Académique Documents
Professionnel Documents
Culture Documents
Department of Electrical & Computer Engineering, College of Engineering, Sultan Qaboos University, Oman
b Power Systems Department, Petroleum Development Oman (PDO), Oman
Received 20 June 2005; received in revised form 27 October 2005; accepted 30 October 2005
Available online 15 December 2005
Abstract
Comprehensive standard tests were conducted on 33 kV line-post porcelain insulators in order to improve their performance in harsh environment
in comparison to the newly introduced polymeric ones. These tests are the lightning impulse withstand and flashover tests, and the AC artificial
pollution tests. The latter were conducted in a salt-fog chamber. Silicone rubber insulators showed superior performance than adding heat-shrinkable
and wraparound creepage extenders to the existing line-post porcelain insulators or using new polymeric insulators.
2005 Elsevier B.V. All rights reserved.
Keywords: Line insulators; Leakage current; Flashover; Silicone rubber; Creepage extenders
1. Introduction
Recently, some of Petroleum Development Oman (PDO)
distribution lines which are near the sea side or pass through
highly contaminated areas, have high leakage current leading
to wooden pole fires, insulator fracture and current breaking
problems. All of these abnormalities have caused inadvertent,
where each pole fire causes up to 600 m3 of oil deferment.
All 33 kV distribution lines have line-post porcelain insulators with different designs at a specific creepage distance of
40 mm/kV.
Wooden pole fires can not be attributed to any single factor
but a number of concurrent conditions with insulator contamination as a prerequisite followed by atmospheric conditions
of wind, fog or heavy mist. The leakage currents can generate
enough localized heat to ignite the wood at the point of contact between wood and metal surfaces and start a pole top fire,
especially when pole crossarms and insulators are near or at
the end of their service life. Live-line washing represents one
of the solutions to reduce the leakage current on the insulator
surface and hence the pole fires. The main drawback of a washing approach is, though, establishing the correct timing of the
operation. In addition, washing is not effective in environments
subject to instantaneous polluting conductive mist conditions,
e.g. marine salt fogs.
This paper introduces two possible solutions to reduce the
wooden pole fire in very heavy polluted areas, namely, adding of
creepage extenders to the existing line-post porcelain insulators
or replacing the latter by silicone rubber ones.
2. Adding of silicone-rubber creepage extenders
Creepage distance is the shortest distance on insulating surface that exists between two conductive parts of an insulator with
different potentials. An approach to improve insulators performance is to increase the creepage distance. This can be achieved
by increasing the shed diameter, and therefore the shed projection, with the application of extenders. For example, should the
creepage be increased from, say, 16 mm/kV to 25 mm/kV, then
the insulator has been effectively upgraded from one suited to a
Light pollution category to a Heavy pollution classification
[13].
Creepage extenders are made of true HTV silicone rubber
material with inherent hydrophobic characteristics and tracking,
erosion and UV resistance, and are attached to the insulators by
means of an RTV silicone rubber adhesive. Even uncoated, the
779
sheds are capable of operating in the most extreme environments. Creepage extenders increase the flashover performance
of insulators by:
reducing the surface electric stress,
reducing the leakage current and
increasing the electric strength of insulators.
There are two types of creepage extenders, namely, heatshrinkable creepage extenders (HSCEs) and wraparound creepage extenders (WACEs). HSCE and WACE add a nominal of
100 mm and 150 mm to the creepage length, respectively [2].
Generally, it is recommended to increase the existing creepage
distance by at least 20%. Creepage extender does not upgrade
the voltage class of the insulator. The disadvantage of creepage
extenders is that the different surface properties of the ceramic
insulator and the polymer extender can create severe voltage
distortions at the transitions between the materials, resulting in
partial discharges and flashover [13].
3. Replacement of existing porcelain by silicone rubber
insulators
Silicone rubber (SiR) as outdoor insulation material has been
used for more than 25 years with good service experience. Today,
SiR is the most used polymeric material for medium and highvoltage outdoor insulation [4]. After about 11 years of operation
in various polluted areas, SiR insulators removed from 110 kV to
220 kV transmission lines still presents a good hydrophobicity
property [5]. Generally, the hydrophobicity distribution of SiR
insulator is non-uniform. It is found that the local deterioration of
hydrophobicity has close correlation with the local strengthening
of electric field. Water droplets induced low-energy discharge is
a very important reason for the hydrophobicity loss of SiR insulators in service. In order to improve the long-term performance
of SiR insulator, it is better to limit the electric field level near
end-fittings 5 kV/cm.
In general, surface degradation of polymeric insulators is
caused by environmental attack related to weather conditions
and electrical activity. Environmental attack includes thermal
degradation from ambient temperature, ultraviolet induced polymer degradation, acidic attack from acid rain or acid fog, chemical attack from salt contamination, sandblast, etc. Electrical
attack includes partial discharges caused by leakage current, dry
band arcing and corona near the metal fittings. The chemical
structure of the polymer changes by chain scission (depolymerization), oxidation, etc. As the result of these changes, the
polymer may lose elasticity, become brittle and lose the mechanical strength. As well, increased surface roughness or loss of the
polymer matrix could cause loss of surface hydrophobicity and
lead to high leakage current [6].
4. Test results and discussion
This section presents the lab tests. Two types of tests were carried out: (1) standard lightning impulse withstand and flashover
tests according to IEC standards [710] and (2) standard AC arti-
780
Table 1
Details of the test samples
A
B
C
D
E
F
Status
Material
Number and
type of sheds
Distance between
large sheds (mm)
Top/bottom shed
diameter (mm)
Top/bottom trunk
diameter (mm)
Axial length
(mm)
Arcing distance
(mm)
Creepage distance
(mm)
Used
Used
Used
Used
New
New
Porcelain
Porcelain
Porcelain
Porcelain
Silicone Rubber
Polymeric
12 Regular
11 Regular
13 Irregular
11 Irregular
17 Irregular
16 Irregular
38
27
50
70
41
52
197/197
191/191
202/202
197/230
135/105
134/113
105/108
92/108
103/115
72/108
53
60
590
520
525
540
580
560
503
493
490
475
460
500
1510
1488
1480
1495
1460
1520
electrons are quickly attracted in the positive terminal and leaving the heavy positive ions behind, i.e. extending the region for
ionization. This leads to a decrease in the flashover voltage.
On contrary for the application of negative impulses, the space
charges (electrons) are repelled into the low-field region and
the ionization region is drastically reduced leading to a higher
flashover voltage. As can be seen the SiR and the polymeric insulators (E and F) have the highest negative U50% . All insulators
have roughly the same U50% under positive application, where
insulator E has the lowest U50% because it has the lowest arcing
distance among all insulators tested (see Table 1). It is worth
mentioning that insulators AD are used ones, therefore their
U50% , under negative applications are lower in comparison with
those of insulators E and F. In addition, the arcing distance of
insulator F is higher than that of insulators B and C (see Table 1).
Insulators with HSCEs are indicated as (CE), e.g. insulator A
with HSCEs is indicated as A (CE).
Impulse tests with CEs were conducted for insulators A and
D. Two of each of HSCEs and WACEs were added for two
insulators of type A and three HSCEs for type D. The aim of
this test is to find out the effect of CEs on the U50% of the
insulator. Table 2 introduces a comparison of the application
of the both types of CEs. From Fig. 3 and Table 2, it can be
Table 2
U50% in kVpeak under positive and negative polarities with and without CEs
Polarity
Positive
Negative
307
284
314
289
356
406
426
447
424
446
781
Fig. 4. Oscillograms of I and V for insulator B: (a) dry condition and (b) cleanfog condition.
Fig. 5. Oscillograms of I and V for insulator E: (a) dry condition and (b) cleanfog condition.
Fig. 6. Oscillograms of I and V for insulator F: (a) dry condition and (b) cleanfog condition.
782
Fig. 8. Oscillograms of I and V for insulator A with and without two HSCEs,
and for dry and clean-fog conditions.
Fig. 7. IV curves for all 33 kV line-post insulators: (a) dry condition and (b)
clean-fog condition.
In this test, the insulator types A and D were tested inside the
salt-fog chamber (100% relative humidity and at room temperature of 25 C). Two CEs were used for insulator A, while three
were used for insulator D. From Figs. 8 and 9, it can be seen
clearly that the effect of the CEs on insulator A. At dry condition, three is no remarkable change in the leakage current with
and without the CEs. At clean-fog condition, it is obviously seen
that the effect of the CEs on decreasing the leakage currents by
about 75% and 44% for adding two HSCEs and two WACEs,
respectively. The latter effect is due to the gap left in the case of
using WACEs (see Fig. 1(g)). It is worth mentioning that adding
CEs not only reduces the leakage current peaks but also shifts
the current waveforms to be more capacitive (see Fig. 8). Similar
trend was also observed when using three HSCEs for insulator
D but with lower efficiency.
4.5. IV characteristics under salt-fog condition
In this test, the insulators were dipped for 20 min in a high
salinity solution with electrical conductivity of = 100 mS/cm
and NaCl concentration of 70 g/l [12]. Thereafter, the insulators
Fig. 9. The IV curves for insulator A with and without two HSCEs and two
WACEs, and for dry and clean-fog conditions.
were tested inside the salt-fog chamber at the rated phase voltage
of 19.05 kVrms .
For a continuous application of sinusoidal voltage, the leakage current causes drying of the wet pollution layer and, therefore, both the current amplitude and pattern can vary with time
[14]. Consequently, a continuous fog generation at a constant
rate was used throughout the whole experimental investigations.
As the electric stress increases, additional short current peaks
may appear at the signal crest due to discharges across dry band
areas, as well as between water droplets; especially the dynamically moved water droplets [14]. Water droplets on insulator
surfaces elongate under electric stress. Corona and dry-band
discharges may appear from and between the droplets causing
current pulses with high amplitudes.
Continuous fog was generated and the voltage was applied
for 30 min, where the leakage current pulses become repetitive. The leakage current dries the conductive layer and dry
bands are formed [13]. The high-voltage flashes over the dry
bands to create partial arcs. Dry-band arcing causes surface
discharges, which change both the leakage current shape and
magnitude. Depending on contamination levels, extension of
the arc generates a non-sinusoidal arc current, which may contain short duration impulses superimposed on the 50 Hz current
and the leakage current becomes intermittent as can be seen in
Figs. 10 and 11.
Fig. 10 illustrates the current pulses for insulator E in mA
range. It can be seen that the silicone rubber insulator (E) has
better performance, where other results reveal that its leakage
current is about 40% of that for the polymeric insulator (F).
These results are consistent with those under clean-fog condition; see Figs. 5 and 6 for insulators E and F, respectively,
where insulator E gives much lower leakage current due to
the hydrophobicity property. In addition, the effect of CEs was
investigated for insulators D and A as shown in Fig. 11. From
Fig. 11(a and b), it is noticed that the use of CEs reduces
the peak of the leakage current pulses by more than 90%.
From Figs. 11(c) and 12(d), it can be seen that the WACEs
give higher leakage current than that for the HSCEs type. It is
worth mentioning that high leakage currents for insulators AD
can be attributed to the surface roughening of the field-aged
insulator, which causes of trapping a large volume of conductive salt-fog pollution. These insulators rapidly establish unstable dry band conditions, i.e. unstable high-amplitude current
pulses.
783
Fig. 11. Oscillograms of I and V for insulators D and A: (a) insulator D without
CEs; (b) insulator D with three HSCEs; (c) insulator A with two HSCEs; (d)
insulator A with two WACEs.
784
Fig. 12. Effect of NaCl concentration on AC wet flashover voltage with and
without HSCEs.
785
[11] Composite Insulators for a.c. Overhead Lines with a Nominal Voltage
Greater than 1000 VDefinitions, Test Methods and Acceptance Criteria, IEC Standards 61109, 1992.
[12] Artificial Pollution Tests On High-Voltage Insulators to be Used on a.c.
Systems, IEC Standards 60507, 1991.
[13] F. Amarh, G.G. Karady, R. Sundararajan, Level crossing analysis of
leakage current envelope of polluted insulators, IEEE Power Eng. Rev.
21 (August (8)) (2001) 4649.
[14] M.A.R.M. Fernando, J. Lambrecht, S.M. Gubanski, Modeling non-linear
leakage currents on artificially polluted polymeric surfaces, in: Conference on Electrical Insulation and Dielectric Phenomena, Annual Report,
vol. 1, October 2528, 1998, pp. 5255.
[15] A. De La O, R.S. Gorur, J.T. Burnham, Laboratory wet tests on artificially contaminated nonceramic and ceramic insulators, in: Tenth International Symposium on High Voltage Engineering, Montreal, Canada,
August 2529, 1997.
[16] R.S. Gorur, A. De La O, H. El-Kishky, M. Chowdhary, H. Mukherjee,
R. Sundaram, J.T. Burnham, Sudden flashover of nonceramic insulators in artificial contamination tests, IEEE Trans. Dielectrics Electrical
Insulation 4 (February (1)) (1997) 7987.