Académique Documents
Professionnel Documents
Culture Documents
AbstractMaintaining dynamic security of a power system subjected to large disturbances is of utmost importance. Fast and accurate online detection of instability is essential in initiating certain
emergency control measures. The techniques reported in the literature involve mainly the application of global phasor measurements
and heuristic algorithms. In this paper, an accurate technique for
the online detection of loss of synchronism based on voltage and
current measurements in a line is presented. The technique makes
use of the concept of potential energy in a line. The conditions for
the system instability are derived from energy function analysis.
However, no assumptions are made regarding the power-angle relationship in a line, nor are any data on the system equivalents necessary in implementing the detection scheme.
Index TermsCritical cutset, energy function, transient stability.
NOMENCLATURE
Rotor angle in centre of inertia (COI) reference.
Rotor speed in COI reference.
Inertia constant.
Mechanical power input to the generator.
Electrical power output of the generator.
Generator quadrature axis voltage.
Direct axis open-circuit transient time constant.
Direct axis reactance.
Direct axis transient reactance.
Generator direct axis current.
Generator field voltage.
Generator direct axis voltage.
Quadrature axis open-circuit transient time constant.
Quadrature axis reactance.
Quadrature axis transient reactance.
Generator quadrature axis current.
Automatic voltage regulator gain.
Exciter time constant.
Generator voltage reference.
Static active power load, assumed to be constant.
Reactive power output at the generator terminal.
Manuscript received March 1, 2004; revised July 5, 2004. This work was
supported by the Department of Science and Technology, Government of
India, under the project Dynamic Security Assessment and Control of Power
Grids. The paper is based on a contribution presented by the authors at the
IEEE Transmission and Distribution Conference and Exposition, Atlanta, GA,
October 2001. Paper no. TPWRD-00104-2004.
K. R. Padiyar is with the Department of Electrical Engineering, Indian Institute of Science, Bangalore 560012, India.
S. Krishna is with the Department of Electrical and Electronics Engineering,
M.S. Ramaiah Institute of Technology, Bangalore 560054, India.
Digital Object Identifier 10.1109/TPWRD.2005.848652
PADIYAR AND KRISHNA: ONLINE DETECTION OF LOSS OF SYNCHRONISM USING ENERGY FUNCTION CRITERION
47
Fig. 1.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Fig. 2. Angle across series elements for the critically unstable case.
(9)
(10)
The static exciter is represented by the block diagram shown
in Fig. 3. An energy function
for this system [2], [10] is
defined as
(11)
48
where
Fig. 4.
Coherent areas.
where
is the number of elements in the critical cutset. It can
be shown that the variation of potential energy in all of the lines
in the critical cutset is similar. If a series element (line or transformer) in the critical cutset connects buses and
(14)
(15)
where and are the voltage magnitudes at buses (in area I)
and (in area II), respectively, and is the susceptance of the
series element. Due to the assumption of coherency, the variations of and are similar for all of the elements in the critical
and . Hence,
cutset. This is also true of the variations of
the variation of potential energy can be monitored from the energy in the individual lines in the cutset. Hence
(16)
where
is the reactive power output at the internal bus of generator . The energy function is defined for the postfault system
is zero along a postfault trajectory.
and the time derivative of
The subscript in the above expressions indicates quantities at
time .
can also be expressed as follows.
The potential energy
The proof is given in the Appendix.
(12)
where
is a constant and subscript
the cutset, and
(17)
to properly account for the
The corrected kinetic energy
portion of the kinetic energy that contributes to system separation [11] is given by
(18)
where
(13)
By assumption of coherency, the rotor speeds of all the generators in an area are equal and the derivative of the angle across
all of the elements in the critical cutset are the same. Hence
(19)
where
is the angle across any line in the critical cutset. The
corrected kinetic energy is given by
(20)
PADIYAR AND KRISHNA: ONLINE DETECTION OF LOSS OF SYNCHRONISM USING ENERGY FUNCTION CRITERION
49
Fig. 5. Variation of power flow and rate of change of angle of the lines 11-12
and 18-19 for the critically stable case.
Fig. 6. Variation of power flow and rate of change of angle of the lines 11-12
and 18-19 for the critically unstable case.
50
bus and, hence, the set is still not a cutset. When instability is
detected in the last line belonging to the critical cutset, then no
path exists between buses and , and then the set is a cutset.
Whenever instability is detected in a line, the matrix
is
is defined. This is done because
updated and a new matrix
the fusion of buses reduces the number of buses and the original connectivity information is lost; the original connectivity
information is again required when instability is detected in a
new line. Therefore, the original connectivity information is preserved in the matrix and the fusions are performed on the matrix .
The fusion of the th bus to the
bus is accomplished by
OR-ing, that is, logically adding the th row to the th row as
well as the th column to the th column of the matrix . In
and
.
logical adding,
Then all of the elements of the th row and the th column of
are set to zero.
the matrix
Whenever instability is detected in a line, the maximum
number of fusions that may have to be performed in this
is a cutset or not,
algorithm in order to check whether
where
is the number of buses. The maximum
is
number of logical additions that may have to be performed is
. Therefore, the upper bound on the execution
time is proportional to
.
VI. PREDICTION OF INSTABILITY
and is
For faster detection of instability, the variation of
predicted by fitting a polynomial curve to the postfault-sampled
measurements. The sampling period is chosen as one cycle.
The measurements separated by two cycles are used for curve
fitting. The algorithm for prediction of instability in a line is as
follows:
1) If measured at the current sampling instant is less than
that measured at the previous sampling instant, stability
reaches a maximum
is indicated in the line since
and
crosses zero during this sampling period.
and
, or
measured at the
If
, instability
current sampling instant is greater than
is indicated in the line.
measured at the current sampling instant is greater
2) If
, a quadratic curve is fit to the three sampled
than
and a cubic curve is fit to the four
measurements of
sampled measurements of . The samples of are mea,
,
, and
sured at the instants
where is the current sampling instant
is the fault clearing time.
is measured at the
and
instants
,
, and
(21)
(22)
3) The following two equations are solved for real positive
and the
values to obtain the instant at which
instant at which
:
(23)
(24)
PADIYAR AND KRISHNA: ONLINE DETECTION OF LOSS OF SYNCHRONISM USING ENERGY FUNCTION CRITERION
51
4) If
and
, or if (23) has a real positive
, and (24) does not have a
solution with
real positive solution, instability is indicated in the line;
otherwise, a new set of measurements is obtained at the
next sampling instant and the procedure from step 1 is
repeated.
The procedure is stopped as soon as stability or instability is
indicated in the line. It is to be noted that curve fitting and the
exsolution of the quadratic equations are required only if
. The condition
is used to limit the error
ceeds
due to extrapolation. As soon as instability is predicted in a line,
the information is sent to the central computing station. System
instability is predicted when the lines in which instability is predicted form a cutset.
VIII. DISCUSSION
The proposed detection criterion is tested on the New England 10-generator system and the IEEE 17-generator system.
The single-line diagram of the New England system is shown in
Fig. 1. The data for this system are given in [2]. The data for the
IEEE 17-generator system are given in [13], [14]. The single
diagram of this system showing only the major lines is given
in [13]. For both systems, network and generator losses are neglected, and the loads are treated as constant impedances. The
proposed detection criterion is tested by simulating three-phase
faults at different locations; the fault is cleared at such an instant
is chosen as 50 for
that the system is critically unstable.
the 10-generator system and 55 for the 17-generator system.
is chosen as 200 .
The angle across the critical lines at the instant of detection/prediction is given in Table I. The instant of instability detection/prediction is also indicated in the table. The instant of instability detection/prediction is the instant at which instability is
detected/predicted in the last line belonging to the critical cutset.
The value in brackets, in the columns 4 and 5, is the time duration in terms of the number of cycles from the instant at which
instability is detected/predicted in the first line to the instant at
which instability is detected/predicted in the last line.
The proposed instability criterion indicates instability in all
of the cases studied. The average time taken for detection of
instability from the instant of fault clearing is 1.004 s for the
10-generator system and 0.333 s for the 17-generator system.
The corresponding values for the prediction of instability are
0.569 and 0.254 s. The average value of the angle across critical lines at the instant of instability detection is 159.2 for the
10-generator system and 128.0 for the 17-generator system.
The corresponding values at the instant of instability prediction
are 54.7 and 63.2 .
For a fault at bus 12 cleared without line tripping and fault
at bus 37 cleared by tripping the line 37-27 (of the 10-generator
system with the classical model of generator), there is a false dismissal with stability detection using the energy function. Therefore, instability is detected when a sampled measurement of
is greater than
. However, for both cases, the prediction
algorithm indicates instability at an earlier instant. There is no
false dismissal in these cases with prediction.
52
TABLE I
ANGLE ACROSS THE CRITICAL LINES AT THE INSTANT OF INSTABILITY DETECTION/PREDICTION
for more stable and more unstable cases. The detection is sped
up by the extrapolation of system trajectories.
PADIYAR AND KRISHNA: ONLINE DETECTION OF LOSS OF SYNCHRONISM USING ENERGY FUNCTION CRITERION
Fig. 8.
Swing curves for a fault at bus 20 cleared by tripping the line 20-33.
The mode of instability is the same for both classical and detailed models for all of the cases studied. For a fault at buses 27
and 28 of the 10-generator system, the critical cutset is different
for classical and detailed models of the generator.
and
are decided based on simulation
The values of
studies. These values are the same for all of the cases for a given
system and the actual values used are not very critical. The detection/prediction procedure starts as soon as the angle across
. In most cases, instability is predicted as
a line exceeds
soon as the angle exceeds
. The method given in [15] involves only checking whether the angle between two areas ex, the value which is not specified.
ceeds
Transient instability may lead to uncontrolled tripping of generators and lines, and may finally result in the formation of islands. Controlled system separation is used as a protective measure in order to retain as much of the system intact as possible.
The proposed instability detection method can be used to initiate this emergency control measure by tripping the elements
of the critical cutset at the instant of instability detection/prediction. Fig. 8 shows the swing curves for the fault at bus 20 (of
the 10-generator system) cleared by tripping the line 20-33 at
0.23 s (critically unstable clearing time). Generator 3 initially
separates from the rest of the system; instability is first detected
in the transformer 20-3 which forms the critical cutset. Controlled system separation is simulated by tripping generator 3.
Fig. 9 shows the plot of swing curves of the group containing
nine generators when the system is separated at the instant of
instability detection/prediction (0.713 s). The system is stable
after tripping generator 3 though the swing curves show that
there is further loss of synchronism without controlled system
separation (Fig. 8).
The proposed algorithm can be readily applied for offline
studies. In most cases, the critical cutset and mode of instability can be detected/predicted within about a second. This is
quite fast as the application of energy function methods for direct evaluation of transient instability (using the potential energy
boundary surface method) involves about 1 s of simulation (unless shortcuts are used). Further, the algorithm presented in this
53
(25)
In a lossless system, power flows satisfy Kirchhoffs current
law and bus frequencies satisfy Kirchhoffs voltage law. Hence,
an equivalent network can be obtained for the power system as
shown in Fig. 10, with power being considered analogous to
current and bus frequencies to voltage [16].
For any electric network, where the branch voltages and currents satisfy Kirchhoffs laws, Tellegens theorem can be applied, which states that at any time, the sum of the power delivered to each branch of the network is zero [17]. Under steadyis equal to
, and
is equal to
; the load
state,
are assumed to be constants. Tellegens theorem is
powers
also valid when branch voltages of one network and the branch
currents of another network are considered, provided the networks have the same graph. Applying Tellegens theorem to the
54
The sum of the last two terms on the right-hand side of (29) and
(30) gives half of the reactive power losses in the generator reac. Substituting the
tances and the network which is equal to
right-hand side of (29) and (30) in (28), the following equation
is obtained:
Fig. 10.
(31)
(27)
The first term on the right-hand side of (25) can be separated
into terms corresponding to power flows in the generator reactances and those corresponding to power flows in the transmission lines/transformers as follows:
(28)
where is the number of lines and transformers, is the power
flow in the series element connecting buses and . The first
term on the right-hand side of (28) is evaluated by integrating
given by (9) with respect to
by
the expression for
parts. It can be shown that [18]
(29)
The second term on the right-hand side of (28) is evaluated by
with respect to
by parts.
integrating
It can be shown that [18]
(30)
[1] IEEE Committee Report, A description of discrete supplementary controls for stability, IEEE Trans. Power App. Syst., vol. 97, no. PAS-1, pp.
149165, Jan./Feb. 1978.
[2] K. R. Padiyar, Power System DynamicsStability and Control, 2nd
ed. Hyderabad, India: B.S. Publications, 2002.
[3] V. Centeno, A. G. Phadke, A. Edris, J. Benton, M. Gaudi, and G. Michel,
An adaptive out-of-step relay, IEEE Trans. Power Del., vol. 12, no. 1,
pp. 6171, Jan. 1997.
[4] S. Rovnyak, C.-W. Liu, J. Lu, W. Ma, and J. Thorp, Predicting future
behavior of transient events rapidly enough to evaluate remedial control options in real-time, IEEE Trans. Power Syst., vol. 10, no. 3, pp.
11951203, Aug. 1995.
[5] L. Wehenkel, M. Pavella, and Y. Zhang, Transient and Voltage Stability
Criteria for Real-Time Emergency Control, Rep., CIGRE Paper 39-111,
1998.
[6] L. Wang and A. A. Girgis, A new method for power system transient
instability detection, IEEE Trans. Power Del., vol. 12, no. 3, pp.
10821089, Jul. 1997.
[7] S. Rovnyak, S. Kretsinger, J. Thorp, and D. Brown, Decision trees for
real-time transient stability prediction, IEEE Trans. Power Syst., vol. 9,
no. 3, pp. 14171426, Aug. 1994.
[8] C.-W. Liu, M.-C. Su, S.-S. Tsay, and Y.-J. Wang, Application of a novel
fuzzy neural network to real-time transient stability swings prediction
based on synchronized phasor measurements, IEEE Trans. Power Syst.,
vol. 14, no. 2, pp. 685692, May 1999.
[9] K. R. Padiyar and K. Uma Rao, Discrete control of series compensation
for stability improvement in power systems, Int. J. Elect. Power Energy
Syst., vol. 19, no. 5, pp. 311319, Jun. 1997.
[10] K. R. Padiyar and K. K. Ghosh, Direct stability evaluation of power
systems with detailed generator models using structure-preserving energy functions, Int. J. Electrical Power Energy Syst., vol. 11, no. 1, pp.
4756, Jan. 1989.
[11] A. A. Fouad and V. Vittal, Power System Transient Stability Analysis
Using Transient Energy Function Method. Englewood Cliffs, NJ:
Prentice-Hall, 1992.
[12] N. Deo, Graph Theory With Applications to Engineering and Computer
Science. Englewood Cliffs, NJ: Prentice-Hall, 1974.
[13] IEEE Committee Report, Transient stability test systems for direct stability methods, IEEE Trans. Power Syst., vol. 7, no. 1, pp. 3743, Feb.
1992.
[14] .
[Online]
Available:
http://www.ee.washington.edu/research/
pstca/dyn17/ pg_tcadd17.htm
[15] C. Counan, M. Trotignon, E. Corradi, G. Bortoni, M. Stubbe, and J.
Deuse, Major incidents on the french electric system: potentiality and
curative measures studies, IEEE Trans. Power Syst., vol. 8, no. 3, pp.
879886, Aug. 1993.
[16] K. R. Padiyar and P. Varaiya, A Network Analogy for Power System
Stability Analysis, 1983.
[17] C. A. Desoer and E. S. Kuh, Basic Circuit Theory. New York: McGraw-Hill, 1969.
[18] S. Krishna, Dynamic security assessment and control using unified
power flow controller, Ph.D. thesis, Indian Inst. Sci., Bangalore, Mar.
2003.
PADIYAR AND KRISHNA: ONLINE DETECTION OF LOSS OF SYNCHRONISM USING ENERGY FUNCTION CRITERION
55