LIST OF GOODS AND DELIVERY SCHEDULE

Item
No

Description

Unit

Quantity

108kV, 10kA, Class 3, outdoor surge arrester:

set

- Hot dip galvanized H-shaped steel structure for LA (including all equipment fixing facilities such as
anchor bolts, bolts, nuts, washer, etc.).

set

- Surge counter

set

- Supporting clamps for (ACSR 500/51) (including all necessary terminal fixing bolts, nuts, washer,
etc.)

set

- Copper bolt clamps for earthing with Cu 120sqmm conductors

set

12

DELIVERY SCHEDULE
Delivery (as per Incoterm) Date (in weeks) (i)
Final Destination as specified in
BDS

Supply at the Thanh Oai 110kV


Substations, Ha Noi, Vietnam

Earliest
Delivery Date
(weeks)
16

Latest Delivery Bidder's offered Delivery Date


Date (weeks) (to be provided by the bidder)

16

1. 108kV SURGE ARRESTOR


Item
No.
1
2
3

Description
Manufacture, Country of Origin
Ordering number
Applicable standards

Required
To be specified
To be specified
IEC 60099-4
ZnO, Outdoor, gapless, use for
overvoltage of the capacitor bank45MVAr, don't have the reactor
damper

Type

5
6

Rated Voltage (Ur)


Rated frequency

> 108 kV
50 Hz

Maximum continuous operating voltage Uc

78 kV

8
9
10
11

Nominal discharge current


IEC long duration discharge class
Fault current for pressure relief test
Maximum energy absorption capability

12

Maximum residual voltage of complete arrestor for


nominal discharge current 8/20s impulse-10kA

13

Leakage current through the complete arrestor at max.


continuous operating voltage.

10 kA
Class 3
25 kA rms.
Rating 4.5 kJ/kV Ur
< 254 kV

- resistive component
- capactive component

mA
mA

14

Material employed in series non-linear resistor

ZnO

15
16

The number of column of ZnO


Surge counter
- Manufacturer/Country of origin
Sensitivity of surge counter:
(a) Current
(b) Corresponding wave shape

17

To be specified
Yes
To be specified
100 A
8/20 s

18

Peak voltage across surge counter when a 8/20s


current surge of peak value equal to the nominal
discharge current of the arrestor is applied.

19

RMS voltage across surge counter when continuous


operating voltage is applied to arrestor.

20
21

Leakage current meter range


Insulator:
- Material
- Lightning impulse voltage withstand

To be specified
> 550 kVpeak

Item
No.

22
23
24

27
28

29
30
31

Description
- Rated power frequency voltage withstand
(50Hz/1min.)
- Minimum creepage distance
Seismic withstand capability
Calculated Wind Load Moment about the base of the
arrestor

Required
> 230 kVpeak
> 25 mm/kV
To be specified
To be specified

Terminal connector (Material/diemension):


- HV terminal
- Earthing
- Surge counter
Cu-PVC-10kV insulator, > 50mm2, to connect from SA
to surge counter
Full of type test reports for SA
- Insulation withstand tests.
- Residual voltage tests
- Long duration impulse withstand test
- Operation duty tests
- Pressure relief tests
Reference lists
02 End users at EVN
Catalogues

To be specified
To be specified
To be specified
Yes
Yes
Yes
Yes
Yes
Yes
Yes
> 3 years
> 20 months
Yes

R
Offered
Tridelta/Germany
SB 108/20.4-0-A
IEC 60099-4

ZnO, Outdoor, gapless

108 kV
50 Hz
86 kV
20 kA
Class 4
25 kA rms.
7.0 kJ/kV Ur
248

<0.5
<1.0
ZnO
1
Yes
Tridelta/Germany
100 A
8/20 s
3000

n.a
0-30mA
Porcelain
774

Offered
374
> 25 mm/kV
0.5g
1

Aluminum/45x45
Aluminum/45x45
Aluminum
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes