Académique Documents
Professionnel Documents
Culture Documents
Cortland, NY 13045
Telephone: (607) 753-6711
Facsimile: (607) 753-1045
www.intertek-etlsemko.com
April 5, 2012
Johan Kuikman
Fortis Wind Energy BV
Aduarderdiepsterweg 9b
9475-EL-HOOGKERK
Netherlands
Phone: 310505515666
email: kuikman@fortiswindenergy.com
Subject: Power performance test report for the Fortis Wind Energy Montana tested at the Intertek Small Wind
Regional Test Center (RTC).
Dear Mr. Kuikman,
This Test Report represents the results of the evaluation and tests of the above referenced equipment under
Intertek Project No. G100146060, as part of the US Department of Energy and National Renewable Energy
Laboratory (DOE/NREL) Subcontract Agreement No. AEE 0-40878-02, to the requirements contained in the
following standard:
IEC 61400-12-1 Wind Turbines - Part 12-1: Power performance measurements of electricity producing wind
turbines; December 2005
This investigation was authorized through signed proposal no. Q500233379, dated May 25, 2010. A production
th
th
sample was installed at the Intertek RTC on January 14 , 2011. Power performance testing began on April 20 ,
nd
2011 and data collection continued through May 2 , 2011.
This Test Report completes the power performance testing phase of the Fortis Wind Energy Montana under
Intertek Project No. G100146060.
If there are any questions regarding the results contained in this report, or any of the other services offered by
Intertek, please do not hesitate to contact the undersigned.
Please note, this Test Report on its own does not represent authorization for the use of any Intertek certification
marks.
Completed by:
Title:
Signature:
Joseph Spossey
Project Engineer
Reviewed by:
Title:
Tom Buchal
Senior Staff Engineer
Signature
Page 1 of 58
This report is for the exclusive use of Interteks Client and is provided pursuant to the agreement between Intertek and its Client. Interteks responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use
of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or
advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only the sample tested. This
report by itself does not imply that the material, product or service is or has ever been under an Intertek certification program.
Page 2 of 58
Intertek Testing Services NA, Inc.
1.0 Background
This test is conducted as part of the DOE/NREL Subcontract Agreement No. AEE-0-40878-02 for the testing of
small wind turbines at regional test centers. The Fortis Wind Energy, B.V., Montana Wind Energy System was
accepted into this program by Intertek and DOE/NREL. The full scope of type testing provided by Intertek for the
Fortis Montana horizontal-axis wind turbine is covered by this agreement. This test report is a summary of the
results of power performance testing, and is one of four tests required on the Fortis Montana turbine; the other
three being duration, safety and function, and acoustics. Results for these other tests are summarized in their
respective Test Reports.
The Fortis Montana turbine is installed at Test Station #2 at the Intertek RTC in Otisco, NY. The Fortis Montana
is designed for grid-connected power delivery, with a maximum power output of 5 kW. It is classified as a Class II
upwind direct drive turbine with speed and power control through horizontal furling and electric dampening. The
Fortis Montana has a three-phase brushless variable speed generator with permanent magnet excitation that is
rated for operation at 220V. The turbine system has multiple output configurations; for testing at the Intertek RTC,
the output and grid interconnect is provided by a WB5000-US WindyBoy inverter at 240V single phase. The
tower and foundation were designed and approved by Nello Corporation. The designs were based off of the
Subsurface Investigation and Geotechnical Evaluation detailed in Atlantic Testing Laboratories report number
CD3119E-01-05-10.
The electrical network at the testing location is single/split phase 120/240 VAC at 60 Hz. Refer to the wiring
diagrams in Appendix A for additional detail. A summary of the test turbine configuration and manufacturers
declared ratings can be found in Table 1 below.
Page 3 of 58
Intertek Testing Services NA, Inc.
Page 4 of 58
Intertek Testing Services NA, Inc.
Turbine manufacturer
Model
Rated Electrical Power (kW)
Rotor Diameter (m)
Hub Height (m)
2
Swept Area (m )
Distance from rotor centre to tower axis
Tower Type(s)
IEC 61400-2 SWT Class (I, II, III, or IV)
Cut-in Wind Speed
Rated Wind Speed
Survival Wind Speed
Generator identification
Generator specifications
Inverter identification
Inverter specifications
Rectifier/Controller identification
Rectifier/Controller specifications
Diversion load identification
Diversion load specifications
Active brake switch identification
Active brake switch specifications
Blade identification
Blade specification
Rotor speed range (rpm)
Fixed or variable pitch
Number of Blades
Blade Tip Pitch Angle (deg)
19.63 m (211.3 ft )
0.43 m (1 ft 5 in)
Lattice
II
2.5 m/s (5.6 mph)
12 m/s (26.8 mph)
60 m/s (134 mph)
Fortis / Inensus 5 kW
Serial # 100709
5 kW, 220 VAC, 50 Hz
3-phase, 350 RPM
SMA, Windy Boy WB5000US
Serial #: 2001308424
5000 W, 240VAC Single phase, 60 Hz
UL 1741 Listed
Windy Boy, WBP-Box 500
Serial #: 1290001136
Inputmax 3 phase 440 VAC, 11.5 A
Outputmax 500 VDC, 30 A
IP54 Outdoor (mounted indoors)
Heine Resistors, RFB 6-7
Serial #: 024261020003c
6kW, 42 10%, IP 23 (mounted outdoors)
Inensus
Serial #: 0191002003
400 V, 15 A
IP40 (mounted indoors)
Fortis
Serial #s: 3311, 3312, 3313
Fiberglass epoxy, NACA 4415 airfoils
20 450
Fixed
3
10
Page 5 of 58
Intertek Testing Services NA, Inc.
Page 6 of 58
Intertek Testing Services NA, Inc.
Figure 2 Topographical survey map and final valid measurement sector of the Fortis Montana test turbine
Page 7 of 58
Intertek Testing Services NA, Inc.
Table 2 below provides detail on obstacles that were determined to be significant as a result of the obstacle
assessment in accordance with the Standard. Based upon the results in Table 2, a valid measurement sector of
38 322 degrees true was established prior to site calibration.
Description
Fortis
Montana
Reference
Point
Distance
Diameter
Equivalent
Bearing
(m)
(m)
(m)
Fortis Met
12.5
5.0
Invalid Sector
Start
Stop
(true)
(true)
(true)
360
323
37
INVALID Sector =
323
37
VALID Sector(s) =
38
322
Site calibration was required due to the combination of average slope and terrain variations within 20 rotor
diameters of the turbine tower. Table 3 below shows the results of the site calibration for the Fortis Montana
power performance test, where:
Direction = each 10-degree wind direction bin, in true degrees, considered during site calibration,
Total Time = total number of hours of data collected in each wind direction bin,
Velocity < 8 m/s = total number of hours where wind speeds are below 8 m/s in each wind direction bin,
Velocity > 8 m/s = total number of hours where wind speeds are above 8 m/s in each wind direction bin,
Turbine Velocity Average = average wind speed measured at the turbine location in each wind direction
bin,
Met2 Velocity Average = average wind speed measured at the meteorological tower location in each
wind direction bin,
Average of Ratios = average flow correction factor due to terrain for each wind direction bin (ratio of
wind speed at the wind turbine location divided by the wind speed at the meteorological tower location),
Red text = INVALID sector resulting from obstacle assessment,
Black text = VALID sector resulting from obstacle assessment, and
Blue shade = FINAL VALID sector resulting from site calibration
Page 8 of 58
Intertek Testing Services NA, Inc.
Direction
Direction
Average
Total
Time
Velocity <
8 m/s
Velocity >
8 m/s
Turbine
Velocity
Average
Met2
Velocity
Average
Average
of
Ratios
(true)
(true)
(hours)
(hours)
(hours)
(m/s)
(m/s)
0-10
10-20
20-30
30-40
40-50
50-60
60-70
70-80
80-90
90-100
100-110
110-120
120-130
130-140
140-150
150-160
160-170
170-180
180-190
190-200
200-210
210-220
220-230
230-240
240-250
250-260
260-270
270-280
280-290
4.57
14.54
25.17
34.59
44.63
54.74
64.77
74.94
85.35
95.77
104.94
114.98
125.20
134.78
144.46
155.67
165.13
175.39
184.98
195.25
205.05
214.87
224.88
235.03
245.23
255.25
264.19
275.16
284.91
20.45
13.25
13.53
10.33
9.37
6.40
3.78
3.57
4.75
7.58
10.55
10.75
11.73
12.60
8.72
12.58
24.35
29.87
32.68
35.60
50.55
46.97
36.50
44.10
43.93
68.48
46.58
30.23
33.02
20.32
13.22
13.43
10.33
9.37
6.40
3.78
3.53
4.53
5.77
6.95
8.72
9.92
10.62
7.58
9.65
16.77
19.92
24.08
21.90
26.70
29.25
24.88
32.57
29.93
36.27
37.63
28.85
31.88
0.13
0.03
0.10
0.00
0.00
0.00
0.00
0.03
0.22
1.82
3.60
2.03
1.82
1.98
1.13
2.93
7.58
9.95
8.60
13.70
23.85
17.72
11.62
11.53
14.00
32.22
8.95
1.38
1.13
4.09
4.10
3.73
3.71
3.77
2.99
2.63
3.08
3.58
5.13
6.02
5.12
5.43
5.62
4.85
5.34
6.19
6.38
6.30
6.88
7.61
6.89
6.36
6.42
6.69
7.57
5.75
4.44
4.32
3.93
3.98
3.56
3.54
3.62
2.91
2.57
3.00
3.46
4.91
5.81
4.98
5.30
5.48
4.74
5.21
6.03
6.22
6.13
6.68
7.37
6.63
6.07
6.10
6.38
7.30
5.60
4.35
4.21
1.04
1.03
1.05
1.05
1.04
1.02
1.03
1.03
1.03
1.04
1.04
1.03
1.03
1.03
1.02
1.02
1.03
1.03
1.03
1.03
1.03
1.04
1.05
1.06
1.05
1.04
1.03
1.02
1.03
290-300
294.56
25.08
24.67
0.42
4.59
4.49
1.03
300-310
304.79
19.85
19.63
0.22
4.65
4.53
1.03
310-320
314.85
17.80
17.50
0.30
4.62
4.52
1.02
320-330
325.38
18.80
18.18
0.62
4.59
4.51
1.02
330-340
334.96
19.85
19.27
0.58
4.66
4.57
1.02
340-350
345.23
20.98
20.68
0.30
4.88
4.73
1.03
350-360
354.12
17.30
17.20
0.10
4.62
4.38
1.06
The combined standard uncertainty of the wind speed ratio at 6 m/s, 10 m/s, and 14 m/s is 0.082 m/s, 0.063 m/s,
and 0.054 m/s respectively.
Page 9 of 58
Intertek Testing Services NA, Inc.
Figure 3 below plots the wind direction bin ratios that resulted from site calibration at the testing location.
Figure 3 - Site calibration ratio binned data. Valid sector from 160 - 270 degrees with respect to true north
Page 10 of 58
Intertek Testing Services NA, Inc.
Manufacturer
Model
Serial No
Calibration
Date
Calibration
Due
Primary Anemometer
4.3351.00.141
04100019
3-May-10
3-May-11
Reference Anemometer
4.3519.00.741
04100712
3-May-10
3-May-11
4-May-11
Wind Vane
4.3150.00.000
04100018
4-May-10
Pressure Sensor
Vaisala Oy
PTB330
F1420001
8-Apr-10
8-Apr-11
Temperature/RH Sensor
1.1005.54.241
85764
15-Apr-10
15-Apr-11
*Power Transducer
Ohio Semitronics
DMT-1040EY40
10051959
19-Apr-11
19-Apr-12
*Current Transformer
Ohio Semitronics
12975
002277039
19-Apr-11
19-Apr-12
A National Instruments cDAQ-9178 backplane and NI-9203 +/- 20 mA 8-channel current module was used for
logging the output signals from the sensors in Table 4 above. A proprietary LabVIEW program was used to
collect and filter data that is stored in raw and 1 Hz data files on the Intertek RTC site computer.
Prior to testing, a signal verification procedure was carried out on the data acquisition system by Intertek to verify
the signals of each transducer against recorded values from the LabVIEW program. Table 5 below summarizes
the results of the signal verification
Measurement
NI 9203 Channel
Primary windspeed
Reference windspeed
Wind direction
Relative humidity
Temperature
Barometric Pressure
Output power
n/a
Injected Signal
{mA}
Measured Value
{mA}
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
not used
Table 5 Signal verification results
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
4.000
12.000
20.000
not used
Offset
{mA}
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
n/a
Page 11 of 58
Intertek Testing Services NA, Inc.
The data acquisition system is located inside the Intertek RTC control building; all signals are measured at this
location. This is also the location of the turbine disconnect and grid-tie inverter, and thus is also where power
measurements are made. The data is stored on two separate computers at the Intertek RTC, and also stored in
the Intertek project file. The power measurement equipment is located inside the control building at an
approximate wire run length of 83.8 meters (275 feet); which satisfies the required wire run length in the
Standard.
Figure 4 below displays the arrangement of the meteorological tower with dimensions of instrument locations.
The height above ground level to the centerline of the cups of the primary anemometer is 36.04 meters. The
reference anemometer height above ground level is 34.19 meters, the wind vane height above ground level is
34.29 meters, the temperature sensor height above ground level is 27.41 meters and the pressure sensor height
above ground level is 27.23 meters. No in situ comparison of anemometers was made during this test period.
The primary method of anemometer calibration verification of post-test calibration was followed; calibration
certificates are found in Appendix C.
.
External conditions other than wind speed are out of the operating range of the wind turbine,
Turbine cannot operate because of a turbine fault condition,
Turbine is manually shut down or in a test or maintenance operating mode,
Failure or degradation (i.e. due to icing) of test equipment,
Wind direction outside the measurement sector as defined in section 5.2 above, or
Wind directions outside valid (complete) site calibration sectors as defined in section 5.2 above.
No maintenance was performed on the Fortis Montana during the test period.
The 1 minute averaged data sets were normalized to sea-level air density, 1.225 kg/m and the RTC average air
density during the test period. Due to the site average air density being outside the specified range of 0.05
3
kg/m of sea-level air density, normalization to actual average site density was required. The calculated site
3
average air density at the Intertek RTC for the measurement period was 1.1537 kg/m . Air density was
determined from measured air temperature and air pressure according to Equation 1 from IEC 61400-12-1. Data
normalization was then applied to the measured power output according to Equation 2 from IEC 61400-12-1.
Page 13 of 58
Intertek Testing Services NA, Inc.
8.0 Uncertainty
Table 6 below summarizes the Category B uncertainty parameters for the power performance measurements.
Total Category B uncertainty is obtained by combining each components uncertainty using the root-sum-squared
method. Combined uncertainty is the root-sum-squared combination of Category A and Category B uncertainties
of power performance measurements. Final Category A, Category B, and combined uncertainties for sea-level
air density and RTC average air density are presented in Tables 7 and 8 in section 9 of this report.
Component
Uncertainty
Source
Power (Inverter)
Voltage transducer
N/A
Current transformer
0.2887 % Amperage
Calibration Sheet
Power transducer
0.2887 % Wattage
Calibration Sheet
0.66 %
Manual
Data acquisition
Wind Speed
Anemometer
0.0289 m/s
Calibration Sheet
Operational Characteristics
IEC 61400-12-1
Terrain effects
0.0501 0.0532*
IEC 61400-12-1
Mounting effects
1%
Assumption
Data Acquisition
0.66 %
Assumption
Temperature
Temperature Sensor
0.0515 C
Calibration Sheet
Radiation Shielding
0.8165 C
IEC 61400-12-1
Mounting Effects
0.1935 C
IEC 61400-12-1
Data Acquisition
0.2656 C
Manual
Pressure Sensor
Pressure Sensor
0.0404 hPa
Calibration Sheet
Mounting Effects
0.0687 hPa
IEC 61400-12-1
Data Acquisition
1.8706 hPa
Manual
Page 14 of 58
Intertek Testing Services NA, Inc.
Bin
(m/s)
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
10.5
11
11.5
12
12.5
13
13.5
14
14.5
15
15.5
16
16.5
17
17.5
18
18.5
19
19.5
20
20.5
21
21.5
-0.08
-53.89
1
0.00
-0.07
-4.06
5
0.01
0.00
-0.05
-1.16
25
0.01
0.00
-0.02
-0.20
51
0.01
0.01
0.01
0.07
85
0.01
0.01
0.07
0.21
89
0.01
0.01
0.14
0.27
100
0.02
0.01
0.18
0.23
138
0.01
0.01
0.27
0.24
138
0.01
0.02
0.40
0.25
138
0.01
0.03
0.53
0.26
269
0.01
0.04
0.69
0.26
374
0.01
0.05
0.89
0.26
490
0.01
0.06
1.11
0.26
458
0.01
0.07
1.36
0.26
544
0.01
0.08
1.63
0.26
591
0.01
0.08
1.89
0.25
645
0.01
0.09
2.17
0.24
657
0.01
0.10
2.45
0.23
642
0.01
0.10
2.76
0.23
573
0.01
0.11
3.03
0.21
467
0.01
0.11
3.31
0.20
390
0.02
0.11
3.58
0.19
316
0.11
0.02
3.82
0.18
322
0.02
0.10
4.01
0.17
288
0.03
0.09
4.22
0.16
221
0.03
0.10
4.34
0.14
250
0.04
0.07
4.48
0.13
174
0.04
0.08
4.48
0.12
178
0.05
0.04
4.38
0.11
124
0.06
0.06
4.29
0.09
112
0.07
0.06
4.27
0.09
82
0.09
0.04
4.02
0.07
78
0.09
0.12
4.01
0.07
77
0.10
0.04
3.69
0.06
64
0.10
0.17
3.70
0.05
76
0.09
0.03
3.36
0.04
63
0.07
0.19
3.55
0.04
64
0.07
0.11
3.47
0.04
50
0.07
0.06
3.51
0.04
26
0.04
0.09
3.62
0.03
27
0.08
0.07
3.56
0.03
17
0.08
0.05
3.68
0.03
13
0.11
0.08
Table 7 Fortis Montana performance at sea-level air density; 1.225 kg/m3
Combined
Standard
Uncertainty
(kW)
0.01
0.01
0.01
0.01
0.02
0.02
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.08
0.09
0.10
0.10
0.11
0.11
0.11
0.11
0.11
0.09
0.10
0.07
0.09
0.06
0.09
0.09
0.10
0.15
0.10
0.20
0.09
0.21
0.13
0.09
0.10
0.11
0.09
0.14
Page 15 of 58
Intertek Testing Services NA, Inc.
Table 8 below shows the normalized and averaged results of the power performance test for the Fortis Montana
turbine at RTC average density. A normalization to test site actual air density was required due to the site
3
average density being outside the tolerance of 0.05 kg/m of sea-level air density.
Bin
(m/s)
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
10.5
11
11.5
12
12.5
13
13.5
14
14.5
15
15.5
16
16.5
17
17.5
18
18.5
19
19.5
20
20.5
21
21.5
-0.08
-50.75
1
0.00
-0.06
-3.82
5
0.01
-0.05
-1.09
25
0.01
-0.02
-0.18
51
0.01
0.01
0.07
85
0.01
0.06
0.20
89
0.01
0.13
0.25
100
0.01
0.17
0.22
138
0.01
0.26
0.23
138
0.01
0.37
0.24
138
0.01
0.50
0.24
269
0.01
0.65
0.24
374
0.01
0.84
0.25
490
0.01
1.05
0.25
458
0.01
1.28
0.25
544
0.01
1.53
0.24
591
0.01
1.78
0.24
645
0.01
2.04
0.23
657
0.01
2.31
0.22
642
0.01
2.60
0.21
573
0.01
2.85
0.20
467
0.01
3.11
0.19
390
0.01
3.37
0.18
316
0.02
3.60
0.17
322
0.02
3.78
0.16
288
0.03
3.97
0.15
221
0.03
4.09
0.14
250
0.03
4.22
0.13
174
0.04
4.22
0.11
178
0.05
4.13
0.10
124
0.06
4.04
0.09
112
0.07
4.02
0.08
82
0.08
3.79
0.07
78
0.08
3.77
0.06
77
0.09
3.47
0.05
64
0.09
3.48
0.05
76
0.08
3.16
0.04
63
0.07
3.34
0.04
64
0.07
3.27
0.04
50
0.06
3.31
0.03
26
0.09
3.40
0.03
27
0.08
3.35
0.03
17
0.08
3.46
0.03
13
0.11
Table 8 Fortis Montana performance at RTC air density; 1.1537 kg/m3
0.00
0.00
0.01
0.01
0.01
0.02
0.01
0.02
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.10
0.11
0.10
0.10
0.08
0.09
0.06
0.07
0.04
0.06
0.06
0.04
0.12
0.03
0.16
0.03
0.18
0.11
0.05
0.04
0.07
0.04
0.07
Combined
Standard
Uncertainty
(kW)
0.01
0.01
0.01
0.01
0.02
0.02
0.01
0.02
0.03
0.03
0.04
0.06
0.06
0.07
0.08
0.08
0.09
0.10
0.11
0.10
0.11
0.11
0.10
0.09
0.10
0.07
0.08
0.06
0.08
0.09
0.09
0.14
0.10
0.19
0.09
0.19
0.13
0.08
0.09
0.10
0.09
0.13
Page 16 of 58
Intertek Testing Services NA, Inc.
Table 9 below summarizes the estimation of expected annual energy production (AEP) at sea-level air density.
1.225
25.00
kg/m
m/s
Standard Uncertainty
kWh
247
347
440
519
583
632
666
685
%
7.6
5.8
4.8
4.2
3.8
3.6
3.5
3.4
Complete if
AEP-Measured
is at least 95%
of AEPExtrapolated
Complete
Complete
Complete
Complete
Complete
Complete
Complete
Complete
AEPExtrapolated
kWh
3232
5939
9114
12348
15322
17855
19864
21332
Table 9 Estimated annual energy production of the Fortis Montana at sea-level air density
Table 10 below summarizes the estimation of expected annual energy production (AEP) at RTC average air
density.
1.1537
25.00
kg/m
m/s
Standard Uncertainty
kWh
232
327
415
489
549
596
627
645
%
7.6
5.8
4.8
4.2
3.8
3.6
3.5
3.4
Complete if
AEP-Measured
is at least 95%
of AEPExtrapolated
Complete
Complete
Complete
Complete
Complete
Complete
Complete
Complete
AEPExtrapolated
kWh
3044
5593
8584
11630
14431
16817
18709
20091
Table 10 Estimated annual energy production of the Fortis Montana at RTC air density
An indication of incomplete in the far-right column of the above tables does not imply that the database for the
test is incomplete. Incomplete means that AEP-Measured is not within 95% of AEP-extrapolated. AEPextrapolated is an estimated extrapolation of annual energy production, where:
AEP-Measured assumes zero power below cut-in wind speed and between the highest valid wind speed
bin and cut-out wind speed, and
AEP-Extrapolated assumes zero power below cut-in wind speed and constant power between the highest
valid wind speed bin and cut-out wind speed.
Page 17 of 58
Figure 5 Fortis Montana power curve at sea-level air density; 1.225 kg/m3
Figure 6 below shows the graphical results of the power performance test for the Fortis Montana at RTC average
air density. The uncertainty of each wind speed bin is shown as error bars on the graph.
Figure 6 Fortis Montana power curve at RTC air density; 1.1537 kg/m3
Page 18 of 58
Intertek Testing Services NA, Inc.
Figure 7 below shows the 1 minute output power values for average, maximum, minimum, and standard deviation
of sampled data.
Figure 7 - Scatter plot of output power average, maximum, minimum, and standard deviation of 1 Hz data with 1 minute averaging.
Page 19 of 58
Intertek Testing Services NA, Inc.
Figure 8 - Coefficient of performance of the Fortis Montana with swept area of 19.95 m at sea-level air density of 1.225 kg/m3
Figure 9 - Coefficient of performance of the Fortis Montana with swept area of 19.95 m at RTC air density of 1.1537 kg/m3
Page 20 of 58
Intertek Testing Services NA, Inc.
Figure 10 below shows the turbulence intensity as a function of wind speed. The graph shows both sampled data
and binned data.
Page 21 of 58
Intertek Testing Services NA, Inc.
Figure 11 below displays both average wind speed measured by the primary anemometer and turbulence
intensity as a function of wind direction.
Page 22 of 58
Intertek Testing Services NA, Inc.
A.0 Appendix
The following sections can be found within this Appendix:
A Wiring diagrams
B Pictures of the test site
C Calibration certificates
Page 23 of 58
Intertek Testing Services NA, Inc.
A Wiring Diagrams
A.1 Typical wiring diagram for the Fortis Montana
Page 24 of 58
Intertek Testing Services NA, Inc.
Page 25 of 58
Intertek Testing Services NA, Inc.
*Note that the pictures included in this Appendix were taken after the turbine and tower had been removed from
the foundation. The tower was removed from the foundation in April 2012. During the testing period of the Fortis
Montana, no additional measurement towers or turbine towers were installed at the Intertek RTC.
Page 26 of 58
Intertek Testing Services NA, Inc.
B.2 Northwest
Page 27 of 58
Intertek Testing Services NA, Inc.
B.3 West
Page 28 of 58
Intertek Testing Services NA, Inc.
B.4 Southwest
Page 29 of 58
Intertek Testing Services NA, Inc.
Page 30 of 58
Intertek Testing Services NA, Inc.
B.6 Southeast
Page 31 of 58
Intertek Testing Services NA, Inc.
B.7 East
Page 32 of 58
Intertek Testing Services NA, Inc.
B.8 Northeast
Page 33 of 58
Intertek Testing Services NA, Inc.
C Calibration Certificates
C.1 Primary Anemometer
Page 34 of 58
Intertek Testing Services NA, Inc.
Page 35 of 58
Intertek Testing Services NA, Inc.
Page 36 of 58
Intertek Testing Services NA, Inc.
Page 37 of 58
Intertek Testing Services NA, Inc.
Page 38 of 58
Intertek Testing Services NA, Inc.
Page 39 of 58
Intertek Testing Services NA, Inc.
Page 40 of 58
Intertek Testing Services NA, Inc.
Page 41 of 58
Intertek Testing Services NA, Inc.
Page 42 of 58
Intertek Testing Services NA, Inc.
Page 43 of 58
Intertek Testing Services NA, Inc.
Page 44 of 58
Intertek Testing Services NA, Inc.
Page 45 of 58
Intertek Testing Services NA, Inc.
Page 46 of 58
Intertek Testing Services NA, Inc.
Page 47 of 58
Intertek Testing Services NA, Inc.
Page 48 of 58
Intertek Testing Services NA, Inc.
Page 49 of 58
Intertek Testing Services NA, Inc.
Page 50 of 58
Intertek Testing Services NA, Inc.
Page 51 of 58
Intertek Testing Services NA, Inc.
Page 52 of 58
Intertek Testing Services NA, Inc.
Page 53 of 58
Intertek Testing Services NA, Inc.
Page 54 of 58
Intertek Testing Services NA, Inc.
Page 55 of 58
Intertek Testing Services NA, Inc.
Page 56 of 58
Intertek Testing Services NA, Inc.
Page 57 of 58
Intertek Testing Services NA, Inc.
Page 58 of 58
Intertek Testing Services NA, Inc.