the workload of the MP. Each I/O module is supported by custom applicationspecific integrated circuits (ASICs), which scan inputs and perform diagnostics to
detect hardware faults. Output module ASICs do the following:
Supply information for voting of output data.
Check I/O loop-back data from the output terminal for final validation of the
output state.
Perform diagnostics to detect hardware and field-wiring problems.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Fault Tolerance

Provides integral online diagnostics with adaptive-repair capabilities.

Supports hot-spare I/O modules for critical applications where prompt service may not
be possible.

Provides integral support for redundant field and logic power sources.

Fault Tolerance
Fault tolerance, the most important capability of the Tri-GP controller, is the ability to detect
transient and steady-state error conditions and take appropriate corrective action online. With
fault tolerance, there is an increase in safety and an increase in the availability of the controller
and the process being controlled.
The Tri-GP controller provides fault tolerance through Triple Modular Redundant (TMR)
architecture. The controller consists of three identical channels, except for the Power Modules
which are dual-redundant. Each channel independently executes the control program (also
referred to as the TriStation 1131 application) in parallel with the other two channels. Hardware
voting mechanisms qualify and verify all digital inputs and outputs from the field; analog
inputs are subject to a mid-value selection process.
Because each channel is isolated from the others, no single-point failure in any channel can pass
to another. If a hardware failure occurs in one channel, the faulty channel is overridden by the
other channels. Repair consists of removing and replacing the failed module in the faulty
channel while the controller is online and without process interruption. The controller then
reconfigures itself to full TMR operation.
Extensive diagnostics on each channel, module, and functional circuit immediately detect and
report operational faults by means of indicators or alarms. All diagnostic fault information is
accessible by the control program and the operator. If faults are detected, the operator can use
the diagnostic information to modify control actions or direct maintenance procedures.
Because the triplicated system operates as one control system, the Tri-GP controller can be
programmed with one control program that terminates sensors and actuators at a single wiring
terminal.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Chapter 1

Introduction

System Configuration
Physically, a basic Tri-GP version 2 controller consists of Main Processors, I/O modules, an
optional Communication Module, the baseplates on which the modules are mounted, field
wiring connections, and a PC running the TriStation 1131 software. This section briefly
describes these components.
A typical Tri-GP system is configured into one or more vertical I/O columns guided by DIN
rails and mounted on a sheet-metal panel. Tri-GP modules are field-replaceable units consisting
of an electronic assembly housed in a metal spine. Each module has a protective cover that
ensures no components or circuits are exposed even when a module is removed from the rail.
Offset backplane connectors make it impossible to plug a module in upside down, and keys on
each module prevent the insertion of modules into incorrect slots. The Tri-GP controller
supports digital and analog input and output points, as well as pulse and thermocouple inputs
and multiple communication protocols.

Controller Configuration
A basic Tri-GP system consists of one MP assembly, an optional CM assembly, and I/O
assemblies. Assemblies are configured into a system on a mounting plate using interconnect
assemblies, extenders, I/O bus cables, and I/O bus terminators. I/O modules communicate
with the MPs by means of a triplicated, RS-485, bi-directional communication bus, called the
I/O bus.
For more information, see System Specifications on page 176.

TriStation 1131 Software


TriStation 1131 software is required to develop and download the control program that runs on
the Tri-GP controller. TriStation 1131 software provides three programming languages which
comply with the IEC 61131-3 standard: Function Block Diagram, Ladder Diagram, and
Structured Text. An optional language, CEMPLE (Cause and Effect Matrix), can be purchased
separately.
For software compatibility, see the Product Release Notice for Tri-GP v2.x, available on the
Invensys Global Customer Support (GCS) website.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Theory of Operation

Theory of Operation
The Tri-GP controller is designed with a Triple Modular Redundant (TMR) architecture, which
is a fully triplicated architecture throughout, from the input modules through the Main
Processors, to the output modules. Each module houses the circuitry for three independent
channels. Each channel on the input modules reads the process data and passes that information
to its respective Main Processor. The three Main Processors communicate with each other using
a proprietary high-speed bus system called the TriBus.
Output Module

Input Module
Hot Spare

Hot Spare

Channel A I/O Bus

Input
Channel A

Output
Channel A
IOP A
(IOX)

Channel B IO/ Bus

MP B
(SX)

Input
Channel C

Output
Channel B

IOP B
(IOX)

Field
Output

Output
Channel C

Channel C I/O Bus

MP C
(SX)

Figure 1

Diagnostic Channel

Input
Channel B

TriBus &TriTime

Field
Input

Output Voter

MP A
(SX)

IOP C
(IOX)

Triplicated Architecture of the Tri-GP Controller

Once per scan, the Main Processors synchronize and communicate with their neighbors over the
TriBus. The TriBus sends copies of all analog and digital input data to each Main Processor, then
compares output data from each Main Processor. The Main Processors vote the input data,
execute the control program, and send outputs generated by the control program to the output
modules.
The Tri-GP controller votes the output data on the output modules as close to the field as
possible to detect and compensate for any errors that could occur between the TriBus voting and
the final output driven to the field.
Each I/O slot can contain two identical I/O modules which means if a fault is detected on one
module, control is automatically switched to the healthy module. A faulty module can also be
replaced online when only one module is installed in the slot. In this case, a healthy module is
inserted in the spare slot and the control is switched to this module, which allows the faulty
module to be pulled and sent for repair.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Chapter 1

Introduction

Main Processor Modules


A Tri-GP controller contains three Main Processors. Each Main Processor controls a separate
channel of the system and operates in parallel with the other Main Processors. A dedicated I/O
Processor on each Main Processor manages the data exchanged between the Main Processor
and the I/O modules. A triplicated I/O bus, located on the baseplates, extends from one column
of I/O modules to another column of I/O modules by means of I/O bus cables.
As each input module is polled, the appropriate channel of the I/O bus transmits new input
data to the Main Processor. The input data is assembled into a table in the Main Processor and
is stored in memory for use in the hardware voting process. The individual input table in each
Main Processor is transferred to its neighboring Main Processors over the TriBus. During this
transfer, hardware voting takes place. The TriBus uses a direct memory access programmable
device to synchronize, transmit, vote and compare data among the three Main Processors.
If a disagreement occurs, the signal value found in two out of three tables prevails, and the third
table is corrected accordingly. One-time differences which result from sample timing variations
are distinguished from a pattern of differing data. Each Main Processor maintains data about
necessary corrections in local memory. Any disparity is flagged and used at the end of the scan
by the controllers fault analyzer routines to determine whether a fault exists on a particular
module.
Program Processor

I/O Processor
Dual 24 V
Power Inputs

Redundant
Alarm
Relays

Alarm 1
Alarm 2

System
Alarm

Debug (RJ-12)

+3.3 V
+5 V

Dual-Power
Regulators

3.6 V
Battery
and Monitor

Program
Alarm

Debug (RJ-12)
I/O Bus

Modbus (DB-9)
MPC860A

Reserved (DB-9)
Ethernet
Network (RJ-45)

Clock/NVRAM
8 KB

Shared
Memory
128 K

36-Bit Bus

Flash
4/8 MB

Tribus
(to other MPS)

Figure 2

TriBus
FPGA

36-Bit Bus

DRAM
16 MB

Up Stream

Down Stream

Up Stream

Down Stream

Diagnostic Bus
Channels
(to other MPs)

MPC860A

Main Processor Architecture

Planning and Installation Guide for Triconex General Purpose v2 Systems

DRAM
16 MB

Theory of Operation

The Main Processors send the corrected data to the control program. Each Main Processor
executes the control program in parallel with the neighboring Main Processor. The control
program generates a table of output values which are based on the table of input values
according to customer-defined rules built into the control program. The I/O Processor on each
Main Processor manages the transmission of output data to the output modules by means of the
I/O bus.
Using the table of output values, the I/O Processor generates smaller tables, each corresponding
to an individual output module in the system. Each small table is transmitted to the appropriate
channel of the corresponding output module over the I/O bus. For example, Main Processor A
transmits the appropriate table to Channel A of each output module over I/O Bus A. The
transmittal of output data has priority over the routine scanning of all I/O modules. The I/O
Processor manages the data exchanged between the Main Processors and the Communication
Module using the communication bus which supports a broadcast mechanism.
Each Main Processor provides a 16-megabyte DRAM for the control program, sequence-ofevents (SOE) and I/O data, diagnostics, and communication buffers. The control program is
stored in flash EPROM and loaded in DRAM for execution. The Main Processors receive power
from redundant 24 VDC power sources. If an external power failure occurs, all critical retentive
data is stored in NVRAM. A failure of one power source does not affect controller performance.
If the controller loses power, the control program and all critical data are retained indefinitely.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Chapter 1

Introduction

Bus Systems and Power Distribution


This figure depicts the three triplicated I/O bus systems which are carried baseplate-tobaseplate using Interconnect Assemblies, I/O Extender Modules, and I/O bus cables. The
redundant logic power distribution system is carried using Interconnect Assemblies and I/O
Extender Modules.
Power
Supply
#1

Power
Supply
#2

~~~

I/O Bus
Channel A
Channel B
Channel C

EM
CM

I/O
Communication
Bus
Interconnect
Assembly

I/O Bus

I/O

I/O Bus
MP
I/O

I/O
Power
Bus

Power
Bus

EM

Figure 3

EM

Tri-GP Bus Systems and Power Distribution

TriBus Operation
The TriBus, which is local to the MP Baseplate, consists of three independent serial links
operating at 25 megabits per second. The TriBus synchronizes the Main Processors at the
beginning of a scan, and performs either of these functions:

Transfers I/O, diagnostic, and communication data.

Compares data and identifies disagreements with the output data and program
memory from the previous scan.

An important feature of Tri-GP controller architecture is the use of a single transmitter to send
data to both the upstream and downstream Main Processors which ensures the same data is
received by the upstream processor and downstream processor.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Theory of Operation

I/O Bus Operation


Field signal distribution is local to each I/O baseplate. Each I/O module transfers signals to or
from the field through its associated baseplate assembly. Two positions on the baseplate tie
together as one logical slot. Each field connection on the baseplate extends to both positions,
which means that both the active module and the hot-spare module receive the same
information from the field termination wiring.
The triplicated I/O bus transfers data between the I/O modules and the Main Processors at 2
megabits per second. The I/O bus is contained within an I/O column and can be extended to
another I/O column by using a set of three I/O bus cables (one for each TMR channel.)

Communication Bus Operation


The communication bus runs between the Main Processors and the Communication Modules at
2 megabits per second.

Power Distribution
Power for the modules on each DIN rail is distributed using two independent power rails. Each
module along the DIN rail draws power from both power rails through dual power regulators.
There are four sets of power regulators on each input and output board: one set for each channel
(A, B, and C) and one set for the status indicators.

Planning and Installation Guide for Triconex General Purpose v2 Systems

10

Chapter 1

Introduction

Logic Power

+24V #1
+24V #2
RTN

Each module is designed to operate directly from redundant 24 VDC power sources. Logic
power is carried baseplate-to-baseplate, allowing a single logic power connection per column.
The power conditioning circuitry is protected against over-voltage, over-temperature, and overload conditions. Integral diagnostic circuitry checks for out-of-range voltages and overtemperature conditions. A short on a channel disables the power regulator rather than affecting
the power sources.

+6.5V
+6.5V

Typical I/O Module


Leg A
REG

Vcc

Vcc
Isolated
DC DC
Converter

DC DC
Converter
REG

Leg B
REG

Vcc

Vcc
Isolated
DC DC
Converter

DC DC
Converter
REG

Logic
(System)
Functional
Earth

REG

Vcc

Vcc
Isolated
DC DC
Converter

Field
Functional
Earth

~~

~~~
Power
Bus

~ ~

Field
Functional
Earth

Leg C
REG

~~

Field
Functional
Earth

Isolation
Barrier

Figure 4

Logic Power Distribution

Controller Communication
The controller can communicate directly with a PC running TriStation 1131 software and other
devices through the Main Processor and the Communication Module.

Main Processor Modules


Each MP can provide direct TriStation 1131 and Modbus communication, including:

One TriStation 1131 (Ethernet) port for downloading an application to the controller
and uploading diagnostic information.

One Modbus RS-232/RS-485 serial port which acts as a slave to an external host
computer. Typically, a distributed control system (DCS) monitorsand optionally
updatesthe controller data directly though an MP.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Theory of Operation

11

Communication Module
The Communication Module (CM) provides an optional, three-to-one interface to the Main
Processors that supports serial and Ethernet communication protocols. A single controller
supports up to two CMs on one CM Baseplate with each CM operating independently. Two
CMs can provide redundant communication connections or independent communication ports.
Each CM provides three RS-232/485 serial ports and two Ethernet ports. These ports support a
variety of communication protocols and physical media types that enable the controller to
communicate with external host computers, distributed control systems, open networks,
network printers, and other Tri-GP, Trident, and Tricon v9v10 controllers.
For CM specifications, see Chapter 2, System Description. For details about communication
protocols, see the Communication Guide for Triconex General Purpose v2 Systems.

Physical Communication Interfaces


This table lists the physical communication interfaces included with the MP and CM.
Interfaces

MP

CM

RS-232/RS-485 Modbus Serial Port

10BaseT Ethernet Port

10BaseT/100BaseTX Auto-negotiable Ethernet Port

Attachment unit interface (AUI) for media access unit (MAU)

Media independent interface (MII) for MAU

Debug port

Communication Protocols
This table lists the protocols supported by serial and network ports on the MP and CM.
Protocols

Port Type

MP

CM

Modbus Slave (ASCII or RTU)

Serial

Modbus Master (RTU)

Serial

Modbus Master or Slave (TCP)

Network

TriStation 1131

Network

TCP/IP

Network

Triconex System Access Application (TSAA) (UDP/IP)

Network

Triconex System Access Application (TSAA) with IP Multicast


(UDP/IP)

Network

Triconex Time Synchronization via DLC

Network

Triconex Time Synchronization via UDP/IP or SNTP

Network

Planning and Installation Guide for Triconex General Purpose v2 Systems

12

Chapter 1

Introduction

Protocols

Port Type

MP

CM

Triconex Peer-to-Peer via UDP/IP

Network

Triconex Peer-to-Peer via DLC

Networka

Hewlett-Packard JetDirect Network Printer Server Data Link Control


(DLC)/Logical Link Control (LLC)

Network

a. NET 1 only

System Diagnostics and Status Indicators


The Tri-GP controller incorporates online diagnostics and specialized fault monitoring circuitry
which are able to detect and alarm all single-fault and most multiple-fault conditions. The
circuitry includesbut is not limited toI/O loop-back, watch-dog timers, and loss-of-power
sensors. Using the alarm information, the response of the system can be customized to the
specific fault sequence and operating priorities of the application.
Each module can activate the system integrity alarm, which consists of normally closed (NC)
relay contacts on each MP. Any failure condition, including loss or brownout of system power,
activates the alarm to summon plant maintenance personnel.
Each controller module can activate the system integrity alarm. The alarm consists of a normally
closed or normally opened (NC or NO) relay contact on each Power Module. Any failure
condition, including loss or brownout of system power, activates the alarm to summon plant
maintenance personnel.
The front panel of each module provides LED (light-emitting-diode) indicators that show the
status of the module or the external systems to which it is connected. Pass, Fault, and Active are
common indicators. Other indicators are specific to each module.

Figure 5

Front Panel Indicators

Maintenance consists of replacing plug-in modules. A lighted Fault indicator shows that the
module has detected a fault and must be replaced. The control circuitry for the indicators is
redundant and is isolated from each of the three channels.
All internal diagnostic and alarm status data is available for remote logging and report
generation. This reporting can be done through a local or remote PC running TriStation 1131
software, or through a host computer. For more information, see the TriStation 1131 Developers
Guide.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Theory of Operation

13

Analog Input Module


For Analog Input Modules, each of the three channels asynchronously measures the input
signals and places the results into a table of values. Each of the three input tables is passed to its
associated Main Processor using the I/O bus. The input table in each Main Processor is
transferred to its neighbors across the TriBus. The middle value is selected by each Main
Processor and the input table in each Main Processor is corrected accordingly. In TMR mode,
the mid-value data is used by the control program; in DUAL mode, the average is used.
AI Modules continuously execute Forced Value Diagnostics (FVD) which is a self-test
diagnostic that detects and signals an alarm for all stuck-at and accuracy fault conditions
typically in less than 500 milliseconds. This safety feature allows unrestricted operation under
a variety of multiple-fault scenarios.
Each AI Module is guaranteed to remain in calibration for the life of the controller. Periodic
manual calibration is not required.
For specifications, see Analog Input Components on page 49.

Analog Input/Digital Input Module


The Analog Input/Digital Input Module has 16 digital input points (points 116) and 16 analog
input points (points 1732).
The AI/DI Module has three isolated sets of electronics, called channels, which independently
process field data input to the module. Sensing of each input point is performed in a manner
that prevents a single failure on one channel from affecting another channel.
For analog input points, each channel receives variable voltage signals from each point, converts
them to digital values, and transmits the values to the three MPs on demand.
For digital input points, an ASIC on each channel scans each input point, compiles data, and
transmits it to the MPs on demand.
For all points, the MPs vote the data before passing it to the control program. In TMR mode, the
data passed is mid-value. In DUAL mode, the data passed is the average.
AI/DI Modules sustain complete, ongoing diagnostics for each channel. If the diagnostics
detect a failure on any channel, the Fault indicator turns on and activates the system alarm. The
Fault indicator identifies a channel fault, not a complete module failure. AI/DI Modules are
guaranteed to operate properly in the presence of a single fault and may continue to operate
properly with multiple faults.
AI/DI Modules include the hot-spare feature which allows online replacement of a faulty
module. The AI/DI Module is mechanically keyed to prevent improper installation in a
configured baseplate.
For specifications, see Analog Input/Digital Input Components on page 72.

Planning and Installation Guide for Triconex General Purpose v2 Systems

14

Chapter 1

Introduction

Analog Output Modules


For Analog Output Modules, each of the three channels includes a proprietary ASIC that
receives its output table from the I/O communication processor on its corresponding Main
Processor. AO Modules use special shunt circuitry to vote on the individual output signals
before they are applied to the load. Voter circuitry ensures only one output channel (A, B, or C)
is driving the field load. The shunt output circuitry provides multiple redundancy for all critical
signal paths, guaranteeing safety and maximum availability.
AO Modules continuously execute Forced Switch Diagnostics (FSD) on each point. By carefully
forcing error conditions and observing proper behavior of the voting circuitry, high reliability
and safe operation is ensured. This safety feature allows unrestricted operation under a variety
of multiple-fault scenarios.
Each AO Module is guaranteed to remain in calibration for the life of the controller. Periodic
manual calibration is not required.
For specifications, see Analog Output Components on page 82.

Digital Input Module


For Digital Input Modules, each of the three channels reside on the same module, however, the
circuitry is completely isolated from each other and operates independently. This isolation
means a fault on one channel cannot pass to another. In addition, each channel contains a
proprietary ASIC which manages communication with its corresponding Main Processor, and
supports run-time diagnostics.
Each of the three input channels asynchronously measures the input signals from each point on
the baseplate, determines the respective states of the input signals, and places the values into
separate input tables A, B and C respectively. Each input table is regularly interrogated over the
I/O bus by the I/O Communication Processor located on the corresponding Main Processor.
For example, Main Processor A interrogates Input Table A over I/O Bus A.
DI Modules continuously execute Forced Value Diagnostics (FVD) which is a self-test
diagnostic that detects and signals an alarm for all stuck-at fault conditions typically in less than
500 milliseconds. This safety feature allows unrestricted operation under a variety of multiplefault scenarios.
DI Module diagnostics are specifically designed to monitor devices which hold points in one
state for long periods of time. The diagnostics ensure complete fault coverage of each input
circuit even if the actual state of the input points never changes.
For specifications, see Digital Input Components on page 101.

Digital Output Module


For Digital Output Modules, each of the three channels includes a proprietary ASIC which
receives its output table from the I/O communication processor on its corresponding Main
Processor. All DO Modules use the patented Quad Voter circuitry, which is a quadruplicated
output circuitry which votes on the individual output signals just before they are applied to the
load. This voter circuitry is based on parallel-series paths which pass power if the drivers for

Planning and Installation Guide for Triconex General Purpose v2 Systems

Theory of Operation

15

Channels A and B, or Channels B and C, or Channels A and C command them to closein other
words, 2-out-of-3 drivers voted On. The quadruplicated output circuitry provides multiple
redundancy for all critical signal paths, guaranteeing safety and maximum availability.
During Output Voter Diagnostics (OVD) execution, the commanded state of each point is
momentarily reversed on one of the output drivers, one after another. Loop-back circuitry on
the module allows each ASIC to read the output value for the point to determine whether a
latent fault exists within the output circuit. The output signal transition is guaranteed to be less
than 2 milliseconds (500 microseconds is typical) and is transparent to most field devices. For
devices that cannot tolerate a signal transition of any length, OVD can be disabled on a per-point
basis.
DO Module diagnostics are specifically designed to monitor outputs which remain in one state
for long periods of time. The OVD diagnostics ensure complete fault coverage of each output
circuit even if the actual state of the output points never changes.

Supervised Digital Output Modules


Supervised Digital Output Modules provide both voltage and current loopback, allowing
complete fault coverage for both energized-to-trip and de-energized-to-trip conditions. In
addition, a Supervised Digital Output Module verifies the presence of the field load by doing
continuous circuit-continuity checks. Any loss of field load causes an open-load field error and
the load indicator to illuminate.

Pulse Input Module


For Pulse Input Modules, each of the three channels independently receives pulse input
voltages from each point and converts the values to frequency (RPM) data. Special algorithms,
optimized for accurately measuring the speed of rotating machinery, are used to compensate for
the irregularly spaced teeth on timing gear or for periodic acceleration or de-acceleration. The
results are placed into a table of values. Each input table is passed to its associated Main
Processor using the corresponding I/O bus. The input table in each MP is transferred to its
neighbors across the TriBus. The middle value is selected by each MP and the input table in each
MP is corrected accordingly. In TMR mode, the mid-value is used by the control program; in
DUAL mode, the average is used.
Special self-test circuitry is provided to diagnose the health state of all input points, even when
an active signal is not present. Each Pulse Input Module is guaranteed to remain in calibration
for the life of the controller. Periodic manual calibration is not required.
For specifications, see Pulse Input Components on page 146.

Solid-State Relay Output Module


For Solid-State Relay Output Modules, output signals are received from the Main Processors on
each of three channels. The three sets of signals are voted and the voted data is used to drive the
32 individual relays. Each output has a loop-back circuit which verifies the operation of each
relay switch independently of the presence of a load. Ongoing diagnostics test the operational
status of the SRO Module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

16

Chapter 1

Introduction

The SRO Module is a non-triplicated module for use on non-critical points which are not
compatible with high-side, solid-state output switches; for example, interfacing with
annunciator panels.
For specifications, see Solid-State Relay Output Components on page 165.

International Certifications and Qualifications


The Tri-GP controller has been certified as complying with multiple internationally recognized
standards by the following internationally recognized certification agencies, these certifications
have qualified the Tri-GP for use around the world in safety critical applications. Test reports
from the various certification agencies are available upon request.
Topics include:

Canadian Standards Association on page 16

Factory Mutual on page 17

TV Rheinland on page 18

European Union CE Mark on page 20

Canadian Standards Association


CSA has certified that the Tri-GP v2.x controller is in full compliance with the following
internationally recognized electrical safety standards and is qualified for general use in North
American and other jurisdictions requiring compliance with these standards.
Standard Number

Title

CAN/CSA-C22.2 No.0-M91

General Requirements-Canadian Electrical Code, Part II

CSA Std C22.2 No.0.4-M1982

Bonding and Grounding of Electrical Equipment (Protective


Grounding)

CAN/CSA C22.2 No 1010.1-92

Safety Requirements for Electrical Equipment for Measurement,


Control, and Laboratory Use, Part 1: General Requirements

UL 3121-1 1998-07-14

Electrical Equipment for Laboratory Use, Part 1: General


Requirements

Planning and Installation Guide for Triconex General Purpose v2 Systems

International Certifications and Qualifications

17

Factory Mutual
FM has certified that the Tri-GP v2.x controller is in full compliance with the following
internationally recognized standards and is qualified for use in Class I, Division 2 Temperature
T4, Groups A, B, C, and D hazardous indoor locations.
In North America, the field signals used with ATEX-compliant external termination panels are
certified for Class I, Division 2, Groups C and D.
Standard Number

Title

3611

Electrical Equipment for use in Class I-Division 2; Class II-Division 2; and


Class III-Divisions 1 and 2, Hazardous Locations

3810

Electrical and Electronic Test, Measuring and Process Control Equipment

3600

Electrical Equipment for Use in Hazardous (Classified) Locations-General


Requirements

Note

For hazardous location applications, redundant power sources should be used for
system power. Also, any signal going to or through a hazardous atmosphere must use
hazardous location protection, such as an IS Barrier.

Planning and Installation Guide for Triconex General Purpose v2 Systems

18

Chapter 1

Introduction

TV Rheinland
TV has certified that the Tri-GP v2.x is in full compliance with the internationally recognized
standards listed below, and thus is qualified for use in the following applications and
jurisdictions.

Emergency safety shut-down or other critical control applications requiring SIL 1-2
certification per the functional safety requirements of IEC 61508.

Emergency safety shut-down or other critical control applications in the process sector
requiring SIL 12 certification per the functional safety requirements of IEC 61511.

Burner management applications requiring certification per the requirements of


EN 50156-1:2004

Burner management applications requiring certification per the requirements of NFPA


85:2007

Fire detection and fire alarm applications requiring certification per the requirements of
EN 54-2:1997/A1:2006a

Standard Number

Title

IEC 61508, Parts 1-7, 2000

Functional safety of electrical/electronic/programmable electronic


safety-related systems

IEC 61511:2004

Functional safety - Safety instrumented systems for the process


industry sector

IEC 61131-2:2007

Programmable Controllers Part 2: Equipment Requirements and Test.


Overvoltage Category II is assumed.

IEC 61326-3-1:2008

Electrical equipment for measurement, control and laboratory use EMC requirements - Part 3-1: Immunity requirements for safetyrelated systems and for equipment intended to perform safety-related
functions (functional safety) - General industrial applications

ANSI/ISA-84.00.01-2004
(IEC 61511-1 Mod)

Functional Safety: Safety Instrumented Systems for the Process


Industry Sector - Part 1: Framework, Definitions, System, Hardware
and Software Requirements

EN 50156-1:2004

Electrical equipment for furnaces and ancillary equipment.


Requirements for application design and installation

EN 50178:1998

Electronic equipment for use in power installations

EN 54-2:1997/A1:2006a

Fire detection and fire alarm systems. Control and indicating


equipment.

NFPA 72:2007

National Fire Alarm Code

NFPA 85:2007

Boiler and Combustion Systems Hazards Code, 2007 Edition

a. To comply with the requirements of EN 54-2:1997/A1:2006, the Tri-GP system must be installed in a
metal enclosure with a sealed bottom and a closed door, connected to Safety Ground, as described in
Enclosing the Controller on page 197, and it must be installed in an area with an access level greater
than 2.

Planning and Installation Guide for Triconex General Purpose v2 Systems

International Certifications and Qualifications

Note

19

To comply with standards related to conducted disturbance, a Schaffner FN 2410 line


filter, or equivalent, must be installed between power supplies and baseplates.

For semiconductor manufacturing applications, compliance with these additional installation


guidelines is highly recommended:

Field and logic power supplies should be approved for use in safety extra-low-voltage
(SELV) circuits according to the requirements of IEC 61010-1.

For installations with voltages greater than 30 Vrms/36 VDC, the controller and
associated equipment must be installed in a locked cabinet restricting access to trained
personnel only, with a hazardous-voltage warning label attached prominently.

For installations with ambient temperatures exceeding 94 F (35 C), the controller and
associated equipment should be installed in a locked cabinet restricting access to
trained personnel only, with a hot-surface warning label attached prominently.

For applications in which continuous, correct system operation must be assured, the
controller and associated equipment should be installed in a locked cabinet restricting
access to trained personnel only, with a general-hazard warning label attached
prominently.

For a physical description of labels, see Appendix D, Warning Labels.

Planning and Installation Guide for Triconex General Purpose v2 Systems

20

Chapter 1

Introduction

European Union CE Mark


Based upon the independent TV evaluation and test results, Invensys has certified the Tri-GP
v2.x controller suitable to use in the European Union and all other jurisdictions requiring
compliance with the European Union EMC Directive No. 2004/108/EC and Low Voltage
Equipment Directive No. 2006/95/EC. See the EC Declaration of Conformity for details.
To ensure maximum reliability and trouble-free operation, the Tri-GP and associated wiring
must be installed per the guidelines outlined in this manual. To comply with the CE Mark
requirement for emissions and radiated susceptibility, and EU directives, these guidelines must
be followed:

The entire Tri-GP system must be mounted in a metal enclosure with the door closed.

Field power supplies must be approved for use in safety extra-low-voltage (SELV)
circuits according to the requirements of IEC 61010-1.

EC Declaration of Conformity
The following declaration of conformity with the European Union directives for
electromagnetic compatibility and low-voltage equipment is provided as a convenience. The
declaration is the latest available at publication time and may have been superseded. For
updates, contact the Invensys Global Customer Support (GCS) center.

Planning and Installation Guide for Triconex General Purpose v2 Systems

International Certifications and Qualifications

21

Invensys Operations Management, a business group of Invensys plc


26561 Rancho Parkway South
Lake Forest, CA 92630 USA
EC Declaration of Conformity
EU Directives Covered by this Declaration

2004/108/EC Electromagnetic Compatibility Directive

2006/95/EC Low Voltage Equipment Directive

Products Covered by this Declaration


Triconex General Purpose System (Triple Modular Redundant Controller) Version 2.x2101S2, 2201S2, 2301S2, 2302S2, 2302AS2, 2342S2,
2351S2, 2352S2, 2352AS2, 2361S2, 2381S2, 2381AS2, 2401S2, 2401LS2, 2402S2, 2402AS2, 2451S2, 2480AS2, 2481S2, 3101S2, 3201S2, 3301S2,
3311S2, 3351S2, 3361S2, 3381S2, 3382S2, 3401S2, 3411S2, 3451S2, 3481S2, 3482S2, 9764-510F, interconnect assemblies, extender modules,
I/O bus cabling, and termination products

Basis on which Conformity is being Declared


The product identified above complies with the requirements of the above EU Directives by meeting these standards.
1.

EN 61000-6-4:2007
EN 55011:2007 Gr. 1 Kl. A
IEC 61131-2:2007
IEC 61000--6-4:2007
IEC 61131-2:2007

EMC - Emissions
Conducted and radiated
Radiated interference (class A)
Radiated interference (class A)
Conducted interference (class A)

2.

EN 61131-2:2007
IEC 61131-2:2007 - 9.5
IEC 61326-3-2:2008
EN 50130-4:2003
EN 61000-4-2:2008
EN 61000-4-3:2006 + A1:2008 + IS1:2009
IEC 61131-2:2007 - 9.8
IEC 61326-3-1:2008
IEC 61326-3-2:2008
EN 50130-4:2003
EN 61000-4-4:2004
IEC 61131-2:2007 - 9.9
IEC 61326-3-2:2008
EN 50130-4:2003
EN 61000-4-5:2006
IEC 61131-2:2007
EN 61000-4-12:2006
IEC 61326-3-1:2008 - Table 1 b-e
EN 61000-4-16:1998 + A1:2004

EMC - Immunity
Electrostatic discharge
Electrostatic discharge
Electrostatic discharge
Electrostatic discharge
Radiated HF fields
Fast transient bursts
Fast transient bursts
Fast transient bursts
Fast transient bursts
Fast transient bursts
High-energy surges
High-energy surges
High-energy surges
High-energy surges
Damped oscillatory wave (Ringwave)
Damped oscillatory wave (Ringwave)
Conducted common mode voltage
Conducted common mode voltage

3.

EN 61131-2:2007
EN 61010-1:2007

Product Safety
Overvoltage Category II

The technical documentation required to demonstrate that the product meets the requirements of the above directives has been compiled
by the signatory below and is available for inspection by the relevant enforcement authorities. The CE mark was first applied in: 2010.

Special Measures and Limitations which Must be Observed


The product must be installed and operated as described in the Planning and Installation Guide for Triconex General Purpose v2 Systems.
Signed:

Gary Hufton, Director, Control H/W Development


Invensys Operations Management
14 September 2010

Planning and Installation Guide for Triconex General Purpose v2 Systems

22

Chapter 1

Introduction

Planning and Installation Guide for Triconex General Purpose v2 Systems

2
System Description

Overview

24

Main Processor Components

35

Communication Components

43

I/O Modules Common Specifications

47

Analog Input Components

49

Analog Input/Digital Input Components

72

Analog Output Components

82

Digital Input Components 101


Digital Output Components 119
Pulse Input Components 146
Solid-State Relay Output Components 165
Interconnect Assemblies 170
I/O Extender Modules 171
End Caps 173
Covers 174

Planning and Installation Guide for Triconex General Purpose v2 Systems

24

Chapter 2

System Description

Overview
This chapter describes the hardware components available for Tri-GP v2.x systems. Physically,
a Tri-GP system consists of field-replaceable modules, the baseplates upon which modules are
mounted, field wiring connections, and a PC used to run the TriStation 1131 software. This
section briefly describes these major elements and provides general specifications.
A basic Tri-GP system consists of one MP assembly, an optional CM assembly, and I/O
assemblies. Assemblies consist of a one or two modules on a baseplate. Assemblies are installed
on a mounting plate using interconnect assemblies, extenders, I/O bus cables, and I/O bus
terminators. I/O modules communicate with the MPs by means of a triplicated, RS-485, bidirectional communication bus, called the I/O bus. The I/O bus cable can be used to join I/O
columns.
Each module is fully enclosed to ensure that no components or circuits are exposedeven when
a module is removed from the baseplate. Offset baseplate connectors make it impossible to plug
a module in upside down, and keys on each module prevent the insertion of modules into
incorrect slots.
Topics include:

General Environmental and EMC Specifications on page 24

Typical Weight of Components on page 25

Cable Flame Test Ratings on page 26

Ground Systems on page 26

Standard Tri-GP Products on page 28

General Environmental and EMC Specifications


The Tri-GP fully meets the requirements of IEC 61131, Part2: Programmable Controllers,
Equipment requirements and tests, for environmental withstand and immunity, and
electromagnetic compatibility. This table outlines the general environmental and EMC
specifications for the Tri-GP controller. For details, see IEC 61131.
Specifications

Parameters

Operating temperature

4 F to +158 F (20 C to +70 C) ambient (which is the air


temperature measured at the bottom of each baseplate), per IEC
60068-2-14, tests Na and Nb

Storage temperature

40 F to +185 F (40 C to +85 C) per IEC 60068-2-2, test Bb,


IEC 60068-2-1, test Ab, and IEC 60068-2-30, test Db

Relative humidity

5% to 95%, non-condensing

Corrosive environment

Class G3 Level as defined in ISA Standard S71.04, based on exposure


testing according to EIA Standard 364-65A, Class III

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

Specifications

Parameters

Sinusoidal vibrations per axis

1.75 mm displacement @ 5 to 8.4 Hz (continuous)

25

0.5 g acceleration @ 8.4 to 150 Hz (continuous)


3.5 mm displacement @ 5 to 8.4 Hz (occasional)
1.0 g acceleration @ 8.4 to 150 Hz (occasional)
All tests per IEC 60068-2-6, test Fc
Shock

15 g, 11 ms, half-sine, 3 axis, per IEC 60068-2-27, test Ea

Electrostatic discharge

IEC 61000-4-2, 4 kV contact, 8 kV air

Conducted susceptibility

IEC 61000-4-4, Fast Transient/Burst, 2 kV power & unshielded AC


I/O, 1 kV signal and communication lines
IEC 61000-4-5, Surge Withstand, 2 kV CM2/1 kV DM2 AC power and
I/O, 1 kV CM2 I/O, shielded and communication, 0.5 kV CM2/0.5
kV DM2 DC power
IEC 61000-4-6, RFI, 0.15-80 MHz, 10 V
IEC 61000-4-18, Damped Oscillatory Wave, 0.5 kV CM shielded, 2.5
kV CM/1 kV DM unshielded AC I/O & power, 1 kV CM/0.5 kV DM
I/O

Radiated susceptibility

IEC 61000-4-3, Radio Frequency Electromagnetic Fields, 801000


MHz: 10 V/m, 1.42.0 GHz: 3 V/m, 2.02.7 GHz: 1 V/m

Conducted emissions

CISPR 11, Group 1, Class A:


0.150.5 MHz: 79 dB(V) quazi-peak/66 dB(V) average
0.530 MHz: 73 dB(V)quazi-peak/60 dB(V) average
when installed following the guidelines in this manual.

Radiated emissions

CISPR 11, Class A:


30230 MHz: 40 dB(V/m) @ 10 m
2301000 MHz: 47 dB(V/m) @ 10 m
when installed following the guidelines in this manual.

Power interruptions

IEC 61000-4-29, 1 ms battery, 10 ms DC power supply

Typical Weight of Components


This table lists the typical weight of components. The baseplate weight is based on baseplate
only, not including modules.
Component

Weight in Pounds

Weight in Kilograms

Analog Input Module

3.0

1.4

Analog Input Baseplate

2.4

1.1

Analog Output Module

3.1

1.4

Analog Output Baseplate

2.1

1.0

Communication Module

3.3

1.5

Planning and Installation Guide for Triconex General Purpose v2 Systems

26

Chapter 2

System Description

Component

Weight in Pounds

Weight in Kilograms

Communication Baseplate

2.8

1.3

Digital Input Baseplate

2.4

1.1

Digital Input Module

3.0

1.3

Digital Output Baseplate

2.1

1.0

Digital Output Module

3.2

1.4

Main Processor Baseplate

2.7

1.2

Main Processor Module

3.4

1.5

Pulse Input Module

3.0

1.4

Pulse Input Baseplate

2.8

1.3

Relay Output Baseplate

2.3

1.0

Solid-State Relay Output Module

2.9

1.3

I/O Extender Module

0.4

0.2

Cable Flame Test Ratings


You can order standard Triconex interface cables and I/O bus cables that meet flame test ratings
as described in this table.
Cable

Rating

Interface cables

FT4 Vertical Flame Test-Cables in Cable Trays


per C.S.A. C22.2 No. 0.3-92 Para 4.11.4a

(connect external termination panels to baseplates)


I/O bus cables
(connect columns of baseplates)

FT6 Horizontal Flame & Smoke Test-per C.S.A.


C22.2 No. 0.3-92 Appendix Bb

a. Cables will be marked with FT4 or CMG rating, but they all actually meet the more stringent FT4
rating.
b. Cables will be marked with FT6 or CMP rating, but they all actually meet the more stringent FT6
rating.

Ground Systems
The Tri-GP has the following four, separate ground systems:

Protective earth

an AC safety ground

Field ground

Fa functional earth

Logic ground

La functional earth

Shield ground

Sa functional earth

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

27

The logic and field portions of each module use separate, isolated signal return paths. Each is
connected to its own functional earth. The metallic portions of the safety ground act as an
electrostatic shield for the internal circuitry. Communication cable shields are terminated to the
safety ground. The metallic portions of the Tri-GP controller are connected to the protective
earth.
For installation procedures, see:

Grounding Baseplates to Protective Earth on page 198

Grounding Logic Power on page 200

Connecting Shields to Earth on page 202

Planning and Installation Guide for Triconex General Purpose v2 Systems

28

Chapter 2

System Description

Standard Tri-GP Products


The following table lists all of the standard Tri-GP products.
Table 1

Standard Tri-GP Products

Model

Product Name

Qty

Description

Consists of

5101S2

Main Processor TriPak

Main Processor Module

3101S2

Main Processor Baseplate Kit

2101S2

Communication Module

3201S2

Communication Module Baseplate Kit

2201S2

Analog Input Module

3351S2

Analog Input Baseplate Kit

2351S2

Analog Input/Digital Input


TriPak

Analog Input/Digital Input Module

3361S2

Analog Input/Digital Input Baseplate Kit

2361S2

Analog Input Tripak,


RTD/TC/4-20 mA

Analog Input Module

3351S2

Analog Input Baseplate, RTD/TC/4-20 mA

2352S2

Analog Input TriPak, HART

Analog Input Module

3351S2

Analog Input Baseplate Kit, HART,

2354S2

Triconex 4850 HART Multiplexer

1600106-001

Analog Input Module

3351S2

Analog Input Baseplate Kit, HART, Hazardous


Location

2354AS2

Triconex 4850 HART Multiplexer

1600106-001

5201S2
5351S2
5361S2
5352S2
5354S2

5354AS2

5481-1S2
5482-1S2
5301S2
5311S2
5312S2
5302S2
5401S2
5401LS2
5411HS2

Communication Module TriPak


Analog Input TriPak

Analog Input TriPak, HART,


Hazardous Location

Analog Output TriPak

Analog Output Module

3481S2

AO Module Baseplate Kit

2481S2

Analog Output Tripak, HighCurrent

High-Current Analog Output Module

3482S2

AO Module Baseplate Kit

2481S2

Digital Input TriPak

Digital Input Module

3301S2

Digital Input Baseplate Kit

2301S2

Digital Input TriPak, High


Resolution

Digital Input Module, High Resolution

3311S2

Digital Input Baseplate Kit

2301S2

Digital Input TriPak, High


Resolution, High Voltage

Digital Input Module, High Resolution

3311S2

Digital Input Baseplate Kit, High Voltage

2302S2

Digital Input TriPak, High


Voltage

Digital Input Module

3301S2

Digital Input Baseplate Kit, High Voltage

2302S2

Digital Output TriPak

Digital Output Module

3401S2

Digital Output Baseplate Kit

2401S2

Digital Output TriPak, Low


Current

Digital Output Module

3401S2

Digital Output Baseplate Kit, Low Current

2401LS2

Digital Output TriPak,


Supervised, High Current

Digital Output Module, Supervised

3411S2

Digital Output Baseplate Kit, High Current

2401HS2

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

Table 1

29

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

5402S2

Digital Output TriPak, High


Voltage

Digital Output Module

3401S2

Digital Output Baseplate Kit, High Voltage

2402S2

5451S2
5382-1S2
5382AS2
5483S2

5483AS2

2101S2

2281

2291

2292

2301S2

Solid-State Relay Output TriPak


Pulse Input TriPak, Enhanced
Pulse Input TriPak, Enhanced,
Hazardous Location
Analog Output TriPak, HART

Analog Output TriPak, HART,


Hazardous Location

Main Processor Baseplate Kit

I/O Bus Extender Module Kit

I/O Bus Termination Kit, I/O


Baseplate

I/O Bus Termination Kit, MP


Baseplate

Digital Input Baseplate Kit

Solid-State Relay Output Module

3451S2

Solid-State Relay Output Baseplate Kit

2451S2

Pulse Input Module, Enhanced

3382S2

Pulse Input Baseplate Kit

2381S2

Pulse Input Module, Enhanced

3382S2

Pulse Input Baseplate Kit, Hazardous Location

2381AS2

Analog Output Module

3481S2

Analog Output Baseplate Kit, HART

2483S2

Triconex 4850 HART Multiplexer

1600106-001

Analog Output Module

3481S2

Analog Output Baseplate Kit, HART,


Hazardous Location

2483AS2

Triconex 4850 HART Multiplexer

1600106-001

MP Baseplate

3000671-110

MP Interconnect Assembly

2920

Triconex General Purpose Systems User


Documentation (hardcopy)

8910-6S2

Accessories Kit

8401

Top End Cap I/O

2910

Top End Cap MP

2912

Bottom End Cap I/O

2911

Bottom End Cap MP

2913

I/O Extender Module

3000678-100

2-ft. I/O Bus Cables

4000212-002

I/O Interconnect Assembly

2921

Top End Cap I/O

2910

Bottom End Cap I/O

2911

I/O Extender Module

3000678-100

I/O Interconnect Assembly

2921

I/O Bus Terminator Kit (Set of 3)

3900064-003

I/O Extender Module

3000678-100

MP Interconnect Assembly

2920

I/O Bus Terminator Kit (Set of 3)

3900064-003

I/O Baseplate

3000673-030

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

Planning and Installation Guide for Triconex General Purpose v2 Systems

30

Chapter 2

Table 1

System Description

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

2302S2

Digital Input Baseplate Kit,


High Voltage

I/O External Termination Baseplate

3000721-310

External Termination Panel (Solid State Relay


Input)

3000762-110

I/O Interconnect Assembly

2921

Slot Cover

2900

Interface Cable, 10 ft

9105-310F

SSR Input Modules for use with SSR Input ETP


100 to 240 VAC (ordered separately)
2302AS2

2342S2

2342AS2

2351S2

2352S2

2352AS2

2354S2

2354AS2

1300447-001

I/O External Termination Baseplate

3000989-315

External Termination Panel Kit

9573-610F

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

Analog Input/Digital Input


Baseplate Kit, External
Termination

I/O External Termination Baseplate

3000721-140

I/O Interconnect Assembly

2921

Slot Cover

2900

Analog Input/Digital Input


Baseplate Kit, Hazardous
Location

I/O External Termination Baseplate

3000989-145

I/O Interconnect Assembly

2921

Slot Cover

2900

AI/DI ETP Kit, Hazardous Location

9793-610F

Digital Input Baseplate Kit,


Hazardous Location

I/O Baseplate

3000675-030

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

Analog Input Baseplate Kit for


TC, RTD, and 4-20mA (requires
2 of part number 9764-510F)

I/O External Termination Baseplate

3000721-110

I/O Interconnect Assembly

2921

Slot Cover

2900

Analog Input Baseplate Kit,


Hazardous Location

I/O External Termination Baseplate

3000989-115

External Termination Panel Kit

9792-310F

I/O Interconnect Assembly

2921

Slot Cover

2900

I/O HART Baseplate

3000851-020

MP Interconnect Assembly

2920

Slot Cover

2900

Terminal Cover

2901

I/O HART Baseplate

3000851-120

MP Interconnect Assembly

2920

Slot Cover

2900

Terminal Cover

2901

Analog Input Baseplate Kit

Analog Input Baseplate Kit,


HART

Analog Input Baseplate Kit,


HART, Hazardous Location

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

Table 1

31

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

2361S2

Analog Input/Digital Input


Baseplate Kit

I/O Baseplate

3000675-040

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

2381S2

2381AS2

2401S2

2401HS2

2401LS2

2402S2

Pulse Input Baseplate Kit

Pulse Input Baseplate Kit,


Hazardous Location

Digital Output Baseplate Kit

Digital Output Baseplate Kit,


High Current

Digital Output Baseplate Kit,


Low Current

Digital Output Baseplate Kit,


High Voltage

I/O Baseplate

3000719-110

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O Hazardous Location Baseplate

3000719-210

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O Baseplate

3000674-040

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O Baseplate

3000975-040

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O Baseplate

3000715-040

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O Baseplate

3000764-310

External Termination Panel (Relay Output ETP)

3000763-110

I/O Interconnect Assembly

2921

Slot Cover

2900

Interface Cable, 10 ft

9106-310F

Relay Output Modules for use with Relay


Output ETP (ordered separately)

2402AS2

Digital Output Baseplate Kit,


Hazardous Location

SSR, 2 A at 75 to 264 VAC

1300462-001

SSR, 2 A at 4 to 60 VDC

1300471-001

SSR, 1.5 A at 40 to 200 VDC

1300472-001

Power (Dry Contact) Relay; 440 VAC max, 125


VDC max

1300463-001

I/O External Termination Baseplate

3000764-310

External Termination Panel Kit

9671-610

I/O Interconnect Assembly

2921

Slot Cover

2900

Planning and Installation Guide for Triconex General Purpose v2 Systems

32

Chapter 2

Table 1

System Description

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

2451S2

Solid-State Relay Output


Baseplate Kit

I/O Baseplate

3000676-320

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O External Termination Baseplate

3000764-510

External Termination Panel Kit

9863-610F

I/O Interconnect Assembly

2921

Slot Cover

2900

2480AS2

2481S2

2483S2

2483AS2

8401

9573-610F

9671-610F

Analog Output Baseplate Kit,


Hazardous Location

I/O Baseplate

3000674-020

I/O Interconnect Assembly

2921

Slot Cover

2900

Terminal Cover

2901

I/O HART Baseplate

3000852-030

MP Interconnect Assembly

2920

Slot Cover

2900

Terminal Cover

2901

I/O HART Baseplate

3000852-130

MP Interconnect Assembly

2920

Slot Cover

2900

Terminal Cover

2901

MTL4546 Intrinsic Safety BarrierIsolator

1600107-001

Set of Spare Fuses

Set of Address Plugs (1 through 10)

3000698-010

Set of Address Plugs (11 through 20)

3000698-020

Set of Address Plugs (21 through 32)

3000698-030

Set of Address Plugs (33 through 43)

3000698-040

Set of Address Plugs (44 through 54)

3000698-050

Set of Address Plugs (55 through 63)

3000698-060

Digital Input Termination Panel


Kit, Hazardous Location
(for use with Model 2302AS2)

External Termination Panel, DI

3000771-880

Interface Cable, 10 ft, DI

4000195-310

Digital Output Termination


Panel Kit, Hazardous Location
(for use with Model 2402AS2)

External Termination Panel, DO

3000769-390

Interface Cable, 10 ft, DO

4000196-310

Analog Output Baseplate Kit

Analog Output Baseplate Kit,


HART

Analog Output Baseplate Kit,


HART, Hazardous Location

Trident/Tri-GP Accessory Kit

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

Table 1

33

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

9764-510F

RTD/TC/AI Termination Panel


Kit (for use with Model 2352S2)

External Termination Panel, RTD/TC/AI

3000712-100

Interface Cable, 10 ft

4000189-510

Signal Conditioning Modules for use with 9764510F (ordered separately)


1600048-220

420 mA
320 F to 3920 F (00 C to 2000C), RTD

1600048-030

320 F

1600048-040

(00C

to

6000C),

RTD

320 F to 14000 F (00C to 7600C), Type J TC

1600048-110

320 F

1600048-120

320 F

9792-310F

to

11120 F

to

23720 F

to

7520 F

(00C

(00C

to

to

13000C),

4000C),

Type K TC

Type T TC

1600048-130

320 F to 16520 F (00C to 9000C), Type E TC

1600048-140

Shorting Plug

1600048-300

Analog Input Termination Panel


Kit, Hazardous Location
(for use with Model 2352AS2)

External Termination Panel, AI

3000771-710

Interface Cable, 10 ft, AI

4000197-510

Analog Input/Digital Input


Termination Panels Kit,
Hazardous Location
(for use with Model 2342AS2)

External Termination Panel, AI

3000771-710

External Termination Panel, DI

3000771-880

Interface Cable, 10 ft, AI

4000197-510

Interface Cable, 10 ft, DI

4000195-310

Analog Output Termination


Panel Kit, Hazardous Location
(for use with Model 2480AS2)

External Termination Panel, AO

3000770-960

Interface Cable, 10 ft, AO

4000198-510

Triconex 4850

Triconex 4850 HART


Multiplexer

Triconex 4850 HART Multiplexer

1600106-001

7254-13S2

TriStation 1131 Developers


Workbench version 4.8.0 for
Tri-GP

CD containing:

3000755-829

9793-610F

9863-610F

7255-13S2

8910-5S2

8747-11

TriStation 1131 Developers


Workbench version 4.8.0 with
CEMPLE for Tri-GP

Developers Workbench (software)


TriStation 1131 Help Documentation (online)
1

TriStation 1131 v4.8.0 Documentation Set

3000760-930

CD containing:

3000755-828

Developers Workbench (software)


TriStation 1131 Help Documentation (online)
1

TriStation 1131 v4.8.0 Documentation Set

3000760-930

Triconex General Purpose


Systems User Documentation
(hardcopy)

Planning and Installation Guide for Triconex


General Purpose v2 Systems

9700122-003

Communication Guide for Triconex General


Purpose v2 Systems

9700123-002

TriStation 1131 version 4.8.0


User Documentation (hardcopy)

TriStation 1131 Developers Guide

9700100-011

TriStation 1131 Libraries Reference

9700098-010

Safety Considerations Guide for Trident v2

9700112-005

Safety Considerations Guide for Tri-GP v2

9700124-003

Safety Considerations Guide for Trident v1

9700096-002

Safety Considerations Guide for Tricon

9700097-009

Planning and Installation Guide for Triconex General Purpose v2 Systems

34

Chapter 2

Table 1

System Description

Standard Tri-GP Products (continued)

Model

Product Name

Qty

Description

Consists of

7523-4

Triconex DDE Server 4.3.0

CD containing DDE Server software and


documentation

3000723-303

DDE Server, v4.3.0 Documentation Set


(hardcopy)

9700108-004

CD containing SOE Recorder and


documentation

3000708-430

SOE Recorder, v4.3.0 Documentation Set


(hardcopy)

9700081-008

CD containing Enhanced Diagnostic Monitor,


v2.5.0 (software)

3000796-009

Enhanced Diagnostic Monitor, v2.5.0


Documentation Set (hardcopy)

9700107-009

CD containing documentation in PDF format

7521-6

7260-7

Contact
Invensys for
current model
number

SOE Recorder version 4.3.0

Enhanced Diagnostic Monitor,


v2.5.0

Triconex Documentation Set

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Components

35

Main Processor Components


These Main Processor components are available with Tri-GP v2.x systems.
Model

Description

3101S2

Main Processor Module, Tri-GP

2101S2

Main Processor Baseplate, Tri-GP

Each of the three Main Processor Modules control a separate channel and operate in parallel
with the other two modules. They communicate with each other by using TriBus, which is a
high-speed, fault-tolerant bus. A dedicated I/O control processor on each Main Processor
manages the data exchanged between the Main Processor and the I/O modules. The I/O Bus
operates at 2 megabits per second.
Program Processor

I/O Processor
Dual 24 V
Power Inputs

Redundant
Alarm
Relays

Alarm 1
Alarm 2

System
Alarm

Debug (RJ-12)

Dual-Power
Regulators

+3.3 V
+5 V
3.6 V
Battery
and Monitor

Program
Alarm

Debug (RJ-12)
I/O Bus

Modbus (DB-9)
Clock/NVRAM
8 KB

MPC860A

Reserved (DB-9)
Ethernet
Network (RJ-45)

Shared
Memory
128 K

36-Bit Bus

Flash
6 MB

Tribus
(to other MPS)

Figure 6

TriBus
FPGA

MPC860A

DRAM
16 MB

Up Stream

Down Stream

Up Stream

Down Stream

Diagnostic Bus
Channels
(to other MPs)

36-Bit Bus

DRAM
16 MB

Main Processor Architecture

Each Main Processor includes 16 megabytes of DRAM for the control program, sequence-ofevents (SOE) and I/O data, diagnostics, and communication buffers. The control program is
stored in flash EPROM and loaded in DRAM for execution. The MP Modules receive power
from redundant 24 VDC power sources. In the event of an external power failure, all critical
retentive data is stored in NVRAM (Non-Volatile Random Access Memory).

Planning and Installation Guide for Triconex General Purpose v2 Systems

36

Chapter 2

System Description

MP Module Specifications
This section includes specifications for the MP Modules, including:

Control Program Processor on page 36

Input/Output Processor on page 37

Logic Power on page 37

Control Program Processor


This table lists the specifications for the Control Program Processor on the MP Modules.
Table 2

Control Program Processor Specifications

Feature

Specification

SX Processor

Motorola MPC860, 32-bit, 50 MHz

Flash PROM

6 MB used for SX, IOX, and control application storage


CRC-protected

DRAM

16 MB used for SX control application execution and program and


SOE data
Byte parity

NVRAM

8 KB, used for retentive variables


CRC-protected

Clock calendar
Accuracy during power on

1 sec/day typical
2.2 sec/day maximum

Accuracy during power off,


with battery backed up

2.2 sec/day typical


9.2 sec/day maximum

Battery

AA lithium, 15-year predicted life

TriBus

25 megabits per second


CRC-protected
32-bit + parity DMA

TriStation 1131 port

1 10BaseT Ethernet connector


RJ-45 shielded connector on baseplate

Modbus port

1 RS-232/485 DTE
DB-9-pin shielded connector on baseplate

Debug port

Used to access diagnostic information


RJ-12 connector located on baseplate, shared with IOX debug port

Communication bus

RS-485 2 megabits per second HDLC

Alarm contacts

Redundant, normally closed

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Components

WARNING

37

There is a danger of explosion if the battery on MP Modules is replaced


incorrectly. To ensure a safe battery replacement, you must return MP
Modules to Invensys for servicing.

Input/Output Processor
This table lists the specifications for the Input/Output Processor on the MP Modules.
Table 3

Input/Output Processor Specifications

Feature

Specification

IOX Processor

Motorola MPC860, 32-bit, 50 MHz

DRAM

16 MB, used for IOX execution; byte parity

Shared Memory

128 KB, used to communicate with SX; byte parity

Diagnostic Bus

2 megabits per second HDLC, used to communicate I/O module diagnostic


information between MP channels

Debug Port

Used to access diagnostic information


RJ-12 connector located on baseplate, shared with SX debug port

I/O Bus

RS-485 2 megabits per second HDLC

Logic Power
This table lists the specifications for the logic power on the MP Modules.
Table 4

Logic Power Specifications for MP Modules

Feature

Specification

Nominal input voltage

24 VDC

Operational voltage range

24 VDC 15% to +20% + 5% AC ripple (+19.2 to +30 VDC)

Logic power

8 W maximum

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input


voltage

0.6 VDC

Input power interruption time from


nominal

1 ms minimum

Repetition rate

1 sec maximum

Reverse current isolation input to input

500 A maximum

In-rush current per input

2.4 A maximum, 1.2 A for 50 ms, typical

Short circuit current limit per input

2.4 A maximum

Functional-earth-to-logic-ground
isolation

0 V, no isolation

Planning and Installation Guide for Triconex General Purpose v2 Systems

38

Chapter 2

System Description

Table 4

Logic Power Specifications for MP Modules (continued)

Feature

Specification

Protective-to-functional-earth isolation

500 VDC

MP Baseplate
This figure depicts a front view of the model 2101S2 Main Processor Baseplate, which includes
connections for alarm contacts and logic power and communication ports. For details, see
Baseplate Connections and Ports on page 39.

Figure 7

Model 2101S2 MP Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Components

39

Baseplate Connections and Ports


This figure depicts the connections for alarm contacts, logic power, and communication ports
on the MP Baseplate. For specifications, see:

Alarm Connections on page 40

Communication Ports on page 41

Logic Power Connections on page 42

Logic Power 1 Fuse


Logic Power 2 Fuse
Logic Power 1

DSP1

Logic Power 1 Blown Fuse Indicator

Logic Return 1

DSP2

Logic Power 2 Blown Fuse Indicator

Logic Power 2
Logic Return 2

+
DSP3
FUSE

DSP4

Safety
FUSE

Alarm 1

Alarm 1 Blown Fuse Indicator


Alarm 1 Fuse
Alarm 2 Blown Fuse Indicator
Alarm 2 Fuse

Alarm 2
Left Serial Port

Middle Serial Port

Right Serial Port

Left TriStation Port

Left Debug Port

Middle TriStation Port

Middle Debug Port


Right Debug Port

Right TriStation Port

Figure 8

Node Address

MP Baseplate Connectors and Ports

Planning and Installation Guide for Triconex General Purpose v2 Systems

40

Chapter 2

System Description

Alarm Connections
Alarms are asserted when the controller detects either a system alarm or a program alarm. Each
MP contains a set of redundant alarm solid-state relays. The relays are normally closed and are
connected in series between MP Modules.

A system alarm indicates a fault in the controller, its power supplies, or field input.

A program alarm indicates a problem detected by the control program.

MP Baseplate

MP A

MP B

MP C

Alarm 1/NC
Alarm 1/C

Alarm 2/NC
Alarm 2/C

This table lists the alarm contacts on the MP Baseplate.


Table 5

Alarm Contact Specifications for MP Baseplates

Feature

Specification

Alarm contacts

2, redundant pair, isolated

Rated voltage

24 VAC/VDC

Operational voltage range

030 VDC

Maximum switch voltage

33 V

Maximum switching power

15 W resistive

Maximum off-state leakage

<50 A

Maximum nominal current

0.5 A per contact, continuous


0.7 A per contact for 100 ms

Voltage drop @ baseplate

<0.25 VDC @ 0.5 A

Fuses, mounted on baseplate

1 per contact, 1 A fast-acting

Blown-fuse indicator

On baseplate

Contact-to-protective-earth isolation

500 VDC, minimum

Contact-to-functional-earth (logic) isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Components

41

Communication Ports
Ports on the MP Baseplate enable the Tri-GP controller to communicate with a PC running
TriStation 1131 software and with other external devices by means of Modbus and Ethernet
protocol.
Ports include:

One Ethernet (IEEE 802.3) TriStation 1131 port for downloading the control program to
the Tri-GP controller and uploading diagnostic information. This port can also be used
to download Tri-GP firmware to the Flash ROM.

One Modbus RS-232 or RS-485 serial port which acts as a Modbus slave while an
external device is the master.

Debug ports used for Technical Support.

Feature

Specification

Connector

DB-9-pin DTE standard, shielded, located on baseplate

RS-232 maximum cable length

50 ft (15 m)

RS-485 maximum cable length

4,000 ft (1.2 km)

Supported transmission rates (bps)

1200, 2400, 4800, 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K

Protocols

Slave, RTU mode, optional parity, 1 stop bit

Galvanic isolation

500 VDC

Feature

Specification

10BaseT connector

RJ-45 standard, shielded, located on baseplate

10BaseT maximum cable length

330 ft (100 m) using category 5 twisted-pair cable

Protocol

TriStation 1131

Network address

Derived from baseplate address plug; range is 1 to 63

Galvanic isolation

500 VDC

Feature

Specification

Connector

RJ-12, Triconex proprietary pin-out

Maximum cable length

25 ft (8 m)

Protocol

RS-232, 9600 bps, ASCII, asynchronous

Galvanic isolation

500 VDC

Planning and Installation Guide for Triconex General Purpose v2 Systems

42

Chapter 2

System Description

Logic Power Connections


The MP Baseplate provides redundant, fused logic power connectors for the MP and I/O
modules, which are directly connected to the MP Baseplate.
Feature

Specification

Logic power

125 W, maximum

Fuse

8 A, slow-acting

Blown fuse indicator

20 mA

Planning and Installation Guide for Triconex General Purpose v2 Systems

Communication Components

43

Communication Components
These communication components are available with Tri-GP v2.x systems.
Model

Description

Type

3201S2

Communication Module

Single or redundant Configuration, non-TMR

2201S2

Communication Baseplate

This section describes the features and specifications for the Communication Module and
Communication Baseplate compatible with Tri-GP v2.x and later systems.
The Communication Module (CM) is an optional, three-to-one interface to the Main Processors.
Using a variety of communication methods, protocols, and physical media types, the CM
enables communication with external computers, distributed control systems (DCS), Ethernet
(open) networks, other Tri-GP, Trident, and Tricon v9v10 systems, and network printers.
A single Tri-GP controller supports up to two CMs on one CM Baseplate. Each CM operates
independently and supports three RS-232/485 serial ports and two Ethernet ports. Two CMs
can provide redundant communication connections or additional independent communication
ports.

Logic Power Specifications


This table lists specifications for logic power, which is supplied by the MP Baseplate.
Table 6

Logic Power Specifications for CM

Feature

Specification

Nominal input voltage

24 VDC

Specified operational voltage range

24 VDC 15% or +20% + 5% AC ripple (19.2 to 30 VDC)

Logic power (without MAUs)

8 W maximum

10 Mb AUI-type MAU

6 W maximum additional per MAU

100 Mb MII-type MAU

3.75 W maximum additional per MAU

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input power interruption time from


nominal value

1 ms maximum

Repetition rate

1 sec minimum

Reverse current isolation input to input

500 A maximum

Inrush current per input

2.4 A maximum, typically 1.2 A for 50 ms

Short circuit current limit per input

2.4 A maximum

Functional-to-logic ground isolation

0 V, no isolation

Protective-to-functional-earth isolation

500 VDC

Planning and Installation Guide for Triconex General Purpose v2 Systems

44

Chapter 2

System Description

Table 6

Logic Power Specifications for CM (continued)

Feature

Specification

+12 V AUI output power

12 V 10%, 6 W maximum, current limited

+5 V MII output power

5 V 5%, 3.75 W maximum, current limited

CM Baseplate
This figure depicts the Communication Module Baseplate, which includes three serial ports,
two Ethernet ports, and two multi-station access unit (MAU) ports. For details, see
Communication Ports on page 45.

Figure 9

Model 2201S2 CM Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

Communication Components

45

Communication Ports
This figure depicts the ports on the CM Baseplate. For specifications, see:

CM Serial Port Specifications on page 46

CM Ethernet Port Specifications on page 46

Left Module
Serial 3
Serial 2
Serial 1

Right Module
Serial 3
Serial 2
Serial 1
Net 1 Left Module
AUI MAU
Net 1 Right Module
AUI MAU
Net 1 Left Module
10BaseT
Net 1 Right Module
10BaseT

Net 2 Left Module


10BaseT/100BaseTX
Net 2 Right Module
10BaseT/100BaseTX

Net 2 Right Module


MII MAU
Net 2 Left Module
MII MAU

Debug

Figure 10

Communication Module Port Connectors

Planning and Installation Guide for Triconex General Purpose v2 Systems

46

Chapter 2

System Description

Table 7

CM Serial Port Specifications

Feature

Specification

Serial (Modbus) ports

3 optically isolated RS-232/485 ports, configurable from


TriStation 1131 software

Connector

DB-9-pin DTE standard, shielded, located on baseplate

RS-232 maximum cable length

50 ft (15 m)

RS-485 maximum cable length

4,000 ft (1.2 km)

Supported transmission rates (bps)

1200, 2400, 4800, 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K

Protocols

TriStation 1131, Modbus Slave (ASCII or RTU), Modbus


Master (RTU)

Serial port Galvanic isolation

500 VDC

Table 8

CM Ethernet Port Specifications

Feature

Specification

10BaseT network port

Ethernet 10 megabits per second, protocol-configurable from


TriStation 1131 software

10BaseT connector

RJ-45 standard, shielded, located on baseplate

10BaseT maximum cable length

100 m, using Category 5 twisted-pair cable

10 Mb AUI-type MAU port

Supports AUI MAU located on baseplate


Disables 10BaseT RJ-45 connector

100BaseTX Ethernet port

100 or 10 megabits per second, speed auto-selected, configurable


from TriStation 1131 software

100BaseTX connector

RJ-45 standard, shielded, located on baseplate

100BaseTX maximum cable length

30 m, using Category 5 twisted-pair cable

100 Mb MII-type MAU port

Supports MII MAU located on baseplate


Disables 100BaseTX RJ-45 connector

Protocols

TriStation 1131
TSAA (UDP/IP)
TSAA with IP Multicast (UDP/IP)
Peer-to-Peer (UDP/IP)
Peer-to-Peer (DLC)
Modbus Master or Slave (TCP)
Triconex Time Synchronization via DLC
Triconex Time Synchronization via UDP/IP
SNTP Triconex Time Synchronization
Network Printing using JetDirect

Network address

Derived from MP Baseplate address plug

Galvanic isolation

500 VDC

Planning and Installation Guide for Triconex General Purpose v2 Systems

I/O Modules Common Specifications

47

I/O Modules Common Specifications


This section includes specifications that are common to all I/O modules. For specifications, see:

Wiring Terminals on page 47

Logic Power on page 47

Field Power on page 48

Wiring Terminals
This table lists the wiring specifications for I/O modules.
Table 9

Wiring Specifications for I/O Modules

Feature

Specification

Compression terminals

Compatible with 24 to 12 (0.2 mm2 to 3.3 mm2) AWG wiring

Logic Power
This table lists the logic power specifications for I/O modules.
Table 10

Logic Power Specifications for I/O Modules

Feature

Specification

Nominal input voltage

24 VDC

Voltage range

24 VDC 15% or +20% + 5% AC ripple (19.2 to 30 VDC)

Logic power

<3 W

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input power interruption time from


nominal

1 ms maximum

Power interruption interval

1 sec minimum

Reverse current isolation input to input

500 A maximum

Inrush current per input

2.4 A maximum

Short circuit current limit per input

2.4 A maximum

Functional-earth-to-logic-ground
isolation

0 V, no isolation

Protective-to-functional-earth isolation

500 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

48

Chapter 2

System Description

Field Power
This table lists the field power specifications for I/O modules.
Table 11

Field Power Specifications for I/O Modules

Feature

Specification

Nominal field voltage

24 VDC

Operational voltage range

24 VDC 15% or +20% + 5% AC ripple


(19.2 to 30 VDC)
(For PI Modules, voltage ranges are configurable in
TriStation 1131 software.)

Power

See module specifications

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input power interruption time from


nominal

Not applicable

Power interruption interval

Not applicable

Reverse current isolation

500 A maximum

Functional- to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic)
isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 49

Analog Input Components


These analog input components are available for Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Current

Type

3351S2

Analog Input Module

420 mA

Commoned

2351S2

Analog Input Baseplate

Direct Termination

n/a

Analog Input External Termination


Baseplate

External Termination

9764-510F

RTD/TC/AI External Termination


Panel

External Termination

9792-310F

Analog Input Hazardous Location


External Termination Panel

External Termination

2354S2

Analog Input HART Baseplate

Direct Termination

2354AS2

Analog Input HART Hazardous


Location Baseplate

Direct Termination

Note

When ordering the 9764-510F ETP or the 9792-310F ETP, you can order longer interface
cables, in increments of 10 feet, by changing the last two digits of the ETP model number
from 10 to the desired length of the cable. The maximum length for interface cables is
normally 100 feet. Contact the Invensys Global Customer Support (GCS) center if you
require cables longer than 100 feet.

The Analog Input (AI) Module has three isolated sets of electronics, called channels, which
independently process field data input to the module. Sensing of each input point is performed
in a manner that prevents a single failure on one channel from affecting another channel. Each
channel receives variable voltage signals from each point, converts them to digital values, and
transmits the values to the three MPs on demand. The MPs vote the data before passing it to the
control program. In TMR mode, the data passed is mid-value. In DUAL mode, the data passed
is the average.
AI Modules sustain complete, ongoing diagnostics for each channel. If the diagnostics detect a
failure on any channel, the Fault indicator turns on and activates the system alarm. The Fault
indicator identifies a channel fault, not a complete module failure. AI Modules are guaranteed
to operate properly in the presence of a single fault and may continue to operate properly with
multiple faults.
AI Modules include the hot-spare feature which allows online replacement of a faulty module.
The AI Module is mechanically keyed to prevent improper installation in a configured
baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

50

Chapter 2

System Description

AI Module 3351S2
This figure is a simplified schematic of the Model 3351S2 AI Module.
Analog Input Module Typical Point (1 of 32)

ADC

Triplicated
I/O Bus
ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

Isolation
Filtering

Individual Point
Field Terminations

DAC

ADC

DAC

ADC

DAC

Figure 11

3351S2 AI Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 51

This table lists the specifications for the Model 3351S2 AI Module.
Table 12

3351S2 AI Module Specifications

Feature

Specification

Points

32, commoned

Nominal input current

420 mA DC

Operational current range

221.2 mA DC

Absolute maximum field voltage

33 VDC

Recommended HART baseplate field voltage

28 VDC

Absolute maximum reverse field voltage

0.6 VDC

Absolute maximum input current

50 mA DC

Input bandwidth (3dB)

16 Hz

Source impedance

180

Input impedance (with baseplate)

250

I to V resistor

100 , 0.01%

Resolution

12 bits

Absolute error

0.15% of full scale (20 mA)

Diagnostic

Force-to-value diagnostic (FVD)

Scan time

<1 ms for all 32 points

Functional-to-protective-earth isolation (ATEX)

500 VDC, minimum (0 VDC)

Functional-to-functional-earth (logic) isolation

800 VDC, minimum

Input impedance (with HART baseplate)

350 , nominal (300400 )

Source impedance (with HART baseplate)

250 , nominal (200300 )

Planning and Installation Guide for Triconex General Purpose v2 Systems

52

Chapter 2

System Description

AI Baseplate
The Model 2351S2 AI Baseplate is
typically used with 420 mA control
programs. The short circuit current
specifications for field short-to-ground
faults are:

130 mA, typical

200 mA, maximum

This figure is a simplified schematic of the Model 3351S2 AI Module and Model 2351S2 AI
Baseplate.
AI Baseplate

32-Point AI Module
Mux
1

Field Power (PS1) +


Field Power (PS2) +

32
To
Spare

180 7
+
In

150 7

Mux
1

100 7
.01%

32

Mux

Field Power (PS1)


Field Power (PS2)

To
Other
Points

1
32

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 53

Figure 12

3351S2 AI Module and 2351S2 AI Baseplate Schematic

Typical Field Connections


This figure depicts typical field connections for the Model 2351S2 AI Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

Typical Point
(1 of 32 Points Shown)

~
~~
~

~
~~
~

4-20 mA
Transmitter

10

10

11

11

12

12

13

13

14

14

15

15

16

16

17
17
18
19
20
21
22
23
24

25
26
27
28

29
30
31

18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

32

~ ~~ ~ ~
Figure 13

2351S2 AI Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

54

Chapter 2

System Description

AI External Termination Baseplate


The AI External Termination Baseplate is
typically used with the Model 9764-510F
RTD/TC/AI External Termination Panel
or the Model 9792-310F AI Hazardous
Location External Termination Panel.
This baseplate contains ELCO
connectors, which allows connection of
External Termination Panels.

This figure is a simplified schematic of the Model 3351S2 AI Module and the AI External
Termination Baseplate.
AI Baseplate

32-Point AI Module
Mux
1

Field Power (PS1) +


Field Power (PS2) +

32
To
Spare

Mux
1

From External
Termination Panels

Field Power (PS1)


Field Power (PS2)

Figure 14

32

Mux
V + To
External
Termination
Panels

1
32

3351S2 AI Module and AI External Termination Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 55

Typical Field Connections


This figure depicts typical field connections for the AI External Termination Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

S
F

~ ~~ ~ ~
Figure 15

AI External Termination Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

56

Chapter 2

System Description

RTD/TC/AI External Termination Panel


The Model 9764-510F RTD/TC/AI External Termination Panel (ETP) includes industrystandard signal-conditioning modules which can be cabled to the Analog Input External
Termination Baseplate. The input-signal conditioners are manufactured by Analog Devices.
The RTD/TC/AI ETP supports 16 points and each AI Module can support up to two ETPs.
The Model 9764-510F RTD/TC/AI ETP has a barrier strip with four compression screw
terminals for connecting an AI Module to 16 analog inputs. The panel accepts power (+24 VDC)
from the AI Baseplate or from a direct connection to the panel. Each 24 volt power source must
be able to provide 0.5 amps minimally. Model 9764-510F RTD/TC/AI ETP includes a 10-foot
cable and mounting plate.
You must use two 16-point term panels for each 32-point AI module. Each term panel comes
with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.
AI
(420 mA)

16
16

13

12

14
15

14
15

13

12

R16

11

11
10

10
9

U16

R15

3
4

3
4

14
15

13

16
16

14
15

13

12

11

12
11

10

10
9

3
4

2
1

14
15

16
16

13

12
11

14
15

13

12

10

3
4

11
10

3
4

16
16

13

12

11

14
15

14
15

13

12

11

10

3
4

10
9

3
4

ISOLATED
RTD INPUT

ANALOG
DEVICES

ISOLATED
RTD INPUT

U15

R14

7B34

ANALOG
DEVICES

U14

R13

7B34

ISOLATED
RTD INPUT

U13

ANALOG
DEVICES

ISOLATED
RTD INPUT

U12
R12

7B34

ANALOG
DEVICES

ISOLATED
RTD INPUT

J5

7B34

ANALOG
DEVICES

R11

7B34

ISOLATED
RTD INPUT

U11

R10

J4

J3

ANALOG
DEVICES

ISOLATED
RTD INPUT

U10

R9

7B34

ANALOG
DEVICES

ISOLATED
RTD INPUT

U9

R8

SN

7B34

ANALOG
DEVICES

U8

R7

7B34

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

U7

R6

7B32

U6

R5

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

SHORTING
PLUG

U5

R4

7B32

7B32

ANALOG
DEVICES

ISOLATED
TC INPUT

U4

R3

7BDS

ANALOG
DEVICES

ISOLATED
TC INPUT

U3

R2

7B47

ANALOG
DEVICES

ISOLATED
TC INPUT

U2

7B47

ANALOG
DEVICES

ISOLATED
TC INPUT

U1
R1

J2

7B47

ANALOG
DEVICES

7B47

REV E

7400225-

3
4

TRICONEX 7B 16 MODULE BASEPLATE

J1

RTD

TC

J6

**

* A signal conditioning module or shorting plug 1600048-300 must be installed on all points.
** Unused points must be shorted at the +, , and x terminals. The diagram shows a typical unused point.

Figure 16

9764-510F RTD/TC/AI External Termination Panel

9764-510F RTD/TC/AI ETP Dimensions


Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

5.22 in (13.26 cm)

19.00 in (48.26 cm)

3.24 in (8.23 cm)

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 57

This figure is a simplified schematic of the Model 3351S2 AI Module and the Model 9764-510F
RTD/TC/AI ETP.
RTD/TC/AI Panel

Baseplate

32-Point AI Module
Mux

V+

To
Spare

V+A

32

V+B
V+
Mux
1
Com

32

Mux
7BXX
Typical Signal
Conditioner

32
y

rfu

CJ

Figure 17

3351S2 AI Module and 9764-510F RTD/TC/AI ETP Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

58

Chapter 2

System Description

Typical Field Connections


These figures show typical field connections using the Model 9764-510F RTD/TC/AI ETP,
which can be used with the Model 3351S2 AI Module and the AI External Termination Baseplate
(these components are supplied together as the Model 5352S2 TriPak).

16
16

13

12

14
15

14
15

13

11

12

11

10

R12

10

U12

R11

3
4

3
4

ISOLATED
RTD INPUT

ANALOG
DEVICES

ISOLATED
RTD INPUT

U11

R10

7B34

ANALOG
DEVICES

ISOLATED
RTD INPUT

ISOLATED
RTD INPUT

U10

R9

7B34

ANALOG
DEVICES

7B34

ANALOG
DEVICES

7B34

U9

J5
Shield

Point #12 Typical, see 9764-510F RTD/TC/AI ETP PinOuts on page 60 for other points

9764-510F RTD/TC/AI ETP Typical RTD Field Connection

16

14
15

14
15

13

13

11

12

R4

12

11

10
9

J3

10

9
8

8
7

U4

R3

3
4

3
4
2

ISOLATED
TC INPUT

ANALOG
DEVICES

ISOLATED
TC INPUT

ISOLATED
TC INPUT

U3

R2

7B47

ANALOG
DEVICES

ISOLATED
TC INPUT

U2

R1

7B47

ANALOG
DEVICES

7B47

ANALOG
DEVICES

7B47

U1

16

Figure 18

Shield

* Install jumper
Point #4 Typical, see 9764-510F RTD/TC/AI ETP
Pin-Outs on page 60 for other points

Figure 19

9764-510F RTD/TC/AI ETP Typical TC Field Connection

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 59

16
16

13

14
15

14
15

11

13

12

R8

12

11
10

10
9

U8

R7

3
4

3
4

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

U7

R6

7B32

U6

R5

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

U5

J4

+
Field
Transmitter

Point #6 Typical, see 9764-510F RTD/TC/AI ETP


Pin-Outs on page 60 for other points

Figure 20

9764-510F RTD/TC/AI ETP Typical AI Field Connection

J2

+24V Power Supplies

Figure 21

9764-510F RTD/TC/AI ETP Typical Power Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

60

Chapter 2

System Description

Pin-Out Information
This table lists pin-out information for the Model 9764-510F RTD/TC/AI ETP.
Table 13
Point

Point 1

Point 2

Point 3

9764-510F RTD/TC/AI ETP Pin-Outs


Connector

Pin #

TC

RTD

AI

J3A (upper)

NCa

NC

NC

J3B (lower)

Jump

NC

NC

J3A (upper)

NC

Xb

NC

J3B (lower)

Jump

NC

NC

J3A (upper)

and SHc

J3B (lower)

NC

NC

NC

J3A (upper)

+ and SH

J3B (lower)

NC

NC

NC

J3A (upper)

NC

NC

NC

J3B (lower)

Jump

NC

NC

J3A (upper)

NC

NC

J3B (lower)

Jump

NC

NC

J3A (upper)

and SH

J3B (lower)

NC

NC

NC

J3A (upper)

+ and SH

J3B (lower)

NC

NC

NC

J3A (upper)

NC

NC

NC

J3B (lower)

Jump

NC

NC

J3A (upper)

10

NC

NC

J3B (lower)

10

Jump

NC

NC

J3A (upper)

11

and SH

J3B (lower)

11

NC

NC

NC

J3A (upper)

12

+ and SH

J3B (lower)

12

NC

NC

NC

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 61

Table 13
Point

Point 4

Point 5

Point 6

Point 7

9764-510F RTD/TC/AI ETP Pin-Outs (continued)


Connector

Pin #

TC

RTD

AI

J3A (upper)

13

NC

NC

NC

J3B (lower)

13

Jump

NC

NC

J3A (upper)

14

NC

NC

J3B (lower)

14

Jump

NC

NC

J3A (upper)

15

and SH

J3B (lower)

15

NC

NC

NC

J3A (upper)

16

+ and SH

J3B (lower)

16

NC

NC

NC

J4A (upper)

NC

NC

NC

J4B (lower)

Jump

NC

NC

J4A (upper)

NC

NC

J4B (lower)

Jump

NC

NC

J4A (upper)

and SH

J4B (lower)

NC

NC

NC

J4A (upper)

+ and SH

J4B (lower)

NC

NC

NC

J4A (upper)

NC

NC

NC

J4B (lower)

Jump

NC

NC

J4A (upper)

NC

NC

J4B (lower)

Jump

NC

NC

J4A (upper)

and SH

J4B (lower)

NC

NC

NC

J4A (upper)

+ and SH

J4B (lower)

NC

NC

NC

J4A (upper)

NC

NC

NC

J4B (lower)

Jump

NC

NC

J4A (upper)

10

NC

NC

J4B (lower)

10

Jump

NC

NC

J4A (upper)

11

and SH

J4B (lower)

11

NC

NC

NC

J4A (upper)

12

+ and SH

J4B (lower)

12

NC

NC

NC

Planning and Installation Guide for Triconex General Purpose v2 Systems

62

Chapter 2

System Description

Table 13
Point

Point 8

Point 9

Point 10

Point 11

9764-510F RTD/TC/AI ETP Pin-Outs (continued)


Connector

Pin #

TC

RTD

AI

J4A (upper)

13

NC

NC

NC

J4B (lower)

13

Jump

NC

NC

J4A (upper)

14

NC

NC

J4B (lower)

14

Jump

NC

NC

J4A (upper)

15

and SH

J4B (lower)

15

NC

NC

NC

J4A (upper)

16

+ and SH

J4B (lower)

16

NC

NC

NC

J5A (upper)

NC

NC

NC

J5B (lower)

Jump

NC

NC

J5A (upper)

NC

NC

J5B (lower)

Jump

NC

NC

J5A (upper)

and SH

J5B (lower)

NC

NC

NC

J5A (upper)

+ and SH

J5B (lower)

NC

NC

NC

J5A (upper)

NC

NC

NC

J5B (lower)

Jump

NC

NC

J5A (upper)

NC

NC

J5B (lower)

Jump

NC

NC

J5A (upper)

and SH

J5B (lower)

NC

NC

NC

J5A (upper)

+ and SH

J5B (lower)

NC

NC

NC

J5A (upper)

NC

NC

NC

J5B (lower)

Jump

NC

NC

J5A (upper)

10

NC

NC

J5B (lower)

10

Jump

NC

NC

J5A (upper)

11

and SH

J5B (lower)

11

NC

NC

NC

J5A (upper)

12

+ and SH

J5B (lower)

12

NC

NC

NC

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 63

Table 13
Point

Point 12

Point 13

Point 14

Point 15

9764-510F RTD/TC/AI ETP Pin-Outs (continued)


Connector

Pin #

TC

RTD

AI

J5A (upper)

13

NC

NC

NC

J5B (lower)

13

Jump

NC

NC

J5A (upper)

14

NC

NC

J5B (lower)

14

Jump

NC

NC

J5A (upper)

15

and SH

J5B (lower)

15

NC

NC

NC

J5A (upper)

16

+ and SH

J5B (lower)

16

NC

NC

NC

J6A (upper)

NC

NC

NC

J6B (lower)

Jump

NC

NC

J6A (upper)

NC

NC

J6B (lower)

Jump

NC

NC

J6A (upper)

and SH

J6B (lower)

NC

NC

NC

J6A (upper)

+ and SH

J6B (lower)

NC

NC

NC

J6A (upper)

NC

NC

NC

J6B (lower)

Jump

NC

NC

J6A (upper)

NC

NC

J6B (lower)

Jump

NC

NC

J6A (upper)

and SH

J6B (lower)

NC

NC

NC

J6A (upper)

+ and SH

J6B (lower)

NC

NC

NC

J6A (upper)

NC

NC

NC

J6B (lower)

Jump

NC

NC

J6A (upper)

10

NC

NC

J6B (lower)

10

Jump

NC

NC

J6A (upper)

11

and SH

J6B (lower)

11

NC

NC

NC

J6A (upper)

12

+ and SH

J6B (lower)

12

NC

NC

NC

Planning and Installation Guide for Triconex General Purpose v2 Systems

64

Chapter 2

System Description

Table 13
Point

Point 16

9764-510F RTD/TC/AI ETP Pin-Outs (continued)


Connector

Pin #

TC

RTD

AI

J6A (upper)

13

NC

NC

NC

J6B (lower)

13

Jump

NC

NC

J6A (upper)

14

NC

NC

J6B (lower)

14

Jump

NC

NC

J6A (upper)

15

and SH

J6B (lower)

15

NC

NC

NC

J6A (upper)

16

+ and SH

J6B (lower)

16

NC

NC

NC

a. NC = No connect
b. X = Third wire (sense signal)
c. SH = Shield

Temperature and Output Ranges


This table gives the temperature and output ranges for available signal conditioning modules.
Signal conditioners must be ordered separately and are available from Invensys or directly from
Analog Devices. For more information, contact your regional customer center.
For detailed specifications, see the Analog Devices catalog, Signal Conditioning and Data
Acquisition Solutions.
Table 14

Temperature and Output Ranges for Signal Conditioning Modules

Description

Part Number

Input Range

Output Range

Non-Isolated, Process Current Input


Module

1600048-220
(7B32NI)

4 mA to 20 mA

0.4 V to 2 V

Isolated, Linearized,
RTD Input,100 Platinum, 2- or 3Wire,
= 0.00385

1600048-030
(7B34)

32 F to 392 F
(0 C to 200 C)

0.4 V to 2 V

1600048-040
(7B34)

32 F to 1112 F
(0 C to 600 C)

0.4 V to 2 V

Isolated, Linearized,
Type J, Thermocouple Input Module

1600048-110
(7B47)

(32 F to 1400 F
(0 C to 760 C)

0.4 V to 2 V

Isolated, Linearized,
Type K, Thermocouple Input Module

1600048-120
(7B47)

32 F to 2372 F
(0 C to 1300 C)

0.4 V to 2 V

Isolated, Linearized,
Type T, Thermocouple Input Module

1600048-130
(7B47)

32 F to 752 F
(0 C to 400 C)

0.4 V to 2 V

Isolated, Linearized,
Type E, Thermocouple Input Module

1600048-140
(7B47)

(32 F to 1652 F
(0 C to 900 C)

0.4 V to 2 V

Shorting Plug for unused points

1600048-300
(7BDS)

Not applicable

0.0 V

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 65

AI Hazardous Location External Termination Panel


The Model 9792-310F ETP is suitable for use in Zone 2, and Class 1, Division 2 field circuits. The
ETP contains extra circuitry designed to limit power available to the field terminals. The circuits
have been examined and certified by TV Rhineland as being nonincendive. This guarantees
that if the field wires are accidentally opened, shorted, or grounded, and the Tri-GP is operating
normally, the wiring and attached devices will not release sufficient energy to cause ignition in
the specified flammable atmosphere.
Each positive terminal is current-limited with a 200-to-300-ohm positive temperature coefficient
(PTC) resistor. Each input has a precision 100-ohm resistor for current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing. However,
recommended field power connections are on the AI External Termination Baseplate and
routed to the ETP through the interface cable with ELCO connectors. Field energy will not be
limited if it is connected to the ETP; it will be limited only if it is connected to the baseplate.
You must use two 16-point term panels for each 32-point AI module. Each term panel comes
with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.
Dimensions for Term Panel 9792-310F
Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.42 in (11.23 cm)

5.02 in (12.75 cm)

4.25 in (10.795 cm)

Specifications
This table describes general specifications for 9792-310F.
Table 15

General Specifications for Term Panel 9792-310F

Feature

Description

Panel type

Hazardous location, 4-20 mA current input, 2.5 V

Points

16

Planning and Installation Guide for Triconex General Purpose v2 Systems

66

Chapter 2

System Description

This table describes cable and load parameters for 9792-310F.


Table 16

Cable and Load Parameters for Term Panel 9792-310F

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

19 to 28 V

Maximum voltage

Um

Um

32 V

Maximum input voltage

Ui

Vmax

9V

Maximum input current

Ii

Imax

0.090 A

Maximum input power

Pi

Pi

0.324 W

C internal, maximum

Ci

Ci

0.088 F

L internal, maximum

Li

Li

43 H

Input Connection (F) Specifications

Output Connection (F+) Specifications

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.160 A

Maximum output power

Po

Po

1.347 W

C external, maximum

Co

Ca

1.18 F

L external, maximum

Lo

La

4.95 mH

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 67

Simplified Schematic
This figure is a simplified schematic of the Model 9792-310F ETP and the Model 3351S2 AI
Module with an AI External Termination Baseplate.
ELCO
CABLE

TERMINATION PANEL

BASEPLATE

32-POINT ANALOG INPUT MODULES


to
spare
Isolation/filtering

Mux

200300 Ohms
F

1
30 V
Zener

Amp

ADC

Amp

ADC

Amp

ADC

To other
points

32

PS1

Hi-Ref
Low-Ref

PS2

Mux

3.3 V
Zener

32

100 ohm
0.01%

Hi-Ref
PS1

To other
points

To AI
modules

Low-Ref

PS2

PS1

Mux

PS2

1
0 ohm

PS1
PS2

32
0 ohm

Hi-Ref
Low-Ref

Figure 22

Simplified Schematic of a 9792-310F Panel and a 3351S2 AI Module with an AI External


Termination Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

68

Chapter 2

System Description

Typical Field Connections


This figure illustrates how to connect a 9792-310F to the field (1 of 16 module points shown).
TRICONEX

R25

18
R

R5

R29

R4

R28

R3

R27

R2

R26

TB1

R6
R7

R31

R8

16

R32

15

24

14

23

TB4

R30

22
R

13
R

DO NOT SEPARATE
WHEN ENERGIZED

19
R
20
R
3
21
R

12
R

R4
R5
R6
R7

J1

R8

SN

R
10
11
R

R3

R2

R1

SN

TB1

7400275

0 CTA+60 C

17

REV C

7400275

EXT TERM
ATEX/EMC

R1

EXT TERM TRICON


ATEX/EMC INPUT

12 AWG,
as short as possible

TB2 TB3 TB5 TB6

J2

J2

L+

L+

J3

J3

L-

P1

P2

L-

Second term panel


if using a 32-point
module

Typical point
(1 of 16 or 32 points shown)

+
-

Field Xmtr
(4-20 mA)

Note: Field power is routed from


the baseplate through the Elco cable
to the ETP. Do not connect field power
to the ETP.

Shield Ground

Energy limited

Figure 23

Not energy limited

Field Wiring for 9792-310F with a 3351S2 AI Module

CAUTION

For more information about installing the Tri-GP in hazardous locations,


see Application-Specific Installation Guidelines on page 182.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 69

AI HART Baseplates
The Model 2354S2 AI HART Baseplate and the
Model 2354AS2 AI HART Hazardous Location
Baseplate are used with Model 3351S2 AI
Modules.
The Triconex 4850 HART Multiplexer mounts
directly onto the Model 2354S2 and 2354AS2
baseplates (the Multiplexer is supplied in the
Model 5354S2 and 5354AS2 TriPaks).
The Model 2354AS2 AI HART Baseplate
should be used in hazardous locations.
The short circuit current specifications for field
short-to-ground faults are:

70 mA, typical

110 mA, maximum

For more information, see Appendix C, HART Communication and the Triconex 4850 HART
Multiplexer Instruction Manual.

Planning and Installation Guide for Triconex General Purpose v2 Systems

70

Chapter 2

System Description

This figure is a simplified schematic of the Model 3351S2 AI Module and the Model 2354 AI
HART Baseplate with the Triconex 4850 HART Multiplexer.
AI HART Baseplate

Triconex 4850

32-Point AI Module
Mux

HART
Field Power (PS1) +

Field Power (PS2) +

32
To
Spare

250 7
In +

Mux
1

250 7
In

32
100 7
.01%
Mux
Field Power (PS1)

To
Other
Points

Field Power (PS2)

Figure 24

1
32

3351S2 AI Module and 2354S2 AI HART Baseplate Schematic

This figure is a simplified schematic of the Model 3351S2 AI Module and the Model 2354AS2 AI
HART Hazardous Location Baseplate with the Triconex 4850 HART Multiplexer.
AI HART Baseplate

Triconex 4850

32-Point AI Module
Mux

HART
Field Power (PS1) +

Field Power (PS2) +

32
To
Spare

250 7
In +

30V
zener

Mux
1

In
250 7

32
100 7
.01%
Mux

Field Power (PS1)


Field Power (PS2)

Figure 25

To
Other
Points

1
32

3351S2 AI Module and 2354AS2 AI HART Hazardous Location Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Components 71

Typical Field Connections

PWR
GND

TDA ()

TDB (+)

This figure depicts typical field connections for the Model 2354S2 AI HART Baseplate and the
Model 2354AS2 AI HART Hazardous Location Baseplate.
RS232/RS485
Converter

24V
DC

+24 V #1

+24 V #2

24 V Return

or

*
To other HART Baseplates or
terminated with 100W resistor

Shield

Safety

SHLD

TA

TB

SHLD

TA

TB

J22
J18

J27

Typical Point
(1 of 32 Points Shown)

1
2

~
~~
~

3
4
5
6
7
8

PWR
FAULT
HOST
HART

~
~~
~

4-20 mA
HART
Transmitter

10
11
12
13
14
15
16

17
18

4850
TRICONEX

19
20
21
22
23
24
25

26
27
28
29
30

31
32
J19

~ ~~ ~ ~
HART AI Baseplate
* For RS485 communication wiring, use twisted-shielded conductors run in metal conduit.

Figure 26

2354S2 and 2354AS2 AI HART Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

72

Chapter 2

System Description

Analog Input/Digital Input Components


These Analog Input/Digital Input components are available with Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Current

Type

3361S2

Analog Input/Digital Input Module

420 mA

Commoned

2361S2

Analog Input/Digital Input Baseplate

Direct Termination

n/a

Analog Input/Digital Input


Hazardous Location External
Termination Baseplate

External Termination

9793-610F

Analog Input/Digital Input


Hazardous Location External
Termination Panel Kit

External Termination

The Analog Input/Digital Input (AI/DI) Module has 16 digital input points (points 116) and
16 analog input points (points 1732).
The AI/DI Module has three isolated sets of electronics, called channels, which independently
process field data input to the module. Sensing of each input point is performed in a manner
that prevents a single failure on one channel from affecting another channel.
For analog input points, each channel receives variable voltage signals from each point, converts
them to digital values, and transmits the values to the three MPs on demand.
For digital input points, an ASIC on each channel scans each input point, compiles data, and
transmits it to the MPs upon demand.
For all points, the MPs vote the data before passing it to the control program. In TMR mode, the
data passed is mid-value. In DUAL mode, the data passed is the average.
AI/DI Modules sustain complete, ongoing diagnostics for each channel. If the diagnostics
detect a failure on any channel, the Fault indicator turns on and activates the system alarm. The
Fault indicator identifies a channel fault, not a complete module failure. AI/DI Modules are
guaranteed to operate properly in the presence of a single fault and may continue to operate
properly with multiple faults.
AI/DI Modules include the hot-spare feature which allows online replacement of a faulty
module. The AI/DI Module is mechanically keyed to prevent improper installation in a
configured baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Components

73

AI/DI Module 3361S2


This figure is a simplified schematic of the Model 3361S2 AI/DI Module.
Analog Input/Digital Input Module Typical Point (1 of 32)

ADC

Isolation
Filtering

Triplicated
I/O Bus

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

Individual Point
Field Terminations

DAC

ADC

*
DAC

ADC

*
DAC

*On DI points only


Figure 27

3361S2 AI/DI Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

74

Chapter 2

System Description

This table lists the specifications for the Model 3361S2 AI/DI Module.
Table 17

3361S2 AI/DI Module Specifications

Features Common to all Points

Specification

Points

32, commoned

Functional earth to protective earth isolation

500 VDC, minimum

Functional earth to functional earth (logic) isolation

800 VDC, minimum

Features of AI Points

Specification

Nominal input current

420 mA DC

Specified operational current range

222 mA DC

Absolute maximum field voltage

33 VDC

Absolute maximum reverse field voltage

0.6 VDC

Absolute maximum input current

50 mA DC

Input bandwidth (3dB)

16 Hz

Source impedance

180

Input impedance (with baseplate)

250

I to V resistor

100 0.01%

Resolution

12 bits

Absolute error

0.15% of full scale (20 mA)

Diagnostic

Force-to-value diagnostic (FVD)

Scan time

< 1 ms for all 32 points

Features of DI Points

Specification

Nominal input voltage

024 VDC

Operational voltage range

1530 VDC

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input Delay

< 10 ms, On to Off, Off to On

Input impedance

> 100 k without baseplate


~ 3 k with baseplate

Input power

0.2 W/pt, @ 24 VDC


0.5 W/pt, @ 33 VDC

Input threshold

05 VDC = Off region


614 VDC = transition region
1530 VDC = On region

Diagnostic (loss of view)

Force-to-value diagnostic (FVD),


< 2 ms/test

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Components

Features of DI Points (continued)

Specification (continued)

Maximum input toggle rate to maintain diagnostic


fault coverage

< 20/sec

75

FVD Off state glitch


Duration
Magnitude
Output impedance

< 2 ms
36% test voltage
05 VDC, 100 k

ADC scan time

< 1 ms for all DI points

AI/DI Baseplate
This figure depicts a front view of the
Model 2361S2 AI/DI Baseplate. The short
circuit current specifications for field
short-to-ground faults are:

130 mA, typical

200 mA, maximum

Planning and Installation Guide for Triconex General Purpose v2 Systems

76

Chapter 2

System Description

This figure is a simplified schematic of the Model 3361S2 AI/DI Module and Model 2361S2
AI/DI Baseplate.
AI/DI Baseplate

32-Point AI/DI Module


Mux
1

Field Power (PS1) +


Field Power (PS2) +

32
To
Spare

180 7
+
In

***
Mux
1

*
32

**

***
Mux

Field Power (PS1)

To
Other
Points

Field Power (PS2)

1
32

*150 7 on AI points **100 7 on AI points


0 7 on DI points

Figure 28

3.01 k7 on DI points

***On DI points only

***

3361S2 AI/DI Module and 2361S2 AI/DI Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Components

77

Typical Field Connections


This figure depicts typical field connections for the Model 2361S2 AI/DI Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

Field
Contact
+

~
~

~
~
Typical DI Point
(1 of 16 DI Points Shown)

10

10

11

11

12

12

13

13

14

14

15

15

16

~
~~
~

16

4-20 mA
Transmitter

17
17

~
~~
~

18
19
20
21
22

Typical AI Point
(1 of 16 AI Points Shown)

23
24
25
26
27
28

29
30
31

18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

32

~ ~~ ~ ~

Figure 29

2361S2 AI/DI Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

78

Chapter 2

System Description

AI/DI External Termination Baseplate


The AI/DI External Termination
Baseplate is typically used with the
Model 9793-610F External Termination
Panel Kit.
This panel contains ELCO connectors,
which allows connection of External
Termination Panels.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Components

79

This figure is a simplified schematic of the Model 9793-610F ETP Kit and the Model 3361S2
AI/DI Module with the AI/DI External Termination Baseplate.
ELCO
CABLE

TERMINATION PANEL

BASEPLATE

32-POINT AI/DI MODULE

**

200300 Ohms

Mux

3 kilohms

30 V
Zener

32

3.3 V
Zener

***

to
other
points

Mux

to
spare

module

PS1

32

PS2
PS1

***

PS1
PS2

PS2

Mux

to
modules

1
32

0 ohm

***
PS1
0 ohm

PS2

* 3.3 V zener on the AI ETP onlyno 3.3 V zener on the DI ETP


** 1 00 ohm 0.01% resist or on AI points 173 2
3.01 kilohm 1 % resi stor on DI points 116
*** On DI point s onl y

Figure 30

3361S2 AI/DI Module and AI/DI External Termination Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

80

Chapter 2

System Description

Typical Field Connections


This figure depicts typical field connections for the AI/DI External Termination Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

S
F

~ ~~ ~ ~
Figure 31

AI/DI External Termination Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Components

81

AI/DI Hazardous Location External Termination Panels


To connect field wiring to the Model 3361S2 AI/DI Module in hazardous locations, you must
use one DI Hazardous Location ETPfor points 1-16and one AI Hazardous Location ETP
for points 17-32.
Model 9793-610F is an ETP kit that includes one AI Hazardous Location ETP (Model 9792-310F)
and one DI Hazardous Location ETP (Model 9573-610F).
For more information on these ETPs, including specifications, simplified schematics, and field
wiring diagrams, see:

AI Hazardous Location External Termination Panel on page 65

DI Hazardous Location External Termination Panel on page 115

You must use two 16-point term panels for each 32-point AI/DI module. Each term panel comes
with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Planning and Installation Guide for Triconex General Purpose v2 Systems

82

Chapter 2

System Description

Analog Output Components


These Analog Output components are available with Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Current

Type

3481S2

Analog Output Module

4 @ 420 mA

Commoned

3482S2

High-Current Analog Output Module

2 @ 420 mA,
2 @ 440 mA

Commoned, High Current

2481S2

Analog Output Baseplate

Direct Termination

n/a

Analog Output External Termination


Baseplate

External Termination

9863-610F

Analog Output Hazardous Location


External Termination Panel

External Termination

2483S2

Analog Output HART Baseplate

Direct Termination

2483AS2

Analog Output HART Hazardous


Location Baseplate

Direct Termination

Note

When ordering the 9863-610F ETP, you can order longer interface cables, in increments
of 10 feet, by changing the last two digits of the ETP model number from 10 to the
desired length of the cable. The maximum length for interface cables is normally 100 feet.
Contact the Invensys Global Customer Support (GCS) center if you require cables longer
than 100 feet.

Analog Output (AO) Modules contain the circuitry for three identical, isolated channels. Each
channel includes a proprietary ASIC that receives its output table from the I/O communication
processor on its corresponding main processor. The AO Modules use special shunt circuitry to
vote on the individual output signals before they are applied to the load. This voter circuitry
insures only one output, A or B or C, is driving the field load. The shunt output circuitry
provides multiple redundancy for all critical signal paths, guaranteeing safety and maximum
availability.
AO Modules continuously execute forced-switch diagnostics (FSD) on each point. By carefully
forcing error conditions and observing proper behavior of the voting circuitry, high reliability
and safe operation is insured. This safety feature allows unrestricted operation under a variety
of multiple-fault scenarios.
AO Modules support hot sparing for online replacement of a faulty module or continuous backup to an active module. The AO Modules are mechanically keyed to prevent improper
installation in a configured baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

83

AO Module 3481S2
This figure is a simplified schematic of the Model 3481S2 AO Module.
Triplicated
I/O Bus

I/O Controller(s)

Isolated
Bus
Transceiver

ASIC

Field Circuitry Typical Point (4)

Selector
Logic

DAC
Voltage Loopback
Current Loopback

Isolated
Bus
Transceiver

ASIC

Selector
Logic

DAC

Voltage Loopback
Current Loopback

Isolated
Bus
Transceiver

ASIC

Output
Termination

Selector
Logic

DAC
Voltage Loopback
Current Loopback

Figure 32

3481S2 AO Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

84

Chapter 2

System Description

This table lists specifications for the Model 3481S2 AO Module.


Table 18

3481S2 AO Module Specifications

Feature

Specification

Points

4, commoned-return, DC-coupled

Output current range

420 mA output, controlled


022 mA over-range
0 mA output capability (step function <2 mA)

Output accuracy

<0.25% (in range of 420 mA) of FSR (022 mA),


from 32 F to 158 F (0 C to 70 C)

Type

TMR

Resolution

12 bits

Diagnostic

Forced-switch diagnostic (FSD)

External loop power (reverse voltage-protected)

32 VDC, maximum
24 VDC, nominal

with 2483AS2 Hazardous Location Baseplate

30 VDC, maximum

Output loop power requirements for specified load

300 @ >16 VDC (1 A minimum)


500 @ >20 VDC (1 A minimum)
700 @ >24 VDC (1 A minimum)
800 @ >28 VDC (1 A minimum)

Over-range protection

36 VDC, continuous
0 VDC, continuous

Switch time on leg failure

1 ms, typical
3 ms, maximum

Functional-to-protective-earth isolation

500 VDC, minimum

with 2483AS2 Hazardous Location Baseplate


Functional-to-functional-earth (logic) isolation

0 VDC
800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

85

AO Module 3482S2
This figure is a simplified schematic of the Model 3482S2 High-Current AO Module.
Triplicated
I/O Bus

I/O Controller(s)

Isolated
Bus
Transceiver

Proc
A

Field Circuitry Typical Point (4)

Selector
Logic

DAC
Voltage Loopback
Current Loopback

Isolated
Bus
Transceiver

Proc
B

Selector
Logic

DAC

Voltage Loopback
Current Loopback

Isolated
Bus
Transceiver

Proc
C

Output
Termination

Selector
Logic

DAC
Voltage Loopback
Current Loopback

Figure 33

3482S2 High-Current AO Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

86

Chapter 2

System Description

This table lists specifications for the Model 3482S2 High-Current AO Module.
Table 19

3482S2 High-Current AO Module Specifications

Feature

Specification

Points

4, commoned-return, DC-coupled

Output current range, Points 12

420 mA output, controlled


022 mA over-range
0 mA output capability (step function <2 mA)

Output accuracy, Points 12

<0.25% (in range of 420 mA) of FSR


(022 mA), from 32 F to 158 F (0 C to +70C)

Output current range, Points 34

440 mA output, controlled


044 mA over-range
0 mA output capability (step function <4 mA)

Output accuracy, Points 34

<0.25% (in range of 440 mA) of FSR


(044 mA), from 32 F to 122 F (0 C to 50C)

Type

TMR

Resolution

12 bits

Diagnostic

Forced-switch diagnostic (FSD)

External loop power (reverse voltage protected)

32 VDC, maximum
24 VDC, nominal

Output loop power requirements


for specified load, Points 12

300 @ >16 VDC (1 A minimum)


500 @ >20 VDC (1 A minimum)
700 @ >24 VDC (1 A minimum)
800 @ >28 VDC (1 A minimum)

Over-range protection, Points 12

36 VDC, continuous
0 VDC, continuous

Output loop power requirements for specified


load, Points 34

125 @ >16 VDC (1 A minimum)


210 @ >20 VDC (1 A minimum)
295 @ >24 VDC (1 A minimum)
340 @ >28 VDC (1 A minimum)

Over-range protection

36 VDC, continuous with thermal de-rating


0 VDC, continuous

Switch time on leg failure

1 ms, typical
3 ms, maximum

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic) isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

87

AO Baseplate
This figure depicts a front view of the
Model 2481S2 AO Baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

88

Chapter 2

System Description

This figure is a simplified schematic of the Model 3481S2 or Model 3482S2 AO Module and
Model 2481S2 AO Baseplate.
4-Point AO Module

AO Baseplate

Loop Power

Field Power (PS1) +


Field Power (PS2) +

A
Selector
Logic
DAC

To
Other
Points

Load +

B
Selector
Logic
DAC

C
Selector
Logic

Load
Field Power (PS1)
Field Power (PS2)

DAC

Figure 34

3481S2 or 3482S2 AO Module and 2481S2 AO Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

89

Typical Field Connections


This figure depicts typical field connections for the Model 2481S2 AO Baseplate.
+24 V #1

+24 V #2

RTN

Safety

Unused Output Jumper *

Typical Point
(1 of 4 Points Shown)

~
~

Field
Load

~
~

9
10
11
12
13
14
15
16

**

9
10
11
12
13
14
15
16

~~~~
* Short unused outputs
** Use points 1 through 4 to wire field devices to the baseplate

Figure 35

2481S2 AO Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

90

Chapter 2

System Description

AO External Termination Baseplate


The AO External Termination Baseplate is used with the Model 9863-610F AO Hazardous
Location ETP.
The baseplate contains ELCO connectors, which allows connection of External Termination
Panels.
This figure depicts a front view of the
Analog Output External Termination
Baseplate, which is available for use
with all Tri-GP systems.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

91

This figure is a simplified schematic of the Model 3481S2 AO Module and the AO External
Termination Baseplate.
4-Point AO Module

AO External Termination Baseplate

Loop Power
Field Power (PS1)
Field Power (PS2)

A
Selector
Logic
V+
DAC

B
Selector
Logic

To External
Termination Panel

DAC

C
Selector
Logic
DAC

Figure 36

Field Power (PS1)


Field Power (PS2)

3481S2 AO Module and AO External Termination Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

92

Chapter 2

System Description

Typical Field Connections


This figure depicts typical field connections for the AO External Termination Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

S
F

~ ~~ ~ ~
Figure 37

AO External Termination Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

93

AO HART Baseplates
The Model 2483S2 AO HART Baseplate and the
Model 2483AS2 AO HART Hazardous Location
Baseplate are used with Model 3481S2 AO
Modules.
The Triconex 4850 HART Multiplexer mounts
directly onto the Model 2483S2 and 2483AS2
baseplates (the Multiplexer is supplied in the
Model 5483S2 and 5483AS2 TriPaks).
The Model 2483AS2 AO HART Hazardous
Location Baseplate should be used in
hazardous locations.

CAUTION

The Model 2483S2 AO HART Baseplate and the Model 2483AS2 AO


HART Hazardous Location Baseplate can be used only with Model
3481S2 AO modules. Using it with other modules will destroy some of the
baseplate components.

For more information, see Appendix C, HART Communication and the Triconex 4850 HART
Multiplexer Instruction Manual.

Planning and Installation Guide for Triconex General Purpose v2 Systems

94

Chapter 2

System Description

This figure is a simplified schematic of the Model 3481S2 AO module and the Model 2483S2 AO
HART Baseplate with the Triconex 4850 HART Multiplexer.
4-Point AO Module

AO HART Baseplate
Triconex 4850
HART
To
RS232-to-RS485
Converter
Connection

Loop Power
RS485

PWR

Selector
Logic

Address

To
Address Plug
Connection

Field Power (PS1) +

DAC

Field Power (PS2) +


B
Selector
Logic

To
Other
Points
Load +

DAC
HART Filter

C
Selector
Logic

Load
Field Power (PS1)

DAC

Field Power (PS2)

Figure 38

3481S2 AO Module and 2483S2 AO HART Baseplate Schematic

This figure is a simplified schematic of the Model 3481S2 AO module and the Model 2483AS2
AO HART Hazardous Location Baseplate with the Triconex 4850 HART Multiplexer.
4-Point AO Module

AO HART Hazardous Location Baseplate


Triconex 4850

Safe Area

HART
To
RS232-to-RS485
Converter
Connection

Loop Power
RS485

PWR

Selector
Logic

Address

To
Address Plug
Connection

Field Power
(PS1) +

DAC

30V
zener

Field Power
(PS2) +

B
Selector
Logic

Safe Area Hazardous


Area

To
Other
Points
Load +

DAC

IS
Isolator

HART Filter

C
Selector
Logic

Load

Load
Field Power (PS1)

DAC

Field Power (PS2)

Figure 39

3481S2 AO Module and 2483AS2 AO HART Hazardous Location Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

95

Typical Field Connections

PWR
GND

TDA ()

TDB (+)

This figure depicts typical field connections for the Model 2483S2 AO HART Baseplate.

24V
DC

+24 V #1

+24 V #2

RTN

or

***
To other HART Baseplates or
terminated with 100W resistor

Safety

Typical Point
(1 of 4 Points Shown)

SHLD

TA

TA

TB

TB

J22
SHLD

Shield

RS232/RS485
Converter

J18

J27

~
~

1
2

3
4

~
~

Field
Load

5
6

PWR

HOST

HART

FAULT

Unused Output Jumper **

10
11
12
13
14
15
16

4850
TRICONEX

F
J19

~~~~ ~
HART AO Baseplate
* Use points 1 through 4 to wire field devices to the baseplate
** On points 1 through 4, short any unused outputs
*** For RS485 communication wiring, use twisted-shielded conductors run in metal conduit

Figure 40

2483S2 AO HART Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

96

Chapter 2

System Description

PWR
GND

TDA ()

TDB (+)

This figure depicts typical field connections for the Model 2483AS2 AO HART Hazardous
Location Baseplate.

24V
DC

+24 V #1

+24 V #2

RTN

***
To other HART Baseplates or
terminated with 100W resistor

or
S

Safety

Typical Point
(1 of 4 Points Shown)

SHLD

TA

TA

TB

TB

J22
SHLD

Shield

RS232/RS485
Converter

J18

J27

~
~

1
2

3
4

~
~

Field
Load

5
6

PWR

HOST

HART

FAULT

Unused Output Jumper **

10
11
12
13
14
15
16

4850
TRICONEX

Intrinsic Safety (IS)


Isolators
****
S

MTL CPS04 Backplane


F
J19

Safe Area

~~~~ ~

Hazardous
Area

HART AO Baseplate
* Use points 1 through 4 to wire field devices to the baseplate
** On points 1 through 4, short any unused outputs
*** For RS485 communication wiring, use twisted-shielded conductors run in metal conduit
**** For ATEX compliance, IS isolators must be used. Triconex tested ATEX compliance using MTL4546 Isolators.

Figure 41

2483AS2 AO HART Hazardous Location Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

97

AO Hazardous Location External Termination Panel


The Model 9863-610F ETP is suitable for use in Zone 2, and Class 1, Division 2 field circuits. The
ETP contains extra circuitry designed to limit power available to the field terminals. The circuits
have been examined and certified by TV Rhineland as being nonincendive. This guarantees
that if the field wires are accidentally opened, shorted, or grounded, and the Tri-GP is operating
normally, the wiring and attached devices will not release sufficient energy to cause ignition in
the specified flammable atmosphere.
The Model 9863-610F ETP is compatible with the Model 3481S2 Analog Output Module. Each
ETP has:

Two, eight-position field terminals; support for eight points (only four points
supported on the 3481S2 Module)

Two terminals per point: Out, Rtn (L+, L)

A four-position terminal for redundant 24 VDC loop power

Two, one-position terminals for protective earth connection

The panel supports redundant 24 VDC power sources with diode ORing. However,
recommended field power connections are on the AO External Termination Baseplate and
routed to the ETP through the interface cable with ELCO connectors. Field energy will not be
limited if it is connected to the ETP; it will be limited only if it is connected to the baseplate.
Dimensions for Term Panel 9863-610F
Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.42 in (11.23 cm)

5.02 in (12.75 cm)

4.25 in (10.795 cm)

Specifications
This table describes general specifications for 9863-610F.
Table 20

General Specifications for Term Panel 9863-610F

Feature

Description

Panel type

Hazardous location, current output

Points

Planning and Installation Guide for Triconex General Purpose v2 Systems

98

Chapter 2

System Description

This table describes cable and load parameters for 9863-610F.


Table 21

Cable and Load Parameters for Term Panel 9863-610F

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

30 V

Maximum voltage

Um

Um

32 V

Output Connection (F+) Specifications

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.250 A

Maximum output power

Po

Po

1.72 W

C external, maximum

Co

Ca

1.18 F

L external, maximum

Lo

La

4.95 mH

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Components

99

Simplified Schematic
This figure is a simplified schematic of the Model 9863-610F ETP and the Model3481S2 AO
Module with an AO External Termination Baseplate.
4-POINT ANALOG OUTPUT MODULE

AO EXTERNAL
TERMINATION BASEPLATE

ELCO
CABLE

TERMINATION PANEL

Loop power
A

0 ohm

PS1 +

Selector
Logic
Current
loopback

to
module

0 ohm

PS2 +

DAC
PS1

Selector
Logic

PS2

Current
loopback

DAC

ATEX
Filter

OUT2
Typical point

RTN2

Selector
Logic
Current
loopback

DAC

Figure 42

Simplified Schematic of a 9863-610F Panel and a 3481S2 AO Module with an AO External


Termination Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

100

Chapter 2

System Description

Typical Connections

C17
L12

SN

C15

C14

REV D

 
L11
L5

C12

L4

C10

C5

C3

C2

L3

L1

TRICONEX

 


L15

 

L13

L14

L9

L10

L7

L8

 

 

C35

TB8

R1

TB1TB4

R2

C44

C43

C42

C41

C40

C39

TB7

C38

C37

L2

J1

C19

C22

C7

C24

L17

C20

L18

C8

EXT TERM
   
7400270

        

This figure illustrates how to connect a 9863-610F to the field (1 of 4 module points shown).

J4



C25

C27
C45

L-

P1

J5

P2

Typical unused point

Typical point
(1 of 8 points shown)

Note: Field power is routed


from the baseplate. Do not
connect field power to the ETP.

Load

Energy limited

Figure 43

Field Wiring for 9863-610F with a 3481S2 AO Module

CAUTION
Note

Not energy limited

Unused points must be shorted together.


For more information about installing the Tri-GP in hazardous
locations, see Application-Specific Installation Guidelines on page 182.

The Model 3481S2 AO Module has only four outputs, so points 5 through 8 on the ETP
are not connected and are not required to be shorted together.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

101

Digital Input Components


These Digital Input components are available with Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Voltage

Type

3301S2

Digital Input Module

24 VDC

Commoned

3311S2

Digital Input Module, High Resolution

24 VDC

Commoned

2301S2

Digital Input Baseplate

Direct Termination

n/a

Digital Input External Termination


Baseplate

External Termination

2302S2

High-Voltage DI Baseplate Kit, includes:


Digital Input External Termination
Baseplate, two Solid State Relay Input
External Termination Panels, two 10-foot
Interface Cables

9573-610F

Digital Input Hazardous Location


External Termination Panel

Note

115 VAC

External Termination,
Interposing Relays

External Termination

When ordering the High-Voltage DI Baseplate Kit, you can order interface cables in
increments of 10 feet by specifying part number 4000195-3xx, where xx equals the length
in feet. When ordering the 9573-610F ETP, you can order interface cables in increments
of 10 feet by changing 9573-610F to 9573-6xx, where xx equals the length in feet. The
maximum length for interface cables is normally 100 feet. Contact the Invensys Global
Customer Support (GCS) center if you require cables longer than 100 feet.

Digital Input (DI) Modules have three independent channels which process all data sent to the
module. An ASIC on each channel scans each input point, compiles data, and transmits it to the
MPs upon demand. Input data is voted at the MPs before processing to ensure the highest
integrity.
DI Modules sustain complete, ongoing diagnostics for each channel. If the diagnostics detect a
failure on any channel, the Fault indicator is activated, which in turn activates the system alarm.
The Fault indicator points to a channel fault, not a complete module failure. The DI Module is
guaranteed to operate properly in the presence of a single fault and may continue to operate
properly with certain multiple faults.
DI Modules continuously verify the ability of the system to detect transitions to the opposite
state. The DI Module supports hot sparing for online replacement of a faulty module or
continuous back-up to an active module. The DI Module is mechanically keyed to prevent
improper installation in a baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

102

Chapter 2

System Description

DI Module 3301S2
This figure is a simplified schematic of the Model 3301S2 DI Module.
Triplicated
I/O Bus

Digital Input Module Typical Point (1 of 32)

ADC

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

Isolation
Filtering

Individual Point
Field Terminations

DAC

ADC

DAC

ADC

DAC

Figure 44

3301S2 DI Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

103

This table lists the specifications for the Model 3301S2 DI Module.
Table 22

3301S2 DI Module Specifications

Feature

Specification

Points

32, commoned

Nominal input voltage

24 VDC

Operational voltage range

19.230 VDC

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input delay

ON to OFF or OFF to ON
Time constant = 2.86 msec, - 3dB @ 55hz

Input impedance

>30 k without baseplate


3 k with baseplate

Input power

0.2 W/pt, @ 24 VDC


0.5 W/pt, @ 33 VDC

Input threshold

05 VDC = Off region


614 VDC = transition region
1530 VDC = On region

Diagnostic (loss of view)

Force-to-value diagnostic (FVD),


<2 ms/test

Maximum input toggle rate to maintain diagnostic fault


coverage

<20/sec

FVD Off-state glitch


Duration

<2 ms

Magnitude

36% test voltage

Output Impedance

05 VDC, 100 k

ADC scan time

<1 ms for all 32 points

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic) isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

104

Chapter 2

System Description

DI Module 3311S2
This figure is a simplified schematic of the Model 3311S2 DI Module.
Triplicated
I/O Bus

Digital Input Module Typical Point (1 of 32)

ADC

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

Isolation
Filtering

Individual Point
Field Terminations

DAC

ADC

DAC

ADC

DAC

Figure 45

3311S2 DI Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

105

This table lists the specifications for the Model 3311S2 DI Module.
Table 23

3311S2 DI Module Specifications

Feature

Specification

Points

32, commoned

Nominal input voltage

24 VDC

Operational voltage range

19.230 VDC

Absolute maximum input voltage

33 VDC

Absolute maximum reverse input voltage

0.6 VDC

Input delay

ON to OFF or OFF to ON
Time constant = 0.13 msec, 3 dB @ 1.2 kHz

Input impedance

>30 k without baseplate


3 k with baseplate

Input power

0.2 W/pt, @ 24 VDC


0.5 W/pt, @ 33 VDC

Input threshold

05 VDC = Off region


614 VDC = transition region
1530 VDC = On region

Diagnostic (loss of view)

Force-to-value diagnostic (FVD),


<2 ms/test
Force-to-trigger diagnostic (FTD),
<2 ms/test

Maximum input toggle rate to maintain diagnostic


fault coverage

<20/sec

FVD and FTD Off-state glitch


Duration

<2 ms

Magnitude

36% test voltage

Output Impedance

05 VDC, 100 k

ADC scan time

<1 ms for all 32 points

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic) isolation

800 VDC, minimum

The Model 3311S2 DI Module reports Sequence of Events (SOE) with a resolution of one
millisecond or less and with an accuracy of one millisecond or less.
These are key terms used to describe the operation of the Model 3311S2 DI Module:

Transitiona transition is defined as a point entering the user-defined trip state (SOE
Trigger State) for the minimum amount of user-specified time (SOE Trigger Time), with
an accuracy of 0/+1 milliseconds.

Planning and Installation Guide for Triconex General Purpose v2 Systems

106

Chapter 2

System Description

Trip statethe trip state is a user-defined property (SOE Trigger State) in TriStation
1131 software that determines if the SOE function is enabled for a point and specifies
the state of transitions (Rising, Falling, Rising/Falling) to be reported.

Trigger timethe trigger time is a user-defined property (SOE Trigger Time) in


TriStation 1131 software that specifies the number of milliseconds that a signal must be
stable before its change in state (transition) causes the reporting of an event. This is also
known as the debounce period. A longer trigger time results in a longer debounce
period, so that pulse widths that fall within the debounce period will not be reported as
an event.

Dead time intervalthe dead time interval is a user-defined property (SOE Dead Time)
in TriStation 1131 software that specifies the length of time (in seconds) that must
elapse after a transition, before a subsequent transition will be reported. A longer dead
time interval is better able to prevent the higher-level SOE application from being
flooded with events, but it also means there is a greater chance of losing subsequent
transition events.

Unreported eventsunreported events are events that have been captured and are
being processed before being reported to the SOE function block in the control
program.

It can take up to three minutes for the Model 3311S2 DI Module to reach the Pass State upon
initial power up, which is indicated by a steady green Pass status indicator on the front panel of
the module.
When an event is triggered on a point, the amount of time before a subsequent event can be
captured on the same point is affected by the number of unreported events in the system and
the number of unreported events on the module.
This formula identifies the typical amount of time before a subsequent event can be captured on
the same point. However, in the presence of certain diagnostics, the worst case time will be 20
seconds or the calculated time, whichever is greater. The calculated time does not exceed 20
seconds until there are 154 unreported events in the system with 32 unreported events on the
individual module.
Time = (0.11 T) + (0.091 P) + 0.23 seconds
T = total number of unreported events in the system. The maximum number of T is the total
number of SOE-enabled points in the system. The maximum number of T is reached only if
all SOE-enabled points in the system are triggered at the same time.
P = unreported events on the individual module. The maximum number of P is the total
number of SOE-enabled points on the module. The maximum number of P is reached only
if all SOE-enabled points on the module are triggered at the same time.
Additional performance characteristics of the Model 3311S2 DI Module:

The module may miss transitions after the SOE function block in the control program
starts, for a period of time up to the amount of the dead time interval.

After the module captures a transition for an input point, a subsequent transition for
that point is reported only after the user-configured dead time interval (SOE Dead
Time) has elapsed.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

107

When the trip state is set to detect both rising and falling transitions
(SOE Trigger State = Rising/Falling), the trailing transition is reported only if the
leading transition is reported, which means that if the point changed state but the
leading change did not meet the minimum transition timeso it was not reportedthe
change back to the original state is not reported.

The module may miss transitions during a change from TMR mode to DUAL mode, or
a change from DUAL mode to TMR mode. The module may not report events in correct
sequence if the events happen at the same time the module changes from TMR mode to
DUAL mode, when the mode change is caused by certain fault conditions.

In DUAL mode, the accuracy of the trigger time can be 1 millisecond if the runtime
diagnostics are running during the transition.

DI Baseplate
This figure depicts a front view of the
Model 2301S2 DI Baseplate.
The short circuit current specifications
for field short-to-ground faults are:

130 mA, typical

200 mA, maximum

Planning and Installation Guide for Triconex General Purpose v2 Systems

108

Chapter 2

System Description

This figure is a simplified schematic of the Model 3301S2 or 3311S2 DI Module and 2301S2 DI
Baseplate.
DI Baseplate

32-Point DI Module
Mux
1

Field Power (PS1) +


Field Power (PS2) +

32
To
Spare

180
+
In

Mux
1

32

3K

Mux

Field Power (PS1)


Field Power (PS2)

To
Other
Points

1
32

Figure 46

3301S2 or 3311S2 DI Module and 2301S2 DI Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

109

Typical Field Connections


This figure depicts typical field connections for the Model 2301S2 DI Baseplate.
+24 V #1

+24 V #2

RTN

Safety

Field
Contact

~
~

~
~

Typical Point
(1 of 32 Points Shown)

10

10

11

11

12

12

13

13

14

14

15

15

16

16

17
18
19
20
21
22
23
24
25
26
27
28

29
30
31
32

~ ~~ ~
Figure 47

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

2301S2 DI Baseplate Typical Field Connections

DI External Termination Baseplate


The DI External Termination Baseplate is used with the Solid State Relay (SSR) Input External
Termination Panel (ETP) or the Model 9573-610F DI Hazardous Location ETP.
The baseplate contains ELCO connectors, which allows connection of External Termination
Panels.

Planning and Installation Guide for Triconex General Purpose v2 Systems

110

Chapter 2

System Description

This figure depicts a front view of the


DI External Termination Baseplate,
which is available for use with all
Tri-GP systems.

This figure is a simplified schematic of the Model 3301S2 or 3311S2 DI Module and DI External
Termination Baseplate.
DI Baseplate

32-Point DI Module
Mux
1

Field Power (PS1) +


Field Power (PS2) +

32
To
Spare

External
Termination Panels

Mux
1
32

Mux

Field Power (PS1)


Field Power (PS2)

1
32

Figure 48

3301S2 or 3311S2 DI Module and DI External Termination Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

111

Typical Field Connections


This figure depicts typical field connections for the DI External Termination Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

S
F

~ ~~ ~ ~
Figure 49

DI External Termination Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

112

Chapter 2

System Description

Solid State Relay Input External Termination Panel


The Solid State Relay (SSR) Input External Termination Panel (ETP) is compatible with
industry-standard solid state relays which can be cabled to the DI External Termination
Baseplate. The solid state relays are manufactured by OMRON.
The SSR Input ETP supports 16 points and each DI Module can support up to two SSR Input
ETPs.
The SSR Input ETP has a barrier strip with four compression screw terminals per point for
connecting a DI Module to 16 digital inputs. The SSR Input ETP accepts power (+24 VDC) from
the DI Baseplate. The 24-volt power source connected to the baseplate must be able to provide
0.5 amps minimally.
You must use two 16-point term panels for each 32-point DI module. Each term panel comes
with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.
This figure depicts a front view of the SSR Input ETP.
J1

DSP5

R4

CR4

R5

CR5

DSP6

DSP9

R9

CR7

CR9

NON-COM DI
RELAY ETP

CR10

DSP10

DSP11

R10

R11

CR11

DSP12

R12

CR12

CR13

BOTTOM VIEW
LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

G3R-IAZR1SN

BOTTOM VIEW

OMRON

IN

F15

IN

F16

DSP14

R13

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

G3R-IAZR1SN

BOTTOM VIEW

IN

F14
DSP13

K16

MADE IN JAPAN
OMRON

AC

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

F13

K15

G3R-IAZR1SN

BOTTOM VIEW

MADE IN JAPAN
OMRON

AC

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

F12

K14

G3R-IAZR1SN

BOTTOM VIEW

MADE IN JAPAN
OMRON

AC

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

F11

K13

G3R-IAZR1SN

BOTTOM VIEW

MADE IN JAPAN
OMRON

AC

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

F10

K12

G3R-IAZR1SN

OMRON

BOTTOM VIEW
LOAD:0.1A
524VDC
INPUT:100240VAC~

MADE IN JAPAN

K11

G3R-IAZR1SN

BOTTOM VIEW

OMRON
AC

R8

7400256

PWR

MADE IN JAPAN

MADE IN JAPAN

DSP8

CR8

Figure 50

IN

F9

R7

CR6

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

K10

G3R-IAZR1SN

OMRON

BOTTOM VIEW

IN

F8
DSP7

R6

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

F7

K9

G3R-IAZR1SN

OMRON

BOTTOM VIEW

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

G3R-IAZR1SN

BOTTOM VIEW

OMRON

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

G3R-IAZR1SN

BOTTOM VIEW

OMRON

IN

F6

K8

DSP15

R14

CR14

REV B

SN

Solid State Relay Input External Termination Panel

Dimensions of the SSR Input ETP


Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.23 in (10.74 cm)

12.54 in (31.85 cm)

4.25 in (10.795 cm)

Planning and Installation Guide for Triconex General Purpose v2 Systems

DSP16

R15

CONTACT

DSP4

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

CONTACT

CR3

IN

F5

K7

PWR

R3

K6

G3R-IAZR1SN

OMRON

BOTTOM VIEW

BOTTOM VIEW
LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

G3R-IAZR1SN

IN

F4
DSP3

MADE IN JAPAN

K5

MADE IN JAPAN
OMRON
AC

R2

CR1

CR2

IN

F3
DSP2

R1

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

K4

G3R-IAZR1SN

BOTTOM VIEW

IN

F2
DSP1

MADE IN JAPAN
OMRON

AC

LOAD:0.1A
524VDC
INPUT:100240VAC~

IN

F1

K3

G3R-IAZR1SN

OMRON

BOTTOM VIEW

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

AC

K2

G3R-IAZR1SN

OMRON

MADE IN JAPAN

K1

R16

CR15

CR16

PWR

AC
Power
Supply
AC

DSP1

CR2

Figure 52
F2
IN
AC

R1
DSP2

CR1
R2

CR3

F3
IN
AC

DSP3
OMRON

F4

R3
DSP4

R4

CR4

Neutral
IN
AC

OMRON

F5
DSP5

R5

CR5

IN
AC

F6
IN
AC

DSP6

R6

CR6
F7
IN
AC

DSP7
OMRON

R7

CR8

F8
IN
AC

DSP8

R8

CR7

NON-COM DI
RELAY ETP

7400256

SN
F9
IN
AC

DSP9

R9

CR9

CR10
F10
IN
AC

DSP10
OMRON

R10

CR11

F11
IN
AC

DSP11

R11
OMRON

F12
IN
AC

DSP12

R12

CR12
OMRON

F13
IN
AC

DSP13

R13

CR13
OMRON

F14
IN
AC

F15
IN
AC

DSP14

R14
DSP15

CR14

LOAD:0.1A
524VDC
INPUT:100240VAC~

OMRON

BOTTOM VIEW

BOTTOM VIEW

MADE IN JAPAN

K15

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K14

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K13

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K12

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K11

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K10

G3R-IAZR1SN

OMRON

K9

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

1A

G3R-IAZR1SN

OMRON

MADE IN JAPAN

K8

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

V+

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K7

G3R-IAZR1SN

OMRON

K6

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

C+

G3R-IAZR1SN

OMRON

K5

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

V+
Other
Points

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K4

G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

K3

G3R-IAZR1SN

OMRON

BOTTOM VIEW

MADE IN JAPAN

K2

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

K1

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

Figure 51

Baseplate

CONTACT

IN

G3R-IAZR1SN

OMRON

MADE IN JAPAN

SSR Panel

PWR

F1

CONTACT

AC
LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

Digital Input Components


113

This figure depicts a simplified schematic of the Model 3301S2 or 3311S2 DI Module and the SSR
Input ETP.
32-Point DI Module

1
Mux

P+
32

To
Spare

1
Mux

C
32

1
Mux

32

3301S2 or 3311S2 DI Module and SSR Input ETP Schematic

Typical Connections

This figure shows how to connect 115 VAC discrete inputs to the SSR Input ETP, which is used
with the Model 3301S2 or 3311S2 DI Module and DI External Termination Baseplate.
J1
K16

F16
IN

R15
DSP16

R16

CR15

REV B
CR16

Hot

Typical point
(1 of 16 points shown).

Field
Contact

SSR Input ETP Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

114

Chapter 2

System Description

Input Ranges
This table lists the input ranges for available SSR modules. SSRs must be ordered separately and
are available from Invensys or directly from OMRON. For more information, contact the
Invensys Global Customer Support (GCS) center.
For detailed specifications, see the OMRON G3R-I/O data sheet.
Table 24

Input Ranges for Solid State Relay (SSR) Modules

Description

Part Number

Input Range

Must
Operate
Voltage

Must
Release
Voltage

Output
Range

Solid-State
Relay Input
Module

1300447-001
(G3R-IAZR1SN)

100 to 240 VAC

60 VAC max.

20 VAC min.

4 to 32 VDC

The OMRON family of input relays are limited to an ambient humidity


range of 45% to 85%, all other Tri-GP environmental and EMC
specifications remain unchanged.

CAUTION

Pin-Out Information
This table lists pin-out information for the SSR Input ETP.
Table 25

Pin-Out Information for the SSR Input ETP

Left
Power
Terminal

Right
Contact
Terminal

Point
1

Point
2

Point
3

Point
4

Point
5

Point
6

Point
7

Point
8

P+

C+

11

13

15

10

12

14

16

Right
Power
Terminal

Right
Contact
Terminal

Point
9

Point
10

Point
11

Point
12

Point
13

Point
14

Point
15

Point
16

P+

C+

11

13

15

10

12

14

16

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

115

DI Hazardous Location External Termination Panel


The Model 9573-610F ETP is suitable for use in Zone 2, and Class 1, Division 2 field circuits. The
ETP contains extra circuitry designed to limit power available to the field terminals. The circuits
have been examined and certified by TV Rhineland as being nonincendive. This guarantees
that if the field wires are accidentally opened, shorted, or grounded, and the Tri-GP is operating
normally, the wiring and attached devices will not release sufficient energy to cause ignition in
the specified flammable atmosphere.
Termination panel 9573-610F is compatible with Model 3301S2 and Model 3311S2 24 VDC
Digital Input Modules. Each panel has:

Two, sixteen-position field terminals; support for sixteen points

Two terminals per point, for dry contact (F+, F)

A four-position terminal for redundant 24 VDC loop power

Two, one-position terminals for protective earth connection

Each positive terminal is current-limited with a 200-to-300-ohm positive temperature coefficient


(PTC) resistor.
The panel supports redundant 24 VDC power sources with diode ORing. However,
recommended field power connections are on the DI External Termination Baseplate and
routed to the ETP through the interface cable with ELCO connectors. Field energy will not be
limited if it is connected to the ETP; it will be limited only if it is connected to the baseplate.
You must use two 16-point term panels for each 32-point DI module. Each term panel comes
with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.
Dimensions for Term Panel 9573-610F
Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.42 in (11.23 cm)

5.02 in (12.75 cm)

4.25 in (10.795 cm)

Specifications
This table describes general specifications for 9573-610F.
Table 26

General Specifications for Term Panel 9573-610F

Feature

Description

Panel type

Hazardous location, commoned 24 V

Points

16

Planning and Installation Guide for Triconex General Purpose v2 Systems

116

Chapter 2

System Description

This table describes cable and load parameters for 9573-610F.


Table 27

Cable and Load Parameters for Term Panel 9573-610F

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

19 to 28 V

Maximum voltage

Um

Um

32 V

Maximum input voltage

Ui

Vmax

32 V

Maximum input current

Ii

Imax

0.962 A

Maximum input power

Pi

Pi

0.03178 W

C internal, maximum

Ci

Ci

0.088 F

L internal, maximum

Li

Li

43 H

Input Connection (F) Specifications

Output Connection (F+) Specifications

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.160 A

Maximum output power

Po

Po

1.347 W

C external, maximum

Co

Ca

1.18 F

L external, maximum

Lo

La

4.95 mH

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Components

117

Simplified Schematic
This figure is a simplified schematic of the Model 9573-610F ETP and the Model 3301S2 or
3311S2 DI Module with a DI External Termination Baseplate.
ELCO
CABLE

TERMINATION PANEL

BASEPLATE

200300 Ohms

32-POINT DIGITAL INPUT MODULE

Mux

3 kilohms

1
32
30 V
Zener

to
other
points

to
spare

Mux
1

module

PS1

32

PS2
PS1
PS1
PS2

PS2

to
modules

Mux
1
32

0 ohm
PS1
0 ohm

Figure 53

PS2

Simplified Schematic of a 9573-610F Panel and a 3301S2 or 3311S2 DI Module with a DI


External Termination Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

118

Chapter 2

System Description

Typical Field Connections


This figure illustrates how to connect a 9573-610F to the field (1 of 16 module points shown).
TRICONEX

REV D

7400275

18

R25

SN

R5

R29

R4

R28

R3

R27

R2

 

TB1

 

R30

19
R
20
R
21
3
R
22
R
23

TB4

R7

!
R

24

R31

    
WHEN ENERGIZED

9
R
10
11
12
13
14
15

R32

R8





R8

R7

 

R5

R4

R3

R2

R1

SN

TB1

EXT TERM
  

 


7400275

17

12 AWG,
as short as possible

R1

EXT TERM
  " 

J1
TB2 TB3 TB5  

J2

J2






J3

J3

L-

P1

P2

L-

Second
term panel
Typical point
(1 of 32 points shown)
Note: Field power is routed from
the baseplate through the Elco cable
to the ETP. Do not connect field power
to the ETP.

Field
Contact

Energy limited

Figure 54

Not energy limited

Field Wiring for 9573-610F with a 3301S2 or 3311S2 DI Module

CAUTION

For more information about installing the Tri-GP in hazardous locations,


see Application-Specific Installation Guidelines on page 182.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

119

Digital Output Components


These Digital Output components are available with Tri-GP v2 systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Voltage

Type

3401S2

Digital Output Module

24 VDC

Commoned

3411S2

Digital Output Module, Supervised

24 VDC

Commoned

2401S2

Digital Output Baseplate

Direct Termination

2401HS2

Digital Output Baseplate

Direct Termination,
High Current Capable

2401LS2

Digital Output Baseplate

Direct Termination,
Current Limited

n/a

Digital Output External Termination


Baseplate

External Termination

2402S2

High-Voltage DO Baseplate Kit,


includes: Digital Output External
Termination Baseplate, Relay
Output External Termination Panel,
and 10 ft Interface Cable

9671-610

Digital Output Hazardous Location


External Termination Panel

Note

48 VDC, 120 VDC,


115 VAC, Dry Contact

External Termination,
Interposing Relays

External Termination

When ordering the High-Voltage DO Baseplate Kit, you can order interface cables in
increments of 10 feet by specifying part number 4000196-3xx, where xx equals the length
in feet. When ordering the 9671-610 ETP, you can order interface cables in increments of
10 feet by changing 9671-610 to 9671-6xx, where xx equals the length in feet. The
maximum length for interface cables is normally 100 feet. Contact the Invensys Global
Customer Support (GCS) center if you require cables longer than 100 feet.

Digital Output (DO) Modules contain the circuitry for three identical, isolated channels. Each
channel includes a proprietary ASIC which receives its output table from the I/O
Communication Processor on its corresponding Main Processor. DO Modules use the patented
Quad Voter output circuitry to vote on the individual output signals just before they are applied
to the load. This voter circuitry is based on parallel-series paths which pass power if the drivers
for channels A and C, or channels B and D (D channel is a combination of A or C) command
them to close; in other words, two out of three drivers are voted on. The quad output circuitry
provides multiple redundancy for all critical signal paths, guaranteeing safety and maximum
availability.
DO Modules periodically execute an output voter diagnostic (OVD) routine on each point. This
safety feature allows unrestricted operation under a variety of multiple-fault scenarios.
OVD detects and provides alarms for the following:

Points all stuck-On and stuck-Off points are detected

Planning and Installation Guide for Triconex General Purpose v2 Systems

120

Chapter 2

System Description

Switchesall stuck-On or stuck-Off switches or their associated drive circuitry are


detected

During OVD execution, the commanded state of each point is momentarily reversed
sequentially on one of the output drivers. Loop-back on the module allows each ASIC to read
the output value for the point to determine whether a latent fault exists within the output circuit.
The output signal transition is guaranteed to be less than two milliseconds and is transparent to
most field devices. For devices that cannot tolerate a signal transition of any length, OVD can be
disabled.
DO Modules include the hot-spare feature which allows online replacement of a faulty module.
DO Modules are mechanically keyed to prevent improper installation in a configured baseplate.

DO Module 3401S2
This figure is a simplified schematic of the Model 3401S2 DO Module, which is self-protected
against over-voltage and over-current conditions.
Triplicated
I/O Bus

I/O Controller(s)

Isolated
Bus
Transceiver

Field Circuitry Typical Point (16)


A
Output
Switch
Drive
Circuitry

+V
A

ASIC
A or C
Output
Switch
Drive
Circuitry

Isolated
Bus
Transceiver

ASIC

A
or
C

B
Output
Switch
Drive
Circuitry

Isolated
Bus
Transceiver

ASIC

C
Output
Switch
Drive
Circuitry

Load
A
B
C

Voltage
Loopback
Detector

To Other Points

Figure 55

3401S2 DO Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Return

Digital Output Components

121

This table lists specifications for the Model 3401S2 DO Module.


Table 28

3401S2 DO Module Specifications

Feature

Specification

Points

16, commoned

Nominal output voltage

24 VDC

Operational voltage range

1930 VDC

Absolute maximum output voltage

33 VDC

Absolute maximum reverse input


voltage

0.6 VDC

Output current
Switching

<4.8 A, self-limiting; 3 A, typical

Carry

700 mA maximum, self limiting

Field alarms

Loss of field power, output point shorted On or Off

Loop-back thresholds

05 VDC = Off region


614 VDC = transition region
1530 VDC = On region

Leakage to load (Off-state)

<1 mA

Diagnostic glitch duration

<2 ms, maximum; 500 s, typical

Diagnostic fault coverage


Maximum toggle rate

>20 ms

Minimum toggle rate

Not applicable

On-state voltage drop

<1 VDC @ 1.5 A

Loop-back scan time

<1 ms for all 16 points

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic)
isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

122

Chapter 2

System Description

DO Module 3411S2
This figure is a simplified schematic of the Model 3411S2 Supervised DO Module, which is selfprotected against over-voltage and over-current conditions.

I/O Controller(s)

Field Circuitry Typical Point (16)

Triplicated
I/O Bus

Isolated
Bus
Transceiver

Output
Switch
Drive
Circuitry
ASIC

Current
Sense
Circuitry
A

A or C
Output
Switch
Drive
Circuitry

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

A
or
C

B
Output
Switch
Drive
Circuitry

+V

C
Output
Switch
Drive
Circuitry

Load
A
B
C

Voltage
Loopback
Detector

Return

To Other Points

Figure 56

3411S2 Supervised DO Module Simplified Schematic

The Model 3411S2 DO Module is called supervised because fault detection includes potential
field problems such as:

Loss of power or blown fuse

Open or missing load

A field short resulting in the load being energized in error

A shorted load in the de-energized state

The module performs supervision of the field load health by using current measurement.
Current that is less than the minimum load (minus accuracy error) causes an open-load field
error and the load indicator to illuminate. The load indicator automatically clears once the field
error condition is removed.
Note that it can take up to three minutes for the Model 3411S2 DO Module to reach the Normal
State, which is indicated by steady green Pass and Active status indicators on the front panel of
the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

123

This table lists specifications for the Model 3411S2 DO Module.


Table 29

3411S2 DO Module Specifications

Feature

Specification

Points

16, commoned

Nominal output voltage

24 VDC

Operational voltage range

19.230 VDC

Absolute maximum output voltage

45 VDC

Absolute maximum reverse input


voltage

0.6 VDC

Minimum required field load

30 mA

Output current
Switching

<4.8 A, self-limiting; 3 A, typical

Carry

700 mA maximum, self limiting; (See Maximum Ambient


Temperature for 3411S2 Module with 2401HS2 Baseplate
on page 124 for extended carry current limits and
conditions.)

Field alarms

Loss of field power, output point shorted On or Off, Open


load

Loop-back thresholds

05 VDC = Off region


614 VDC = transition region
1530 VDC = On region

Leakage to load (Off-state)

<1 mA

Diagnostic glitch duration

<2 ms, maximum

Diagnostic fault coverage


Maximum toggle rate

>20 ms

Minimum toggle rate

Not applicable

On-state voltage drop

<1.6 VDC @ 1.6 A

Loop-back scan time

<8 ms for all 16 points

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic)
isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

124

Chapter 2

System Description

When using the Model 2401HS2 High-Current Baseplate with a Model 3411S2 DO Module, a
higher 1.6 A carry current is possible. Be careful not to exceed the recommended maximum
ambient temperatures, described in this table, as accuracy and component life will be degraded.
Table 30

Maximum Ambient Temperature for 3411S2 Module with 2401HS2 Baseplate

Number of points
@ 0.7 A

Number of points
@ 1.6 A

Maximum Ambient
Temperaturea

15

158 F (70 C)

14

158 F (70 C)

13

154.4 F (68 C)

12

150.8 F (66 C)

11

147.2 F (64 C)

10

143.6 F (62 C)

140 F (60 C)

138.2 F (59 C)

134.6 F (57 C)

10

131 F (55 C)

11

127.4 F (53 C)

12

123.8 F (51 C)

13

120.2 F (49 C)

14

116.6 F (47 C)

15

114.8 F (46 C)

16

111.2 F (44 C)

a. As measured at the bottom of the baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

125

DO Baseplate
This figure depicts the front view
of the Model 2401S2 DO
Baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

126

Chapter 2

System Description

This figure is a simplified schematic of the Model 3401S2 DO Module and Model 2401S2 DO
Baseplate.
DO Baseplate

16-Point DO Module

Field Power (PS1)


Field Power (PS2)
A
or
C
A

To
Other
Points

Load +
B

~
Load

~
Figure 57

Voltage
Loopback
Detector

Field Power (PS1)


Field Power (PS2)

3401S2 DO Module and 2401S2 DO Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

127

Typical Field Connections


This figure depicts typical field connections for the Model 2401S2 DO Baseplate.
+24V #1

+24V #2

RTN

Safety

Typical Point
(1 of 16 Points Shown)

1
1
2
3

~
~

5
6
7
8

~
~

Low
Power
Field
Load

9
10
11
12
13
14
15

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

16

~~~~
Figure 58

2401S2 DO Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

128

Chapter 2

System Description

DO High-Current Baseplate
This figure depicts the front view
of the Model 2401HS2 HighCurrent DO Baseplate, which is
recommended for use with highcurrent power loads.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

129

This figure is a simplified schematic of the Model 3411S2 DO Module and the Model 2401HS2
DO High-Current Baseplate.
16-Point DO Module

DO Baseplate

~
~

Current
Sense
Circuitry*

Field Power (PS1)


Field Power (PS2)

A
or
C

To
Other
Points

C
B

Load +

~
Load

Voltage
Loopback
Detector

Field Power (PS1)


Field Power (PS2)

*Only on the 3411S2 module

Figure 59

3411S2 DO Module and 2401HS2 DO High-Current Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

130

Chapter 2

System Description

Typical Field Connections


This figure depicts typical field connections for the Model 2401HS2 DO High-Current Baseplate.
+24V #1

+24V #2

RTN

Safety

Typical Point
(1 of 16 Points Shown)

1
1
2
3

~
~

5
6
7
8

~
~

Low
Power
Field
Load

9
10
11
12
13
14
15

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

16

~~~~
Figure 60

2401HS2 DO High-Current Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

131

DO Low-Current Baseplate
This figure depicts the front view
of the Model 2401LS2 DO LowCurrent Baseplate, which is
recommended for use only with
low-current power loads.

Planning and Installation Guide for Triconex General Purpose v2 Systems

132

Chapter 2

System Description

This figure is a simplified schematic of the Model 3401S2 DO Module and Model 2401LS2 DO
Low-Current Baseplate.
DO Baseplate

16-Point DO Module

Field Power (PS1)


Field Power (PS2)

A
or
C

To
Other
Points

180

Load +

Load
Voltage
Loopback
Detector

Figure 61

Field Power (PS1)


Field Power (PS2)

3401S2 DO Module and 2401LS2 DO Low-Current Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

133

Typical Field Connections


This figure depicts typical field connections for the Model 2401LS2 DO Low-Current Baseplate.
+24V #1

+24V #2

RTN

Safety

Typical Point
(1 of 16 Points Shown)

1
1
2
3

~
~

5
6
7
8

~
~

Low
Power
Field
Load

9
10
11
12
13
14
15

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

16

~~~~
Figure 62

2401LS2 DO Low-Current Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

134

Chapter 2

System Description

DO External Termination Baseplate


The DO External Termination Baseplate is used with the Relay Output External Termination
Panel (ETP) or the Model 9671-610 DO Hazardous Location ETP.
The baseplate contains ELCO connectors, which allows connection of External Termination
Panels.
This figure depicts a front view of the
Digital Output External Termination
Baseplate, which is available for use
with all Tri-GP systems.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

135

This figure is a simplified schematic of the Model 3401S2 or 3411S2 DO Module and the DO
External Termination Baseplate.
16-Point DO Module

DO External Termination Baseplate

~
~

Current
Sense
Circuitry*

Field Power (PS1)


Field Power (PS2)

A
or
C

V+

To External
Termination Panel

~
~

Voltage
Loopback
Detector

Field Power (PS1)


Field Power (PS2)

*Only on the 3411S2 module

Figure 63

3401S2 or 3411S2 DO Module and DO External Termination Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

136

Chapter 2

System Description

Typical Field Connections


This figure depicts typical field connections for the DO External Termination Baseplate.
+24 V #1

+24 V #2

24 V Return

Shield

Safety

S
F

~ ~~ ~ ~
Figure 64

DO External Termination Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

137

Relay Output External Termination Panel


The Relay Output External Termination Panel (ETP) includes industry-standard relays which
can be cabled to the DO External Termination Baseplate. The interposing relays are
manufactured by OMRON. Each relay output contact is protected with a 2.5 A fast-acting fuse
with a blown fuse indicator1 and a 200 V Transient Voltage suppressor.
The Relay Output ETP supports 16 points and each DO Baseplate supports one Relay Output
ETP.
The Relay Output ETP has a barrier strip with four compression screw terminals per point for
connecting a DO Module to 16 digital outputs. The Relay Output ETP accepts power (+24 VDC)
from the DO Baseplate. The 24-volt power source connected to the baseplate must be able to
provide 0.5 amps minimally.
This figure depicts a front view of the Relay Output ETP.
J1

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

MADE IN JA PAN

K16
F16

DSP15

R14

DSP16

R15

CR14

AC

LOAD

CR13

BOTTOM VIE W

K15
F15

DSP14

R13

MADE IN JA PAN

DSP13

BOTTOM VIE W

CR12

MADE IN JA PAN

AC

IN

AC

IN

AC

IN

REV B

R16

CR15

CR16

PWR

AC

IN

AC

IN

AC

IN

AC

IN

AC

IN

AC

IN

IN

AC

IN

LOAD

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

PWR

IN

AC

IN

AC

IN

AC

IN

AC

IN

OMRON

R12

BOTTOM VIE W

MADE IN JA PAN

DSP12

K14
F14

AC

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

K13
F13

OMRON

OMRON

BOTTOM VIE W

MADE IN JA PAN

BOTTOM VIE W

BOTTOM VIE W

MADE IN JA PAN

MADE IN JA PAN

R11

CR11

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

DSP11

R10

OMRON

OMRON

BOTTOM VIE W

K12
F12

CR9

CR8

Figure 65

MADE IN JA PAN

CR10

CR7

K11
F11

DSP10

R9

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

DSP9

R8

7400255

K10
F10

OMRON

OMRON

BOTTOM VIE W

DSP8

R7

CR6

K9
F9

F8
DSP7

R6

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

MADE IN JA PAN

K8

F7
DSP6

OMRON

BOTTOM VIE W

CR5

MADE IN JA PAN

R5

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

DSP5

CR4

BOTTOM VIE W

K7

F6

R4

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

BOTTOM VIE W

K6

F5

DSP4

MADE IN JA PAN

MADE IN JA PAN

K5

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

BOTTOM VIE W

CR3

MADE IN JA PAN

R3

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

CR2

OMRON

CR1

K4
F4

DSP3

R2

BOTTOM VIE W

K3
F3

DSP2

R1

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

BOTTOM VIE W

MADE IN JA PAN

MADE IN JA PAN

BOTTOM VIE W

MADE IN JA PAN

BOTTOM VIE W

K2
F2

DSP1

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

OMRON

OMRON

G3R-IAZR1SN
LOAD:0.1A
524VDC
INPU T:100240 VAC~

K1
F1

SN

Relay Output External Termination Panel

Dimensions for Relay Output Term Panel

1.

Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.23 in (10.74 cm)

12.54 in (31.85 cm)

4.25 in (10.795 cm)

When using AC, the blown fuse indicator will blink when a blown fuse is detected.

Planning and Installation Guide for Triconex General Purpose v2 Systems

138

Chapter 2

System Description

Table 31

General Specifications for Termination Panel 2402

Feature

Specification

Panel Type

Non-commoned interposing relay

Points

16

Contact Fuse Rating

2.5 A fast-acting

Max Applied Contact Voltage

200 VAC/VDC

WARNING

This fuse must not be replaced with a larger value.


Continued output current in excess of 2.5 A will cause a loss of power due to
the fuse opening.
Contact voltages above 200 V will cause a loss of power due to engagment of
safety devices. If current is not limited, physical damage to the ETP will occur.

This figure depicts a simplified schematic of the Model 3401S2 DO Module and the Relay
Output ETP.
16-Point DO Module

DO External Termination Panel Baseplate

Relay Output Termination Panel

~
~

Current
Sense
Circuitry

Field Power (PS1+)


Field Power (PS2+)
OMRON

A
or
C

PWR +
2.5A

C
LOAD +

~
~
Figure 66

Voltage
Loopback
Detector

Field Power (PS1)

LOAD

Field Power (PS2)

PWR

3401S2 DO Module and Relay Output ETP Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

AC
AC

IN

PWR

LOAD

AC

IN
AC

IN

AC

IN
AC

IN

AC

IN
AC

IN

AC

IN
AC

IN

AC

IN

AC

IN

AC

IN

AC

IN

AC

IN

AC

IN

LOAD

AC

IN

PWR

AC

LOAD

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

PWR

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN

AC

IN

AC

IN

BOTTOM VIEW

MADE IN JAPAN
AC

IN

AC

IN

BOTTOM VIEW

CR16
LOAD

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON
G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

PWR

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

SN

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON
G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

Relay Output ETP Typical DC Field Connections

Figure 68

REV B

7400255

CR15
CR14
CR13
CR12
CR11
CR10
CR7
CR6
CR5
CR4
CR3
CR1

DSP16
DSP15
DSP14
DSP13

R16
R15
R14
R13
R12
R11

DSP12
DSP11
DSP10
DSP9

R10
R9
R8
R7
R6

DSP8
DSP7
DSP6
DSP5
DSP4

R5
R4
R3
R2
R1

DSP3
DSP2
DSP1

SN

K16
K15
K14
K13

F16
F15
F14
F13
F12
F11
F10

K12
K11
K10
K9
K8
K7

F9
F8
F7
F6
F5
F4

CR9
CR8
CR2

Typical point
(1 of 16 points shown)
Hot

K6
K5
K4
K3
K2
K1

F3
F2
F1

Relay Output ETP Typical AC Field Connections


Figure 67

Typical point
(1 of 16 points shown)

Power
Supply

Neutral
Power
Supply

REV B

7400255

CR16
CR9
CR8
CR2

CR15
CR14
CR13
CR12
CR11
CR10
CR7
CR6
CR5
CR4
CR3
CR1

R16
R15
R14
R13

DSP16
DSP15
DSP14
DSP13
DSP12
DSP11
DSP10

R12
R11
R10
R9
R8
R7

DSP9
DSP8
DSP7
DSP6
DSP5
DSP4

R6
R5
R4
R3
R2
R1

DSP3
DSP2
DSP1

K16
K15
K14
K13

F16
F15
F14
F13
F12
F11
F10

K12
K11
K10
K9
K8
K7

F9
F8
F7
F6
F5
F4

K6
K5
K4
K3
K2
K1

F3
F2
F1

139
Digital Output Components

Typical Field Connections

These figures show typical connections to the Relay Output ETP, which is used with the Model
3401S2 DO Module and DO External Termination Baseplate.
This figure shows how to connect AC discreet outputs to the Relay Output ETP.
J1

Load

This figure shows how to connect DC discreet outputs to the Relay Output ETP.
J1

Load

Planning and Installation Guide for Triconex General Purpose v2 Systems

IN

IN

PWR

AC

LOAD

BOTTOM VIEW

MADE IN JAPAN

MADE IN JAPAN

AC

IN
BOTTOM VIEW

MADE IN JAPAN

AC

IN
BOTTOM VIEW

AC

IN
BOTTOM VIEW

MADE IN JAPAN

MADE IN JAPAN

AC

IN
BOTTOM VIEW

MADE IN JAPAN

AC

IN
BOTTOM VIEW

AC

IN
AC

IN
AC

IN
AC

IN

LOAD

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON
G3R-IAZR1SN
LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

MADE IN JAPAN

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

BOTTOM VIEW

MADE IN JAPAN

AC

IN
BOTTOM VIEW

AC

IN
BOTTOM VIEW

MADE IN JAPAN

MADE IN JAPAN

AC

IN
BOTTOM VIEW

MADE IN JAPAN

Planning and Installation Guide for Triconex General Purpose v2 Systems

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON
G3R-IAZR1SN

AC

IN

LOAD:0.1A
524VDC
INPUT:100240VAC~

BOTTOM VIEW

AC

IN
BOTTOM VIEW

MADE IN JAPAN

MADE IN JAPAN

AC

IN

BOTTOM VIEW

When switching reactive or DC loads, you should carefully observe the


maximum switching power specifications of the output contacts.

CAUTION

Typical point
(1 of 16 points shown)
C
C

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON

LOAD:0.1A
524VDC
INPUT:100240VAC~

G3R-IAZR1SN

OMRON
G3R-IAZR1SN

LOAD:0.1A
524VDC
INPUT:100240VAC~

Relay Output ETP Typical Dry Contact Field Connections


Figure 69

SN

CR16
CR9
CR8
CR2

CR15
CR14
CR13
CR12
CR11
CR10
CR7
CR6
CR5
CR4
CR3
CR1

DSP16
DSP15
DSP14
DSP13

R16
R15
R14
R13
R12
R11

DSP12
DSP11
DSP10
DSP9

R10
R9
R8
R7
R6

DSP8
DSP7
DSP6
DSP5
DSP4

R5
R4
R3
R2
R1

DSP3
DSP2
DSP1

K16
K15
K14

F16
F15
F14
F13
F12
F11

K13
K12
K11
K10
K9
K8

F10
F9
F8
F7
F6
F5

K7
K6
K5
K4
K3
K2
K1

F4
F3
F2
F1

REV B

7400255
PWR

System Description
Chapter 2
140

This figure shows how to connect points requiring a dry contact to the Relay Output ETP.
J1

When switching incandescent lamps, the inrush current can be 10 to 15


times the rated nominal load current of the lamp. Use the inrush
current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush
amplitude and duration.

IN

Digital Output Components

141

Interposing Relay Modules


This table gives the output ranges for available interposing relay modules. Relays must be
ordered separately and are available from Invensys or directly from OMRON. For more
information, contact the Invensys Global Customer Support (GCS) center.
For detailed specifications, see the OMRON G3R-I/O and G2R data sheets.
Table 32

Output Ranges for Interposing Relay Modulesa

Description

Invensys Part
Number

AC Solid State Relay


(SSR) Output Module

Max Inrush
Current

Rated Input

Applicable Output Load

1300462-001
(G3R-OA202SZN)

524 VDC

2 A at 75264 VAC

30 A, (60 Hz,
1 cycle)

DC SSR Output Module

1300471-001
(G3R-ODX02SN)

524 VDC

2 A at 460 VDC

8 A, 10 msec

DC SSR Output Module

1300472-001
(G3R-OD201SN)

524 VDC

1.5 A at 40200 VDC

8 A, 10 msec

a. Relay output contact ratings may be higher than module protection specification.

CAUTION

Table 33

When using the AC SSR Output Module, Invensys recommends disabling


the Output Voter Diagnostics (OVD) of the Model 3401S2 DO Module.
When de-energized, the normal execution of the OVD can glitch the AC
SSR output on for up to half of a cycle. For details, see Enabling
Disabled Output Voter Diagnostics on page 205.

Output Ranges for Power (Dry Contact) Relaysa

Description

Invensys
Part Number

Input Range
Logic Supply

Max
Switching
Voltage

Rated
Carry
Current

Power
(Dry Contact)
Relay

1300463-001
(G2R-1-SNDC24(S))

1726 VDC,
21.6 mA max

440 VAC,
125 VDC

10 A

Max
Switching
Capacity Resistive

Max
Switching
Capacity Inductive

2500 VA,
300 W

1875 VA,
150 W

a. Relay output contact ratings may be higher than module protection specification.

CAUTION

The OMRON family of output relays are limited to an ambient humidity


range of 45% to 85%, all other Tri-GP environmental and EMC
specifications remain unchanged.

Planning and Installation Guide for Triconex General Purpose v2 Systems

142

Chapter 2

System Description

Pin-Out Information
This table lists pin-out information for the Relay Output ETP.
Table 34

Pin-Out Information for Relay Output ETP

Left
Power
Terminal

Left Load
Terminal

Point
1

Point
2

Point
3

Point
4

Point
5

Point
6

Point
7

Point
8

P+

C+

11

13

15

10

12

14

16

Right
Power
Terminal

Right
Load
Terminal

Point
9

Point
10

Point
11

Point
12

Point
13

Point
14

Point
15

Point
16

P+

C+

11

13

15

10

12

14

16

DO Hazardous Location External Termination Panel


Termination panel 9671-610 is compatible with the Model 3401S2 and Model 3411S2 24 VDC
commoned digital output modules. Each panel has:

Two, sixteen-position field terminals; support for 16 points

Two terminals per point, (L+, L)

A four-position terminal for redundant 24 VDC loop power

Two, one-position terminals for protective earth connection

The panel supports redundant 24 VDC power sources with diode ORing. However,
recommended field power connections are on the DO External Termination Baseplate and
routed to the ETP through the interface cable with ELCO connectors.
Dimensions for Term Panel 9671-610
Width (across DIN rail)

Length (along DIN rail)

Height (out from DIN rail)

4.42 in (11.23 cm)

5.02 in (12.75 cm)

4.25 in (10.795 cm)

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

143

Specifications
This table describes general specifications for 9671-610.
Table 35

General Specifications for Term Panel 9671-610

Feature

Description

Panel type

Hazardous location, commoned, supervised

Points

16

This table describes cable and load parameters for 9671-610.


Table 36

Cable and Load Parameters for Term Panel 9671-610

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

1628 VDC

Maximum voltage

Um

Um

32 V

Output Connection (F+) Specifications

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.160 A

Maximum output power

Po

Po

1.347 W

C external, maximum

Co

Ca

1.18 F

L external, maximum

Lo

La

4.95 mH

Planning and Installation Guide for Triconex General Purpose v2 Systems

144

Chapter 2

System Description

Simplified Schematic
This figure is a simplified schematic of the Model 9671-610 ETP and the Model 3401S2 or 3411S2
DO Module with a DO External Termination Baseplate.
16-POINT DIGITAL OUTPUT MODULE

BASEPLATE

ELCO
CABLE

TERMINATION PANEL

~
Current
Sense
Circuitry*
A
PS1 +

Output
Switch
Drive
Circuitry

PS2 +
A

to other
points

L+
190310 Ohms

A "B

Output
Switch
Drive
Circuitry

L
PS1

to
hot
spare

Output
Switch
Drive
Circuitry
C

to other
points

PS2

Output
Switch
Drive
Circuitry

A
B
C

Voltage
Loopback
Detector

*Only on the 3411S2 module

Figure 70

Simplified Schematic of a 9671-610 Panel and a 3401S2 or 3411S2 DO Module with a DO


External Termination Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Components

145

Typical Connections
This figure illustrates how to connect a 9671-610 to the field (16 of 16 points shown).

TRICONEX

J1

7400274
REV C

TB2


!
15

DO NOT REMOVE FUSE WHEN ENERGIZED


12

13

11

10



TB5

TB4

14

EXT TERM ATEX/EMC


COMMONED DO ETP

TB1
TB3

DO NOT SEPARATE WHEN ENERGIZED

SN

 


J2
P1

Load

L-

P2

J3

Note: Field power is routed from


the baseplate through the Elco cable
to the ETP. Do not connect field power
to the ETP.

Not energy limited

Energy limited

* A load must be installed at every point to prevent missing-load alarm.


If a field load is not available, install a 470 Ohm, 10 W load resistor.

Figure 71

Field Wiring for 9671-610 with a 3401S2 or 3411S2 DO Module

CAUTION

For more information about installing the Tri-GP in hazardous locations,


see Application-Specific Installation Guidelines on page 182.

Planning and Installation Guide for Triconex General Purpose v2 Systems

146

Chapter 2

System Description

Pulse Input Components


These Pulse Input components are available with Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Frequency Range

Type

3382S2

Pulse Input Module, Enhanced

0.5 Hz32 kHz

Commoned

2381S2

Pulse Input Baseplate

Direct Termination

2381AS2

Pulse Input Hazardous


Location Baseplate

Direct Termination

Pulse Input (PI) Modules provide six very sensitive, high-frequency inputs. The inputs can be
individually configured for non-amplified and amplified magnetic speed sensors common on
rotating equipment, such as turbines or compressors. PI Modules sense voltage transitions from
the speed sensors. Every input transition is sampled, and time is measured for an optimized
number of input gear pulses. The resulting count and time are used to generate a frequency
(revolutions per minute), which is transmitted to the Main Processors.
The type of speed sensor typically used with PI Modules consists of an inductive coil and
rotating teeth. The sensor is physically close to the teeth of a gear on the rotating shaft. As the
shaft rotates and the teeth move past the sensor, the resulting change in the magnetic field
causes a sinusoidal signal to be induced in the sensor.
The magnitude of the output voltage depends on:

How fast the teeth pass the sensor

The distance between the sensor and the teeth

The construction of the sensor

A typical gear has 30 to 120 teeth spaced at equal distances around its perimeter. The output
frequency is proportional to the rotational speed of the shaft and the number of teeth.

CAUTION

A PI Module uses fully differential, input-signal-conditioning circuitry


which is AC-coupled and has high bandwidth. The circuitry is designed
for high-frequency operation with de-bounced edge detection, but is still
sensitive to any type of waveform distortion that could result in
erroneous measurements. The module counts transitions by examining
one edge of each pulse, consequently, ringing on the input signal can
result in many additional transitions being counted. The module is
capable of counting over 32,000 transitions per second.

PI Modules have three independent input channels. Each input channel:

Receives pulse input voltages from each point

Converts the values to frequency (RPM) data

Transmits the values to the MPs on demand

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

147

To ensure correct data for each scan, one value is selected using a mid-value selection algorithm.
Sensing of each input point is designed to prevent a single failure on one channel from affecting
another channel.
For critical control programs, we recommend using redundant sensors.
PI Modules sustain complete, on-going diagnostics for each channel. If the diagnostics detect a
failure on any channel, the Fault indicator is activated, which in turn activates the system alarm.
The Fault indicator points to a channel fault, not a complete module failure. PI Modules are
guaranteed to operate properly in the presence of a single fault and may continue to operate
properly with multiple faults.
PI Modules support hot sparing for online replacement of a faulty module or continuous backup to an active module. PI Modules are mechanically keyed to prevent improper installation in
a configured baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

148

Chapter 2

System Description

PI Module 3382S2
This figure is a simplified schematic of the Model 3382S2 PI Module.
Triplicated
I/O Bus

PI Module Typical Point (1 of 6)

+
Isolation
Filtering

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

Individual Point
Field Terminations

Isolation
Filtering

Isolation
Filtering

Isolation
Filtering

Isolation
Filtering

Isolation
Filtering

Figure 72

3382S2 PI Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

149

This table lists specifications for the Model 3382S2 PI Module.


Table 37

3382S2 PI Module Specifications

Feature

Specification

Points

Input type

Differential, channel-isolated
Single-ended, commoned ground

Sensor compatibility

Magnetic, active, open collector

Maximum operating voltage

33 VDC

Minimum operating voltage


Differential

500 mV P-P, 2 Hz32,000 Hz


1 V P-P, 0.5 Hz2 Hz

Single-ended

1V P-P, 2 Hz32,000 Hz
2V P-P, 0.5 Hz2 Hz

Input frequency range

0.5 Hz32 kHz

Duty cycle

20% to 80%, or 10 sec minimum pulse width


(positive and negative)

Absolute error of input frequencya

0.01%, 2,00032,000 Hz
0.1%, 0.52,000 Hz

Maximum acceleration rate

4,000 Hz/sec

Absolute error of acceleration (Hz/sec)a

< 0.01 times the numeric value of the input


frequency when the frequency range is 3kHz32
kHz

Maximum jerk rate

500,000 Hz/sec2

Absolute error of jerk (Hz/sec2)a

< 2.5 times the numeric value of the input frequency


when the frequency range is 3 kHz32 kHz

Programmable number of gear teeth (G) per


point

1255b

Termination resistor

Baseplate configurable

Pull-up resistor

Baseplate configurable

Measurement algorithm

Gear multiple tracking

Diagnostic

Precision frequency reference test

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to -functional-earth (logic) isolation

800 VDC, minimum

a. Absolute error of speed, acceleration, and jerk, does not include error introduced by the field device.
The reporting of speed acceleration and jerk is susceptible to noise and inaccuracies in the gear
manufacturing (tooth-tooth spacing).
b. Absolute error of acceleration and jerk may exceed the specified values if the number of gear teeth per
point G is not within the range of 255 > n*G >= 240, where n is an integer.

Planning and Installation Guide for Triconex General Purpose v2 Systems

150

Chapter 2

System Description

The Model 3382S2 PI Module is compatible with Tri-GP v2.1 and later systems. For more
compatibility information, see the Product Release Notice for Tri-GP v2.x, available on the
Invensys Global Customer Support (GCS) website.
The Model 3382S2 PI Module measures speed, angular acceleration (rate of speed change), and
jerk rate (rate of acceleration change). The speed is reported to the control program in
revolutions per minute (RPM). Acceleration is reported in RPM/second and Jerk is reported as
RPM/second2.
The absolute error of the acceleration measurement is less than 0.01 times the numeric value of
the input frequency, with a frequency greater than 3000 Hz.
The absolute error of the jerk measurement is less than 2.5 times the numeric value of the input
frequency, with a frequency greater than 3000 Hz.
Note

To meet the specifications for absolute error of acceleration and absolute error of jerk,
the number of gear teeth per point must be a number that when multiplied by an integer
is greater than or equal to 240 and less than 255.
A formulaic expression of this is:

240 n G < 255


Where:
- n must be an integer
- G equals the number of gear teeth
Absolute error of acceleration and absolute error of jerk may exceed the specified value
if the number of gear teeth is not within this range.
Examples
Gear:120
Input Frequency:3,000 Hz
Frequency Error Calculations
Input frequency:3,000 Hz
Absolute error of Acceleration:[0.01 * (3,000 Hz)]/sec = 30 Hz/sec
Absolute error of Jerk:[2.5 * (3,000 Hz)]/sec2 = 7,500 Hz/sec2
RPM Error Calculations
RPM:(3,000 Hz * 60 sec/min)/Gear = 1,500 RPM
Absolute error of Acceleration:[0.01 * (1,5000 RPM)]/sec = 15 RPM/sec
Absolute error of Jerk:[2.5 * (1,500 RPM)]/sec2 = 3,750 RPM/sec2
It can take up to three minutes for the Model 3382S2 PI Module to reach the Pass State, upon
initial power-up, which is indicated by steady, green Pass status indicator on the front panel of
the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

151

PI Baseplate
This figure depicts a front view of the Model
2381S2 PI Baseplate.
The short circuit current specifications for
field short-to-ground faults are:

130 mA, typical

200 mA, maximum

Planning and Installation Guide for Triconex General Purpose v2 Systems

152

Chapter 2

System Description

This figure is a simplified schematic of the Model 3382S2 PI Module and Model 2381S2 PI
Baseplate.
PI Baseplate

6-Point PI Module

Field Power (PS1) +


Field Power (PS2) +
J29
J24
V+

J23
1

1
499

R+

Blown
Fuse
Indicator
Comparator
1

FE

To
Spare

IN+

Comparator
4

IN-

4
5

FE

4
Shield

Comparator

499

1
6

Field Power (PS1)


Field Power (PS2)

Figure 73

To
Other
Points

3382S2 PI Module and 2381S2 PI Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

153

Typical Field Connections


This figure depicts typical field connections for the Model 2381S2 PI Baseplate.
Note

Unused points must be terminated.


+24 V #1

+24 V #2
24 V Return

Safety

1
1
2
3
4
5
6
7

J23
Configuration Block

8
9
10
11
12

J24
Sensor Block

13
14
15
16

17
18
19
20
21

J26
Configuration Block

22
23
24
25

J25
Sensor Block

26
27
28
29
30
31
32

Figure 74

3
4

J29
Resistor Block

10

11

12

10

13

11

14

12

15
16

17
18
19

13

20

14

21

15

22

16

23

17

24

18

25

19

26

20

27

21

28

22

29

23

30

24

31
32

J30
Resistor Block

~~~~

2381S2 PI Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

154

Chapter 2

System Description

Connecting an Unused Point


This figure depicts a typical connection for point 2.
J23

J24
1

3
4
5
6
7
8
9
10
11
12
13
14
15
16

6
7

10

11

12

10

13

11

14
15
16

Figure 75

12

J29

2381S2 PI Baseplate Unused Point Connection

Connecting a Passive Magnetic Sensor


This figure depicts a typical connection for point 3.
J23
1
2
3
4
5
6
7
8
9
10

Passive
Magnetic
Sensor

11

In+
In
Shield

12
13
14
15

J24
1
2
3
4

6
7

10

11

12

10

13

11

14
15
16

12

Optional
Termination
Resistor

J29

16

Figure 76

2381S2 PI Baseplate Passive Magnetic Sensor Connection

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

155

Connecting an Active Open-Collector Sensor with an Internal Resistor


This figure depicts a typical connection for point 4.
Active
OpenCollector
Sensor

J26
V+
In+
In
Shield

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Figure 77

J25
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

13
14
15

Internal
Pull-Up
Resistor
Jumper

16
17
18
19
20
21
22
23
24

J30

32

2381S2 PI Baseplate Active Open-Collector Sensor with an Internal Resistor Connection

Connecting an Active Open-Collector Sensor with an External Resistor


This figure depicts a typical connection for point 5.
J26
17
18
19
20

Active
OpenCollector
Sensor

21

V+
In+
In
Shield

22
23
24
25
26
27
28
29
30
31
32

Figure 78

J25
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

13
14
15
16
17
18
19
20

External
Pull-Up
Resistor

21
22
23
24

J30

2381S2 PI Baseplate Active Open-Collector Sensor with an External Resistor Connection

Planning and Installation Guide for Triconex General Purpose v2 Systems

156

Chapter 2

System Description

Connecting an Active Sensor


This figure depicts a typical connection for point 6.
J26
17
18
19
20
21
22
23
24
25
26
27

V+
In+
In
Shield

Active
Sensor

28
29
30
31
32

Figure 79

J25
17
18
19

13

20

14

21

15

22

16

23

17

24

18

25

19

26

20

27

21

28

22

29

23

30

24

31
32

J30

2381S2 PI Baseplate Active Sensor Connection

Terminal Blocks
The Model 2381S2 PI Baseplate has three types of terminal blocks: configuration, sensor, and
resistor.

The configuration block is used to select passive or active magnetic sensors and to
select an internal pull-up resistor when using an active open-collector sensor.

The sensor block is used to connect sensors to the baseplate.

The resistor block is used to attach a user-supplied termination resistor for passive
sensors, or a user-supplied pull-up resistor for an active open-collector sensor.

The Model 2381S2 PI Baseplate is factory-configured with the configuration blocks set to
differential mode for each point. The sensory blocks are configured to no points (spare) with the
inputs shorted together. When a point is selected for use, the installed jumpers should be moved
or removed as appropriate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

157

Model 2381S2 PI Baseplate Terminal Block Pin-Out Information


This table contains pin-out information for the Model 2381S2 PI Baseplate terminal block.
Configuration
J23/J26 Signal

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

V+

12

17

22

28

R+

13

18

23

29

FE

14

19

24

30

IN1

15

20

25

31

FE

10

16

21

26

32

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

V+

13

17

23

29

IN+

14

18

24

30

IN

15

19

25

31

Shield

10

16

20

26

32

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

V+

13

17

22

IN+

10

14

18

23

IN+

11

15

19

24

IN

12

16

20

25

Sensor
J24/J25 Signal

Resistor
J29/J30 Signal

Planning and Installation Guide for Triconex General Purpose v2 Systems

158

Chapter 2

System Description

PI Hazardous Location Baseplate


This figure depicts a front view of the Model
2381AS2 PI Hazardous Location Baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

159

This figure is a simplified schematic of the Model 3382S2 PI Module and the Model 2381AS2 PI
Hazardous Location Baseplate.
PI Hazardous Location Baseplate

6-Point PI Module
Module Field Power

Field Power (PS1) +


Field Power (PS2) +
J29

J24

J23
1

499 :

R+

Comparator
1

FE

To
Spare

IN+
2

Comparator
4

IN-

4
5

FE

4
Shield

Comparator

499 :

1
6

Field Power (PS1)


Field Power (PS2)

Figure 80

To
Other
Points

3382S2 PI Module and 2381AS2 PI Hazardous Location Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

160

Chapter 2

System Description

This table describes cable and load parameters for the Model 2381AS2 PI Hazardous Location
Baseplate.
Table 38

Cable and Load Parameters for Baseplate 2381AS2

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

4 F to 158 F (20 C to 70 C)

Working voltage

Uw

Uw

19 to 28 V

Maximum voltage

Um

Um

32 V

Input Connection (In+ In) Specifications

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

2.13 mA

Maximum output power

Po

Po

0.068 W

C external, maximum

Co

Ca

550 nF

L external, maximum

Lo

La

0.99 mH

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

161

Typical Field Connections


This figure depicts typical field connections for the Model 2381AS2 Hazardous Location PI
Baseplate.
Note

Unused points must be terminated.


+24 V #1

+24 V #2
24 V Return

Safety

1
2
3
4
5
6
7

J23
Configuration Block

8
9
10
11
12

J24
Sensor Block

13
14
15

1
2
3
4

J29
Resistor Block

10

11

12

10

13

11

14

12

15
16

16

17
18
19
20
21

J26
Configuration Block

22
23
24
25

J25
Sensor Block

26
27
28
29
30
31
32

Figure 81

18
19

13

20

14

21

15

22

16

23

17

24

18

25

19

26

20

27

21

28

22

29

23

30

24

31
32

J30
Resistor Block

~~~~

17

2381AS2 PI Hazardous Location Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

162

Chapter 2

System Description

Connecting an Unused Point


This figure depicts a typical connection for point 2.
J23

J24
1

3
4
5
6
7
8
9
10
11
12
13
14
15
16

6
7

10

11

12

10

13

11

14
15
16

Figure 82

12

J29

2381AS2 Hazardous Location PI Baseplate Unused Point Connection

Connecting a Passive Magnetic Sensor


This figure depicts a typical connection for point 3.
J23
1
2
3
4
5
6
7
8
9
10

Passive
Magnetic
Sensor

11

In+
In
Shield

12
13
14
15
16

Figure 83

J24
1
2
3
4

6
7

10

11

12

10

13

11

14
15
16

12

Optional
Termination
Resistor

J29

2381AS2 Hazardous Location PI Baseplate Passive Magnetic Sensor Connection

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Components

163

Terminal Blocks
The Model 2381AS2 Hazardous Location PI Baseplate has three types of terminal blocks:
configuration, sensor, and resistor.

The configuration block is used to select passive or active magnetic sensors and to
select an internal pull-up resistor when using an active open-collector sensor.

The sensor block is used to connect sensors to the baseplate.

The resistor block is used to attach a user-supplied termination resistor for passive
sensors, or a user-supplied pull-up resistor for an active open-collector sensor.

The Model 2381AS2 Hazardous Location PI Baseplate is factory-configured with the


configuration blocks set to differential mode for each point. The sensory blocks are configured
to no points (spare) with the inputs shorted together. When a point is selected for use, the
installed jumpers should be moved or removed as appropriate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

164

Chapter 2

System Description

Model 2381AS2 Hazardous Location PI Baseplate Terminal Block Pin-Out


Information
This table contains pin-out information for the Model 2381AS2 Hazardous Location PI
Baseplate terminal block.
Configuration
J23/J26 Signal

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

R+

13

18

23

29

FE

14

19

24

30

IN1

15

20

25

31

FE

10

16

21

26

32

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

IN+

14

18

24

30

IN

15

19

25

31

Shield

10

16

20

26

32

Point 1

Point 2

Point 3

Point 4

Point 5

Point 6

IN+

10

14

18

23

IN+

11

15

19

24

IN

12

16

20

25

Sensor
J24/J25 Signal

Resistor
J29/J30 Signal

Planning and Installation Guide for Triconex General Purpose v2 Systems

Solid-State Relay Output Components

165

Solid-State Relay Output Components


These Solid-State Relay Output components are available with Tri-GP v2.x systems.
For installation procedures, see Component Installation on page 185.
Model

Description

Voltage

Type

3451S2

Solid-State Relay Output Module

24 VDC

Commoned, in groups of 2

2451S2

Solid-State Relay Output Baseplate

Direct Termination

The Solid-State Relay Output (SRO) Module is a non-triplicated module for use on non-critical
points which are not compatible with high-side, solid-state output switches; for example,
interfacing with annunciator panels. The SRO Module receives output signals from the Main
Processors on each of three channels. The three sets of signals are then voted, and the voted data
is used to drive the 32 individual relays. Each output has an I/O loop-back circuit which verifies
the operation of each relay switch independently of the presence of a load. Ongoing diagnostics
test the operational status of the SRO Module.
The SRO Module supports hot sparing for online replacement of a faulty module or continuous
back-up to an active module. The SRO Module is mechanically keyed to prevent improper
installation in a configured baseplate.

SRO Module Schematic


This figure is a simplified schematic of the Model 3451S2 SRO Module.
Triplicated
I/O Bus

I/O Controller(s)

Field Circuitry Typical Point (2 of 32)

C1
A

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

Isolated
Bus
Transceiver

ASIC

ASIC

Com

C2

Figure 84

3451S2 SRO Module Simplified Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

166

Chapter 2

System Description

This table lists specifications for the Model 3451S2 SRO Module.
Table 39

3451S2 SRO Module Specifications

Feature

Specification

Points

32, commoned in pairs

Nominal input voltage

24 V

Operational voltage range

30 V

Maximum switching voltage

33 V peak

Maximum switching power

15 W resistive

Maximum off-state leakage

<100 A

Maximum nominal current

0.5 A per channel

Maximum over current

0.7 A per channel

Voltage drop at baseplate

<0.25 V @ 0.5 A

Fuses, mounted on baseplate

1 per output, 0.75 A, fast-acting

Functional-to-protective-earth isolation

500 VDC, minimum

Functional-to-functional-earth (logic) isolation

800 VDC, minimum

Planning and Installation Guide for Triconex General Purpose v2 Systems

Solid-State Relay Output Components

167

SRO Baseplate
This figure depicts a front view of the
Model 2451S2 SRO Module Baseplate.

Planning and Installation Guide for Triconex General Purpose v2 Systems

168

Chapter 2

System Description

This figure is a simplified schematic of the Model 3451S2 SRO Module and Model 2451S2 SRO
Baseplate.
32-Point RO Module

RO Baseplate
Blown
Fuse
Indicator

C1
Fuse
750 mA
Com
Blown
Fuse
Indicator

C2
Fuse
750 mA

Figure 85

3451S2 SRO Module and 2451S2 SRO Baseplate Schematic

Planning and Installation Guide for Triconex General Purpose v2 Systems

Solid-State Relay Output Components

169

Typical Field Connections


This figure depicts typical field connections for the Model 2451S2 SRO Baseplate.
Note

Points on left terminal blocks are commoned together in pairs; for example, 1-2 and 3-4.

Safety

DC Power
Supply

1
2
3
4
5

Field
Load 2

Field
Load 1

6
7
8
9
10

DC Power
Supply

11

12
13

14
15
16

Field
Load 2

Field
Load 1

17
18
19
20

AC Power
Supply

AC Power
Supply

Field Load 1

22
23

21

Field Load
2
Field Load 1

24
25
26
27
28
29

30

Field Load
2

31
32

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

~
Figure 86

2451S2 SRO Baseplate Typical Field Connections

Planning and Installation Guide for Triconex General Purpose v2 Systems

170

Chapter 2

System Description

Interconnect Assemblies
These interconnect assemblies are available.
Model

Description

2920

MP Interconnect Assembly

2921

I/O Interconnect Assembly

Interconnect Assemblies consist of a passive PCB in a molded plastic housing with two DIN-C
96-pin male connectors which enables I/O messages, logic power, and system power to be
carried from one baseplate to the next. For connections between I/O Baseplates, the I/O
Interconnect Assembly is used. For connections between an MP Baseplate and either an I/O or
CM Baseplate, the MP Interconnect Assembly is used which also carries communication
messages between the CM and MP Baseplates.

Each MP Baseplate assembly includes one MP Interconnect Assembly.

Each I/O Baseplate assembly includes one I/O Interconnect Assembly.

For installation procedures, see Connecting Columns with I/O Extender Modules on page 192.

I/O Interconnect Assembly

Figure 87

MP Interconnect Assembly

2920 MP Interconnect Assembly and 2921 I/O Interconnect Assembly

Planning and Installation Guide for Triconex General Purpose v2 Systems

I/O Extender Modules

171

I/O Extender Modules


These I/O Extender Modules Kits are available with Tri-GP v2.x systems.
Model

Description

2281

I/O Extender Module Kit (without termination)

2291

I/O Extender Module Kit for I/O Baseplate (with termination)

2292

I/O Extender Module Kit for MP Baseplate (with termination)

I/O Extender Modules are used to extend the I/O bus from one column to another, provide I/O
bus termination, provide additional input terminals for I/O module logic power, and provide
a protective earth (safety ground) connection. For installation procedures, see Connecting
Columns with I/O Extender Modules on page 192.

Figure 88

I/O Extender Module

An I/O Extender Module includes three DB-9-pin I/O bus connectors, two 24-volt logic power
input terminal blocks, each with fuse and blown-fuse indicators, and one protective earth
terminal block. This table identifies specifications for the logic power.
Table 40

Logic Power Specifications for I/O Extender Modules

Feature

Specification

Logic power

125 W maximum

Fuse

8 A, slow-acting

Blown fuse indicator

20 mA

Planning and Installation Guide for Triconex General Purpose v2 Systems

172

Chapter 2

System Description

I/O Bus Cables


An I/O Bus Cable set includes three I/O bus extension cables, which can be from 2 feet
(.6 meters) to 650 feet (200 meters) in length. The terminators should be installed on the open
I/O bus connectors on the I/O Extender Modules at each end of the I/O bus.
For distances greater than 650 feet (200 meters) or for applications requiring isolation, fiberoptic transceivers are commercially available. For compatible units and supported distances,
contact the Invensys Global Customer Support (GCS) center.

I/O Bus Terminators


I/O Bus Terminators plug into the open connectors on I/O Extender Modules and provide a
known electrical load. The terminators consist of male 9-pin D connectors with two 120-ohm
resistors mounted in the boot (or shell) of the connector.
To maintain acceptable signal integrity when the I/O bus exceeds 20 feet (6 meters), you must
install terminators on both ends of the I/O bus. Invensys part number 3900064-003 is a set of
three terminators.
If your I/O bus length is less then 20 feet (6 meters), no terminators are required.

Figure 89

I/O Bus Terminator

Planning and Installation Guide for Triconex General Purpose v2 Systems

End Caps

173

End Caps
These End Caps are available.
Model

Description

2910

I/O Baseplate/I/O Extender Module Top

2911

I/O Baseplate/I/O Extender Module Bottom

2912

MP Baseplate Top

2913

MP Baseplate Bottom

End Caps are used to protect the top and bottom of each end-of-column baseplate, cover the
Interconnect Assembly, and serve as a baseplate guide.

MP Baseplate End Caps


This figure depicts the MP Baseplate top and bottom end caps.

Bottom End Cap

Top End Cap

Figure 90

MP Baseplate End Caps

I/O Baseplate and I/O Extender Module End Caps


This figure depicts the I/O Baseplate and I/O Extender Module top and bottom End Caps.

Top End Cap

Figure 91

Bottom End Cap

I/O Baseplate and I/O Extender Module End Caps

Planning and Installation Guide for Triconex General Purpose v2 Systems

174

Chapter 2

System Description

Covers
These covers are available.
Model

Description

2900

Slot Cover

2911

Terminal Cover

Covers minimize exposure to dust, dripping and splashing liquids, and corrosive atmospheres.
One Slot Cover and one Terminal Cover are included with each I/O Baseplate.

Slot Cover

Figure 92

Terminal Cover

Slot Cover and Terminal Cover

Planning and Installation Guide for Triconex General Purpose v2 Systems

3
Installation and Maintenance

System Configuration 176


Installation Guidelines 179
Component Installation 185
Controller Grounding 198
Implementation and Maintenance 204
Module Replacement 207

Planning and Installation Guide for Triconex General Purpose v2 Systems

176

Chapter 3

Installation and Maintenance

System Configuration
This section includes configuration information and guidelines for a Tri-GP system.
Topics include:

System Specifications on page 176

Determining Logic Power on page 177

General Cooling Guidelines on page 177

Determining Cooling Requirements on page 177

System Specifications
This table includes specifications for determining the number and types of components that can
be installed in a Tri-GP v2.x system.
Table 41

Tri-GP v2.x System Specifications

Component

Quantity

I/O baseplates, maximum

25 (requires TriStation 1131 v4.5


software or later)

Number of baseplates on column, maximum

Length of I/O bus, maximum

650 feet (200 meters)

Communication components, maximum

1 CM baseplate and 2 CMs

Analog Input points, maximum

416 (13 AI baseplates, 13 AI/DI


baseplates, or any combination that does
not exceed 416 total AI or AI/DI points)

Analog Output points, maximum

20 (5 baseplates)

Digital Input points, maximum

640 (20 DI baseplates, 13 AI/DI


baseplates, or any combination that does
not exceed 640 total DI points)

Digital Output points, maximum

320 (20 baseplates)

Pulse Input points, maximum

30 (5 baseplates)

Solid-State Relay Output points, maximum

640 (20 baseplates)

Interconnect Assemblies, maximum

32

Planning and Installation Guide for Triconex General Purpose v2 Systems

System Configuration

177

Determining Logic Power


Logic power refers to the maximum power needed to power all the modules in the system. This
calculation is based on the assumption that only one of the redundant power sources is
operational. Under normal operating conditions, both power sources share the load.
This table can be used as a worksheet to determine the maximum logic power needed. To do so:

Enter the number of Communication Modules and I/O modules, including hot-spare
modules.

Multiply the number of modules by the maximum logic power for the type.

Add the logic power by type to get the total power requirement for the system.
Maximum Logic
Power (Watts)a

Module
Main Processor

Communicationb

All I/O Modules including hotspare modules

Number of
Modules

Logic Power
by Type

24

Total Power Requirement


a. To convert watts to British thermal units: BTU = watts x 3.414.
b. Without MAU connections.

General Cooling Guidelines


Adequate convection or forced-air cooling should be provided. These general guidelines can be
used for typical environments where the maximum ambient temperature is 120 F (50 C) with
20 C internal temperature rise.

In sealed environments, the external surface area of the enclosure should be at least
0.009 m2/watt.

In vented environments, the internal air flow should be at least 7 m3/watt. Air flow
should be directed to flow into vents at the bottom of the enclosure (for example, a vent
at the bottom of the door) and to exit at the top of the enclosure (for example, a pagoda
top).

For maximum reliability of the system, the average ambient temperature should be
below 120 F (50 C).

Determining Cooling Requirements


This table can be used to determine the total heat dissipation, which is the total logic and field
power used by the modules in the system. To do so:

Multiply the number of modules (primary and hot-spares) by the maximum logic
power to get the logic power by module type.

Planning and Installation Guide for Triconex General Purpose v2 Systems

178

Chapter 3

Installation and Maintenance

Multiply the number of modules by the maximum field power to get the field power by
module type.

Add the field power and logic power by module type to get the total power
requirement for the system.
Maximum
Logic Power
(Watts)a

Maximum
Field Power
(Watts)

Main Processor; 3101S2

Communicationc; 3201S2

Analog Input; 3351S2

Analog Input/Digital Input;


3361S2

Analog Output; 3481S2

Analog Output; 3482S2

Digital Input; 3301S2, 3311S2

Digital Output; 3401S2

Digital Output; 3411S2

20

Pulse Input; 3382S2

Solid-State Relay Output;


3451S2

Module

Logic
Power by
Module

Field
Power by
Module

Total Heat Dissipation


a. To convert watts to British thermal units: BTU = watts x 3.414
b. Means not applicable or negligible.
c. Does not include MAU connections.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Logic
and Field
Power

Installation Guidelines

179

Installation Guidelines
This section includes installation guidelines for the Tri-GP controller.
Topics include:

General Installation Guidelines on page 179

Plant Power and Grounding on page 179

Tri-GP Field, Power, and Ground Wiring on page 180Tri-GP Field, Power, and Ground
Wiring on page 180

Application-Specific Installation Guidelines on page 182

General Installation Guidelines


Due to the critical applications the Tri-GP is typically used in, it has been designed to operate
under worst cases conditions in the harsh environments typically found in industrial
environments.
To ensure adequate operational margins are maintained even under these worst case
conditions, the Tri-GP should be installed in a controlled environment according to the general
guidelines contained in:
IEC 61131, Part 4, Programmable controllers, User Guidelines
Section 7 of this standard includes checklists to help control the following environmental
conditions:

Temperature

Contaminants

Shock and vibration

Electromagnetic interference

Typical guidelines include:

Locate the Tri-GP away from obvious sources of heat: space heaters, solar radiation, etc.

Locate or isolate the Tri-GP from obvious sources of corrosive gases or dust.

Locate or isolate the Tri-GP from obvious sources of shocks or periodic vibrations:
rotating machinery, engines, compressors, presses, etc.

Locate or isolate the Tri-GP from obvious sources of electromagnetic interference: large
motors or motor controllers, power converters, radio controlled equipment, welding
equipment, etc.

Plant Power and Grounding


All plant and control room power distribution and safety grounding (protective earthing) must
be done according to the applicable national electric codes. Typical examples include:
IEC 60364, Electrical Installations of Buildings
Planning and Installation Guide for Triconex General Purpose v2 Systems

180

Chapter 3

Installation and Maintenance

National Fire Protection Association, 2002 Edition of the National Electrical Code Handbook
For new construction, or where simple retrofits are feasible, the plant and/or control room
safety grounding system should employ a supplemental Zero Reference Signal Plane or Grid
(ZRSG). Installation of such a system for the plant or control room is not required for a
successful Tri-GP application, but does represent modern best industry practice and should be
followed wherever possible. Even when not implemented at the plant or control room level, the
concepts of a modern ZRSG should be included in the Tri-GP cabinet and interconnecting cable
routing. The ZRSG implementation should be extended to include all equipment racks and
interconnecting cable paths: metal conduits, cable trays, wireways, etc. Detailed installation
guidelines can be found in:

EPRI TR- 102400, Volume 2, Handbook for Electromagnetic Compatibility of Digital


Equipment in Power Plants, Implementation Guide for EMI Control

IEC 61000, Part 5, Section 2, Electromagnetic compatibility (EMC), Installation and


mitigation guidelines, Earthing and cabling

IEEE Std 1100-1999, IEEE Recommended Practice for Powering and Grounding
Electronic Equipment

Tri-GP Field, Power, and Ground Wiring


All Tri-GP power distribution and safety grounding (protective earthing) must be done
according to the applicable national electric codes and the information contained in this manual.
Typical examples include:
National Fire Protection Association, 2002 Edition of the National Electrical Code Handbook
IEC 60364, Electrical Installations of Buildings
Typically, the Tri-GP is installed in an equipment rack, cabinet, or wall-mounted box located in
a control or equipment room. All wiring internal to that cabinet and leading to and from that
cabinet should be segregated into different types and bundled accordingly, for example:

Measurement and low-power analog control signals. These signals require shielded
twisted pair cabling.

24 VDC discrete signals. These signals require twisted pair cabling.

High-power control signals and conditioned power distributiontypically nonsensitive higher-voltage signals: 48-120 V discrete signals, 24-120 VDC I/O power
distribution, and so on. These signals should always use twisted pair cabling.

Input coming power and miscellaneous circuitstypically noisy, higher power circuits:
115 VAC discrete signals, AC power distribution, cabinet fans or lights, and so on.
These signals should always use twisted-pair cabling, and the Grounding Electrode
Conductor (the green wire) should be twisted along with the power leads, wherever
possible.

Earth bonding connections.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Installation Guidelines

181

All cable routing and installation should be done to minimize EMI, detailed guidelines can be
found in:
EPRI TR- 102400, Volume 2, Handbook for Electromagnetic Compatibility of Digital
Equipment in Power Plants, Implementation Guide for EMI Control
IEC 61000-5-2, Electromagnetic compatibility (EMC), Installation and mitigation guidelines,
Earthing and cabling
IEEE Std 1100-1999, IEEE Recommended Practice for Powering and Grounding Electronic
Equipment
Typical guidelines include the following:

Use ferrous metal cabinets, cable trays, and conduits.

Electrically bond all surfaces of the cabinet and it's contents together with multiple
conductive metal strapping, not simple wire. Particular attention should be paid to
doors, and removable panels. In turn the cabinet must be bonded to the control room or
plant safety ground system or ZRSG.

Routinely use twisted pair cabling, use shielded twisted pair cabling for all sensitive
signals. Allow the minimum amount of un-twisted wire that accommodates
connection.

Signals of different types should never be bundled together.

Bundles of different types should be separated by a minimum of 10 times the largest


lead diameter.

Bundles of different types of signals should only cross at right angles to each other.

All wires and/or bundles should be routed along the ZRSG, for example along the
along the cabinet walls, within a cable tray or conduit, along building steel or the floor
ground grid.

Where an inline filter or power conditioning is used, the input and output leads should
never be routed in the same bundle.

Maintain shield continuity and ensure that shield leads are not broken. Allow the
minimum amount of unshielded wire that accommodates connection. Terminate the
shield at both ends, use capacitive coupling at one end if potential ground loops are
suspected.

Where ferrites or line filters are to be installed on signals or cables entering or leaving
the cabinet, they must be installed as close to the cabinet egress point as possible.
Cables must be routed to minimize coupling between the filtered and non-filtered
signals. The non-filtered wire lengths in the cabinet must be minimized to the
maximum extent possible.

Note

To comply with standards related to conducted disturbance, a Schaffner FN 2410 line


filter, or equivalent, must be installed between power supplies and baseplates.

Planning and Installation Guide for Triconex General Purpose v2 Systems

182

Chapter 3

Installation and Maintenance

Application-Specific Installation Guidelines


The following guidelines apply when installing the Tri-GP in application-specific locations.

Class 1 Division 2 Hazardous Locations


For North American hazardous location applications, the Tri-GP and associated equipment
must be mounted in an enclosure that provides protection from fire and from personal injury
resulting from access to live parts. The enclosure must require access via a tool, and if nonmetallic, have the appropriate flammability rating.
The replacement of fuses, I/O Modules, Main Processors, Power Modules, Communications
Modules, HART Multiplexers, or I/O Interconnects must not be attempted unless the area is
known to be free of ignitable gas concentrations.
All cabling connected between the Hazardous Location Baseplates and External Termination
Panels (ETPs) must be nonincendive as described in Appendix B, Non-Incendive Circuit
Parameters. Communication cabling that extends through a hazardous area must be certified as
being nonincendive.
Only these modules and baseplates, which are approved for use in Class 1 Division 2 hazardous
locations, can be used:

2201S2 Communication Baseplate

2281 I/O Extender Module Kit (without termination)

2291 I/O Extender Module Kit for I/O Baseplate (with termination)

2292 I/O Extender Module Kit for MP Baseplate (with termination)

2301S2 Digital Input Baseplate

2302S2 Digital Input External Termination Baseplate and Solid State Relay Input
External Termination Panel

2351S2 Analog Input Baseplate

2352S2 Analog Input External Termination Baseplate

2354AS2 Analog Input HART Hazardous Location Baseplate

2361S2 Analog Input/Digital Input Baseplate

2381S2 Pulse Input Baseplate

2401S2 Digital Output Baseplate

2401LS2 Digital Output Baseplate (low current)

2402S2 Digital Output External Termination Baseplate and Relay Output External
Termination Panel

2451S2 Solid-State Relay Output Baseplate

2481S2 Analog Output Baseplate

2483AS2 Analog Output HART Hazardous Location Baseplate

3101S2 Main Processor

Planning and Installation Guide for Triconex General Purpose v2 Systems

Installation Guidelines

3201S2 Communication Module

3301S2 24V Digital Input Module

3311S2 Digital Input Module, High Resolution

3351S2 Analog Input Module

3361S2 Analog Input/Digital Input Module

3382S2 Enhanced Pulse Input Module

3401S2 24VDC Digital Output Module

3411S2 Digital Output Module, Supervised

3451S2 Solid-State Relay Output Module

3481S2 Analog Output Module

3482S2 High-Current Analog Output Module

9764-510F RTD/TC/AI Termination Panel

WARNING

183

You must take additional explosion protection measures for field circuits
when the field apparatus are in a hazardous area.

Zone 2 European Hazardous Locations


For European (ATEX) hazardous location applications, the Tri-GP and associated equipment
must be installed in an enclosure that provides an IP54 minimum degree of protection per the
requirements of EN 60529, Specification of protection provided by enclosures (IP Code). Simply
stated, the enclosure must provide protection against dust and splashing water.
Additionally, the enclosure must meet the applicable requirements of EN 60079-15 or EN 50021.
The following points must be taken into account:

Mechanical strength

Non-metallic enclosures and non-metallic parts of enclosures

Earthing or equipotential bonding connection facilities

The ambient temperature range for European (ATEX) hazardous location applications is:
4 F Ta 158 F (20 C Ta 70 C)
The following warning label must be placed on the outside of the Tri-GP system enclosure:
DO NOT REMOVE OR REPLACE MODULES OR CABLES WHILE ENERGIZED UNLESS THE
AREA IS KNOWN TO BE FREE OF IGNITABLE GAS CONCENTRATIONS.
The replacement of fuses, I/O Modules, Main Processors, Power Modules, Communications
Modules, HART Multiplexers, or I/O Interconnects must not be attempted unless the area is
known to be free of ignitable gas concentrations.
All connecting screws must be securely tightened, so that loosening and separating are
prevented.

Planning and Installation Guide for Triconex General Purpose v2 Systems

184

Chapter 3

Installation and Maintenance

Male ELCO connectors must have a gasket installed, and it must be replaced before the end of
its five-year life span. (Invensys part number 3000793-001 is a kit containing 25 gaskets.)
All cabling connected between the Hazardous Location Baseplates and External Termination
Panels (ETPs) must be nonincendive as described in Appendix B, Non-Incendive Circuit
Parameters. Communication cabling that extends through a hazardous area must be certified as
being nonincendive.
Only these modules and baseplates, which are approved for use in Zone 2 hazardous locations,
can be used:

2101S2 Main Processor Baseplate

2201S2 Communication Baseplate

2281 I/O Extender Module Kit (without termination)

2291 I/O Extender Module Kit for I/O Baseplate (with termination)

2292 I/O Extender Module Kit for MP Baseplate (with termination)

2302AS2 Digital Input External Termination Baseplate and Solid State Relay Input
External Termination Panel

2342AS2 Analog Input/Digital Input Baseplate Kit, Hazardous Location

2352AS2 Analog Input Baseplate Kit, Hazardous Location

2354AS2 Analog Input Baseplate Kit, HART, Hazardous Location

2381S2 Pulse Input Baseplate Kit

2381AS2 Pulse Input Hazardous Location Baseplate

2402AS2 Digital Output Baseplate Kit, Hazardous Location

2480AS2 Analog Output Baseplate Kit, Hazardous Location

2483AS2 Analog Output Baseplate Kit, HART, Hazardous Location

3101S2 Main Processor

3201S2 Communication Module

3301S2 24V Digital Input Module

3311S2 Digital Input Module, High Resolution

3351S2 Analog Input Module

3361S2 Analog Input/Digital Input Module

3382S2 Enhanced Pulse Input Module

3401S2 24VDC Digital Output Module

3411S2 Digital Output Module, Supervised

3481S2 Analog Output Module

9573-610F Digital Input Termination Panel Kit, Hazardous Location

9671-610F Digital Output Termination Panel Kit, Hazardous Location

9792-310F Analog Input Termination Panel Kit, Hazardous Location

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

185

9863-610F Analog Output Termination Panel Kit, Hazardous Location

When using the 2483AS2 Analog Output HART Hazardous Location Baseplate Kit, you must
use an external isolator, such as an MTL4546, to achieve Ex nL IIB T4 ATEX certification.

WARNING

You must take additional explosion protection measures for field circuits
when the field apparatus are in a hazardous area.

Component Installation
This section provides installation procedures for assembling the components in a Tri-GP
system. When unpacking materials, check the items against the shipping list to verify that
everything ordered is included. Keep the boxes and packing materials in case you need to return
items to Invensys.
Topics include:

Mounting a Panel on page 185

Installing Baseplates on a Column on page 191

Connecting Columns with I/O Extender Modules on page 192

Installing Modules on Baseplates on page 195

Installing the Module Address Plug on page 196

Installing Other Components on page 197

Enclosing the Controller on page 197

Mounting a Panel
The Tri-GP system is mechanically packaged into functional units that are aligned on DIN rails
on a panel mount. Each unit comprises one or more modules connected to a baseplate.
Baseplates are installed on a DIN rail to form vertical columns. Each rail can support up to eight
units, which are linked by MP Interconnect and I/O Interconnect Assemblies. Additional rails
can be connected in a daisy-chain fashion by using I/O Extender Modules.
These are guidelines for mounting components:

All assemblies should be mounted on a 12-gauge (or heavier) steel panel aligned
vertically using DIN 50 022-compatible rails.

All DIN system and field power supplies should be mounted on horizontal DIN 50 022compatible rails. DIN rails should be mounted on a 12-gauge (or heavier) steel panel.

The DIN rails and baseplate assemblies should be located on the panel to allow for the
installation of wiring channels (for example, Panduit) along the left side of vertical
columns and along the bottom of horizontal rails.

Clearance should be provided for adequate air flow around system modules.

Planning and Installation Guide for Triconex General Purpose v2 Systems

186

Chapter 3

Installation and Maintenance

For typical environments, there should be at least 5 inches (15 centimeters) of clearance
between active modules and the walls of the enclosure.

For detailed specifications, see:

Mounting Panel Drill Template on page 186

Baseplate and Module Depth Dimensions on page 188

MP Baseplate Dimensions and Clearances on page 189

I/O Baseplates Dimensions and Clearances on page 190

I/O Extender Modules Dimensions and Clearances on page 191

Mounting Panel Drill Template


This figure shows where the mounting holes should be located on the panel.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

187

DIN Rail
Tap, #10-32

MP or CM Baseplate

Number Equal Spaces


@ 9.84 in. = 39.50 in.
252.6 mm = 1002.2 mm
Ref
39.30 in.
995.7 mm
Ref for
5 Baseplates
As Illustrated

I/O Module Baseplate

2.50 in.
63.5 mm

7.30 in.
185.4 mm

Extender Module Baseplate

3.29 in.
83.6 mm
6.56 in.
166.6 mm

2.50 in.
63.5 mm

* Typical, non-accumulating

1.25 in.
31.8 mm
Ref

8.56 in.
217.4 mm

Figure 93

Mounting Panel Drill Template

Planning and Installation Guide for Triconex General Purpose v2 Systems

188

Chapter 3

Installation and Maintenance

Baseplate and Module Depth Dimensions


This figure shows the depth dimensions for a baseplate and module, which is 7.10 inches
(18.03 cm). Vertically mounted I/O baseplates measure approximately 7.00 inches (17.78 cm)
wide by 9.79 inches (24.87 cm) long.

Figure 94

Baseplate and Module Dimensions

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

189

MP Baseplate Dimensions and Clearances


This figure shows dimensions and clearances for MP Baseplate installation. The vertically railaligned MP Baseplate measures approximately 9 inches wide by 9.79 inches long per logical slot.
9.02 in.
229.1 mm

9.76 in.
247.9 mm
7.30 in.
185.4 mm

8.53 in.
216.7 mm

1.23 in.
31.2 mm

8.56 in.
217.4 mm

0.23 in.
5.8 mm

3.29 in.
83.6 mm
3.52 in.
89.4 mm
C
L

Figure 95

MP Baseplate Dimensions and Clearances

Planning and Installation Guide for Triconex General Purpose v2 Systems

190

Chapter 3

Installation and Maintenance

I/O Baseplates Dimensions and Clearances


This figure shows dimensions and clearances for I/O Baseplate installation.
7.02 in.
166.7 mm

7.30 in.
185.4 mm
9.76 in.
247.9 mm

8.53 in.
216.7 mm

1.23 in.
31.2 mm

6.56 in.
166.7 mm

0.23 in.
5.8 mm

3.29 in.
83.6 mm
3.52 in.
89.4 mm
C
L

Figure 96

I/O Baseplate Dimensions and Clearances

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

191

I/O Extender Modules Dimensions and Clearances


This figure shows dimension and clearances for I/O Extender Module installation.
1.23 in.
31.2 mm

1.23 in.
31.2 mm

6.56 in.
166.7 mm

Figure 97

0.23 in.
5.8 mm

I/O Extender Module Dimensions and Clearances

Installing Baseplates on a Column


This procedure explains how to install baseplates on a column.

Procedure
1

On a mounting panel, locate, drill, and tap mounting holes. For specifications, see
Mounting Panel Drill Template on page 186.

Install the DIN rail according to the manufacturers instructions.

Install the first baseplate, which is typically either the MP or CM Baseplate. The CM
Baseplate must be directly above or below the MP Baseplate.

Use four #10 mounting screws with flat and lock washers and positioning the baseplate
along the DIN rail so that the mounting screws are centered in the oblong mounting
holes. Tighten the screws to 16 inch-pounds of torque.

Install the next baseplate either at the top or bottom of the previous baseplate. Use four
#10 mounting screws with flat and lock washers and positioning the baseplate along the
DIN rail so that the mounting screws are centered in the oblong mounting holes. Do not
tighten the screws.

Attach an Interconnect Assembly between the two baseplates, allowing the second
baseplate to move until the Interconnect Assembly snaps into place.

For baseplates next to an MP Baseplate, use an MP Interconnect Assembly.

For baseplates next to an I/O Baseplate, use an I/O Interconnect Assembly.

Tighten the mounting screws on the second baseplate to 16 inch-pounds of torque.

Install additional baseplates and interconnect assemblies.

Planning and Installation Guide for Triconex General Purpose v2 Systems

192

Chapter 3

Installation and Maintenance

Interconnect Assembly

Screws
(4 places)
Baseplate

Screws (4 places)

End Cap

Connecting Columns with I/O Extender Modules


This procedure explains how to use I/O Extender Modules to connect a column of baseplates to
another column, which is required if the system includes more than eight baseplates or more
than one column. I/O Extender Modules are used to extend the I/O bus from one column to
another. Logic power also may be connected through the I/O Extender Module.

Procedure
1

Determine the length of the I/O bus by adding these dimensions:

The length between the top and bottom of the first column and the top and bottom
of the second column

The length of the I/O Interconnect Modules

The length of the cable between the columns

If the length does not exceed 20 feet (6 meters), go to step 3. If it does, go to step 4.

If the length does not exceed 20 feet (6 meters), do this:

Install an I/O Extender Module at the top or bottom of each column, depending on
where you want the cables to be.

Connect the cables between the two I/O Extender Modules as shown in this figure.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

193

If there are additional columns, repeat the steps.

Planning and Installation Guide for Triconex General Purpose v2 Systems

194

Chapter 3

Installation and Maintenance

If the length exceeds 20 feet (6 meters), do this:

Install an I/O Extender Module at the top or bottom of each column, depending on
where you want the cables to be.

Connect the cables between the two I/O Extender Modules.

Install an I/O Extender Module at the other end of each column and insert an I/O
bus terminator (male 9-pin D connector) to each connection, as shown in this figure.

Note

To maintain acceptable signal integrity when the I/O bus exceeds 20 feet (6
meters), you must install terminators on both ends of the I/O bus. Invensys part
number 3900064-003 is a set of three terminators.

DB-9 Plug with Terminator

If there are additional columns, repeat the procedure as needed.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

195

Installing Modules on Baseplates


This procedure explains how to install a module on a baseplate. Each baseplate is keyed to allow
only modules appropriate for the baseplate. For MP Baseplates, there are three slots. For
Communication and I/O modules, there are two slots for modules.

Procedure
1

Seat a module on its corresponding baseplate.

Turn the lock lever manually 90 to 180.

Insert a 1/4 inch flat-blade screwdriver into the lock and turn clock-wise to the locked
position (360).
Typically, 25 in./lbs. of torque are required to rotate the lock lever.
When the module is installed, the Fault indicator goes on while the diagnostics are
running. At the same time, the Point indicators go on briefly, go off, then resume the
normal state of blinking. The Pass Indicator should go on within about one minute. If it
does not, and the Fault light persists longer than five minutes, check the diagnostic log
to determine if there is a problem.

Figure 98

Module Assembly on Baseplate

Planning and Installation Guide for Triconex General Purpose v2 Systems

196

Chapter 3

Installation and Maintenance

Installing the Module Address Plug


This procedure explains how to install the address plug, which is a device that identifies the I/O
baseplate to the Main Processors. Each baseplate, except the Communication Module, must
have an address plug. Invensys includes a package of address plugs to be used with the I/O
baseplates.

Procedure
1

Insert the desired address plug on to the baseplate.

Do either of these:

Cycle power or re-install the module

Change the node address for the module in the TriStation 1131 project

This figure shows the general location of an address plug on a baseplate.

Figure 99

Address Plug Location

Planning and Installation Guide for Triconex General Purpose v2 Systems

Component Installation

197

Installing Other Components


Interconnect Assemblies
Attach the appropriate interconnect assembly between baseplates.

Installing End Caps


Each end-of-column baseplate should be covered with an end cap to protect the top and bottom
of each end-of-column baseplate, cover the interconnect connector, and serve as a card guide.

Installing Slot Covers


Unused baseplate slots should be covered with a Slot Cover to minimize exposure to dust,
dripping and splashing liquids, and corrosive atmospheres.

Installing Terminal Covers


On I/O baseplates, field terminals should be covered with a Terminal Cover to minimize
exposure to dust, dripping and splashing liquids, and corrosive atmospheres.

Enclosing the Controller


After all of the components are mounted on a panel, the entire system should be installed in a
user-supplied metal enclosure with a sealed bottom and a closed door, connected to Safety
Ground.
Either of these can be used:

For a single column, a floor-mounted enclosure such as a Rittal cabinet.

For two or more columns, a wall-mounted enclosure such as a Hoffman box.

Note

To comply with the requirements of EN 54-2:1998, the Tri-GP system must be installed
in a metal enclosure connected to Safety Ground, and it must be installed in an area with
an access level greater than 2.

Planning and Installation Guide for Triconex General Purpose v2 Systems

198

Chapter 3

Installation and Maintenance

Controller Grounding
This section includes information about grounding the controller.

WARNING

During installation of a Tri-GP controller, take special care with all power
sources to minimize the hazard of electrical shock.

Topics include:

Grounding Baseplates to Protective Earth on page 198

Grounding Logic Power on page 200

Grounding Field Power on page 201

Connecting Shields to Earth on page 202

Grounding Baseplates to Protective Earth


The Tri-GP system should be permanently connected to a protective earth to protect operations
and maintenance personnel from electrical shock, and to protect the system from damage or
malfunction caused by lightning or other electrical noise transients.

WARNING

Do not operate a Tri-GP system without connecting each baseplate to a


protective earth (AC safety ground) with a low-impedance cable. Improper
grounding creates the potential for dangerous electrical shockthe Tri-GP
controller can produce significant leakage currents which must be shunted to
earth.
To ensure that the Tri-GP controller and the equipment connected to it operate
safely, you should follow all applicable local and national codes and
standards. At a minimum, these include national fire and electrical codes.
Because codes and standards vary geographically and change over time, it is
your responsibility to determine which standards apply to your specific case
and to comply with them. If necessary, contact your local Fire Marshall and
Electrical Inspector for assistance.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Controller Grounding

199

Procedure
Connect each baseplate in the system to a common tie point, such as a copper bar, according to
the applicable electrical codes. The same copper bar can be used to provide a protective earth
connection for the field devices and wiring.
The wire should be heavy, solid or stranded, bare or insulated. A 12 AWG (3.3 mm2) wire is
adequate in most environments.

EM

CM

Typical
Ground
Connection
AI
6

MP

DI

1
1

Green/Yellow Wire

AI

DO

DI

RO

EM

Protective Earth
(Safety Ground)

Planning and Installation Guide for Triconex General Purpose v2 Systems

200

Chapter 3

Installation and Maintenance

Grounding Logic Power


This procedure explains how to ground logic power. An independent power source, equipped
with its own fuse and switch, can be shared by all the baseplates in the system. You should
connect each baseplate to two independent power sources. In critical environments, at least one
power source should be an uninterruptible power supply (UPS). The UPS should be rated for
the total number of baseplates to be powered and for the duration of the maximum expected
down time.
The internal signal grounds (logic and field) are allowed to float with respect to the protective
earth (safety ground). In most installations, it is best to tie the signal ground and safety ground
together at one and only one point. In simple environments, logic and field power can be
combined and treated as one ground system. For more information, see Grounding Field Power
on page 201.

Procedure
Ground logic power from the MP and I/O Extender Modules in either of these ways:

Connect L

to protective earth

Connect L

to a DCS master reference ground or other quiet earth.


Power
Supply 1
+

L
Distribution
Block

at only one place for the entire system

Power
Supply 2
+

Power
Disconnect

Power
Disconnect

J5

Extender
DSP1

DSP2

DSP3

DSP4

MP
Baseplate
1

1
2

Protective Earth
(Safety Ground)

Planning and Installation Guide for Triconex General Purpose v2 Systems

Typical I/O
Baseplate

Controller Grounding

201

Grounding Field Power


This procedure explains how to ground field power, which must be done for all I/O baseplates.
Multiple I/O modules can share a single set of power supplies, or each I/O module or group of
modules can use separate power supplies referenced to alternate grounds. For more
information, see Grounding Logic Power on page 200.

Procedure
Ground field power from the I/O Baseplates in either of these ways:

Connect L
to protective earth
power supplies.

Connect L

to a DCS master reference ground or other quiet earth.


Power
Supply 1

F
Distribution
Block

at only one place for each set of redundant field

Power
Supply 2
+

Power
Disconnect

Power
Disconnect

J5

Extender

1
2

Typical I/O
Baseplate

2
3

Planning and Installation Guide for Triconex General Purpose v2 Systems

202

Chapter 3

Installation and Maintenance

Connecting Shields to Earth


This procedure explains how to connect shields to earth, which may be required for some field
input connections.

Procedure
1

Connect a cable shield at one end of the cable, typically the controller.

Make a connection near the termination panel using an external shield bus bar, which is
available from Phoenix Contact or other terminal block suppliers.

Individually connect each shield bus bar to a suitable, quiet ground point, such as a
dedicated protective earth or a DCS master reference ground.

~~
~
~

Typical Point
(1 of 32 Points Shown)

1
2
3
4
5
6

4-20 mA
Transmitter

~~
~
~

8
9
10
11
12
13
14
15
16

17
18
19
20
21
22
23
24
25
26
27
28

Shield Bus Bar

29
30
31
32

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Dedicated Shield Ground,


DCS Master Reference Ground
(Functional Earth), or
Protective Earth

Planning and Installation Guide for Triconex General Purpose v2 Systems

Controller Grounding

203

Alarm Wiring
Each Main Processor Module includes two sets of redundant alarm contacts; each with a
normally closed contact and common.
Typically, alarm wiring is connected to a local or remote annunciator. These devices can be
wired in parallel with the alarm wiring so that the designated alarm goes off when either contact
signals an alarm condition.
The Program Alarm indicator is lit when the control program detects a specified condition and
sets the MP.SET_PROG_ALARM_ON attribute to True.
For a simplified schematic and specifications, see Alarm Connections on page 40.

DSP1

DSP2

NC
Load

24 VDC +
Power Source

Alarm 1

DSP3
FUSE

C
NC

24 VDC +

DSP4
FUSE

Alarm 2

Power Source

Figure 100

Alarm Wiring

Planning and Installation Guide for Triconex General Purpose v2 Systems

204

Chapter 3

Installation and Maintenance

Implementation and Maintenance


This section includes information about implementation and maintenance that should be
considered when installing a Tri-GP system. To ensure maximum safety and long service,
Invensys recommends you establish a schedule for routine maintenance at the time that the
Tri-GP controller is installed and adhere to it.
Topics include:

Disabling Output Voter Diagnostics on page 204

Checking Controller Power Sources on page 205

Enabling Disabled Output Voter Diagnostics on page 205

Toggling Field I/O Points on page 206

Verifying Spare Modules on page 206

Disabling Output Voter Diagnostics


Output Voter Diagnostics (OVD) is a set of tests that detect failures in the quad-output voting
mechanism of Digital Output Modules except Relay Output Modules. Because of glitches
caused by forcing simulated failures, OVD may affect the controlled process. If this is not
acceptable, OVD can be disabled, but should be enabled every three months. To ensure safety,
you should analyze the sensitivity of each load device attached to the controller for proper
operation.

WARNING

A safety program may not disable the Output Voter Diagnostic.

Invensys guarantees that an OVD-forced glitch has the following duration:


Less than 2 milliseconds, which is a period that is tolerated well by electro-mechanical
devices such as relays, solenoids and contactors.
For assistance with load devices that might be sensitive to such glitches, please contact the
Invensys Global Customer Support (GCS) center.

Procedure
1

From TriStation 1131 software, disable OVD on all or on specific Digital Output
Modules. For instructions, see the guide for the version of TriStation 1131 software being
used.

Log the date when OVD was disabled so that OVD can be enabled and tested at a later
period. For information on OVD enabling, see Enabling Disabled Output Voter
Diagnostics on page 205

Planning and Installation Guide for Triconex General Purpose v2 Systems

Implementation and Maintenance

205

Checking Controller Power Sources


Typically, Tri-GP controllers use redundant sources to power the controller and field circuitry.
Under normal operating conditions, the required power is shared between the two power
sources. Under abnormal conditions, one of the power sources may be required to provide 100
percent of the controller power. To verify the integrity of the power source and the Power
Modules, you must periodically test each power source for its ability to provide power for the
entire system when the redundant source is disabled.
This procedure explains how to test the power sources used for the controller. Ideally, this test
is performed when the controlled process is offlinefor example, during a normally scheduled
plant maintenance period.

Procedure
1

If possible, take the control process offline.

Every three to six months, turn off one of the power sources and leave it off for several
minutes.

After restoring power, repeat the test for the other power source.

Turn on both power sources prior to restarting the controlled process.

Enabling Disabled Output Voter Diagnostics


This procedure explains how to enable disabled Output Voter Diagnostics (OVD) tests used
by Digital Output Modules. In some systems, these diagnostic can cause glitches that affect the
controlled process. If OVD has been disabled, it should be enabled periodically.

CAUTION

Invensys does not recommend running with OVD disabled for periods
greater than three months.

Procedure
1

Ensure the controlled process is shut down. (Do not stop the TriStation 1131 application
from running.)

In TriStation 1131 software, go to the Controller Panel and enable the disabled OVD
points or modules.

Leave OVD enabled for several minutes to verify the stability of the modules.
This action provides 100 percent failure detection for all components.

If required, disable OVD.

Planning and Installation Guide for Triconex General Purpose v2 Systems

206

Chapter 3

Installation and Maintenance

Toggling Field I/O Points


During a normally scheduled plant maintenance period, you should toggle the field points from
the normal operational state to the opposite state to guarantee complete fault coverage of the
digital circuitry. Leave each point in the opposite state for several minutes. Ideally, this type of
testing is performed with the controlled process offline. For instructions, see the TriStation 1131
Developers Guide.

Verifying Spare Modules


The controller automatically tests all modules installed in the system. The only action needed to
guarantee the integrity of a spare module is to periodically install it in an online system. Spare
I/O modules should be installed as hot-spare modules because the controller automatically
shifts control between the active and hot-spare modules.
Control changes as follows:

Periodically, approximately once an hour

After a power failure

After an MP re-education

Spare MP and I/O modules that cannot be used as hot-spare modules should be periodically
rotated into an online system to ensure the integrity of spare inventory. A rotation schedule
should be established so that a spare module is not allowed to sit on the shelf more that six
months.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Module Replacement

207

Module Replacement
This section explains how to replace modules after a system has been installed.
Topics include:

Guidelines for Replacing Modules on page 207

Replacing a Communication Module on page 209

Replacing an I/O Module on page 210

Guidelines for Replacing Modules


Before installing any module, these guidelines should be observed.

WARNING

CAUTION

Wait until the Active indicator of the replaced module goes on, then
replace the second faulty module.

Inserting modules with damaged pins may cause the controller to


malfunction and may affected the controlled process. If the module has
damaged pins, return it to Invensys for repair.

If a controller has two faults, one in an MP and one in another type of module, replace
the MP first.

If an I/O module has a field fault and a module fault, resolve the field fault first. Before
replacing the I/O module, try clearing the fault by using the Diagnostic Monitor
(TriStation 1131 v4 software) or the Diagnostic Panel (TriStation 1131 v3 software). If
the I/O module fails to go to Pass or wont stay in Pass, replace it.

Before inserting any module into the baseplate, check for damaged pins. If damaged
pins are present, do not insert the module.

When replacing a module, you must use a 1/4 inch flat-blade screwdriver to lock or
unlock the module.

For optimal performance, store spare I/O modules in vacant slots of the controller as
hot-spare modules.

Store any remaining, unused modules in their original shipping cartons.

Planning and Installation Guide for Triconex General Purpose v2 Systems

208

Chapter 3

Installation and Maintenance

Replacing a Main Processor Module


This procedure explains how to replace a Main Processor Module. Before replacing an MP,
verify that all I/O modules are locked.

CAUTION

After replacing an MP, allow the module to fully re-educate before


unlocking another MP. Never unlock more than one MP at a time.

Procedure
1

If the controlled process is online, verify that at least one MP has an Active indicator with
a blinking yellow light.

On the faulty module, use a 1/4 inch flat-blade screwdriver to rotate the lock lever
counter-clockwise until the module ejects from the baseplate.

Insert the replacement module and use the screwdriver to rotate the lock lever clockwise
to draw the module into the baseplate.

The following should occur:

The Pass indicator should go on and stay on within one to six minutes.

The Active indicator on the replacement module should blink at the same rate as
the other MP Modules within one to six minutes.

The Lock indicator goes off. (If the module is not properly seated, the Lock
indicator stays on and the Active indicator does not go on.)

For the faulty module, identify the model and serial numbers. Contact the Invensys
Global Customer Support (GCS) center to obtain a Returned Material Authorization
(RMA) number. Then return the module to Invensys for repair.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Module Replacement

209

Replacing a Communication Module


This procedure explains how to replace a Communication Module.

CAUTION

The CM does not have hot-spare capability which means communication


is disrupted while the module is being replaced.

Procedure
1

If possible, make a note of the diagnostic message, model, and serial numbers.

Detach all communication cables from the faulty module.

On the faulty module, use a 1/4 inch flat-blade screwdriver to rotate the lock lever
counter-clockwise until the module ejects from the baseplate.
Note

If communication has not been disrupted by the fault, removing the module
disrupts communication until the module is replaced. If redundant CM,
replacing the faulty module does not affect communication on this module.

Insert the replacement module and use the screwdriver to rotate the lock lever clockwise
to draw the module into the baseplate.

The following should occur:

The Pass indicator should go on and stay on within one minute.

The Active indicator should go on within one to two minutes.

The Lock indicator goes off. (If the module is not properly seated, the Lock
indicator stays on and the Active indicator does not go on.)

Re-attach all communication cables to the CM.

For the faulty module, identify the model and serial numbers. Contact the Invensys
Global Customer Support (GCS) center to obtain a Returned Material Authorization
(RMA) number. Then return the module to Invensys for repair.

Planning and Installation Guide for Triconex General Purpose v2 Systems

210

Chapter 3

Installation and Maintenance

Replacing an I/O Module


This procedure explains how to replace an I/O module. If an I/O module has a field fault and
a module fault, the field fault should be resolved first.
You need a 1/4 inch flat-blade screwdriver to install the module.

Procedure
1

If two modules are installed and one has an Active indicator, remove the other (faulty)
module by turning the lock counter-clockwise with the screwdriver until the module
ejects from the baseplate. (If neither module has an Active indicator on, contact the
Invensys Global Customer Support (GCS) center.)

Install an identical type module in the empty slot and push the module in until it is
firmly seated. Turn the lock clockwise to lock the module on to the baseplate.
When the module is installed, the Fault indicator goes on while the diagnostics are
running. At the same time, the Point indicators go on briefly, go off, then resume the
normal state of blinking. The Pass Indicator should go on within about one minute. If it
does not, and the Fault light persists longer than five minutes, check the diagnostic log
to determine if there is a problem.
If the module is not properly seated, the Lock indicator stays on. The Active indicator
does not go on until the I/O module is properly seated and locked.
The Active indicator should go on within one to two minutes. Then the Active indicator
on the faulty module goes off. If the Active indicator on the newly inserted module does
not go on within five minutes, replace it with another module.

Identify the model and serial number of the faulty module. Contact the Invensys Global
Customer Support (GCS) center to obtain a Returned Material Authorization (RMA)
number. Then return the module to Invensys for repair.

Planning and Installation Guide for Triconex General Purpose v2 Systems

4
Fault and Alarm Indicators

Overview 212
Main Processor Indicators 213
Communication Module Indicators 218
Analog Input Module Indicators 221
Analog Input/Digital Input Module Indicators 224
Analog Output Module Indicators 227
Digital Input Module Indicators 230
Digital Output Module Indicators 233
Pulse Input Module Indicators 237
Solid-State Relay Output Module Indicators 240

Planning and Installation Guide for Triconex General Purpose v2 Systems

212

Chapter 4

Fault and Alarm Indicators

Overview
Indicators are lights on the front panel of each module that identify the state of each module.
Each module includes indicators that identify the general state of the module and other
indicators related to the function of the module.

CAUTION

The Tri-GP controller can be repaired while operating. However, the


integrity of the controller can only be assured if the operator follows
repair procedures correctly. If in doubt about the procedures, the
operator should take whatever steps are necessary to ensure the safety of
the plant and personnel, and then contact Invensys for assistance in
implementing the repair procedures.

The types of indicators include:

Status indicators which identify the processing state of the module. Each module
includes a Pass, Fault, and Active indicator.

A lock indicator which identifies whether the module is unlocked.

Mode indicators which identify the current operating state of the controller. (Only on
MP Modules.)

Field power and power load indicators which identify whether a power problem has
occurred. (Only on some I/O modules.)

Communication indicators which identify the type of communication occurring. (Only


on MPs and CMs.)

Points indicators which identify whether the point is energized.

Alarm indicators which identify alarm conditions for the controller. (Only on MP
Modules.)

Fault and Alarm Indicators


Fault indicators identify potentially serious problems with a module. Alarm conditions identify
abnormal field conditions such as loss of power and loss of communication.
If a fault or alarm indicator is on, you should consult the appropriate section of this chapter and
take appropriate action. This action may include replacing a faulty module or repairing a faulty
circuit or device.

Identifying Fault and Alarm Conditions


You can identify alarm and fault conditions in these ways:

By examining the indicators on the front panel of each module and comparing the
indicators with the descriptions in this chapter

By using the Enhanced Diagnostic Monitor

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Indicators

213

Main Processor Indicators


This section describes indicators for the MP Module, including:

MP Status Indicators on page 214

MP System Mode Indicators on page 215

MP Alarm Indicators on page 216

MP Communication Indicators on page 217


Pass (Green)
PASS

MP Status
Indicators

Fault (Red)

FAULT
ACTIVE

Active (Yellow)
Remote Mode (Green)

MODE
REMOTE

System Mode
Indicators

Run Mode (Green)

RUN

Program Mode (Yellow)

PROGRAM
HALT

Halt Mode (Yellow)


Field Power (Red)

ALARMS
FIELD POWER

Alarm
Indicators

Logic Power (Red)

LOGIC POWER

System Alarm (Red)

SYSTEM ALARM
PROGRAM ALARM

Program Alarm (Blue)

OVER TEMPERATURE

Over Temperature (Red)

LOCK

Unlock (Red)

COMMUNICATIONS
IO BUS

COMM BUS

Communication
Indicators
SERIAL

TX
RX

TX
RX

TX
RX

LINK
TRISTATION

TX
RX

TX/RX I/O Bus (Green/Green)


TX/RX Communication Bus (Green/Green)
TX/RX Modbus (Green/Green)
Link TriStation(Green)
TX/RX TriStation (Green/Green)

MP3101S2
Figure 101

MP Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

214

Chapter 4

Fault and Alarm Indicators

MP Status Indicators
The MP status indicators identify the processing state for the MP Module.
A fault light indicates that the processor has an internal fault.

Normal States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Yellow
blinking

No
light

Module is operating normally.


Active indicator blinks once per
scan when executing a control
program.

Normal status. No action


is required.

Green
steady

No
light

No
light

No
light

Module is operating normally.


Possible conditions include:
Control program has not been
loaded into the MP.

Load control program.

Control program has been


loaded into the MP, but has not
been started up.

Start control program.

Module has just been installed


and is currently being educated
by the other MP Modules.

Wait for the module to be


educated.

Fault States
Pass

Fault

Active

Lock

Description

Action

No
light

Red
steady

No
light

Module may have failed.


Possible conditions include:

See mode indicator status


for power-up states.

Module may be in the process


of power-up self-test.

If the Pass indicator does


not go on within five
minutes, replace the
module.

Module has detected a fault.

Module is operational, but


should be replaced.

No
light

Red
steady

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry on
the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry on
the module are malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Main Processor Indicators

215

MP System Mode Indicators


The MP system mode indicators identify the current operating state of the controller.
(Operational modes are set in TriStation 1131 software. For more information, see the TriStation
1131 Developers Guide.)
Remote

Run

Program

Halt

Description

Green
steady

Green
steady

Yellow
steady

No
light

Normal operation with write capability.


Allows writes to program variables by TriStation 1131
software, Modbus master, and external hosts.
Allows control of the controller from TriStation 1131
software, including Download All and Download
Change.

Green
steady

Green
steady

No
light

No
light

Normal operation with read-write capability.

No
light

Green
steady

No
light

No
light

Normal operation with read-only capability.

No
light

No
light

Yellow
steady

Yellow
steady

Control program loading and checkout is enabled.

Green
slow
blinking

Green
slow
blinking

Yellow
slow
blinking

Yellow
slow
blinking

Indicators change every few seconds; module is in its


power-up state.

Green
fast
blinking

Green
fast
blinking

Yellow
fast
blinking

Yellow
fast
blinking

Module is ready to download new internal firmware.


Condition is caused by removing the MP Baseplate
address plug before module power-up.

No
light

No
light

No
light

Yellow
steady

Control program has stopped.

Green
steady

Green
steady

Yellow
steady

Yellow
steady

Module is faulty or has detected a bad address plug.

Allows writes to program variables by Modbus


masters and external hosts. (Download All and
Download Change by TriStation 1131 software are not
allowed.)
MP Modules execute the previously loaded control
program. Attempts to modify program variables by
Modbus masters and external hosts are rejected.
Allows control of the controller from the TriStation
1131 control program, including Download All and
Download Change. Control program has also been
stopped.

Planning and Installation Guide for Triconex General Purpose v2 Systems

216

Chapter 4

Fault and Alarm Indicators

MP Alarm Indicators
The MP alarm indicators identify alarm conditions for the controller.
Field
Power

Logic
Power

System
Alarm

Program
Alarm

Over
Temp

Red
steady

Red
steady

Red
steady

Red
steady

Red
steady

Description

Action

System power
supply is
missing/bad.

Correct the problem.

Field power supply


is missing/bad.

Correct the problem.

MP or I/O module
is malfunctioning.

Identify the condition by


looking at the Pass or
Fault indicators of other
modules or by using the
TriStation 1131
Diagnostic Panel.
Replace faulty module.

Red
steady

Blue
steady

Red
steady

I/O module has


detected a field
fault.

Correct field fault.

Control program
has detected an
alarm condition.

Check control program


for bypass or overridden
points or other abnormal
condition.

Control program
has detected an
alarm condition.
Alarm contacts also
indicate an alarm
(open contacts).

Identify the fault


condition by using the
control program.

Normal operation,
but the ambient
temperature is too
high (greater than
140F/60C).

Correct the
environmental problem
or the controller may fail
prematurely.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Correct the condition.

Main Processor Indicators

217

MP Communication Indicators
The MP communication indicators identify the type of communication occurring on the
controller. The TX light indicates the MP is transmitting a message and the RX light indicates
the MP is receiving a message.
IO Bus

Comm Bus

Serial

TriStation

RX/TX

RX/TX

RX/TX

Link

RX/TX

Description

Green
blinking

Normal response. MP is polling and


sending responses to the I/O
modules.

Green
blinking

Normal response. MP is polling and


sending responses to the CMs.

Green
blinking

Normal response. MP is polling and


sending responses to the Modbus
master.

Green
steady

Green
blinking

MP is communicating with TriStation


1131 software.

No
light

MP is not communicating with


TriStation 1131 software or a network
hub.
Note: The hub or Ethernet card in the
PC running the TriStation 1131
software has a link indicator that
shows whether a hardware connection
has been established with the MP.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

218

Chapter 4

Fault and Alarm Indicators

Communication Module Indicators


This section describes indicators for the CM, including:

CM Status Indicators on page 219

CM Communication Indicators on page 220


Pass (Green)

CM Status
Indicators

PASS

Fault (Red)

FAULT
ACTIVE

Active (Yellow)

LOCK

Unlock (Red)

COMMUNICATIONS
SERIAL

TX
RX

SERIAL

TX
RX

Communication
Indicators

SERIAL

TX
RX

LINK
NET 1 TX
RX

LINK
NET 2

TX
RX

Serial 1 (Green/Green)
Serial 2 (Green/Green)
Serial 3 (Green/Green)
Net 1 Link (Green)
Net 1 TX/RX (Green/Green)
Net 2 Link (Green)
Net 2 TX/RX (Green/Green)

CM 3201S2
Figure 102

CM Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

Communication Module Indicators

219

CM Status Indicators
The CM status indicators identify the processing state for the CM.
A fault light indicates that the processor has an internal fault.

Normal States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating
normally.

Normal status. No action is


required.

Green
steady

No
light

Green
blinking

No
light

Module is downloading
firmware.

Normal status. To cancel,


pull module then re-seat
module.

Green
steady

No
light

No light

No
light

Module is operating
normally. Possible
conditions include:
Control program has not
been loaded into the MP.

Load control program.

Control program has been


loaded into the MP, but has
not been started up.

Start control program.

Module has just been


installed and is currently
being educated by the other
MP Modules.

Wait for module to be


educated.

Fault States
Pass

Fault

Active

Lock

Description

Action

No
light

Red
steady

No light

No
light

Module may have failed.


Possible conditions include:

See mode indicator status for


power-up states.

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace module.

No
light

Red
steady

Green
steady

No
light

Module has detected a


minor error.

Module is operational, but


should be replaced.

No
light

Red
steady

Red
steady

Module is unlocked from the


baseplate.

Lock module.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

220

Chapter 4

Fault and Alarm Indicators

a. This symbol ( ) means the indicator is not important for this condition.

CM Communication Indicators
The CM communication indicators identify the type of communication occurring on the
controller. The TX light indicates the CM is transmitting a message and the RX light indicates
the CM is receiving a message.
Serial 1

Serial 2

Serial 3

Net 1

RX/TX

RX/TX

RX/TX

Link

Green
blinking

Normal response. CM is
communicating with the
attached Modbus
master/slave device.

Green
blinking

Normal response. CM is
communicating with the
attached Modbus
master/slave device.

Green
blinking

Normal response. CM is
communicating with the
attached Modbus
master/slave device.

Green
steady

Green
blinking

CM is communicating
with TriStation 1131
software or with an
Ethernet device through
the Net 1 port.

Green
steady

Green
blinking

CM is communicating
with TriStation 1131
software or with an
Ethernet device through
the Net 2 port.

RX/TX

Net 2
Link

RX/TX

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Description

Analog Input Module Indicators

221

Analog Input Module Indicators


This section describes the AI Module indicators including:

AI Status Indicators on page 222

AI Field Power Indicator on page 223


Pass (Green)

AI Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
FIELD PWR

Field Power (Yellow)

LOCK

Unlock (Red)

AI 3351S2
Figure 103

AI Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

222

Chapter 4

Fault and Alarm Indicators

AI Status Indicators
The AI status indicators identify the processing state for the AI Module.
A fault light indicates that the module has an internal fault.

Normal States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:

If this is the hot-spare


module, no action is
required.

Control program has not


been loaded into the MP.
Control program has been
loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
The other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Module has detected a fault.

Module is operational, but


should be replaced.

Module has detected


marginal input voltage in a
steady-state condition.

Check sensor signal


strength.
Check sensor positioning.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input Module Indicators

223

AI Field Power Indicator


The AI field power indicator is lit when a field power problem has occurred.
Field
Power
Yellow
steady

Description

Action

Field power or logic power from one


or more of the redundant sources is
missing.

To isolate the missing power source, use the


TriStation 1131 software.
To determine the actual state, use a voltmeter,
then correct the problem in the external circuit.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

224

Chapter 4

Fault and Alarm Indicators

Analog Input/Digital Input Module Indicators


This section describes the AI/DI Module indicators including:

AI/DI Status Indicators on page 225

AI/DI Field Power Indicator on page 226


Pass (Green)

AI/DI Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
FIELD PWR

Field Power (Yellow)


1
2
3
4
5
6
7

Points
Indicators

116 DI Points (Green)

9
10
11
12
13
14
15
16

LOCK

Unlock (Red)

AI/DI 3361S2
Figure 104

AI/DI Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Input/Digital Input Module Indicators

225

AI/DI Status Indicators


The AI/DI status indicators identify the processing state for the AI/DI Module.
A fault light indicates that the module has an internal fault.

Normal States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:

If this is the hot-spare


module, no action is
required.

Control program has not


been loaded into the MP.
Control program has been
loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
The other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Module has detected a fault.

Module is operational, but


should be replaced.

Module has detected


marginal input voltage in a
steady-state condition.

Check sensor signal


strength.
Check sensor positioning.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

226

Chapter 4

Fault and Alarm Indicators

AI/DI Field Power Indicator


The AI/DI field power indicator is lit when a field power problem has occurred.
Field
Power
Yellow
steady

Description

Action

Field power or logic power from one


or more of the redundant sources is
missing.

To isolate the missing power source, use the


TriStation 1131 software.
To determine the actual state, use a voltmeter,
then correct the problem in the external circuit.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Module Indicators

227

Analog Output Module Indicators


This section describes the AO Module indicators including:

AO Status Indicators on page 228

AO Field Alarm Indicator on page 229


Pass (Green)

AO Status
Indicators
Field Alarm
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
PWR/LOAD

Field Alarm (Yellow)

LOCK

Unlock (Red)

AO 3481S2
Figure 105

AO Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

228

Chapter 4

Fault and Alarm Indicators

AO Status Indicators
The AO status indicators identify the processing state for the AO Modules. A fault light
indicates that the module has an internal fault or is missing field power.

Normal State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No light

No
light

No
light

Module may have failed.


Possible conditions include:

If this is the hot-spare


module, no action is
required.

Control program has not


been loaded into the MP.
Control program has been
loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
The other module is active.
No light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator


does not go on within
five minutes, replace the
module.

Field power is missing, if


field power light is also on.

Restore field power and


reseat the module.

Module has detected a fault.

Module is operational,
but should be replaced.

Module has detected


marginal input voltage in a
steady-state condition.

Check sensor signal


strength.
Check sensor
positioning.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Analog Output Module Indicators

Pass

Fault

Active

Lock

Description

Action

No light

No light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

229

a. This symbol ( ) means the indicator is not important for this condition.

AO Field Alarm Indicator


The AO field fault indicator is lit when a field power problem has occurred.
Field
Alarm
Yellow
steady

Description

Action

Field power or logic power from one or


more of the redundant sources is
missing or a field error is detected. A
field error may be an open load or an
out-of-compliance error.

To isolate the missing power source, use the


TriStation 1131 software.
To determine the actual state, use a voltmeter,
then correct the problem in the external circuit.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Triconex General Purpose v2 Systems

230

Chapter 4

Fault and Alarm Indicators

Digital Input Module Indicators


This section describes the DI Module indicators including:

DI Status Indicators on page 231

DI Field Power Indicator on page 232

DI Point Indicators on page 232


Pass (Green)

DI Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
FIELD PWR

Field Power (Yellow)


1
2
3
4
5
6
7

Points
Indicators

8
9
10
11
12
13
14
15
16

LOCK

Unlock (Red)
132 Points (Green)

17
18
19
20
21
22

Points
Indicators

23
24
25
26
27
28
29
30
31
32

DI 3301S2
Figure 106

24v

DI Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Input Module Indicators

231

DI Status Indicators
The DI status indicators identify the processing state for the DI Module.
A fault light indicates that the module has an internal fault.

Normal State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:
Control program has not
been loaded into the MP.

If this is the hot-spare


module, no action is
required.

Control program has been


loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
Other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Module has detected a fault.

Module is operational, but


should be replaced.

Red
steady

Module is unlocked from the


baseplate.

Lock the module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

232

Chapter 4

Fault and Alarm Indicators

DI Field Power Indicator


The DI field power indicator is lit when a field power problem has occurred.
Field
Power
Yellow
steady

Description

Action

Field power or logic power from


one or more of the redundant
sources is missing.

To isolate the missing power source, use the


TriStation 1131 software.
Correct the problem in the field circuit.
If these steps do not solve the problem, replace the
module.

DI Point Indicators
The DI point indicators identify whether the point is energized or not energized.
Point (1-32)

Description

Green steady

Field circuit is energized.

No light

Field circuit is not energized.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Module Indicators

233

Digital Output Module Indicators


This section describes the DO Module 3401S2 and SDO Module 3411S2 indicators, including:

Status Indicators on DO and SDO Modules on page 235

Power/Load Indicator on DO and SDO Modules on page 236

Point Indicators on DO and SDO Modules on page 236

Point Indicators on DO and SDO Modules on page 236

Load Indicators on SDO Modules on page 236


Pass (Green)

DO Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
PWR/LOAD

Power/Load (Yellow)
1
2
3
4
5
6
7

Points
Indicators

116 Points (Green)

9
10
11
12
13
14
15
16

LOCK

DO3401S2
Figure 107

Unlock (Red)

24v

DO Module 3401S2 Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

234

Chapter 4

Fault and Alarm Indicators

Pass (Green)
Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
PWR/LOAD

Power/Load (Yellow)
1
2
3
4
5
6
7

Point
Indicators

POINTS

116 Points (Green)

9
10
11
12
13
14
15
16

LOCK

Unlock (Red)

1
2
3
4
5
6
7

Load
Indicators

LOAD

8
9

116 Points (Yellow)

10
11
12
13
14
15
16

SDO 3411S2 24VDC

Figure 108

SDO Module 3411S2 Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

Digital Output Module Indicators

235

Status Indicators on DO and SDO Modules


The status indicators on the DO and SDO modules identify the processing state.
A fault light indicates that the module has an internal fault. If you have a field fault and a
module fault, resolve the field fault first.

Normal State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault States
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:
Control program has not
been loaded into the MP.

If this is the hot-spare


module, no action is required.

Control program has been


loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
Other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Excessive load current


required.

Correct field fault condition.

Module has detected a fault.

Module is operational, but


should be replaced.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

236

Chapter 4

Fault and Alarm Indicators

Power/Load Indicator on DO and SDO Modules


The power/load indicator on DO and SDO modules is lit when a power/load problem has
occurred.
Power/Load

Description

Action

Yellow
steady

For at least one point, the


commanded state and the
measured state do not agree,
logic power for one or more of
the redundant sources is
missing, or field power for
one or both redundant
sources is outside the
operational range.

To isolate the suspected point or determine the


commanded state of the point, use the TriStation
1131 software.
To determine the actual state of the output, use a
voltmeter, then correct the problem in the external
circuit.
Verify that load current is within product
specification.
If these steps do not solve the problem, replace the
module.

Point Indicators on DO and SDO Modules


The point indicators on DO and SDO modules identify whether the point is energized or not
energized.
Point (1-16)

Description

Green steady

Field circuit is energized.

No light

Field circuit is not energized.

Load Indicators on SDO Modules


The load indicators on SDO modules identify whether there is a fault in the field circuitry.
Point (1-16)

Description

Action

Yellow steady

A fault is detected in the field circuit or


the load is not connected to one or
more output points.

Check for shorted or open loads and fix.


Connect all output points that are not
connected.
Use the TriStation 1131 software to set the
DO Point Options to Non-Supervised for
unused points and points being used to
drive loads that do not draw the
minimum current required for
supervision.

No light

The field circuit is operating properly.

No action is required.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Module Indicators

237

Pulse Input Module Indicators


This section describes the PI Module indicators including:

PI Status Indicators on page 238

PI Field Fault Indicator on page 239

PI Point Indicators on page 239


Pass (Green)

PI Status
Indicators
Field Power
Indicator

PASS

Fault (Red)

FAULT

Active (Green)

ACTIVE
FIELD PWR

Field Power (Yellow)

1
2

Points
Indicators

16 Points (Green)

4
5
6

LOCK

Unlock (Red)

PI 3382S2
Figure 109

PI Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

238

Chapter 4

Fault and Alarm Indicators

PI Status Indicators
The PI status indicators identify the processing state for the PI Module.
A fault light indicates that the module has an internal fault.

Normal State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:
Control program has not
been loaded into the MP.

If this is the hot-spare


module, no action is
required.

Control program has been


loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
The other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Module has detected a fault.

Module is operational, but


should be replaced.

Module has detected


marginal input voltage in a
steady-state condition.

Check sensor signal strength.


Check sensor positioning.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Pulse Input Module Indicators

239

PI Field Fault Indicator


The PI field fault indicator is lit when a field power problem has occurred.
Field

Description

Action

Yellow
steady

Field power or logic power from


one or more of the redundant
sources is missing.

To isolate the missing power source, use the


TriStation 1131 software.

PI Point Indicators
The PI point indicators identify whether the point is greater than or less than 0.5 hertz.
Point (1-6)

Description

Green steady

Input frequency is greater than 0.5 Hz.

No light

Input frequency is less than 0.5 Hz.

Planning and Installation Guide for Triconex General Purpose v2 Systems

240

Chapter 4

Fault and Alarm Indicators

Solid-State Relay Output Module Indicators


This section describes the SRO Module indicators including:

SRO Status Indicators on page 241

SRO Point Indicators on page 242


Pass (Green)

SRO Status
Indicators

PASS

Fault (Red)

FAULT
ACTIVE

Active (Green)
1
2
3
4
5
6
7

Points
Indicators

8
9
10
11
12
13
14
15
16

LOCK

Unlock (Red)
132 Points (Green)

17
18
19
20
21
22
23

Points
Indicators

24
25
26
27
28
29
30
31
32

RO 3451S2
Figure 110

24v

SRO Front Panel Indicators

Planning and Installation Guide for Triconex General Purpose v2 Systems

Solid-State Relay Output Module Indicators

241

SRO Status Indicators


The SRO status indicators identify the processing state for the SRO Module.
A fault light indicates that the module has an internal fault.

Normal State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

Green
steady

No
light

Module is operating normally.

No action is required.

Fault State
Pass

Fault

Active

Lock

Description

Action

Green
steady

No
light

No
light

No
light

Module may have failed.


Possible conditions include:
Control program has not
been loaded into the MP.

If this is the hot-spare


module, no action is
required.

Control program has been


loaded into the MP, but has
not been started up.

If the module is active,


replace module.

Module has just been


installed and is currently
running start-up diagnostics.
The other module is active.
No
light

Red
steady

No
light

Module may be in the


process of power-up selftest.

If the Pass indicator does not


go on within five minutes,
replace the module.

Module has detected a fault.

Module is operational, but


should be replaced.

Module has detected


marginal input voltage in a
steady-state condition.

Check sensor signal strength.


Check sensor positioning.

Red
steady

Module is unlocked from the


baseplate.

Lock module using a


1/4-inch flat-blade
screwdriver.

Green
steady

Red
steady

Indicators/signal circuitry
on the module are
malfunctioning.

Replace the module.

No
light

No
light

Indicators/signal circuitry
on the module are
malfunctioning

Replace the module.

a. This symbol ( ) means the indicator is not important for this condition.

Planning and Installation Guide for Triconex General Purpose v2 Systems

242

Chapter 4

Fault and Alarm Indicators

SRO Point Indicators


The SRO point indicators identify whether the point is energized or not energized.
Point (1-32)

Description

Green steady

Field circuit is energized.

No light

Field circuit is not energized.

Planning and Installation Guide for Triconex General Purpose v2 Systems

A
Pin-Outs for Cables and Connectors

Ethernet Connectors 244


Serial Connectors 247
Ethernet Cables 250
Serial Cables 251
Diagread Cables and Debug Connectors 255

Planning and Installation Guide for Triconex General Purpose v2 Systems

244

Appendix A

Pin-Outs for Cables and Connectors

Ethernet Connectors
This section includes pin-out information for these Ethernet connectors:

10BaseT and 100BaseTX Ethernet Connectors on page 244

AUI 10 Megabit Ethernet MAU Connectors on page 244

MII Ethernet MAU Connectors on page 245

10BaseT and 100BaseTX Ethernet Connectors


This section includes pin-out information for 10BaseT and 100BaseTX Ethernet connectors. The
MP Baseplate and CM Baseplate include these type of connectors, which are typically used to
connect to a PC running the TriStation 1131 software.
Shield
1 TD+
2 TD
3 RD+
4
5
6 RD
7
8

Table 42
RJ-45 Pin

10BaseT and 100BaseTX Ethernet Connector Pin-Outs


Signal

Direction

Function

TD+

Out

Transmit data +

TD-

Out

Transmit data

RD+

In

Receive data +

NC

NC

RD-

In

NC

NC

Shield

Housing

Receive data

Safety ground

AUI 10 Megabit Ethernet MAU Connectors


This section includes pin-out information for AUI 10 megabit Ethernet MAU connectors, which
are included on the CM Baseplate.
Slide Clip

Table 43
DB15 Pin

1
2
3
4
5
6
7
8
Shield

9
10
11
12
13
14
15

AUI 10 Megabit Ethernet MAU Connector Pin-Outs


Signal

Direction

Ground

CI+

In

Transmit data

DO+

Out

Data output +

Ground

DI+

In

Data input +

Ground

Receive data

Planning and Installation Guide for Triconex General Purpose v2 Systems

Function

Ethernet Connectors

Table 43
DB15 Pin

245

AUI 10 Megabit Ethernet MAU Connector Pin-Outs (continued)


Signal

Direction

Function

NC

Ground

In

MAU present detect

CI

In

Collision input

10

DO

Out

Data output

11

Ground

12

DI

In

Data input

13

+12 V

Out

MAU power

14

Ground

15

NC

MII Ethernet MAU Connectors


This section includes pin-out information for MII Ethernet MAU connectors, which are included
on the CM Baseplate.
Table 44
1

20

Shield

21

40

DB40Pin

MII Ethernet MAU Connector Pin-Outs


Signal

Direction

Function

+5 V

Out

MII MAU power

MDIO

In/Out

Management data

MDC

Out

Management data clock

RxD<3>

In

Receive data 3

RxD<2>

In

Receive data 2

RxD<1>

In

Receive data 1

RxD<0>

In

Receive data 0

Rx DV

In

Receive data valid

Rx_Clk

In

Receive clock

10

Rx_Er

In

Receive error

11

Tx_Er

Out

Transmit error

12

Tx_Clk

In

Transmit clock

13

Tx_En

Out

Transmit enable

14

TxD<0>

Out

Transmit data 0

15

TxD<1>

Out

Transmit data 1

16

TxD<2>

Out

Transmit data 2

17

TxD<3>

Out

Transmit data 3

Planning and Installation Guide for Triconex General Purpose v2 Systems

246

Appendix A

Pin-Outs for Cables and Connectors

Table 44
DB40Pin

MII Ethernet MAU Connector Pin-Outs (continued)


Signal

Direction

Function

18

Col

In

Collision (half-duplex)

19

CRS

In

Carrier receive sense

20

+5 V

Out

MII MAU power

21

+5 V

Out

MII MAU power

22

Logic ground

MII MAU logic ground

23

Logic ground

MII MAU logic ground

24

Logic ground

MII MAU logic ground

25

Logic ground

MII MAU logic ground

26

Logic ground

MII MAU logic ground

27

Logic ground

MII MAU logic ground

28

Logic ground

MII MAU logic ground

29

Logic ground

MII MAU logic ground

30

Logic ground

MII MAU logic ground

31

Logic ground

MII MAU logic ground

32

Logic ground

MII MAU logic ground

33

Logic ground

MII MAU logic ground

34

Logic ground

MII MAU logic ground

35

Logic ground

MII MAU logic ground

36

Logic ground

MII MAU logic ground

37

Logic ground

MII MAU logic ground

38

Logic ground

MII MAU logic ground

39

Logic ground

MII MAU logic ground

40

+5 V

Out

MII MAU power

Planning and Installation Guide for Triconex General Purpose v2 Systems

Serial Connectors

247

Serial Connectors
This section includes pin-out information for these serial connectors:

RS232 Pin-Outs on page 247

RS485 Pin-Outs on page 248

RS232 Pin-Outs
This section includes pin-out information for RS232 serial connections, which are typically
used for Modbus communication. The serial ports on the MP and CM Baseplate can be
configured in TriStation 1131 software as RS232 or RS485.
Table 45
6
7
8
9

1
2
3
4
5

DB9 Pin

Shield

RS232 Pin-Outs
Signal

Direction

RS232 Function

CD

In

Carrier detect

RXD

In

Receive data

TXD

Out

Transmit data

DTR

Out

Data terminal ready

GND

Signal ground

DSR

Not used (data set ready)

RTS

Out

Request to send

CTS

In

Clear to send

RI

Not used (ring indicator)

Shield

Safety ground

Housing

Behavior and Effects of the RS232 Signals


This table describes the interaction between a module and RS232 signals. Spacing (on or 0)
occurs when RS232 signals are between +6 and +12 VDC; marking (off or 1) occurs when they
are between 6 and 12 VDC. The maximum cable length is 50 feet (15 meters), but can be
extended using modems.
Table 46

Behavior and Effects of the RS232 Signal

Signals

Designator

Description

Carrier Detect

CD

In HRDWR handshake mode, module ignores any data received


while CD is not asserted. The CD signal must be asserted by the
connected equipment for the module to receive messages.
When not in HRDWR handshake mode, the module ignores the
CD signal.

Receive Data

RXD

Module receives serial data

Planning and Installation Guide for Triconex General Purpose v2 Systems

248

Appendix A

Pin-Outs for Cables and Connectors

Table 46

Behavior and Effects of the RS232 Signal

Signals

Designator

Description

Transmit Data

TXD

Module transmits serial data

Data Terminal
Ready

DTR

Always asserted by the module when the port is configured.

Data Set Ready

DSR

Input signal to module. Ignored in all cases.

Request to Send

RTS

When in HRDWR handshake mode, the module set RTS on


when it has data to send.
When not in HRDWR handshake mode, the module asserts the
RTS signal continuously.

Clear to Send

CTS

When in HRDWR handshake mode, the module waits for CTS to


go on before transmitting data.
When not in HRDWR handshake mode, the module ignores CTS
and transmits data as soon as it is available.

Data Carrier
Detect

DCD

Module ignores DCD and always accepts data from RXD

Transmitted Data

TD

Transmitted data from the module

Received Data

RD

Received data from the equipment connected to the port

RS485 Pin-Outs
This section includes pin-out information for RS485 serial connections, which are typically
used for Modbus communication. The serial ports on the MP and CM Baseplate can be
configured in TriStation 1131 software as RS232 or RS485.
Table 47
6
7
8
9
Shield

1
2
3
4
5

DB9 Pin

RS485 Pin-Outs
Signal

Direction

RS485 Function

RD-A

In

Receive data

SD-A

Out

Transmit data

GND

Signal ground

SD-B

Out

Transmit data, invert

RD-B

In

Receive data, invert

OUT

Term

5 VDC through 1k

Shield

Safety ground

Housing

Planning and Installation Guide for Triconex General Purpose v2 Systems

Serial Connectors

249

RS485 Signal Descriptions


This table describes RS485 signals, which are transmitted over a cable of twisted-pair-wires.
The polarity of the 2-to-6-volt differential between the two wires indicates whether the data is
marking or spacing. If terminal A is negative with respect to terminal B, the line is marking. If
terminal A is positive with respect to terminal B, the line is spacing. The maximum cable length
is dependent on the wire used. For example, using 24AWG twisted-pair wire, the maximum
length is 4,000 feet (1.2 kilometers), but can be extended using modems.
Table 48

RS485 Signal Descriptions

Signal

Designator

Description

Transmit Data
Transmit Data
Inverted

SD-A
SD-B

Module transmits serial data

Receive Data
Receive Data
Inverted

RD-A
RD-B

Module receives serial data

Signal Ground

GND

Signal ground

5 VDC through 1k

Not used

Planning and Installation Guide for Triconex General Purpose v2 Systems

250

Appendix A

Pin-Outs for Cables and Connectors

Ethernet Cables
Ethernet cables can be used to connect the MP Modules or CMs to a PC running the TriStation
1131 software or an Ethernet hub.

Cross-Over Cable
Cross-over cables can be used to link the Ethernet card on a PC to the Ethernet connectors on
the MP or CM Baseplate. The cable can be used for 10BaseT or 100BaseTX communication.
Crossover
cable
TD+ 1
TD 2
RD+ 3
4
5
RD 6
7
8
Shield

1 TD+
2 TD
3 RD+
4
5
6 RD
7
8
Shield

Crossover
cable

Crossover
cable
RJ-45
Connector

1
2
3
4
5
6
7
8

RJ-45
Connector

1
2
3
4
5
6
7
8

Shield

Straight-Through Cable
Straight-through cables can be used to link the Ethernet connector on the MP or CM Baseplate
to an Ethernet hub, or link the PC running TriStation 1131 software to an Ethernet hub. The cable
can be used for 10BaseT or 100BaseTX communication.

Straight-Through Cable
TD+ 1
TD 2
RD+ 3
4
5
RD 6
7
8
Shield

1 TD+
2 TD
3 RD+
4
5
6 RD
7
8
Shield
Straight-Through Cable

Straight-Through Cable
1
2
3
4
5
6
7
8

RJ-45
Connector

RJ-45
Connector

Shield

Planning and Installation Guide for Triconex General Purpose v2 Systems

1
2
3
4
5
6
7
8

Serial Cables

251

Serial Cables
This section describes serial cables which are generally used for Modbus communication. Cable
types include:

RS-232 Serial Cable on page 251

RS-485 Serial Cables on page 251

RS-232 Serial Cable


This figure depicts the RS-232 serial cable, which is a standard null-modem cable used to link
the serial connector on the MP Baseplate to a PC acting as the Modbus master.

RS-232 Modbus Serial Cable


(Null Modem)
Housing D9
TXD 3
RXD 2
Signal Ground 5
DTR 4
DSR 6
CD 1
RTS 7
CTS 8

D9 Housing
2 RXD
3 TXD
5 Signal Ground
4 DTR
6 DSR
1 CD
7 RTS
8 CTS

MP Baseplate
Female Connector
P2 (9 pins) (molded hood)

PC Female Connector
P1 (9 pins)

Housing
Ground

RS-485 Serial Cables


RS485 serial cables are typically used for point-to-point (direct) and multi-point (network)
connections between a CM and a Modbus master, or point-to-point (direct) connections
between an MP and a Modbus master. The CM serial ports are configurable for multi-point RS485 operation without using modems.

Planning and Installation Guide for Triconex General Purpose v2 Systems

252

Appendix A

Pin-Outs for Cables and Connectors

This table identifies the RS-485 network specifications.


Table 49

RS-485 Serial Cable Specifications

Item

Specification

Nodes

One Modbus master and one slave

Cable length

Cable dependent4,000 ft (1.2 km) maximum using


24-AWG twisted-pair wire (shielding recommended)

Transmission rate (bps)

1200, 2400, 4800, 9600, 19.2 K, 38.4 K, 57.6 K, 115.2 K

The network trunk should consist of double twisted-pair wires. When the trunk consists of
double twisted pairs, one pair serves as the output line for the Modbus master (input line to all
slaves). The other pair serves as the input line to the Modbus master (output line from all
slaves). When the trunk consists of a single twisted pair, it serves as both the output and input
lines to the Modbus master and all slaves. The trunk accommodates up to 32 two-foot branches,
without restriction on the distance between branches.

RS485 Slave Network


When a CM is a slave in a multi-point network, multiple transmitters connect to the same
conductor. One transmitter can be active at any time; otherwise, the signal is distorted. Each
node must be in the tristate (or off) mode. To set the tristate mode for the CM, set the Handshake
mode to Hardware in the TriStation 1131 application.
Network Trunk
Trunk R
Trunk T
RD-A RD-B
SD-A SD-B

CM or MP
Serial Port
1

Shield

RD-A

SD-B

7
3

SD-A
RD-B

8
4

5 VDC through 1 K7 (optional)

9
5

Signal Ground (optional)


1 K7

Planning and Installation Guide for Triconex General Purpose v2 Systems

Serial Cables

253

RS485 Master Network


Network Trunk
Trunk R
Trunk T
RD-A RD-B
SD-A SD-B

CM or MP
Serial Port
1

Shield

RD-A

SD-B

7
3

SD-A
RD-B

8
4

5 VDC through 1 K7 (optional)

9
5

Signal Ground (optional)


1 K7

RS485 Cable Selection


These are guidelines for selecting an RS485 cable for a Modbus network.

Maintain a cable impedance of greater than or equal to 100 ohms.

Supply a separate shield for each twisted pair.

Use double twisted-pair networks to house the pairs in a single sheath or in separate
sheaths.

Use branch cable of the same quality as the trunk cable, but of less rigid construction.
For example, use Belden 9182 (150-ohm) for the trunk and Belden 9729 (150-ohm) for
the branches.

Follow all applicable local codes.

Terminate the cable in the characteristic impedance of the cable.

RS485 Cable Termination


RS-485 trunk cable termination (point-to-point or multi-point for the CM, point-to-point for the
MP) greater than 650 feet (200 meters) requires termination at each end. Traditionally, resistors
are connected to each end of the cable. This technique matches the cable impedance and
prevents signal reflections which could cause data errors. However, this technique has the
following three undesirable side effects:

When no driver is active on the pair, the resistors pull the two wires together. Noise
even very low-level noisecan appear to be data when the wires are in this state.

When a driver is active on the pair but not sending data, the resistors cause 33 mA of
DC current to flow in the cable. This is an excessive load on the driver.

When a driver is transmitting data over the cable, the resistors lower the signal level
and consequently lower the immunity to noise.

Planning and Installation Guide for Triconex General Purpose v2 Systems

254

Appendix A

Pin-Outs for Cables and Connectors

A better technique for terminating the cable pair is to use an RC network and pull-up/pulldown resistors. This reduces power consumption and forces the pair to a valid data state when
no driver is active.
For both types of termination, resistor values must match the characteristic impedance of the
cable.

Traditional Network Termination


Cable R

Modbus
Master

SD-A
SD-B
Ground
RD-A
RD-B
+ 5 VDC through 1 kW

SD-A
SD-B
Ground
RD-A
RD-B
+ 5 VDC through 1 kW

Cable T

MP
Slave

Recommended Network Termination Using a Double-Pair Network


.01 mf

.01 mf

Cable T

.01 mf

Modbus
Master

SD-A
SD-B
Ground
RD-A
RD-B
+ 5 VDC through 1 k

Cable R

SD-A
SD-B
Ground
RD-A
RD-B
+ 5 VDC through 1 kW

.01 mf

MP
Slave

Planning and Installation Guide for Triconex General Purpose v2 Systems

Diagread Cables and Debug Connectors

255

Diagread Cables and Debug Connectors


This section includes information about diagread cables and Debug connectors that are
available for the MP, CM, and I/O modules.

Diagread Cable
This figure depicts a diagread cable.
Diagread Cable

MP and
Left-Position CM
Debug Connector
1
2
3
4
5
6

1
2
3
4
5
6

2
3
5

9-pin D-Sub-to-Modular

Straight-Through RJ-12 Cable


(standard 6-wire telephone cable)
6-pin RJ12 Adapter

Debug Connector for MP and Left-Position CMs


For the MP and left-position CMs, the Debug connector uses pins 1, 2 and 3.
Table 50
1
2
3
4
5
6

RJ12 Pin

MP and Left-Position CM Debug Connector Pin-Outs


Signal

Direction

Description

TXD

Out

Module Diagread Transmit Data

RXD

In

Module Diagread Receive Data

GND

Module Ground

Debug Connector for I/O and Right-Position CMs


For I/O and right-position CMs, the Debug connector uses pins 4, 5 and 6.
Table 51
1
2
3
4
5
6

RJ12 Pin

I/O and Right-Position CM Debug Connector Pin-Outs


Signal

Direction

Description

TXD

Out

Module Diagread Transmit Data

RXD

In

Module Diagread Receive Data

GND

Module Ground

Planning and Installation Guide for Triconex General Purpose v2 Systems

256

Appendix A

Pin-Outs for Cables and Connectors

Planning and Installation Guide for Triconex General Purpose v2 Systems

B
Non-Incendive Circuit Parameters

MP and CM Non-Incendive Circuit Parameters 258


Hazardous Location HART Baseplate Non-Incendive Circuit Parameters 259

Planning and Installation Guide for Triconex General Purpose v2 Systems

258

Appendix B

Non-Incendive Circuit Parameters

MP and CM Non-Incendive Circuit Parameters


This figure depicts special parameters which apply to Main Processor and Communication
Modules for non-incendive communication circuits in the field. These parameters are extracted
from Triconex Drawing 9110043-001, REV. A.

MP
Model
3101S2

CM
Model
3201S2

Figure 111

CLASS 1, DIV 2
HAZARDOUS LOCATION

CLASS 1, DIV 2
OR NON-HAZARDOUS

NETWORK

(9) SHIELDED TWISTED PAIR IN/OUT SIGNALS

SERIAL PORT

(9) SHIELDED IN/OUT SIGNALS

RS-232 DIAG READ

(5) IN/OUT SIGNALS

NETWORK #1

(9) SHIELDED TWISTED PAIR IN/OUT SIGNALS

NETWORK #2

(9) SHIELDED TWISTED PAIR IN/OUT SIGNALS

SERIAL PORT #1

(9) SHIELDED IN/OUT SIGNALS

SERIAL PORT #2

(9) SHIELDED IN/OUT SIGNALS

SERIAL PORT #3

(9) SHIELDED IN/OUT SIGNALS

RS-232 DIAG READ

(3) IN/OUT SIGNALS

ASSOCIATED
APPARATUS
(NOTE 1)

ASSOCIATED
APPARATUS
(NOTE 1)

Non-Incendive Communication Circuits Simplified Schematic

Note 1 in the figure applies to FMRC-approved apparatus. The voltage (Vmax) and current
(Imax) that the load device can receive must be equal to or greater than the maximum open
circuit voltage (Voc) and maximum short circuit current (Isc) that can be delivered by the source
device. In addition, the maximum capacitance (Ci) and inductance (Li) of the load, which is not
prevented by circuit components from providing a stored energy charge to the field wiring (for
example, diode across a winding to clamp an inductive discharge), and the capacitance and
inductance of the interconnecting wiring must be equal to or less than the capacitance (Ca) or
inductance (La) that can be driven by the source device.
MP Model 3101S2

CM Model 3201S2

NETWORK

SERIAL PORT and


RS-232 DIAG READ

NETWORKS
1 and 2

SERIAL PORTS 1, 2, 3
and RS-232 DIAG READ

Voc/Vmax

1V/1V

10V/10V

1V/1V

10V/10V

Isc/Imax

1mA/1mA

30mA/30mA

1mA/1mA

30mA/30mA

Ca/Ci

11nf/11nf

15uF/0

11nf/11nf

15uF/0

La/Li

1.3mH/1.3mH

85mH/0

1.3mH/1.3mH

85mH/0

Figure 112

Signal Levels for Non-Incendive Communication Circuits

For detailed information on signal data (inputs or outputs), see the manufacturers
documentation.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Hazardous Location HART Baseplate Non-Incendive Circuit Parameters

259

Hazardous Location HART Baseplate Non-Incendive


Circuit Parameters
The following tables describe non-incendive circuit parameters for hazardous location HART
baseplates. While reading these tables, please note the following:

For C, ATEXmax = C internal, max (Ci) + C external, max (Co)

For L, ATEXmax = L internal, max (Li) + L external, max (Lo)

Note

The external maximums (Lo and Co) include field wiring and the field device.

This table describes non-incendive circuit parameters for the 2354AS2 Analog Input HART
Hazardous Location Baseplate.
Table 52

Cable and Load Parameters for AI HART Baseplate 2354AS2

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

19 to 30 V

Maximum voltage

Um

Um

32 V

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.160 A

Maximum output power

Po

Po

1.280 W

C external, maximum

Co

Ca

1.162 F

L external, maximum

Lo

La

4.969 mH

Maximum input voltage

Ui

Vmax

9V

Maximum input current

Ii

Imax

0.030 A

Maximum input power

Pi

Pi

0.270 W

C internal, maximum

Ci

Ci

0.0683 F

L internal, maximum

Li

Li

30.85 H

AI Field + Connection Specifications

AI Field Connection Specifications

Planning and Installation Guide for Triconex General Purpose v2 Systems

260

Appendix B

Non-Incendive Circuit Parameters

This table describes non-incendive circuit parameters for the 2483AS2 Analog Output HART
Hazardous Location Baseplate.
Table 53

Cable and Load Parameters for AO HART Baseplate 2483AS2

Feature

IEC
Symbol

ISA
Symbol

Description for Zone 2 Group IIB

Operating temperature range

Tamb

Tamb

32 F to 140 F (0 C to 60 C)

Working voltage

Uw

Uw

30 V

Maximum voltage

Um

Um

32 V

Maximum output voltage

Uo

Voc

32 V

Maximum output current

Io

Isc

0.256 A

Maximum output power

Po

Po

1.856 W

C external, maximum

Co

Ca

1.15 F

L external, maximum

Lo

La

4.95 H

C internal, maximum

Ci

Ci

Additional isolation required; MTL 4546 or


similar.

L internal, maximum

Li

Li

Additional isolation required; MTL 4546 or


similar.

Output Connection (L+) Specifications

Planning and Installation Guide for Triconex General Purpose v2 Systems

C
HART Communication

Overview 262
Triconex 4850 Hart Multiplexer 265

Planning and Installation Guide for Triconex General Purpose v2 Systems

262

Appendix C

HART Communication

Overview
This appendix describes HART communication through Tri-GP systems.
Highway Addressable Remote Transducer protocol (HART) is a bi-directional industrial field
communication protocol used to communicate between intelligent field instruments and host
systems over 420 mA instrumentation wiring.
Invensys offers these components to enable HART communication between HART devices in
the field and Configuration and Asset Management Software running on a PC.

2354S2 Analog Input HART Baseplate

2354AS2 Analog Input HART Hazardous Location Baseplate

2483S2 Analog Output HART Baseplate

2483AS2 Analog Output HART Hazardous Location Baseplate

Triconex 4850 HART Multiplexer


Workstation PC
running instrument management
software
RS232

RS232/RS485
converter

RS485

SHLD

TA

TB

SHLD

TA

TB

J22
J18

J27
1

TRICONEX

TRICONEX

PASS
FAULT
ACTIVE
FIELD PWR

PASS
FAULT
ACTIVE
FIELD PWR

2
3
4

420 mA

5
6
7
8

PWR
FAULT
HOST
HART

9
10
11
12
13

14
15
16

17

HART transmitter
and valve

18

4850
TRICONEX

19
20
21
22
23
24
25
26
27
28
29
30
31
32
J19

HART AI Baseplate

Figure 113

Typical Tri-GP HART Analog Input Installation

Planning and Installation Guide for Triconex General Purpose v2 Systems

Overview

263

Workstation PC
running instrument management
software
RS232

RS232/RS485
converter

RS485

SHLD

TA

TB

SHLD

TB

TA

J22

420 mA

J18

J27
1

TRICONEX

TRICONEX

PASS
FAULT
ACTIVE
FIELD PWR

PASS
FAULT
ACTIVE
FIELD PWR

2
3
4

I
P

5
6

PWR

HOST

HART

FAULT

9
10
11
12
13
14
15
16

4850
TRICONEX

420 mA

I
P
HART transmitters
and valves

J19

HART AO Baseplate

Figure 114

Typical Tri-GP HART Analog Output Installation

Planning and Installation Guide for Triconex General Purpose v2 Systems

264

Appendix C

HART Communication

Workstation PC
running instrument management
software
RS232

RS232/RS485
converter

RS485

SHLD

TA

TB

SHLD

TB

MTL4546
Isolator

TA

J22

420 mA

J18

J27
1

TRICONEX

TRICONEX

PASS
FAULT
ACTIVE
FIELD PWR

PASS
FAULT
ACTIVE
FIELD PWR

MTL4546
Isolator

MTL4546
Isolator

3
4
5
6

PWR

HOST

HART

FAULT

9
10
11

MTL4546
Isolator

12
13
14
15
16

4850
TRICONEX

420 mA

I
P
HART transmitters
and valves

J19

HART AO Baseplate

Figure 115

Typical Tri-GP HART Analog Output Hazardous Location Installation

If you are using HART communication in a safety-related application, see the Safety
Considerations Guide for Triconex General Purpose v2 Systems for more information.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Triconex 4850 Hart Multiplexer

265

Triconex 4850 Hart Multiplexer


The Triconex 4850 HART Multiplexer provides an interface between HART smart devices in the
field and Configuration and Asset Management Software running on a PC.
The Triconex 4850 HART Multiplexer mounts directly onto these Tri-GP baseplates:

2354S2 Analog Input HART Baseplate

2354AS2 Analog Input HART Hazardous Location Baseplate

2483S2 Analog Output HART Baseplate

2483AS2 Analog Output HART Hazardous Location Baseplate

Note

The Triconex 4850 HART Multiplexer operates independently of the AI and the AO
modules, so there is no interference from the multiplexer to these modules.

For more information about the HART compatible baseplates, including simplified schematics
and field connection diagrams, see Analog Input Components on page 49 and Analog Output
Components on page 82.
For more information about the Triconex 4850 HART Multiplexer, including PC software
installation and configuration, see the Triconex 4850 HART Multiplexer Instruction Manual.

Planning and Installation Guide for Triconex General Purpose v2 Systems

266

Appendix C

HART Communication

Installing the Triconex 4850 HART Multiplexer


The Triconex 4850 HART Multiplexer mounts directly onto the Tri-GP baseplate in socket J42 as
shown in this figure.
Triconex 4850 Multiplexer

Figure 116

Triconex 4850 Multiplexer Mounted on Tri-GP Baseplate

After you mount the Triconex 4850 HART Multiplexer onto the baseplate, secure it by
tightening the screws on the back of the baseplate using a Phillips-head screwdriver with a shaft
smaller than 4 millimeters.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Triconex 4850 Hart Multiplexer

267

Triconex 4850 HART Multiplexer Indicators


This section describes the LED status indicators on the front of the Triconex 4850 HART
Multiplexer.
Table 54

Triconex 4850 HART Multiplexer Status Indicators

Indicator

Color

State

Description

PWR

Green

Off

Multiplexer is not receiving power.

On

Multiplexer is receiving power.

Off

Multiplexer is in the running state.

Steady flash

Multiplexer rebuild is in progress.

Short/long flash

No HART loops found.

On (steady)

A fault was detected and multiplexer operation


has halted.

Off

No communication on the channel.

Short flash (0.25 sec)

Correctly framed message received by the


multiplexer.

Long flash (1 sec)

Response transmittedthis is re-triggerable so


repeated transmissions will leave the indicator
permanently on.

Off

No communication on the channel.

Short flash (0.25 sec)

Message transmitted.

Long flash (1 sec)

Response receivedthis is re-triggerable so


repeated receptions will leave the indicator
permanently on.

FAULT

HOST

HART

Red

Yellow

Yellow

Planning and Installation Guide for Triconex General Purpose v2 Systems

268

Appendix C

HART Communication

Planning and Installation Guide for Triconex General Purpose v2 Systems

D
Warning Labels

This appendix provides a physical description of warning labels which must be prominently
attached to the controller for systems in which these hazards apply.
Labels must meet the requirements of ANSI Z535, ISO 3864, and IEC 1310-1.
Labels are available from Invensys upon request.

General Hazard
This figure is an example of a general hazard label.

Safety alert symbol


Black triangle, orange exclamation point

Signal word panel


Safety orange per ANSI Z535.1
Pantone 152C
13 parts yellow, 3 parts warm red, part black
Signal word
Sans serif font, all capital letters,
minimum letter height 1.5 x
message panel text height

White background
Yellow background

WARNING
GENERAL HAZARD.
Service restricted to
trained personnel only.

Optional
black border

Base width
30 mm (1.2 inch)
minimum

Figure 117

Black border
0.06 x base width

Black letters on
white background
Sans serif font
Upper or lower case
2.54 mm (0.10 inch) high

General Hazard Label

Planning and Installation Guide for Triconex General Purpose v2 Systems

270

Appendix D

Warning Labels

Hazardous Voltage
This figure is an example of a hazardous voltage label.

Safety alert symbol


Black triangle, orange exclamation point

Signal word panel


Safety orange per ANSI Z535.1
Pantone 152C
13 parts yellow, 3 parts warm red, part black
Signal word
Sans serif font, all capital letters,
minimum letter height 1.5 x
message panel text height

White background
Yellow background

WARNING
HAZARDOUS VOLTAGE.
Contact may cause electric shock
or burn.
Service restricted to
trained personnel only.

Optional
black border

Base width
30 mm (1.2 inch)
minimum

Figure 118

Black border
0.06 x base width

Black letters on
white background
Sans serif font
Upper or lower case
2.54 mm (0.10 inch) high

Hazardous Voltage Label

Hot Surface
This figure is an example of a hot surface label.

Safety alert symbol


Black triangle, orange exclamation point

Signal word panel


Safety orange per ANSI Z535.1
Pantone 152C
13 parts yellow, 3 parts warm red, part black
Signal word
Sans serif font, all capital letters,
minimum letter height 1.5 x
message panel text height

White background
Yellow background

WARNING
HOT SURFACE.
Contact may cause burns.
Service restricted to
trained personnel only.

Optional
black border

Base width
30 mm (1.2 inch)
minimum

Figure 119

Black border
0.06 x base width

Black letters on
white background
Sans serif font
Upper or lower case
2.54 mm (0.10 inch) high

Hot Surface Label

Planning and Installation Guide for Triconex General Purpose v2 Systems

E
Recommended Parts for Replacement

This table lists information on the recommended parts for replacement of Tri-GP components.
Part Description

Manufacturer

Part Number

Usage

Fuse, A

Invensys

1410054-001

Littlefuse

273.75

SRO Baseplate and MP


Baseplate

Fuse, 5x20 mm, 8 A,


slow-acting

Invensys

1410056-001

Littlefuse

218008

MP Baseplate and I/O


Extender Module

16-point plug connector

Invensys

1420048-016

I/O Baseplate

Phoenix

1901742

Expansion cable, 2-foot

Invensys

4000212-002

I/O Extender Module

Terminator

Invensys

4000138-001

I/O Extender Module

Address plug
(available only as part of
the Trident/Tri-GP
Accessory Kit)

Invensys

7400215-0xx

MP and I/O Baseplates

Trident/Tri-GP Accessory
Kitincludes one set of
spare fuses, two sets of
address plugs (1 through
10), one set of address
plugs (11 through 20), one
set of address plugs (21
through 32), one set of
address plugs (33 through
43), one set of address
plugs (44 through 54), and
one set of address plugs (55
through 63)

Invensys

(xx = address 01-63)

3000696-001
(Model 8401)

MP, I/O, and SRO Baseplates;


I/O Extender Module

Planning and Installation Guide for Triconex General Purpose v2 Systems

272

Appendix E

Recommended Parts for Replacement

Planning and Installation Guide for Triconex General Purpose v2 Systems

F
Panel Labels

AI/DI Hazardous Location External Termination Panels 275


RTD/TC/AI External Termination Panels 276
SSR Input External Termination Panels 277

Planning and Installation Guide for Triconex General Purpose v2 Systems

274

Appendix F

Panel Labels

Overview
This appendix shows how to apply external termination panel (ETP) labels. Because some
modules require a two-panel arrangement to accommodate all points, each standard panel must
have a set of labels that indicate the correct range of points. Panels that are not used in a twopanel arrangement are labelled at the factory.
Standard panels that require labels include the appropriate labels as loose-piece parts. Since a
panel can be connected as the first or second panel, a set of labels appropriate for either range is
provided with every panel, with a duplicate label for each row of terminals on each terminal
block. Any unused labels can be stored or discarded.
Attach the appropriate labels to each panel as shown in these illustrations.

Planning and Installation Guide for Triconex General Purpose v2 Systems

AI/DI Hazardous Location External Termination Panels

275

AI/DI Hazardous Location External Termination Panels


This figure illustrates placement of labels for 32-point AI and DI hazardous location ETPs.
TRICONEX

EXT TERM
   

 


17

REV B


R27
R28

23

TB4

R29

22
R

13
R

14

24

R
15

R32

R



   
    

19
R
20
R
3
21
R

12
R

R4
R5

R7
R8

R25

18
R

9
R
10
11
R

R3

R2

R1

SN

TB1

R30

7400275

R31

Panel
Type
9573-610F DI
9792-310F AI

J1
TB2 TB3 TB5 

J2

J3

L-

P1

P2

Labels (for front and back row)


1

9 10 11 12 13 14 15 16

First Panel

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Second Panel

Figure 120

AI/DI Hazardous Location ETP Label Placement

Planning and Installation Guide for Triconex General Purpose v2 Systems

276

Appendix F

Panel Labels

RTD/TC/AI External Termination Panels


This figure illustrates placement of labels for Model 9764-510F 16-point RTD/TC/AI ETPs.

16
16

13

12

14
15

14
15

13

12

11

R16

11

10

10
9

3
4

U16

R15

3
4

14
15

13

12

16
16

14
15

13

12

11

11

10
9

10

3
4

3
4

14
15

13

16
16

14
15

12
11

13

12

11
10

3
4

10
9

3
4

16
16

14
15

13

12
11

14
15

13

12

11
10

3
4

10
9

3
4

ISOLATED
RTD INPUT

ANALOG
DEVICES

ISOLATED
RTD INPUT

U15

R14

7B34

ANALOG
DEVICES

U14

R13

7B34

ISOLATED
RTD INPUT

ISOLATED
RTD INPUT

U13

ANALOG
DEVICES

ISOLATED
RTD INPUT

U12
R12

7B34

ANALOG
DEVICES

7B34

ANALOG
DEVICES

R11

7B34

ISOLATED
RTD INPUT

U11

R10

J4

J3

ANALOG
DEVICES

ISOLATED
RTD INPUT

U10

R9

7B34

ANALOG
DEVICES

ISOLATED
RTD INPUT

U9

R8

SN

7B34

ANALOG
DEVICES

U8

R7

7B34

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

U7

R6

7B32

U6

R5

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

U5

R4

ISOLATED

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

U4

R3

ISOLATED

ISOLATED
TC INPUT

PROCESS
ANALOG
DEVICES CURRENT INPUT

7B32

ANALOG
DEVICES

ISOLATED
TC INPUT

ISOLATED
TC INPUT

U3

R2

7B47

ANALOG
DEVICES

7B47

ANALOG
DEVICES

ISOLATED
TC INPUT

U2

R1

J2

7B47

ANALOG
DEVICES

7B47

U1

REV E

7400225-

TRICONEX 7B 16 MODULE BASEPLATE

J1

J6

J5

First Panel
Labels (for front and back row)
1

10 11 12 13 14 15 16

Labels (for front and back row)


1

Labels (for front and back row)

10 11 12 13 14 15 16

10 11 12 13 14 15 16

Labels (for front and back row)


1

10 11 12 13 14 15 16

Second Panel
Labels (for front and back row)
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Figure 121

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

RTD/TC/AI ETP Label Placement

Planning and Installation Guide for Triconex General Purpose v2 Systems

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

SSR Input External Termination Panels

277

SSR Input External Termination Panels


This figure illustrates placement of labels for 16-point SSR Input ETPs.
J1

DSP1

R1

DSP3

R5

CR5

R9

CR7

CR9

NON-COM DI
RELAY ETP

+2 +3

R10

DSP12

+6 +7

CR13

CR10

LOAD:0.1A
524VDC

G3R-IAZR1SN

OMRON
MADE IN JAPAN

F16
DSP15

R14

SN

+4 +5

AC

F15
DSP14

R13

CR12

LOAD:0.1A
524VDC

AC

F14
DSP13

R12

K16

G3R-IAZR1SN

OMRON
MADE IN JAPAN

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

K15

AC

F13

R11

CR11

LOAD:0.1A
524VDC

AC

F12
DSP11

K14

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

LOAD:0.1A
524VDC

OMRON
MADE IN JAPAN

AC

F11
DSP10

K13

DSP16

R15

CR14

R16

CR15

CR16

REV B

Labels (for front and back row)


+1

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

R8

K12

AC

F10
DSP9

7400256

PWR

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

DSP8

CR8

K11

AC

F9

R7

CR6

K10

AC

F8
DSP7

R6

K9

AC

F7
DSP6

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

OMRON
MADE IN JAPAN

CR4

DSP5

K8

AC

F6

CONTACT

CR3

R4

K7

AC

F5
DSP4

R3

K6

AC

F4

R2

CR1

LOAD:0.1A
524VDC

AC

F3
DSP2

K5

G3R-IAZR1SN

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

G3R-IAZR1SN

AC

F2

CR2

K4

CONTACT

AC

F1

OMRON
MADE IN JAPAN

G3R-IAZR1SN

LOAD:0.1A
524VDC

K3

PWR

AC

OMRON
MADE IN JAPAN

LOAD:0.1A
524VDC

K2

G3R-IAZR1SN

OMRON
MADE IN JAPAN

K1

Labels (for front and back row)


+8

+9

+ 10 +11

+ 12

+13

+ 14 + 15

+ 16

First Panel

Labels (for front and back row)


+ 17

+ 18 + 19

+ 20 + 21

+22 + 23

Labels (for front and back row)


+24

+ 25

+ 26 +27

+ 28

+29

+ 30 + 31

+ 32

Second Panel

Figure 122

SSR Input ETP Label Placement

Planning and Installation Guide for Triconex General Purpose v2 Systems

278

Appendix F

Panel Labels

Planning and Installation Guide for Triconex General Purpose v2 Systems

Glossary

AI Module
Analog Input Module.
AI/DI Module
Analog Input/Digital Input Module. Each AI/DI Module contains 16 AI points and 16 DI
points.
alias
Five-digit number that the system uses in place of a variable name when communicating with
an external host. The alias is a convention of Modbus, an industry-standard protocol adopted
by Invensys for use with its communication modules. Each alias contains a Modbus message
type and the address of the variable in the system.
ASIC
Application-specific integrated circuit.
availability
Probability that the controller is operational at some instant of time.
bin
Address range of system aliased variables based on class and type combinations. For example,
all Read Only Input Discrete variables are grouped into Bin 2, and all Read/Write Memory
Integer variables are grouped into Bin 12.
CE Mark
Certification by the European Union which ensures the electro-magnetic compatibility of the
system with other pieces of electrical/electronic equipment.
channel
Data path from input point to output point. Triple modular redundant (TMR) systems have
three channels.
CSA
Canadian Standards Association, a not-for-profit membership organization which develops
standards and tests in areas ranging from nuclear power, health care, occupational health and
safety, housing and construction materials to the electrical, electronic and telecommunications
fields. CSA certification of a product generates consumer confidence in many countries.
configuration
Arrangement of the programmable electronics within a system and the combination of
programmable and non-programmable equipment within the installation.

Planning and Installation Guide for Triconex General Purpose v2 Systems

280

Glossary

control system
Governs the operation of plant, machinery or other equipment by producing appropriate
instructions in response to input signals.
coverage
Probability that a particular class of fault is successfully detected before a system failure occurs.
DCS
Distributed control system.
DDE
Dynamic data exchange (DDE) is an interprocess communication mechanism provided by the
Microsoft Windows operating system. Applications running the Windows operating system
can use DDE to send and receive data and instructions to and from each other.
debug
Act of locating and correcting faults: 1) one of the normal operations in software development;
such as editing, compiling, debugging, loading, and verifying; or 2) the identification and
isolation of a faulty physical component, including its replacement or repair to return the
system to operational status.
DI Module
Digital Input Module.
DO Module
Digital Output Module.
environment
Stimuli at an interface (or interfaces) of the system.
error
Element of a system resource assumes an undesired state. Such a state is then contrary to the
specification of the resource or the expectation (requirement) of the user.
event
State change of a discrete aliased variable which has been designated for event logging. An
event is said is to occur if such a variable changes from the normal state. If the variable later
changes back to the normal state, another event is said to have occurred.
event logger
Program that logs, displays and/or prints critical events in real time, based on state changes of
discrete variables in the program. Proper use of an event logger warns users about dangerous
conditions and printouts of events can help identify the sequence of events that led to a trip.
event variable
Discrete memory variable or discrete input point that has been assigned to an SOE block.
external host
Computer, such as a mainframe, minicomputer, workstation, or PC that communicates with the
controller over an Ethernet open network.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Glossary 281

fail-safe
Characteristic of a device or system to always revert to a safe, predictable state, even when one
or more of its internal elements has failed.
failure
System resource perceives that a service resource ceases to deliver the expected services. The
fault-tolerant system masks most failures. See fault.
failure rate
Rate at which failures occur over time. Usually expressed in failures per million hours. The
inverse of failure rate is MTTF.
fault
Cause of a resource failure or an error within the resource.
fault avoidance
Result of conservative design techniques using high-reliability components, system burn-in,
and careful design. The goal of fault avoidance is to reduce the possibility of a failure by
designing a device with performance margins so large that the probability of a detrimental
failure is negligible.
fault masking
Means of removing failed elements from influencing system operation while enabling properly
operating redundant elements to continue the control process.
fault tolerance
Ability to identify and compensate for failed control system elements and allow repair while
continuing an assigned task without process interruption. Fault tolerance is achieved by
incorporating redundancy and fault masking.
FE
Functional earth.
FSR
Full-scale range. Specifies an operating range for input or output signals. For example, if 0-5V
is the range, then 5V is the full scale.
HART
Highway Addressable Remote Transducer protocol is a bi-directional industrial field
communication protocol used to communicate between intelligent field instruments and host
systems over 420 mA instrumentation wiring.
host
See external host.
hot-spare modules
A unique feature of the Tri-GP controller which allows you to install a second identical I/O
module which becomes active if the other module fails.

Planning and Installation Guide for Triconex General Purpose v2 Systems

282

Glossary

input poll time


Time required by the controller to collect input data from the controlled process. Input polling
is asynchronous and overlaps application execution.
I/A Series DCS
Foxboro Industrial Automation (I/A) Series Distributed Control System.
IEEE
Institute of Electrical and Electronics Engineers (IEEE) is a professional society for engineers.
ISO
International Organization for Standardization (ISO) is a world-wide federation of national
standards bodies (ISO member bodies) that promulgates standards affecting international
commerce and communications.
intermittent fault
Fault or error that is only occasionally present due to unstable hardware or varying software
states.
LED
Light-emitting diode. One of the color-coded signal lights on each controller circuit board that
indicates the boards status. Each system component includes at least the Pass, Fail, and Active
LEDs.
logical slot
Logical slot comprises a primary module, a hot-spare module, and associated field termination
components. A baseplate is a physical representation of a logical slot.
Markov model
Generalized modeling technique which can be used to represent a system with an arbitrary
number of modules, failure events, and repair events. A Markov model can be mathematically
solved to produce a resultant probability.
MP
Main Processor Module.
module
Active field-replaceable unit consisting of an electronic circuit assembly housed in a metal
cover.
MTBF
Mean-time-between-failure. The expected average time between failures of a system, including
the time taken to repair the system. Usually expressed in hours.
MTTF
Mean-time-to-failure. The expected average time to a system failure in a population of identical
systems. Usually expressed in hours.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Glossary 283

MTTR
Mean-time-to-repair. The expected time to repair a failed system or subsystem. Usually
expressed in hours.
node
Any of the machines on a network.
node number
Physical address of a node.
non-triplicated module
I/O module with a single set of field-interface circuitry for communication with all three main
processor modules. Non-triplicated modules provide a cost-effective alternative to the use of
TMR modules for non-critical environments.
open network
Network to which an external host can be connected.
output poll time
Time required by the controller to implement the outputs generated by the application in
response to inputs from the controlled process.
PE
Protective earth.
PES
Programmable electronic system.
peer-to-peer
Protocol that allow multiple systems on a proprietary network to exchange process and safety
information.
permanent fault
Failure, fault or error in the system that is continuous and stable.
PHA
Process hazard analysis.
process demand
Occurrence of a process deviation that results in the SIS initiating a trip of the process unit.
program
Basic programming unit within a project. A set of instructions, commands, and/or other
directions. In the TriStation 1131 software, programs are written in any of the available
languages, and are subsequently placed within a projects hierarchy.
programmable logic controller
Black box device which accepts analog or digital input signals, acts upon them in a welldefined way, and produces appropriate output signals as a result.

Planning and Installation Guide for Triconex General Purpose v2 Systems

284

Glossary

proprietary network
Network of controllers.
protocol
Set of rules describing the format used for data exchange between two entities.
quad output circuit
Provides fault-tolerant outputs. Each output is composed of four identical switching elements
in a quad arrangement.
reliability
Probability that no failure of the system will occur in a given period of time.
scan time
Period of the controllers cycle of required control functions. Scan time is composed of three
elements:

Input poll time (asynchronous with program execution)

Time required to execute the program

Output poll time

SIL
Safety integrity level.
single module
Digital Input Module which is optimized for safety-critical environments where low cost is
more important than maximum availability. On a single module, only those portions of the
signal path which are required to ensure safe operation are triplicated. Special self-test circuitry
detects all stuck-On and stuck-Off fault conditions in less than half a second.
SIS
Safety instrumented system.
SRS
Safety requirements specification.
SRO Module
Solid-State Relay Output Module.
system
Set of components which interact under the control of a design.
TCP/IP
Transmission Control Protocol/Internet Protocol (TCP/IP) are protocols for the transport and
network layers of the OSI network model. TCP/IP provides reliable, sequenced data delivery.
time sync
Triconex Time Synchronization protocol.

Planning and Installation Guide for Triconex General Purpose v2 Systems

Glossary 285

transient fault
Fault or error resulting from a temporary environmental condition.
TMR
Triple-Modular-Redundant architecture, which allows the system to achieve fault tolerance.
The complete system is triplicated; each of the three identical systems is called a channel. Each
channel independently executes the application in parallel with the other channels.
Tri-GP
State-of-the-art programmable logic and process controller that provides a high level of fault
tolerance.
trip
Safety-related shutdown of the controlled process, or a portion of the controlled process.
TriStation 1131 software
TriStation 1131 software is a Windows-based developers workbench for writing and
downloading applications and for performing maintenance and diagnostics on Triconex
systems.
TriStation 1131 protocol
Master/slave protocol used by TriStation 1131 software for communication with the system.
The TriStation 1131 protocol supports a maximum of 10 systems, but each master can
communicate with only one slave at a time.
TSAA
Triconex System Access Application (TSAA) protocol is a master-slave protocol in which the
master (an external host) communicates with one or more slaves over an open network. TSAA
supports a maximum of ten controllers.
TV Rheinland
Technischer berwachungs-Verein in German or Technical Supervisory Association in English.
In Germany, TV Rheinland is an authorized technical inspection agency for a wide variety of
products, processes, installations, plants, and equipment. In addition, the agency is authorized
to carry out statutory inspections and acceptance tests by more than 25 other countries.
UDP/IP
User Datagram Protocol/Internet Protocol (UDP/IP) are protocols for the Transport and
network layers of the OSI network model. UDP/IP provides best-effort datagram delivery.
voting
Mechanism whereby each channel of a TMR system compares and corrects the data in each
channel using a two-out-of-three majority voting scheme.

Planning and Installation Guide for Triconex General Purpose v2 Systems

286

Glossary

Planning and Installation Guide for Triconex General Purpose v2 Systems

Index

2481S2 schematic, 88
2483AS2 figure, 93
2483AS2 schematic, 94
2483S2 figure, 93
2483S2 schematic, 94
3481S2 schematic, 83
3481S2 specifications, 83
3482S2 schematic, 85
3482S2 specifications, 85
description, 82
external termination baseplate figure, 90
field connections, 89, 92, 95, 100
hazardous location termination panel, 97
indicators, 227229
operation, 14

Numerics
100BaseTX connectors, pin-outs, 244
10BaseT connectors, pin-outs, 244

A
addresses
node, 196
plugs, 196
alarms
definition, 212
MP Module contacts, 40
overview, 212
system integrity, 12
wiring, 203
Analog Input
2351S2 figure, 52
2351S2 schematic, 52
2354AS2 figure, 69
2354AS2 schematic, 70
2354S2 figure, 69
2354S2 schematic, 70
3351S2 schematic, 50
3351S2 specifications, 50
description, 49
external termination baseplate figure, 54
external termination baseplate schematic, 54
field connections, 53, 55, 68, 71
hazardous location termination panel, 65
indicators, 221223
operation, 13
Analog Input/Digital Input
2361S2 figure, 75
2361S2 schematic, 76
3361S2 schematic, 73
3361S2 specifications, 73
description, 72
external termination baseplate figure, 78
external termination baseplate schematic, 79
field connections, 77, 80
hazardous location termination panels, 81
indicators, 224226
operation, 13

application., See control program


approvals, Factory Mutual, 17
architecture
MP Module, 6
system, 3, 5
assemblies
installing Interconnect, 197
Interconnect, 170
ATEX, installation guidelines, 183
AUI Ethernet MAU connectors, 244

B
baseplates
depth dimensions, 188
maximum number, 4
buses
I/O distribution, 8
TriBus, 5, 8

C
cables
CM diagread, 255
cross-over, 250

Analog Output
2481S2 figure, 87

Planning and Installation Guide for Triconex General Purpose v2 Systems

288

Index

cables (continued)
flame test ratings, 26
guidelines for selection, 253
MP Module diagread, 255
RS-232 serial, 251
RS-485 serial, 251
shield, 202
straight-through, 250
terminating, 253
caps
description, 173
installing, 197
CD designator, 247
CE Mark certification, 20
certifications
CE Mark, 20
TV, 18
columns, connecting, 192
communication
bus operation, 9
Communication Module features, 11
controller, 10
MP Modules, 10
physcial interfaces, 11
Communication Module
AUI Ethernet MAU connectors, 244
baseplate figure, 44
communication ports, 45
Debug connectors, 255
description, 43
diagread cables, 255
indicators, 218220
installation, 209
MII Ethernet MAU connectors, 245
operations, 11
communication protocols
Communication Module, 11
Main Processor Modules, 11
connectors
AUI Ethernet MAU, 244
Ethernet, 244
MII Ethernet MAU, 245
Modbus RS-232 serial, 247
control program, TriStation 1131, 4
controller
configuration, 4
environmental specifications, 24
features, 2
safety certification, 16

cooling
convection, 177
forced-air, 177
covers
description, 174
installing, 197
customer support, x

D
Debug connectors, Communication Module, 255
debug ports, Main Processor, 41
diagnostics
fault tolerance, 3
Tri-GP controller, 12
diagread cables
CMs, 255
MP Modules, 255
Digital Input
2301S2 figure, 107
2301S2 schematic, 108
3301S2 schematic, 102
3301S2 specifications, 102
3311S2 schematic, 104
3311S2 specifications, 105
description, 101
external termination baseplate figure, 109
external termination baseplate schematic, 110
field connections, 109, 111, 118
hazardous location external termination panel, 115
indicators, 230232
operation, 14
Digital Output
2401HS2 figure, 128
2401HS2 schematic, 129
2401LS2 figure, 131
2401LS2 schematic, 132
2401S2 figure, 125
2401S2 schematic, 126
3401S2 schematic, 120
3401S2 specifications, 120
3411S2 schematic, 122
3411S2 specifications, 123
description, 119120
external termination baseplate figure, 134
field connections, 127, 130, 133, 136, 139, 145
indicators, 233236
operation, 14
dimensions
I/O baseplates, 190
I/O Extender Modules, 191
Main Processor Baseplates, 189
drill templates, mounting panels, 186

Planning and Installation Guide for Triconex General Purpose v2 Systems

Index

ground (continued)
logic power, 200
system, 26

earth, connecting shield, 202


end caps
description, 173
installing, 197

H
HART
AI baseplates, 69
AO baseplates, 9396
overview, 262
Triconex 4850 Multiplexer description, 265
Triconex 4850 Multiplexer indicators, 267
Triconex 4850 Multiplexer installation, 266

environment, requirements, 24
Ethernet
100BaseTX connectors, 244
10BaseT connectors, 244
cross-over cables, 250
straight-through cables, 250
EU Declaration of Conformity, 20

hazardous locations
approved modules for, 184
installation guidelines, 182185

F
Factory Mutual approval, 17

fault tolerance, defined, 3

I/O baseplates, dimensions, 190

faults
definition, 212
overview, 212
field alarm indicator, AO Module, 229
field connections
2381AS2 pulse input, 161
2381S2 pulse input, 153
AI Baseplate model 2351S2, 53
analog input, 53, 55, 58, 68, 71
analog input/digital input, 77, 80
analog output, 89, 92, 95, 100
digital input, 109, 111, 113, 118
digital output, 127, 130, 133, 136, 139, 145
relay output, 139
solid-state relay input, 113
solid-state relay output, 169
field power, grounding, 201
field power indicator
Analog Input Module, 223
Analog Input/Digital Input Module, 226
Digital Input Module, 232
field signal distribution, 9
forced-air cooling, 177

G
ground
field power, 201

289

I/O Bus
cables, 172
distribution, 8
operation, 9
terminators, 172
I/O Extender Modules
connecting, 192
description, 171
dimensions, 191
I/O modules
common specifications, 47
installing, 210
I/O points, toggling to opposite, 206
I/O processors, MP Module, 37
indicators
AI Module, 221223
AI/DI Module, 224226
AO Module, 227229
Communication Module, 218220
DI Module, 230232
DO Modules, 233236
MP Modules, 213217
overview, 212
PI Module, 237239
SRO Module, 240242
installation
application-specific guidelines, 182
mechanical, 185
Interconnect Assemblies, description, 170
interconnect assemblies, installing, 197
interfaces, physical communication, 11

Planning and Installation Guide for Triconex General Purpose v2 Systems

290

Index

L
logic power
Communication Module, 43
determining, 177
grounding, 200
MP Baseplate, 42
MP Module, 37
overview, 10

M
Main Processor
alarm contacts, 40
application processors, 36
baseplate dimensions, 189
communication ports, 41
Debug connectors, 255
description, 35
I/O processors, 37
indicators, 213217
installing modules, 208
logic power, 37
logic power connectors, 42
Modbus ports, 41
overview, 6
maintenance, routine, 204
mechanical installation, 185
MII Ethernet MAU connectors, 245
Modbus ports
Main Processor Module, 41
ports on Communication Module, 45
Modbus RS-232 serial connectors, 247
modules
Analog Input, 49
Analog Input/Digital Input, 72
Analog Output, 82
Communication, 11, 43
depth dimensions, 188
Digital Input, 101
Digital Output, 119120
I/O Extender Modules, 171
Main Processor Module, 35
Pulse Input, 146147
Solid-State Relay Output, 165
spare, 206
mounting panels
drill templates, 186
guidelines, 185

network ports (continued)


Main Processor, 41

O
operations, Communication Module, 11
Output Voter Diagnostics
disabling, 204
enabling, 205
operation, 14
OVD. See Output Voter Diagnostics
overview, 16

P
panels, mounting, 185
parts, recommended, 271
physical interfaces, communication, 11
pin-outs
2381AS2 PI baseplate, 164
2381S2 PI baseplate, 157
RS-232, 247
RS-485, 248
RTD/TC/AI termination panel, 60
solid-state relay input termination panel, 114
point indicators, Digital Input Module, 232
ports
CM serial ports, 45
MP Module communication, 41
MP Module I/O and system executive, 41
power
Communication Module, 43
distribution, 8, 9
MP Baseplate, 42
MP Module logic, 37
testing sources, 205
power/load indicators, DO and SDO Module, 236
processors
MP Module application, 36
MP Module I/O, 37
programs, alarms, 40
protective earth
connecting shield, 202
grounding baseplates, 198
Pulse Input
2381AS2 field connections, 161
2381AS2 figure, 158
2381AS2 schematic, 158
2381S2 field connections, 153

network ports
Communication Module, 45

Planning and Installation Guide for Triconex General Purpose v2 Systems

Index

291

schematics (continued)
DO hazardous location external termination
baseplate, 135
DO hazardous location termination panel, 144
DO module 3401S2, 120
DO module 3411S2, 122
PI baseplate 2381S2, 151
PI hazardous location baseplate 2381AS2, 158
PI module 3382S2, 148
RTD/TC/AI termination panel, 57

Pulse Input (continued)


2381S2 figure, 151
2381S2 schematic, 151
3382S2 schematic, 148
3382S2 specifications, 148
description, 146147
indicators, 237239
operation, 15

SD-A designator, 249

RD-A designator, 249

SD-B designator, 249

RD-B designator, 249

shields, connecting, 202

recommended parts, 271

signals
connecting ground, 200
field distribution, 9
RS-232, 247
RS-485 description, 249

replacing modules, guidelines, 207


routine maintenance, 204
RS-232
pin-outs, 247
serial cables, 251
signals, 247

Slot Covers
description, 174
installing, 197

RS-485
pin-outs, 248
selecting cables, 253
serial cables, 251
signal description, 249
terminating cables, 253

solid state relay input external termination panel, 112


Solid-State Relay Output
2451S2 figure, 167
2451S2 schematic, 168
3451S2 schematic, 165
3451S2 specifications, 165
description, 165
field connections, 169
indicators, 240242
operation, 15

RTD/TC/AI Termination Panel


description, 56
pin-out information, 60
schematic, 57

spare modules, verifying, 206

safety certifications, 16
schematics
AI HART baseplates, 70
AI hazardous location termination panel, 67
AI module 3351S2, 50
AI/DI module 3361S2, 73
AO baseplate 2481S2, 88
AO HART Baseplates, 94
AO hazardous location external termination
baseplate, 91
AO hazardous location termination panel, 99
AO module 3481S2, 83
AO module 3482S2, 85
DI baseplate 2301S2, 108
DI Hazardous Location Termination Panel, 117
DI module 3301S2, 102
DI module 3311S2, 104
DO baseplate 2401LS2, 132
DO baseplate 2401S2, 126

specifications
environmental, 24
I/O common, 47
status indicators
AI/DI Module, 222, 225
AO Module, 228
DI Module, 231
diagnostic, 12
DO Module, 235
system executive debug ports, MP Module, 41
systems
ground, 26
overview, 24

T
technical support, x
temperature and output ranges, signal conditioning
modules, 64

Planning and Installation Guide for Triconex General Purpose v2 Systems

292

Index

Terminal Covers, installing, 197


terminal covers, description, 174
termination panels
AI hazardous location, 65
AI/DI hazardous location, 81
AO hazardous location, 97
DI hazardous location, 115
DO hazardous location, 142
relay output, 137
RTD/TC/AI, 56
solid state relay input, 112
TMR.See Triple Modular Redundant architecture
training, x
TriBus
description, 5
operation, 8
Triconex contact information, x
Tri-GP controller
architecture, 5
fault tolerance, 3
triple modular redundant, architecture, 3
TriStation 1131
Ethernet connectors, 244
software, 4
TRM, architecture, 5
trunks, cables, 253
TV certification, 18

V
verifying spare modules, 206

W
wiring, alarms, 203

Planning and Installation Guide for Triconex General Purpose v2 Systems

Invensys Operations Management


5601 Granite Parkway, Suite 1000
Plano, TX 75024
United States of America
http://www.iom.invensys.com

Global Customer Support


Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424 or contact your
local Invensys representative.
Website: http://support.ips.invensys.com