Académique Documents
Professionnel Documents
Culture Documents
SECTION -A24
PART-2: UNIT PROTECTION SETTINGS
380kV Bus Bar Protection Settings Set-2
Applicable for 380kV Bus Bars
RELAY DATA
Type of Relay
Make
Rated Current
Rated Frequency
7SJ80
Siemens
1 Amp.
60 Hz.
Relay Application
High Impedance Bus Bar Protection (87BB)
System Data
System Service Voltage
System Frequency, f
Busbar Rated Current Capacity
Busbar Short Time withstand current
=
=
=
=
380 kV
60 Hz
3150 A
63000 A
=
=
=
for 1 sec
CT Data
Class
CT Rated Primary Current
CT Rated Secondary Current
Adopted Tap
CT Secondary Resistance, Rct
<
TPS
3000-2500-2000-1500-1250-1000-750
1A
3000 A
4.7 Ohm
>
=
5550 V
50 mA
Rl
=
=
=
=
=
=
=
250 m
300 m
6 sqmm
0.00356 ohm/m
Distance x Res/m
(300) * (0.00356)
1.07 ohm
RWIRE
2.14 ohm
Cable Data
Distance between Relay and CT:
( with 20 % margin)
CT Cable size
CT Cable resistance (ohm/m):
One way CT Cable Resistance:
IMAX,EXT/kr(RCT + RWIRE)
And the minimum knee point voltage (EK) of the CT must be:
EK
2USET
Ek Calculation formula
As per 7SJ80 relay for High Impedance Diff. protection, the CT knee point emf (Ek) shall meet the following
requirement
EK
2USET
USTAB
IMAX,EXT/kr(RCT + RWIRE)
IMAX,EXT
USTAB
=
=
=
IMAX,EXT/kr(RCT + RWIRE)
The setting voltage USET of the scheme over the differential branch shall be made equal or greater than the
required stability voltage
Therefore
USET
EK
>
150 V
2*150
EK
>
300 V
3000 A
= 150 V
= 450
C = constant of Metrosil
= 0.25
= Index of Metrosil
Ivar = Current drawn by Metrosil at setting voltage,
Therefore,
Ivar
Ivar
Ivar
=
=
0.52 x [2 x 150/450]^(1/0.25)
0.0257 A
Having chosen the primary fault sensitivity Ip,des of the scheme, the secondary setting of the relay Iset can be
calculated as below, where the varistor spill current will be at this stage neglected:
Where
NCT
NCT
Iset
Iset
1.0 A
(USet/Iset) - (RRelay)
=
=
(150/1)
150.0
=
=
=
Uset2 / Rstab
(150)^2 / 150
150.00 W
Furthermore, Rstab must have a short time rating large enough to withstand the fault current before the fault
is cleared. Thereby, the rms voltage developed across the stabilizing resistor during maximal prospective
internal fault Urms,f is decisive for the thermal stress of the stabilizing resistor. It is calculated according to
below formula.
Urms,f
=
=
The time duration of 0.5 seconds can be typically considered for the stabilizing resistor ( Pstab,0.5s ).
The resulting short-time rating Pstab,0.5s shall be then chosen as per below
=
=
=
Urms,f2 / Rstab
(6262.4)^2 / 150
261451.03 W
Rstab
150.0
Pstab,cont
150.00 W
Pstab,0.5s
261451.03 W
Pstab,0.5s
Pstab,0.5s
Therefore:
Resistor chosen (per relay input):
Metrosils Requirement :
With reference to the Metrosil Catalogue the selected Metrosil is 600-A/S1/256 or higher model.