Edition VIII
Engineered Lumber is an important part of every flooring system that is sturdy enough
to support heavy furniture like pool tables, pianos or china cabinets.
more consistent and has more loadcarrying capacity and spanning ability
than regular sawn lumber.
Easy installation
Every piece is consistently true to size.
Even though its extremely strong,
GP engineered lumber is lightweight
and easy to cut. Plus, wiring and
plumbing pass easily through the
web of Wood I Beam joists for more
clearance and higher ceilings.
Environmentally sound
Engineered lumber makes more
efficient use of trees because it is made
using smaller, computer-evaluated
lumber and plywood veneers.
Engineered lumber requires between
40 to 50% less wood fiber than the
equivalent conventional lumber.
engineeredlumber.
Cost effective
The advantages of GP engineered
lumber go beyond superior
performance. Youll find engineered
lumber is the lowest total cost
solution in the marketplace. The GP
Value Length method of ordering
and shipping materials minimizes
waste in labor and materials. Now,
you can think like a framer instead
of an engineer with a selection of
standard sizes that can be trimmed
on site to meet the needs of the job.
Jigsaw puzzle job packs with
dozens of lengths are eliminated,
helping to greatly reduce the need for
handling and cutting before joists get
to the job.
Dependable delivery
and availability
BlueLinx maintains an extensive
inventory thats ready to be delivered
through the largest distribution
network in the U.S. What does that
mean to you? The quality engineered
lumber you need is on your job site,
when you need it.
Details
Dead Load Material Weights . . . .17
Storage, Handling,
Safety and Installation . . . . . .18-19
Typical Framing . . . . . . . . . . . . . . .20
Fire Rated Assemblies . . . . . . . . .21
Plumbing Details . . . . . . . . . . . . .21
Floor Details . . . . . . . . . . . . . . .22-25
Simple-to-use software
Georgia-Pacifics exclusive FASTBeam
software helps you make the most of
engineered lumber.
FASTBeam analyzes a variety of load
conditions to determine the optimum
joist or beam based on cost, availability,
size and spacing while dramatically
reducing the time it takes to spec plans.
GP Lam LVL
Bearing Details . . . . . . . . . . . . . . .34
Handling and Installation . . . . . . .35
Floor Beams . . . . . . . . . . . . . . . . .35
Window, Patio Door
and Garage Door Headers . . .36-37
Roof Hip and Valley Beam . . .38-39
Bearing Length Requirements . .49
Allowable Uniform Loads . . . .41-47
Fastening
Recommendations . . . . . . . . .48-49
Tapered Cut Allowable
End Reactions . . . . . . . . . . . . .50-51
Framing Connectors . . . . . . . .52-53
Beam and Header
Design Properties . . . . . . . . . . . . .54
Allowable Holes in
GP Lam LVL . . . . . . . . . . . . . . . . . .54
Architectural Specifications . . . .55
GPI Series
9
WI Series
9
9
9
9
9
9
9
99
System Performance
The ultimate goal in the design of a floor or roof system is the end users safety and satisfaction. Although joists used at spans indicated in this guide meet or exceed minimum code
criteria and will safely support the loads imposed on them, judgement must be used to adequately meet user expectation levels. These expectations may vary from one user to another.
The specifier should consider the meaning of a given deflection limit in terms of allowable
deflection and the effects this could have on the system. For example, L/360 (span/360) for a
308 span is 19 of deflection. L/240 would be 112,9 and L/180 would be 29 of deflection.
Consideration might also be given to cases in which a joist with a long span parallels a
short span or a foundation end wall. For example, a 308 span with up to 19 of allowable live
load deflection could be adjacent to an end wall with no deflection, causing a noticeable
difference in floor levels under full design load.
A stiffer floor will result from using a live load deflection limit of L/480 versus the code
minimum L/360. A roof system with less total load deflection than the code required L/180
may be achieved by using a criterion of L/240.
In addition to more stringent deflection limits, several other factors may improve overall
floor performance. Reducing joist spacing and/or increasing the subfloor thickness will
lessen deflection between adjacent joists and increase load sharing. For increased floor
stiffness, BlueLinx recommends gluing the subfloor to the joists before nailing or screwing
rather than nailing alone. For additional stiffness, glue tongue and groove joints. Surfaces
must be clean and dry before gluing.
As with any construction, it is essential to follow proper installation procedures. Joists
must be plumb and anchored securely to supports before system sheathing is attached.
Supports for multiple span joists must be level. To minimize settlement when using hangers,
joists should be firmly seated in the hanger bottoms. Leave a 1169 gap between joist end
and header.
Vibrations may occur in floor systems with very little dead load, as in large empty rooms.
A ceiling attached to the bottom of the joists will generally dampen vibration as will interior
partition walls running perpendicular to the joists. If a ceiling will not be attached to the
bottom of the joists, vibration can be minimized by nailing a continuous 2 x 4 perpendicular
to the bottom of the joists at midspan running from end wall to end wall. Where future
finishing of the ceiling is likely, x-bridging or Wood I Beam blocking panels may be used
in place of the 2 x 4.
Span
Illustrations
(see note 4)
GPI 65
WI 40
WI 60
WI 80
Joist
Depth
11789
91 29
11789
149
11789
149
169
9129
11789
149
11789
149
169
11789
149
169
1299 o.c.
208-059
188-009
218-069
248-049
238-039
268-059
298-049
188-009
218-059
248-049
228-079
258-099
288-069
248-119
288-039
318-049
GPI 65
WI 40
WI 60
WI 80
Multiple Spans
Joist
Depth
11789
9129
11789
149
11789
149
169
9129
11789
149
11789
149
169
11789
149
169
1299 o.c.
208-059
188-009
218-069
248-049
238-039
268-059
298-049
188-009
218-059
238-099
228-079
258-099
288-069
248-119
288-039
318-049
1299 o.c.
228-029
198-079
238-049
268-069
258-039
288-099
318-119
198-079
238-059
258-119
248-089
288-009
318-019
278-019
308-109
348-029
2499 o.c.
178-059
158-069
178-089
198-049
208-039
208-089
208-089
148-079
168-079
188-039
198-079
198-099
198-099
218-079
238-119
238-119
2499 o.c.
158-059
148-029
168-019
17'-019
178-029
178-029
178-029
138-039
158-029
168-059
168-059
168-059
168-059
188-029
198-119
198-119
NOTES:
1. These span charts are based on uniform loads, as noted above; live load deflection is limited
to L/480 for better performance. Floor performance is greatly influenced by the stiffness of the
floor joists. Experience has shown that joists designed to the code minimum live load deflection
(L/360) will result in a floor which may not meet the expectations of some end users. BlueLinx
strongly recommends floor spans for Wood I Beam joists in accordance with those given
above, which are based on L/480 live load deflection. (One-third stiffer than required by code.)
2. Spans are clear distances between supports, and are based on composite action with gluednailed APA Rated Sheathing or Sturd-I-Floor of minimum thickness 19 32 9 (40/20 or 20 oc) for
joist spacing of 19.29 or less, or 23 32 9 (48/24 or 24 oc) for a joist spacing of 249. Adhesive must
2499 o.c.
168-069
148-069
178-049
198-059
188-089
218-039
238-079
148-069
168-089
188-049
188-029
208-089
228-109
198-109
228-079
258-009
2499 o.c.
158-119
148-029
168-029
178-099
188-089
218-039
228-039
138-049
158-039
168-099
178-119
198-089
198-109
198-109
218-029
218-029
1299 o.c.
228-029
198-079
228-109
258-019
258-039
288-099
318-119
188-119
218-069
238-089
248-089
278-109
308-009
278-019
308-109
348-029
meet APA AFG-01 or ASTM D3498. Apply a continuous line of glue (about 14 9 diameter) to top
flange of joists. All surfaces must be clean and dry. If sheathing is nailed only (not recommended), reduce spans by 129.
3. Minimum end bearing length is 1 34 9. Minimum intermediate bearing length is 3 12 9.
4. For multiple-span joists: End spans must be at least 40% of the adjacent span. Spans shown
above cover a broad range of applications. It may be possible to exceed these spans by
analyzing a specific application with GP FASTBeam selection software.
5. For loading other than that shown above, refer to Uniform Load Tables, use FASTBeam software, or contact BlueLinx Engineered Lumber Technical Services.
6. Not all products are available at all distribution centers; contact BlueLinx for availability.
208
228
248
268
X
(Kneewall
Location)
1299 o.c.
7
2499 o.c.
1299 o.c.
7
GPI 65 (Depth)
Spacing
1699 o.c.
19.299 o.c.
2499 o.c.
48
60-11 89
60-149
60-169
80-169
11 89
149
149
169
58
60-149
60-149
60-169
80-169
11789
149
169
169
68
60-149
60-149
60-169
80-169
11789
149
149
169
48
60-149
60-169
80-169
80-169
149
169
169
Call BlueLinx
58
60-149
60-169
80-169
Call BlueLinx
149
169
169
Call BlueLinx
68
60-149
60-169
80-169
Call BlueLinx
149
169
169
Call BlueLinx
48
60-169
80-169
Call BlueLinx
Call BlueLinx
169
169*
Call BlueLinx
Call BlueLinx
58
60-169
80-169
Call BlueLinx
Call BlueLinx
169
Call BlueLinx
Call BlueLinx
Call BlueLinx
68
60-169
80-169
Call BlueLinx
Call BlueLinx
169
Call BlueLinx
Call BlueLinx
Call BlueLinx
78
60-169
80-169
Call BlueLinx
Call BlueLinx
169
Call BlueLinx
Call BlueLinx
Call BlueLinx
48
80-169
Call BlueLinx
Call BlueLinx
Call BlueLinx
169
Call BlueLinx
Call BlueLinx
Call BlueLinx
58
80-169
Call BlueLinx
Call BlueLinx
Call BlueLinx
169*
Call BlueLinx
Call BlueLinx
Call BlueLinx
68
80-169
Call BlueLinx
Call BlueLinx
Call BlueLinx
169*
Call BlueLinx
Call BlueLinx
Call BlueLinx
78
80-169
Call BlueLinx
Call BlueLinx
Call BlueLinx
169*
Call BlueLinx
Call BlueLinx
Call BlueLinx
*Under these conditions, live load deflection meets building code, but does not meet L/480. Worst case is L/467.
Design Parameters:
1. Glued and nailed floor sheathing.
2. Deflection limits: L/240 total load, L/480 live load, unless noted otherwise.
3. Roof loads of 30 PSF live load at 115% (snow load).
4. Roof dead load of 12 PSF (asphalt shingles).
5. Roof rafter slope between 8/12 and 12/12.
6. Kneewall weight of 40 PLF.
7. Attic storage load of 20 PSF live load (outside the kneewalls).
8. Floor live load of 40 PSF (between the kneewalls).
9. Attic and floor dead load of 10 PSF.
10. Straight gable roof framing. No hip framing is permitted.
11. For other conditions, including holes, use FASTBeam software
or call BlueLinx.
DO NOT
2 x __ roof and
wall framing
Bonus Room
Wood I Beam Floor Joist
DO
or DO
r
r
Live Load
Deflection
Total Load
Deflection
L/360
L/240
249
2. Improved performance
L/480
L/360
3. High performance
L/600
L/480
Product Selection Guide based on joist span. Determine span, select desired performance level, choose joist option.
Products above the bold line in each column are limited to 1/2( live load deflection when fully loaded.
Floor
Span
148
158
168
178
188
198
208
218
228
238
248
Joist
GPI 20
40 Series
WI 60
GPI 65
WI 80
GPI 20
40 Series
WI 60
GPI 65
WI 80
GPI 20
40 Series
WI 60
GPI 65
WI 80
GPI 20
40 Series
WI 60
GPI 65
WI 80
GPI 20
40 Series
WI 60
GPI 65
WI 80
GPI 20
40 Series
WI 60
GPI 65
WI 80
40 Series
WI 60
GPI 65
WI 80
40 Series
WI 60
GPI 65
WI 80
40 Series
WI 60
GPI 65
WI 80
40 Series
WI 60
GPI 65
WI 80
WI 60
GPI 65
WI 80
NOTE:
Please refer to
Improved Performance
or High Performance
2. IMPROVED PERFORMANCE
Depth
Spacing
1178 9
19.29 o.c.
1
9 2 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
249 o.c.
1178 9
19.29 o.c.
912 9
19.29 o.c.
1178 9
19.29 o.c.
7
11 8 9
19.29 o.c.
1178 9
249 o.c.
7
11 8 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
249 o.c.
7
11 8 9
19.29 o.c.
7
11 8 9
19.29 o.c.
1178 9
19.29 o.c.
7
11 8 9
19.29 o.c.
1178 9
249 o.c.
1178 9
169 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
7
11 8 9
249 o.c.
7
11 8 9
129 o.c.
149
19.29 o.c.
1178 9
19.29 o.c.
1178 9
19.29 o.c.
1178 9
249 o.c.
149
19.29 o.c.
149
19.29 o.c.
1178 9
19.29 o.c.
149
249 o.c.
149
169 o.c.
149
19.29 o.c.
149
19.29 o.c.
149
249 o.c.
149
169 o.c.
149
19.29 o.c.
149
19.29 o.c.
149
249 o.c.
149
129 o.c.
169
19.29 o.c.
169
19.29 o.c.
169
249 o.c.
169
19.29 o.c.
169
19.29 o.c.
169
249 o.c.
3. HIGH PERFORMANCE
Depth
Spacing
7
11 8 9
169 o.c.
1
9 2 9
169 o.c.
7
11 8 9
169 o.c.
1178 9
169 o.c.
1178 9
19.29 o.c.
1178 9
169 o.c.
912 9
169 o.c.
7
11 8 9
169 o.c.
7
11 8 9
169 o.c.
1178 9
19.29 o.c.
7
11 8 9
169 o.c.
1178 9
169 o.c.
1178 9
169 o.c.
1178 9
169 o.c.
1178 9
19.29 o.c.
7
11 8 9
169 o.c.
1178 9
169 o.c.
7
11 8 9
169 o.c.
7
11 8 9
169 o.c.
1178 9
19.29 o.c.
1178 9
129 o.c.
1178 9
169 o.c.
1178 9
169 o.c.
7
11 8 9
169 o.c.
7
11 8 9
19.29 o.c.
7
11 8 9*
129 o.c.
149
169 o.c.
1178 9
169 o.c.
1178 9
169 o.c.
1178 9
19.29 o.c.
149
169 o.c.
149
169 o.c.
149
169 o.c.
149
19.29 o.c.
149
129 o.c.
149
169 o.c.
149
169 o.c.
149
19.29 o.c.
149
129 o.c.
169
169 o.c.
169
169 o.c.
169
19.29 o.c.
Does not work
169
169 o.c.
169
19.29 o.c.
169
19.29 o.c.
169
169 o.c.
169
169 o.c.
169
19.29 o.c.
*Not Recommended. Experience suggests the end user may not be satisfied with the minimum system performance.
NOTES:
1. Table assumes normal residential loads of 40 PSF live load and 10 PSF dead load except for High
Performance column. High Performance system is based on 40 PSF live load, 20 PSF dead load.
2. Table assumes simple span applications.
3. If load bearing walls from above do not stack directly to walls or beams below, call BlueLinx.
4. Many combinations of series, depth and on-center spacing can provide desired performance levels; the
recommendations in this table are based on performance, costs and installation factors. For other
options contact BlueLinx.
19 16 9
38 38 9
57 58 9
76 1316 9
969 (88)
6
7
8
9
10
115 316 9
134 38 9
153 58 9
172 1316 9
1929 (168)
11
12
13
14
15
211 316 9
230 38 9
249 58 9
268 1316 9
2889 (248)
Capacities
Vertical Load:
Rim or starter joist = 4850 plf.
Horizontal load (lateral seismic or wind):
200 plf using a load duration factor of 160%
1/2 9 lag or through bolt attaching ledger to rim board:
350 lbs. lateral load per bolt
Depth
Weight (plf)
Thickness 11/8 9
91/2 9
117/8 9
3.0
3.7
149
4.4
16 9
5.0
Length 128
Constructed according to
connection requirements below.
Refer to details F5 and F6 for
additional information.
Connection Requirements
To joist: Face-nail rim board to each joist with two (2) 8d nails, one
each into top and bottom flange.
To plate: Toe-nail rim board to wall plate with 8d nails at 69 oc or 16d
nails at 129 oc. See note I, page 19 for information regarding
fasteners and preservative treated wood.
Subfloor: Attach floor sheathing to rim board per building code or
structural panel manufacturers specifications (closest oncenter nail spacing is 69). For shear transfer (lateral seismic
or wind) of up to 200 PLF, use 8d at 69 oc.
To rim:
Approved Applications
FiberStrong rim board has been tested and approved as a rim board and starter joist by APA-EWS. FiberStrong
rim board is not recommended as a structural joist, rafter, header or ledger. For such applications, consider
Wood I Beam joists or GP Lam LVL or contact BlueLinx. GP Lam LVL may be substituted for FiberStrong rim
board in all rim board and rim joist applications shown in this product guide.
Load
(PSF)
Joist
GPI 20
GPI 40
Non-Snow
125%
GPI 65
Live 20
Dead 10
WI 40
WI 60
WI 80
Load
(PSF)
Joist
GPI 20
GPI 40
Non-Snow
125%
GPI 65
Live 20
Dead 15
WI 40
WI 60
WI 80
Load
(PSF)
Joist
GPI 20
GPI 40
Non-Snow
125%
GPI 65
Live 20
Dead 20
WI 40
WI 60
WI 80
10
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
268-039
238-049
278-119
318-089
308-079
348-109
388-089
238-049
278-119
318-089
298-089
338-099
378-069
338-009
378-069
418-079
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
248-109
228-019
268-059
308-009
288-119
338-009
368-089
228-019
268-059
298-089
288-019
328-009
358-069
318-039
358-069
398-059
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
238-089
218-009
258-029
288-089
278-079
318-059
348-119
218-009
258-029
278-089
268-099
308-069
338-119
298-099
338-109
378-079
Joist
GPI 20
GPI 40
Snow
115%
GPI 65
Live 25
Dead 15
WI 40
WI 60
WI 80
Load
(PSF)
Joist
GPI 20
GPI 40
Snow
115%
GPI 65
Live 30
Dead 15
WI 40
WI 60
WI 80
Load
(PSF)
Joist
GPI 20
GPI 40
Snow
115%
GPI 65
Live 40
Dead 15
WI 40
WI 60
WI 80
Load
(PSF)
Joist
GPI 20
GPI 40
Snow
115%
GPI 65
Live 50
Dead 15
WI 40
WI 60
WI 80
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
238-099
218-019
258-039
288-039
278-089
318-069
358-009
218-019
248-039
268-089
268-109
308-079
338-099
298-109
338-119
378-089
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
228-109
208-039
248-039
268-089
268-079
308-039
338-089
208-019
228-119
258-029
258-099
298-059
318-109
288-089
328-079
368-029
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
218-049
188-119
228-009
248-019
248-109
288-039
318-059
188-029
208-099
228-099
248-019
268-099
288-109
268-099
308-069
338-109
Joist
Depth
11789
912 9
11789
149
11789
149
169
912 9
11789
149
11789
149
169
11789
149
169
1699 o.c.
198-119
178-099
208-039
228-029
238-049
268-079
278-069
168-099
198-019
208-119
228-059
248-089
268-049
258-029
288-089
318-089
11
1. Table values are based on clear distance between supports and may be
used for simple or multiple spans. End spans of multiple span joists must be
at least 40% of adjacent span.
2. Uniform loads shown below cover a broad range of applications. It may be
possible to exceed these loads by analyzing a specific application using
GP FASTBeam software. For cases with cantilevers or point loads, use
FASTBeam software or contact BlueLinx.
3. Both live and total loads must be checked live load against the Live row
and total load against the Total row. When no value is shown in the Live
row, total load will govern.
Joist
Depth
117/89 Live
Total
91/29
GPI 40
Joist Span:
Live
Total
117/89 Live
Total
149
Live
Total
11 /89 Live
Total
GPI 65
149
Live
Total
169 Live
Total
9 /29 Live
Total
WI 40
117/89 Live
Total
149
Live
Total
WI 60
117/89 Live
Total
149
Live
Total
169 Live
Total
WI 80
117/89 Live
Total
Live
149
Total
169 Live
Total
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
L/600
L/480
L/240
68
138
94
118
142
67
84
141
111
139
334 288 253 226 204 185 170 157
88
98
148
77
96
132
55
69
122
91
113
146
129
158
64
79
123
45
57
107
75
94
137
107
134
137
95
119
137
136
336 289 254 226 204 186 171 158 147 137
336 289 254 226 204 186
180 137 106
133
278 239 210 187 169 154
172
322 277 243 217 196 178 164 151 141 131
160 129 106 88
133 110
322 277 243 217 196 178 164 151 141 131
126
322 277 243 217 196 178 164 151 141 131
322 277 243 217 196 178 164 151 141 131
139 116
355 306 269 240 216 197 181 167 155 145
389 335 294 262 236 215 198 183 170 159
389 335 294 262 236 215 198 183 170 159
NOTES:
1. Refer to General Notes above.
2. Table does not include additional
stiffness from composite action with
glue-nailed or nailed decking.
3. L/480 live load deflection is recommended (See System Performance
narrative.) For L/360 (minimum code
deflection) multiply L/480 value times
1.33.
4. Total load deflection is limited
to L/240.
12
78
spacing
factor
129
169
19.29
1.00
1.33
1.60
249
2.00
168
53
66
115
38
47
94
63
79
121
90
112
128
80
100
129
115
22
28
56
32
41
71
29
36
73
42
53
90
57
71
90
29
36
65
26
32
60
23
28
56
20
26
51
37
47
86
51
63
86
33
42
83
45
56
83
30
37
74
40
50
80
27
33
67
36
45
77
26
32
54
23
28
50
20
26
46
31
38
74
41
52
79
27
34
68
37
46
76
41
51
96
55
69
96
37
46
92
49
62
92
22
28
53
32 29
41 36
63 58
27
33
67
39 34
48 43
86 80
52 46
65 58
86 83
36
45
90
52 46
65 58
104 100
69 62
87 77
104 100
33
41
74
30
37
71
27
33
67
25
31
61
33
41
73
30
37
69
27
34
64
25
31
60
33
41
83
44
55
89
40
50
86
36
45
83
33
41
80
Joist Spacing
75
75
100
120
40 50 60 70 80 90 100 110 120 130 140 150
WI 80
WI 60
WI 40
GPI 65
GPI 40
GPI 20
Joist
Depth
Joist Span:
Live L /240
117/89 Total 115%
125%
Live L /240
91/29 Total 115%
125%
Live L /240
7
11 /89 Total 115%
125%
Live L /240
149 Total 115%
125%
Live L /240
7
11 /89 Total 115%
125%
Live L /240
149 Total 115%
125%
Live L /240
169 Total 115%
125%
Live L /240
1
9 /29 Total 115%
125%
Live L /240
117/89 Total 115%
125%
Live L /240
149 Total 115%
125%
Live L /240
7
11 /89 Total 115%
125%
Live L /240
149 Total 115%
125%
Live L /240
169 Total 115%
125%
Live L /240
117/89 Total 115%
125%
Live L /240
149
Total 115%
125%
Live L /240
169
Total 115%
125%
68
78
88
98
178
112
234
120
254
131
79
246
96
267
104
133
259 234 213 196 181 168 157 140 124
282 254 232 213 197 183 171 152 135
385 331 291 259 234 213 196 181 168 157 147
418 360 316 282 254 232 213 197 183 171 160
386 333 292 260 235 214 197 182 169 158 148
420 362 318 283 255 233 214 197 184 171 161
386 333 292 260 235 214 197 182 169 158 148
420 362 318 283 255 233 214 197 184 171 161
238
47
63
63
33
44
44
56
68
74
81
139
82
151
89
73
139
97
152
97
105
139 132 125 119 113 108 103
152 143 136 129 123 117 112
386 333 292 260 235 214 197 182 169 158 148
420 362 318 283 255 233 214 197 184 171 161
113 94
320 275 242 216 194 177 163 144 124 109 96
347 299 263 234 211 193 177 157 135 118 104
228
53
71
71
38
51
51
64
74
81
92
89
97
82
108
110
106 96 87
116 104 95
115 99 86
120 110 100
130 120 109
370 319 280 249 225 205 188 174 162 151 142 134 126 120 114 108
402 346 304 271 245 223 205 189 176 164 154 145 137 130 124 118
370 319 280 249 225 205 188 174 162 151 142 134 126 120 114
402 346 304 271 245 223 205 189 176 164 154 145 137 130 124
133
408 352 309 275 248 226 208 192 179 167 157 147 139 132 126
444 382 336 299 270 246 226 209 194 181 170 160 151 144 137
108
118
116
120
130
447 385 338 301 272 248 227 210 195 183 171 161 153 145 137 131
486 418 367 328 296 269 247 228 212 198 186 175 166 157 149 142
447 385 338 301 272 248 227 210 195 183 171 161 153 145 137 131
486 418 367 328 296 269 247 228 212 198 186 175 166 157 149 142
NOTES:
1. Refer to General Notes on the previous page.
2. All roof joists to be sloped 14 9 in 129 minimum.
248
42
55
55
29
39
39
50
63
66
72
75
82
64
86
86
94
99
108
258
37
49
49
26
35
35
44
58
59
64
69
75
57
76
76
83
95
103
268
33
44
44
23
31
31
39
53
53
57
64
70
51
68
68
74
92
99
278
29
39
39
35
47
47
51
59
65
46
61
61
67
88
89
91
88
96
32
42
42
46
55
60
41
55
55
60
80
80
82
85
92
103 99 95 92
112 108 103 100
33 29 26 23
44 39 35 31
44 39 35 31
56 50 44 39 35
60 56 51 47 44
66 60 56 52 47
72 64 57 51
73 67 62 57 53
79 73 67 62 58
67 59 53 47 42
84 77 70 63 56
89 79 70 63 56
97 86 76 68 61
99 92 85 79 73
108 101 93 86 80
92 83
99 95 91 88 85
108 103 99 95 92
90 80 71 64 57
109 105 95 85 76
119 107 95 85 76
115 103 92 83
120 115 110 106 102
130 125 120 115 110
29
38
38
42
52
55
37
50
50
54
73
73
74
82
89
26
35
35
38
48
50
34
45
45
49
66
66
67
79
86
32 29 26
41 38 35
42 38 35
46 42 38
80
49 46 43
86
54 50 47
76
38 34 31
91
50 46 41
99
50 46 41
110
55 50 45
104
68 64 59
113
74 67 60
75 68 61
104
79 74 69
113
86 80 75
102
51 47 42
114
69 62 56
124
69 62 56
74 67 61
125
97 90 81
136
99 90 81
100 91 82
125 120 115 110 106 102 98 95 92
136 130 125 120 115 111 107 103 100
3. Use of this table for horizontal spans should be limited to roof slopes of 29 per foot or less.
For greater slopes, convert horizontal span to up-the-slope span using the chart below.
4. Total load deflection is limited to L/180. For less deflection use the L/240 row.
Slope
Factor
1.021
1.031
1.042
1.054
1.068
1.083
1.118
1.158
1.202
1.250
1.302
1.357
1.414
Joist Depth
9129
11789
1499
1699
Amount to Increase Length for Plumb Cut (Lp in feet)
0.165
0.206
0.243
0.278
0.198
0.247
0.292
0.333
0.231
0.289
0.340
0.389
0.264
0.330
0.389
0.444
0.297
0.371
0.438
0.500
0.330
0.412
0.486
0.556
0.396
0.495
0.583
0.667
0.462
0.577
0.681
0.778
0.528
0.660
0.778
0.889
0.594
0.742
0.875
1.000
0.660
0.825
0.972
1.111
0.726
0.907
1.069
1.222
0.792
0.990
1.167
1.333
EXAMPLE:
7/12 slope and 208-09
horizontal span,
28-0 9 overhang (horizontal)
one end, 2x4 walls
Up-the-slope span: 208 x 1.158 = 23.168, use 248 joist span column to check load capacity.
Overall length:
13
GPI 65
WI 40
WI 60
WI 80
Joist
Depth
11 789
9 129
11 789
149
11 789
149
169
9 129
11 789
149
11 789
149
EI
(106 inch2 lbs)
274
193
330
482
434
640
877
193
330
482
396
584
Allowable
Moment a,b
(ft-lbs)
3870
3090
3990
4790
6325
7605
8755
2735
3545
4270
4900
5895
169
11 789
149
169
799
547
802
1092
6835
6940
8360
9690
Allowable
Shear b
(lbs)
1435
1200
1460
1715
1495
1740
2000
1120
1420
1710
1420
Allowable Reactions
End b,c
Intermediate b,d
(lbs)
(lbs)
1100
2340
1120
2600
1225
2600
1250
2600
1230
2610
1335
2610
1345
2610
1080
2160
1200
2500
1200
2500
1200
2500
1710
1970
1420
1710
1970
1200
1200
1280
1280
1280
C
(10 6 ft-lbs/in)
0.515
0.412
0.515
0.607
0.515
0.607
0.693
0.412
0.515
0.607
0.515
Weight e
(lbs/ft)
2.6
2.9
3.1
3.5
3.1
3.5
3.7
2.6
2.9
3.3
3.2
0.607
0.693
0.515
0.607
0.693
3.4
3.7
3.9
4.2
4.5
2500
2500
2760
3020
3020
NOTES:
a. Allowable moment may not be increased for any code allowed repetitive member use factor.
b. Allowable moment, shear, and reaction values are for normal duration loading and may be increased for other load durations in accordance with code.
c. Allowable end reaction is based on a minimum bearing length of 1 3 4 9 without bearing stiffeners. For a bearing length of 49, the allowable end reaction may be set
equal to the tabulated shear value. Interpolation of the end reaction between 1 3 4 9 and 4 9 bearing is permitted. For end reaction values over 1,550 lbs., bearing
stiffeners are required.
d. Allowable intermediate reaction is based on a minimum bearing length of 3 12 9.
e. Weight of joists for dead load calculations. For shipping weights contact BlueLinx.
22.5 x W x L4
EI
W x L2
W
L
EI
C
=
=
=
=
WI Series
99
99
9 9
9 9 9 9
9 9
9
9
99
9 9
9 9 9
99
99
99
9
9
14
B. Characteristics:
1. Flanges:
High-grade lumber flanges.
a. WI 40: 2129.
b. WI 60: 2 129.
c. WI 80: 3129.
LVL flanges.
a. GPI 20: 1349.
b. GPI 40: 2 5169.
c. GPI 65: 2 7169.
2. Webs:
3
89 thick APA Rated enhanced OSB.
3. Beam depths:
a. GPI 20: 11789 as required for loading,
deflection and span.
b. GPI 40 or WI 40: 9129, 11789 and 149
as required for loading, deflection and span.
c. WI 60: 11789, 149 and 169
as required for loading, deflection and span.
d. GPI 65: 11789, 149 and 169
as required for loading, deflection and span.
e. WI 80: 11789, 149 and 169
as required for loading, deflection and span.
4. Beam length:
As required for span and bearing.
2.2Accessories:
A. Nails:
8d, 10d, and 12d box, sinker, and common nails.
B. Bracing and blocking:
1. Bearing stiffeners: 2x4 or combination of 389, 129 or
5
89 Plywood Sturd-I-Floor or OSB.
2. Band joists and continuous closure at load-bearing walls:
per standard approved Wood I Beam details.
3. Lateral support at intermediate supports of multiple span
joists: Wood I Beam blocking.
C. Joist hangers:
1. Model numbers are shown for United Steel Products and
Simpson Strong-Tie connectors. Contact BlueLinx for
other acceptable connectors.
Part 3Execution
3.0General:
A. Provide Wood I Beam floor and roof joists where indicated on
drawings using hangers and accessories specified.
B. Install Wood I Beam joists in accordance with manufacturers
recommendations.
C. Install and brace Wood I Beam floor and roof joists to
prevent dominoing of system and buckling of top flange.
3.2Accessories:
Install accessories where indicated and in accordance with
manufacturers instructions.
NOTE:
GP engineered lumber products may support mold growth if exposed to certain conditions, including moisture, dampness, condensation,
humidity, water or wet conditions. Mold, mildew, fungi, algae, moss, bacterial growth, decay, rot or similar conditions are not manufacturing
or product defects and Georgia-Pacific and BlueLinx assume no responsibility or liability for such conditions, regardless of cause.
The user is responsible for proper installation of GP engineered lumber products. The products must be installed in strict conformity with
Georgia-Pacifics instructions and all applicable building code requirements and other regulations. In addition, if not specifically covered by
Georgia-Pacific's installation instructions or construction detail illustrations, the products must be installed in accordance with generally
accepted design and construction practices. When installing engineered lumber products, the user should also consider the effects of local
climate and geography. Georgia-Pacific and BlueLinx do not warrant and are not responsible for any finished structure or system that GP
engineered lumber products may be incorporated into or other building components that may be used with these products.
Georgia-Pacific Corporation, June 2006
15
TMP
TMPH
Cpcy 1, 2
Lbs100%
Nailing 7
Joist
Joist
Depth
Top
Mount
GPI 20
11789
TH017118
9129
THO23950
GPI 40
11789
THO23118
1499
THO23140
9129
THO25950
11789
1499
WI 40, 60 &
GPI 65
WI 80
Face
Mount
Cpcy 1, 3
Lbs100%
Double
Face
Mount
Nailing 7
H
Cpcy1,3,4
Lbs100%
Nailing 7
H
Field Cpcy 1, 3, 5
Sloped
Lbs& Skewed 115%
Cpcy 1, 6
Variable LbsPitch 115%
Nailing 7
H
Nailing 7
P
1795
LSSH179
1290
1150
1345
1575
LSSH23
1290
TMP23
1970
1570
1800
10d
10d x 1129
LSSH23
1290
TMP23
1970
2025
2370
10d
10d x 1129
LSSH23
1290
TMP23
1970
1345
1350
10d
10d
LSSH25
1825
1970
THO25118
1570
1350
10d
10d
LSSH25
1825
1970
THO25140
2015
1800
10d
10d
LSSH25
1825
1970
1699
THO25160
2465
1800
10d
10d
LSSH25
1825
1970
11789
THO35118
1550
10d 10d x 1 29
HD7120
2175
16d
10d
LSSH35
1920
16d 10d x 1 29
TMP4
1970
1499
THO35140
1940
HD7140
2720
16d
10d
LSSH35
1920
TMP4
1970
1699
THO35160
2135
HD7140
2720
16d
10d
LSSH35
1920
TMP4
1970
Double
Face
Mount
Cpcy1,3,4
Lbs100%
1795
Simpson
Strong-Tie
Connectors
Joist
GPI 20
WI 40, 60 &
GPI 65
WI 80
Nailing 7
Top
Mount
11789
ITT11.88
ITT359.5
9129
GPI 40
Cpcy 1, 2
Lbs100%
Joist
Depth
11789
Face
Mount
Cpcy 1, 3
Lbs100%
960
Nailing 7
H
Nailing 7
H
Field
Cpcy 1, 3, 5
Nailing 7
Sloped
Lbs& Skewed 115% H
J
LSSUI25
1275
Variable
Pitch
Cpcy 1
Lbs115%
870
10d
10d x 1129
Nailing 7
890
MIU4.75/9 1930
LSSUI35
1275
1020
10d
10d x 1129
1110
LSSUI35
1275
1020
10d
10d x 1129
LSSUI35
10d x 1129
1499
ITT3514
1555
1275
1020
10d
9129
ITT39.5
890
MIU5.12/9 1930
1345
VPA3
1020
10d
10d x 1129
1110
1345
VPA3
1020
10d
10d x 1129
10d x 1129
1499
ITT314
1400
1345
VPA3
1020
10d
1699
MIT316
1400
1345
VPA3
1020
10d
10d x 1129
960
HU412-2
16d
1610
VPA4
1025
10d
10d x 1129
1855
16d
LSSU410
1499
ITT414
1345
HU414-2
2320
16d
16d
LSSU410
1610
VPA4
1025
10d
10d x 1129
1699
MIT416
1535
HU414-2
2320
16d
16d
LSSU410
1610
VPA4
1025
10d
10d x 1129
NOTES:
1. Capacity is for the stated duration of load 100% floor loading 115% roof snow loading. Connector capacity depends on the model selected, quantity and size of nails used, and the size
and type of fastener support. Douglas Fir-Larch or Southern Pine web filler material has been assumed for all I-joist series and depths except for all WI 80 depths where S-P-F has been
used. Higher capacities may be available based on different header materials; please refer to appropriate reference/design guide from the connector manufacturer for expanded design
information. Some connector/header/fastener combinations may not meet maximum joist reaction capacities and a qualified engineer should be consulted. VPA and TMP connectors are
based on S-P-F wood plates. Clinch nails across grain when possible.
2. Top mount hanger capacities shown are based on the same series and depth of Wood I Beam joists carried. To achieve design capacity shown, use 10d nails for single 1 34 9 thick GP
Lam LVL beams and 16d nails for double 1 34 9 thick (3 12 9) GP LVL, Douglas Fir-Larch or Southern Pine glulam beams. Refer to detail F12.
3. Hangers capacities are based on the lesser value of single 1 34 9 thick GP Lam LVL, Douglas Fir-Larch or Southern Pine Glulam beams or the same series and depth of Wood I Beam
joists carried. Refer to detail F13 and R1.
4. Bearing stiffeners required for Wood I Beam applications. Refer to detail F13.
5. Beveled bearing stiffeners are required. Refer to detail R8. Maximum slope is 12/12. A tie strap is required for all Wood I Beam applications with 169 joist depths or slopes of 7/12 and
greater. Refer to detail R1.
6. TMP connectors may be used for slopes of 1/12 through 6/12. For greater slopes use TMPH series connectors with bearing stiffeners.
7. Nailing key. H column indicates size of nails to connect hanger to supporting header. J column indicates nails to attach the hanger to the joist. P indicates nails to connect to plate.
Fill all nail holes as required by hanger manufacturer. 10d x 11 2 9 is 9 gauge x 11 2 9, 10d is 9 gauge x 39, 16d is 8 gauge x 3 12 9.
NOTE: Model numbers shown are for United Steel Products Company, Inc. 1-800-328-5934 (East) & 1-800-227-0470 (West) and Simpson Strong-Tie Company, Inc. 1-800-999-5099.
Some locations carry similar products produced by other manufacturers. Contact your local building material retailer for conversion information and details. Other designs are available
for specialized applications.
16
PSF
Material
PSF
Miscellaneous
Mechanical ducts . . . . . . . . . . . . . . . .2.0-4.0
Skylight, metal frame 38 9 glass . . . . . . . . . 8.0
Stucco . . . . . . . . . . . . . . . . . . . . . . . . . . . .10.0
Floor Fill
112 9 lightweight concrete . . . . . . . . . . . .14.0
112 9 regular concrete . . . . . . . . . . . . . . . .18.0
3
49 GYP-CRETE . . . . . . . . . . . . . . . . . . . . . .6.5
Floor Finish
Hardwood (nominal 19) . . . . . . . . . . . . . . .4.0
Carpet and pad . . . . . . . . . . . . . . . . . . . . .2.0
Linoleum or soft tile . . . . . . . . . . . . . . . . . .1.5
3
49 ceramic or quarry
tile (without mortar) . . . . . . . . . . . . . .10.0
1
2 9 mortar bed . . . . . . . . . . . . . . . . . . . . .+ 6.0
19 mortar bed . . . . . . . . . . . . . . . . . . . .+ 12.0
Storage, Handling,
Safety and Installation . . . . . .18-19
Typical Framing . . . . . . . . . . . . . . .20
Fire Rated Assemblies . . . . . . . . .21
Plumbing Details . . . . . . . . . . . . .21
Floor Details . . . . . . . . . . . . . . .22-25
Cantilever Details . . . . . . . . . .26-27
Roof Details . . . . . . . . . . . . . . .28-29
Hole Location Charts . . . . . . . .30-31
17
DO NOT store
Wood I Beam joists flat.
Stack and handle Wood I Beam joists in the upright position. Stack
and handle FiberStrong rim board flatwise.
Twisting of joists, or applying loads to the joist when flat can
damage the joist.
Damaged products should not be used.
DO NOT lift
Wood I Beam joists
by top flange.
DO NOT lift
Wood I Beam joists
in the flat orientation.
Safety Warning
Handlers and installers should use appropriate personal protective
equipment such as gloves and goggles.
Wood I Beam joists will not support workers or other loads
until properly installed and braced. To minimize risk of injury,
each Wood I Beam joist shall be properly fastened as it is erected.
Continuous closure and/or blocking panels must be installed and
attached prior to installing floor or roof sheathing. Lateral restraint,
such as an existing deck or braced end wall, must be established at
the ends of the bay. Alternatively, a temporary or permanent deck
(sheathing) may be nailed to the first 4 feet of joists at the end of the bay.
Rows of temporary bracing at right angles to joists must be fastened
18
with a minimum of two 8d nails (10d box nails if net thickness of bracing
exceeds 19) to the upper surface of each parallel joist and the established
lateral restraint. Bracing should be 1x4 minimum and at least 8* long
with on-center spacing not to exceed 108. Ends of adjoining bracing
should lap over at least two joists. Stack building materials over main
beams or walls only.
The following can result in serious accidents: improper storage or
installation, failure to follow applicable building codes, failure to follow
proper load tables, failure to use acceptable hole sizes and locations,
or failure to use bearing stiffeners when required. Installation notes
must be followed carefully.
Installation Notes
A. Engineered lumber must not be installed in direct contact with
concrete or masonry construction and shall be used in covered,
dry use conditions only, where the in-service moisture content
does not exceed 16%.
B. Except for cutting to length and birdsmouth cuts, top and bottom
flanges of Wood I Beam joists shall not be cut, drilled or notched.
C. Concentrated loads shall only be applied to the upper surface of
the top flange, not suspended from the bottom flange. Contact
BlueLinx for exceptions.
D. When nailing sheathing to top flange, follow sheathing manufacturers nailing recommendations, but maintain spacing in the
ranges shown below:
Sheathing Nail Spacing Requirements
GPI 20
GPI 40,
WI 40, WI 60,
Nail Size
GPI 65
WI 80
Min. Max. Min. Max. Min. Max.
8d Box, 8d Common
39
169
29
249
49
249
10d Box, 12d Box
39
169
29
249
49
249
169
39
249
49
249
10d Common, 12d Common 4129
NOTES:
1. If more than one row of nails is required, rows must be offset by at
least 1 2 9 ( 34 9 for WI joists) and staggered.
2. 14 gauge staples may be substituted for 8d nails if staples penetrate
the joist flange at least 19.
3. Do not use nails larger than those shown above when attaching
sheathing to flanges of Wood I Beam joists.
Example: When using 8d common nails and GPI 20 series joists, space
no closer (min.) than 39 o.c. and no farther (max.) than 169 o.c.
Installation Donts
Support beam
Wood I Beam
19
Typical Framing
20
yyy
yyy @@@
@@@
Fire Rated Assemblies for Wood I Beam Joists
For alternate assemblies, including a two-hour rated system, contact BlueLinx.
Plumbing Details
P1
P2
Joist Spacing
Joist
2x4 Wall
2x6 Wall
GPI 20
5 149
7 149
69
89
WI 80
79
99
Non-load
bearing only
Tub above
21
F1
Floor Details
ATTACHMENT AT END BEARING
F2
8d nails at 69 o.c. (or per design professionals specs., but complying with
Installation Note D, page 19).
F3
F4
Wood I Beam
rim joist
Squash Blocks
(2x4 minimum)
8d nails
1/169
%
%
Check local building code for appropriate detail in areas of high lateral load.
F5
F6
Starter
joist
8d nails
top and bottom
flange
GP FiberStrong
rim board
GP FiberStrong
rim board
3 - 8d nails
at corners
22
Siding
Weather Barrier
Sheathing
GP FiberStrong
rim board
2-4 galvanized
or stainless steel
washers for spacers.
Extend flashing
below 2 x _
ledger and over
siding.
Floor Details
F7
F8
Check local building code for appropriate detail in areas of high lateral load.
F9
Check local building code for appropriate detail in areas of high lateral load.
F10
Vertical load transfer = 2000 plf max. along load bearing wall.
1/169
Attach joist with one
10d box or sinker nail on
each side of bearing.
*Non-stacking
load bearing
walls require
additional
consideration.
Squash block
(2x4 minimum)
Required only if load
bearing wall exists above.
8d nails
F11
Joist
Joist
Depth
GPI 20
11 789
9 129
11 789
149
9 129
11 789
149
169
11 789
149
169
2x6
2x6 + 389 OSB/Plywood
2x6 + 389 OSB/Plywood
2x8 + 389 OSB/Plywood
2x6 + 589 OSB/Plywood
2x6 + 589 OSB/Plywood
2x8 + 589 OSB/Plywood
2x8 + 589 OSB/Plywood
(2) 2x8
(2) 2x8
(2) 2x8
GPI 40
GPI 65
WI 40
WI 60
WI 80
Filler blocking
1/89 gap
Floor Details
F12
Backer Blocks*
Joist
GPI 20
Joist Depth
11 78 9
GPI 40
9 129, 11 78 9
149
GPI 65,
WI 40, WI 60
9 2 9, 11 8 9
149, 169
WI 80
11 78 9, 149, 169
Material
23
329
Depth
5 129
8 9
8 9
69
7 14 9
7
7
2 9 + 2 9
2 9 + 12 9
69
7 14 9
2 x8
7 14 9
1
1
Assemble double
joist per detail F11.
(regular filler)
Backer
blocks
required
both sides
of web.
F13
Backer Block
Before installing a backer to a double joist,
drive an additional (3) 10d nails into the web
where the backer will fit. Clinch when possible.
Install backer tight to top flange. Use (10) 10d
nails, clinched when possible.
Backer Blocks*
Joist
GPI 20
Joist Depth
11 78 9
GPI 40
9 12 9, 11 78 9, 149
GPI 65,
WI 40, WI 60
9 12 9, 11 78 9, 149, 169
WI 80
11 8 9, 149, 169
7
Material
23
329
Depth
8349
8 9
6 14 9, 8 34 9, 10 349
2 9 + 12 9
6 14 9, 8 34 9, 10 34 9,12 34 9
1 2 9 net
1
Backer blocks
both sides of web.
8 34 9, 10 34 9, 12 34 9
F14
Hangers for
148 (max) Stringer
United Steel Products MSH 218
OR
Simpson Strong-Tie THA 218
Nailing Requirement
Minimum (12) 10d nails into double joists or
single or double LVL header. Minimum
(4) 10d x 112 9 nails into stringer.
For stringers longer than 148 or stringer reaction greater than 700 lbs., call BlueLinx.
24
F15
Floor Details
F16
GP Lam LVL or
Glulam Beam
A
Bearing stiffeners
may be required
at hangers. (See
detail F18)
Top mount
hangers*
Top mount
hangers*
Steel Beam
F17
GP Lam LVL or
Glulam Beam
*Appropriate face
mount hangers may
be substituted.
Ledger for
floor
sheathing
attachment
F18
BEARING STIFFENERS
Gap (1/49 )
23/329 48/24
APA rated
sheathing or
GP approved
rim.
29
8d nails
GP Lam LVL
or Glulam
Beam
Joist
Stiffener Size
Nails
GPI 20
GPI 40
GPI 65
WI 40
WI 60
WI 80
8922 169
29 + 129225169
1
29 + 129225169
1
29 + 129225169
1
29 + 129225169
1129225169
(3) 10d
(3) 10d
(3) 10d
(3) 10d
(3) 10d
(3) 12d
Plytanium Plywood,
OSB, or 2x4 stiffeners
each side at:
- Hangers with side
nailing
- Hangers with sides
not containing top
flange of joists.
- Birdsmouth cuts
F19
Tight fit
Hanger
1/169 gap
See detail F7
for blocking
requirements.
F20
WEB STIFFENERS
Concentrated
load from above
1/49 gap
Joist Depth
all series
9 12 9
1178 9
149
169
25
9 12 9
1178 9
149
169
Roof
Truss
Span
TL = 35 psf
LL not to exceed 20 psf
Joist spacing
129
169
19.29
249
26*
28*
30*
32*
34*
36*
26*
28*
30*
32*
34*
36*
38*
26*
28*
30*
32*
34*
36*
38*
40*
26*
28*
30*
32*
34*
36*
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
2
2
2
2
0
1
1
1
1
1
1
0
0
0
1
1
1
1
1
1
1
1
1
1
1
38*
40*
42*
0
0
0
0
0
0
0
0
1
1
1
1
TL = 45 psf
LL not to exceed 30 psf
Joist spacing
129
169
19.29
249
TL = 55 psf
LL not to exceed 40 psf
Joist spacing
129
169
19.29
249
TL = 65 psf
LL not to exceed 50 psf
Joist spacing
129
169
19.29
249
0
0
0
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
2
2
0
0
0
0
1
1
1
0
0
0
0
0
0
0
1
0
0
0
0
0
1
2
2
2
2
X
0
1
1
1
1
1
1
0
0
0
1
1
1
1
1
0
0
0
1
1
2
X
X
X
X
X
1
1
1
2
2
2
2
1
1
1
1
1
1
1
2
1
1
1
1
2
1
1
1
2
2
2
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
2
2
2
X
X
X
1
1
1
1
1
2
2
0
0
0
1
1
1
1
1
0
0
0
1
1
X
X
X
X
X
X
1
1
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
X
X
X
X
X
X
2
2
2
X
X
X
X
1
1
1
2
2
2
2
2
1
2
2
2
2
2
2
2
2
X
X
1
1
1
1
1
1
2
0
0
0
0
0
1
1
1
0
0
0
0
0
X
X
X
X
X
X
1
2
2
2
2
2
X
1
1
1
1
1
1
1
1
1
1
1
1
1
X
X
X
X
X
X
2
2
2
X
X
X
X
1
1
1
1
2
2
2
2
1
1
1
1
1
X
X
X
X
X
X
X
X
X
X
X
X
X
2
2
2
2
2
X
X
X
1
2
2
2
2
0
0
0
0
0
0
1
1
1
1
1
1
2
2
2
2
0
0
0
0
1
1
1
1
1
1
1
1
2
2
2
X
0
1
1
1
1
1
1
1
2
2
2
2
X
X
X
X
ROOF SPAN
See detail F9
C1
CANTILEVER, UNREINFORCED
Cantilever Details
C2
CANTILEVER, REINFORCED
Single Sheathing (Option I)
28-09
*Cantilever length may not
exceed 1/4 the adjacent span (L).
In addition:
23/329 APA
rated sheathing
or FiberStrong
rim board.
C3
23/329 APA
rated sheathing
or FiberStrong
rim board.
28-09 max*
Note: FiberStrong rim board or 48/24 APA rated sheathing (face grain horizontal) required one side of
joist. Depth must match the full depth of the joist. Nail to joist flange with 8d nails at 69 o.c.
CANTILEVER, REINFORCED
Double Sheathing (Option II)
69
69
28-09
69
29
23/329 APA
rated sheathing
or FiberStrong
rim board.
69
28-09 max*
69
59
C4
Note: FiberStrong rim board or 48/24 APA rated sheathing (face grain horizontal) required both sides of joist. Depth must match the full
depth of the joist. Nail to joist flanges with 8d nails at 69 o.c. Offset nailing on opposite sides of flange to avoid splitting.
CANTILEVER, REINFORCED
Double Joist (Option III)
C5
CANTILEVER, DROPPED
48-09
23/329 APA rated
sheathing or
FiberStrong
rim board.
129
28-09 max*
Note: Block together full length with full-depth filler blocking. See detail F11 for filler size. Use 2 rows of
10d nails at 129 o.c. from each side; offset opposite side nailing by 69. For flange widths greater
than 2 129, use 3 rows of 10d nails at 129 o.c. from each side; offset opposite side nailing by 69 o.c.
Clinch nails when possible.
27
R1
Roof Details
RIDGE-JOIST CONNECTION
R2
Beveled bearing
stiffener each side
(see detail R8)
Ridge beam
(GP Lam LVL
or Glulam)
*Strap required for 169 joist depth or members
with slope of 7/12 or greater.
R3
R4
BIRDSMOUTH CUT
Low end of joist only.
23/329 x 28-09 Plytanium Plywood or OSB gusset (face grain horizontal) each side with (12) 8d
nails clinched or strap with (16) 10d x11/29 nails applied to top flange per detail R1.
Wood I Beam blocking panel
(see detail F2)
Bearing stiffener
each side
(See detail R8)
Double beveled
wood plate.
GP Lam LVL or
glulam support
beam.
Wood I Beam
blocking panel
or x-bridging
(see detail F2)
R5
Optional overhang
20 (max)
R6
BIRDSMOUTH CUT
Low end of joist only
Bearing stiffener
each side
(see detail R8)
L
x.
ma
09
28-
2x4 block
to attach fascia
Cantilever length may not exceed
1/4 of the adjacent span (L).
Follow detail F1 for nailing to
bearing plate. Additional uplift
connections may be required.
28
x.*
ma
L/4
Continuous
beveled plate
or variable pitch
connector.
28-09 max.
R7
Roof Details
R8
Beveled
backer
block (see
detail F13)
GP Lam LVL or
double joist
(see detail F11)
Adjustable
slope
hanger
R10
R11
Follow detail F1
for nailing
to bearing plate.
Additional uplift
connections may
be required.
L
When L exceeds joist spacing,
double joist may be required.
L (28-09 max.)
Bearing stiffener
each side.
(see detail R8)
in.
9m
-0
48
2x4 cripple
9
24
2809 m
ax.
.
ax
.m
o.c
Slope
Factor
1.021
1.031
1.042
1.054
1.068
1.083
1.118
1.158
1.202
1.250
1.302
1.357
1.414
Joist Depth
9 12 9
11 78 9
14 9
16 9
Amount to Increase Length for Plumb Cut (Lp in feet)
0.165
0.206
0.243
0.278
0.198
0.247
0.292
0.333
0.231
0.289
0.340
0.389
0.264
0.330
0.389
0.444
0.297
0.371
0.438
0.500
0.330
0.412
0.486
0.556
0.396
0.495
0.583
0.667
0.462
0.577
0.681
0.778
0.528
0.660
0.778
0.889
0.594
0.742
0.875
1.000
0.660
0.825
0.972
1.111
0.726
0.907
1.069
1.222
0.792
0.990
1.167
1.333
EXAMPLE:
7/12 slope and 228-09 horizontal length (Lh)
228 x 1.158 = 25.4768 up-the-slope
If a 149 joist will be used, add 0.681 feet.
fk
Chart dimension is minimum distance from inside face of support to nearest edge of hole.
Joist
Depth
9129
11789
149
169
Joist
Clear Span
108
128
148
168
188
128
148
168
188
208
228
248
108
128
148
168
188
208
228
248
268
288
148
168
188
208
228
248
268
288
308
29
08-69
08-69
18-09
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
39
08-69
08-99
28-09
08-69
08-69
08-69
08-69
18-09
08-69
18-39
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
49
08-99
18-99
38-09
18-39
08-99
08-99
08-99
28-09
18-39
28-69
18-39
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
59
18-69
28-99
48-39
38-09
18-99
18-09
18-99
38-09
28-69
48-09
38-09
18-09
18-09
18-09
18-09
18-09
18-09
18-39
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
69
28-69
48-09
58-69
48-99
48-09
18-69
28-99
48-09
48-09
58-39
48-69
28-69
18-09
18-09
18-09
18-99
18-39
28-69
18-39
28-69
18-39
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
NOTES:
1. Hole locations are based on worst case of simple and multiple span conditions with
uniform floor loads of 40 PSF live load and 10 or 20 PSF dead load, and spans from
page 6.
2. Small holes not greater than 1.59 in diameter can be placed anywhere in the web, but
each hole must be spaced a minimum horizontal clear distance of 2 times its diameter
(but not less than 19) from any adjacent hole. No more than two small holes can be
placed next to each other and/or adjacent to larger holes following the guidelines in
this note. More than one group of small holes is permitted on a joist, but adjacent
groups must be spaced a minimum horizontal clear distance of the greater of 129
or twice the diameter of the largest hole in the adjacent groups.
3. For holes greater than 1.59 diameter, minimum clear distance between
a) two round holes is 2 times the diameter of the larger hole
b) a round hole and a rectangular hole is the larger of 2 times the hole
diameter or twice the rectangular hole width
4. For rectangular holes, the longest side may not exceed 75% of a round hole diameter
permitted at that location; i.e., if an 8 inch round hole is permitted, the longest side of a
rectangular hole centered at that location is 89 x 0.75 = 69.
30
8 789
48-99
68-39
78-69
88-69
108-09
108-09
98-39
18-09
28-09
38-69
58-09
58-39
68-69
68-09
78-69
78-09
78-09
18-09
28-69
28-39
38-69
28-69
38-99
28-99
48-09
38-99
99
109
119
129
139
ted
t
i
erm
P
t
No
18-09
28-39
38-99
58-09
58-39
68-99
68-39
78-99
78-39
78-39
18-39
28-69
28-39
38-99
28-99
48-09
38-09
48-39
48-09
Example below
28-09
38-09
38-39
48-69
48-99
68-09
68-39
78-69
68-99
88-69
88-39
88-09
108-39
98-99
98-69
128-09
98-99
128-39
28-39
38-69
38-99
48-99
38-99
58-09
58-09
68-69
48-39
68-09
58-99
78-69
58-09
78-09
68-39
88-69
68-39
88-69
48-69
68-09
68-69
88-39
88-09
98-69
98-39
108-99
118-09
68-09
78-39
88-39
118-99
138-99
5. A group of round holes at approximately the same location shall be permitted if they
meet the requirements for a single round hole circumscribed around them.
6. For joists with more than one span, use the longest span to determine hole location
in either span.
7. All holes shown on this chart may be located vertically anywhere within the web;
a clear distance of at least 189 must be maintained from the hole edge to the inner
surface of the closest flange.
8. For other conditions use FASTBeam. Analysis using FASTBeam software could
permit larger holes, or holes closer to the supports than shown in this chart.
EXAMPLE:
Determine the allowable location of a 99 round hole in a 149 deep GPI Series
joist which spans 208.
Enter the chart in the left column and find 149 joist depth, move to the right and
find 208 in the joist span column and move across the chart to intersect the 99
round hole column. The nearest allowable location to either bearing is 68-99.
fk
Chart dimension is minimum distance from inside face of support to nearest edge of hole.
Joist
Depth
9 1/29
11 7/89
149
169
Joist
Clear Span
108
128
148
168
188
128
148
168
188
208
228
248
128
148
168
188
208
228
248
268
288
148
168
188
208
228
248
268
288
308
328
29
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
18-69
08-99
18-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
39
08-69
18-39
18-09
08-69
08-69
08-69
08-69
18-39
28-69
28-09
28-99
18-99
08-69
08-69
08-69
08-69
08-69
08-69
18-09
08-69
08-99
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
08-69
49
08-99
28-39
28-39
28-09
08-99
08-99
08-99
28-39
38-69
38-39
48-09
38-39
08-99
08-99
08-99
18-09
08-99
18-69
28-39
18-09
28-39
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
08-99
59
18-99
38-39
38-69
38-69
28-69
18-09
18-99
38-39
48-69
48-69
58-69
48-99
18-09
18-09
18-09
28-09
18-69
28-99
38-69
28-69
38-99
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-09
18-99
18-09
NOTES:
1. Hole locations are based on worst case of simple and multiple span conditions with
uniform floor loads of 40 PSF live load and 10 or 20 PSF dead load, and spans from
page 6.
2. Small holes not greater than 1.59 in diameter can be placed anywhere in the web, but
each hole must be spaced a minimum horizontal clear distance of 2 times its diameter
(but not less than 19) from any adjacent hole. No more than two small holes can be
placed next to each other and/or adjacent to larger holes following the guidelines in
this note. More than one group of small holes is permitted on a joist, but adjacent
groups must be spaced a minimum horizontal clear distance of the greater of 129
or twice the diameter of the largest hole in the adjacent groups.
3. For holes greater than 1.59 diameter, minimum clear distance between
a) two round holes is 2 times the diameter of the larger hole
b) a round hole and a rectangular hole is the larger of 2 times the hole
diameter or twice the rectangular hole width
4. For rectangular holes, the longest side may not exceed 75% of a round hole diameter
permitted at that location; i.e., if an 8 inch round hole is permitted, the longest side of a
rectangular hole centered at that location is 89 x 0.75 = 69.
8 589
48-69
68-09
78-69
98-09
98-99
108-99
118-39
18-99
38-39
48-69
68-09
68-39
78-99
88-99
88-69
108-09
18-09
28-39
38-69
38-39
48-99
58-69
58-09
68-39
78-69
48-99
99
109
10349
119
129
12 349
ted
t
i
erm
P
t
No
Example below
28-39
38-99
58-09
68-69
68-99
88-39
98-39
98-39
108-69
18-39
28-99
48-09
38-99
58-39
68-39
58-69
78-09
88-39
58-69
38-69
48-99
68-39
78-99
88-69
108-09
108-99
118-39
128-69
28-69
38-99
58-39
58-39
68-99
78-69
78-39
88-99
108-09
78-99
48-39
58-99
78-39
38-39
48-99
68-09
68-39
78-99
88-99
88-99
108-39
118-69
98-69
38-69
58-09
68-39
68-99
88-39
98-09
98-39
108-99
118-99
108-39
48-99
68-39
78-69
88-39
98-99
108-99
118-39
128-99
138-99
128-99
58-69
78-09
148-69
5. A group of round holes at approximately the same location shall be permitted if they
meet the requirements for a single round hole circumscribed around them.
6. For joists with more than one span, use the longest span to determine hole location
in either span.
7. All holes shown on this chart may be located vertically anywhere within the web;
a clear distance of at least 1 8 9 must be maintained from the hole edge to the inner
surface of the closest flange.
8. For other conditions use FASTBeam. Analysis using FASTBeam software could
permit larger holes, or holes closer to the supports than shown in this chart.
EXAMPLE:
Determine the allowable location of a 9 9 round hole in a 14 9 deep WI Series joist which
has multiple spans of 168 and 208.
Enter the chart in the left column and find 149 joist depth, move to the right and find 208 in
the joist span column and move across the chart to intersect the 9 9 round hole column.
The nearest allowable location to either bearing is 68-99.
31
GP Lam LVL
Depths:
7 149
9 149 9 129
11149 11789
149
169 189
23 789
209
229 (special order)
Thickness:
1349
Lengths:
Available in lengths up to 60 feet.
32
Bearing Details . . . . . . . . . . . . . . . 34
Handling and Installation . . . . . . . 35
Floor Beams. . . . . . . . . . . . . . . . . . 35
Window and Patio Door
Headers 2-Story . . . . . . . . . . . . . 36
Garage Door Headers
2-Story . . . . . . . . . . . . . . . . . . . . . . 36
Window and Patio Door
Headers Roof Only . . . . . . . . . . . 37
Garage Door Headers
Roof Only. . . . . . . . . . . . . . . . . . . . 37
Roof Hip and
Valley Beam Charts . . . . . . . . . 38-39
Bearing Length
Requirements . . . . . . . . . . . . . . . . 40
Notes for Allowable Uniform
Load Charts . . . . . . . . . . . . . . . . . . 41
Allowable Uniform Loads
Floor 100% . . . . . . . . . . . . . . . 42-43
Roof 115% (Snow). . . . . . . . . 44-45
Roof 125% (Non-Snow). . . . . 46-47
Fastening Recommendations
for Top-Loaded, Multiple Piece
Members . . . . . . . . . . . . . . . . . . . . 48
Fastening Recommendations
for Side-Loaded, Multiple Piece
Members . . . . . . . . . . . . . . . . . . . . 49
Tapered Cut Allowable
End Reaction Truss Roof . . . . . . 50
Tapered Cut Allowable
End Reaction
Conventional (Stick) Roof . . . . . . . 51
Framing Connectors . . . . . . . .52-53
Beam and Header
Design Properties . . . . . . . . . . . . . 54
Allowable Holes in
GP Lam LVL . . . . . . . . . . . . . . . . . .54
Architectural Specifications . . . . . 55
33
Bearing on
Wood Column
Bearing on
Steel Column
Verify the required bearing area and the ability of the supporting column member
to provide adequate strength. Side plates may be required. Consult designer of
record. See chart on page 53 for column cap suggestions.
Beam Pocket in
Masonry Wall
Bearing on
Exterior Wall
For fastening recommendations for multiple-piece GP Lam LVL members, see pages 48 & 49.
34
GP Lam LVL shall not be stored in direct contact with the ground
and should be protected from weather. Provide air circulation under
covering and around stacks of materials.
Bundles should be stored level and should not be opened until time
of installation.
Stack and handle GP Lam LVL flatwise.
Handlers and installers should use appropriate personal protective
equipment such as gloves and goggles.
Engineered lumber must not be installed in direct contact with
concrete or masonry construction and shall be used in covered,
dry use conditions only, where in-service moisture content does
not exceed 16%.
Minimum bearing length for GP Lam LVL beams and headers: end
bearing 112 9, intermediate bearing 3 9.
Ends of GP Lam LVL beams and headers must be restrained against
rotation and the top (or compression edge) must be laterally supported
by perpendicular framing or bracing at 249 on-center or closer.
1 34 9 x 16 9 and deeper GP Lam LVL beams must only be used in multiplepiece members.
Nails installed in the narrow face of GP Lam LVL shall not be spaced
closer than 49 (10d common nails) or 39 (8d common nails).
Multiple piece GP Lam LVL may not be stagger-spliced as is commonly
done with dimension lumber. If the required length of a multiple-span
beam exceeds the available length of the LVL, the LVL beams must
be installed so as to butt together over a common bearing.
Column
Spacing
A
Column
Spacing
248
Total
Floor
Joist
Span
"A"
288
328
368
408
1188
2-111/49
3-91/49
2-111/49
3-91/49
2-111/49
2-117/89+
3-111/49
2-117/89+
3-11 1/49
1288
2-111/49
3-91/29
2-117/89
3-111/49
2-149+
3-111/49
2-149+
3-111/49
2-149+
3-111/49
1388
2-117/89
3-111/49
2-149+
3-111/49
2-149+
3-117/89
2-149+
3-117/89
2-149+
1488
2-149
3-111/49
2-149+
3-117/89
2-149+
2-169+
3-149
2-169+
3-149
1588
2-149
3-11789
2-169+
3-149
2-169+
3-149
2-169+
3-149
2-169+
3-149
NOTES:
1. Table is based on continuous floor joist span and simple or continuous beam span conditions.
If floor joists are not continuous above the beam, take the sum of the joist spans then multiply
by 0.8. This is the total floor joist span to consider.
2. Required end bearing length (based on 565 psi) is 3.09 unless the subscript + is shown. In that
case, 4.59 is required.
3. At intermediate supports of continuous spans, use the following guidelines or refer to page 40.
- 7 1/2 9 bearing length for beams requiring 3 9 bearing at the beam ends
- 10 1/2 9 bearing length for beams requiring 4 1/2 9 bearing at the beam ends
Georgia-Pacific Corporation, June 2006
1688
2-169+
3-149
2-169+
3-149
2-169+
3-149
2-189+
3-149
1788
2-169+
3-149
2-169+
3-149
2-189+
3-169
1888
2-189+
3-169
2-189+
3-169
2-189+
3-169
1988
2-189+
3-169
2-189+
3-169
2088
2-189+
3-169
3-169+
3-189+
3-169+
3-169+
3-189+
3-189+
3-169+
3-169+
3-169+
3-189+
3-189+
3-169
4. Beams require full width bearing. Minimum cripple size for 5 1/4 9 thick beams is 2x6.
5. Table is based on residential floor loading of 40 psf live load and 12 psf dead load.
6. Live load reductions have been applied per IBC section 1607.9.1.
7. Deflection is limited to L/360 at live load and L/240 at total load.
8. For other loading conditions refer to page 42.
35
B
Rough
Opening
Snow (115%)
Roof Loading
Rough Opening
688
208
Roof
Truss
Span
with
288
Soffit
Assumed
25 psf LL + 20 psf DL
888
988
1088
248
288
328
368
1-91/49 1-111/49+
2-71/49 2-91/49
3-71/49
1-91/49 1-117/89+
2-71/49 2-9149
1288
688
Non-Snow (125%)
40 psf LL + 20 psf DL
888
988
1088
1-91/49+ 1-117/89+
2-169 2-71/49 2-91/49 2-111/49
3-149
3-91/49
1-91/49+
2-169 2-71/49 2-9129 2-111/49
3-149
3-91/49 3-91/29
1
1-91/29+
1-9 /49+
2-71/49 2-91/49 2-111/49 2-149 2-169+ 2-71/49 2-111/49 2-117/89+
3-91/29 3-111/49 3-149
3-91/49 3-111/49
1-91/49+
2-71/49 2-111/49 2-111/49 2-149+ 2-189+ 2-71/49 2-111/49+ 2-149+
3-91/49
3-111/49 3-169
3-91/49 3-111/49
1-91/29+
1
1
7
1
2-7 /49 2-11 /49 2-11 /89+ 2-149+ 2-189+ 2-9 /49 2-111/49+ 2-149+
3-91/49 3-111/49 3-117/89 3-169 3-71/49 3-91/49 3-111/49
1-149+
2-111/49 2-111/49
3-91/49
1-149+
2-111/49 2-117/89
3-91/49 3-111/49
1288
2-149
3-111/49
2-149
3-111/49
2-149+
3-117/89
2-169+
3-117/89
2-169+
3-149
688
20 psf LL + 15 psf DL
888
988
1088
1288
1-71/49 1-111/49
2-91/49
3-71/49
1-91/49 1-111/49+
2-71/49 2-9149
3-71/49
1-91/49 1-117/89+
2-71/49 2-91/49
20 psf LL + 25 psf DL
888
988
1088
688
1-149+ 1-149+
1-91/49
2-169+
2-91/49 2-111/49 2-149 2-71/49
3-149
3-91/49 3-117/89
1-149+
1-91/49
2-189+
2-111/49 2-111/49 2-169 2-71/49
1
3-149
3-9 /49
3-149
1-149+
1-91/49+
1
7
2-189+
2-11 /49 2-11 /89 2-169 2-71/49
3-169
3-91/49 3-111/49 3-149
1-91/49+ 1-149+
1-91/49+
2-71/49 2-91/49 2-111/49 2-149 2-169+ 2-71/49
3-169+
3-91/49 3-111/49 3-149
1-91/49+
1-91/49+
1
1
2-7 /49 2-9 /29 2-111/49 2-149+ 2-189+ 2-71/49
1
1
3-169+
3-9 /49
3-11 /49 3-149
1-111/49+
2-91/49
3-71/49
1-117/89+
2-9149
2-91/49
1288
1-149+
2-111/49 2-111/49
3-91/49
1-149+
2-111/49 2-117/89
3-91/49 3-111/49
2-169
3-149
2-169
3-149
+ See note 1.
NOTES:
1. Required end bearing length (based on 625 psi) is 3.09 unless the subscript + is shown.
In that case, 4.59 is required.
2. Headers require full width bearing. Minimum cripple size for 5 1/4 9 thick beams is 2x6.
3. Table is based on residential floor loading of 40 psf live load and 12 psf dead load
and exterior wall weight of 100 plf.
Roof Loading
Rough Opening
25 psf LL + 20 psf DL
988399
1688399 1888399
208
Roof
Truss
Span
with
288
Soffit
Assumed
248
1-117/89+
2-91/49 2-169+
3-149
2-91/49
288
2-111/49
3-91/49
328
2-11 /49
3-91/49
368
2-189+
3-149
3-169+
2-189+
3-169
Snow (115%)
30 psf LL + 20 psf DL
988399 1688399
1888399
1-117/89+
2-91/49 2-169+
3-149
3-169
2-91/29
3-91/49
3-189+
2-111/49
3-91/49 3-169+
3-189+
2-11 /49+
3-91/49 3-169+
3-189+
2-11 /49+
3-91/49 3-189+
2-189+
3-169
2-11 /49+
3-91/49 3-169+
1
40 psf LL + 20 psf DL
988399
1688399
1888399
2-189+
3-169
2-91/29
3-91/49
2-189+
3-149
3-169+
2-111/49
3-91/49
3-169+
3-189+
2-111/49+
3-91/49 3-169+
3-189+
3-169+
20 psf LL + 15 psf DL
988399
1688399 1888399
1-111/49+
2-91/49
2-169
3-169+ 3-71/49
3-149
1-117/89+
2-91/49 2-169+
3-189+
3-149
2-91/49
2-169+
3-149
2-11 /49+
3-91/49 3-189+
2-9 /29
3-91/49
2-189+
3-169
2-11 /49+
2-11 /49
3-91/49
Rough
Opening
3-189+
1
2-189 +
3-169
2-189+
3-169
Non-Snow (125%)
20 psf LL + 20 psf DL
988399
1688399 1888399
1-111/49+
2-91/49 2-169+
3-149
1-117/89+
2-91/49 2-169+
3-149
2-189+
3-169
2-91/29
3-91/49
3-189+
2-11 /49
3-91/49
3-189+
2-11 /49
3-91/49
2-189+
3-169
2-189 +
3-169
2-189 +
3-169
2-91/49
3-169
3-169+
2-111/49
3-91/49
3-169+
3-189+
3-189+
2-11 /49
3-91/49
3-169+
3-189+
3-189+
2-11 /49+
3-91/49
3-169+
3-189+
3-169+
3-169+
1-117/89+
2-91/49 2-169 + 2-189 +
3-149
3-169
2-189+
3-149
20 psf LL + 25 psf DL
988399
1688399 1888399
3-169+
+ See note 1.
NOTES:
1. Required end bearing length (based on 625 psi) is 3.09 unless the subscript + is shown.
In that case, 4.59 is required.
2. Headers require full width bearing. Minimum cripple size for 5 1/4 9 thick beams is 2x6.
3. Table is based on residential floor loading of 40 psf live load and 12 psf dead load
and exterior wall weight of 100 plf.
36
Roof Truss
Span
Rough
Opening
288 Soffit
Assumed
Snow (115%)
Roof Loading
Rough Opening
688
1-71/49
1-91/49
2-71/49
1-71/49
1-91/29
2-91/49
3-71/49
1-111/49
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
208
Roof
Truss
Span
with
288
Soffit
Assumed
248
1-71/49
288
1-71/49
328
368
25 psf LL + 20 psf DL
888
988
1088
1-91/49
2-71/49
1288
Non-Snow (125%)
40 psf LL + 20 psf DL
888
988
1088
688
1-111/49 1-149
1-71/49
2-91/49 2-91/29 2-149
3-71/49 3-91/49 3-111/49
1-111/49 1-149
1-71/49
2-91/49 2-111/49 2-149
1
1
3-9 /49 3-11 /49
1-117/89+ 1-149+
1-91/49
1
2-9 /49 2-111/49 2-149 2-71/49
3-91/49 3-117/89
1-149+
1-91/49+
2-91/29 2-111/49 2-149 2-71/49
3-91/49 3-91/29
1-149+
1-91/49+
2-111/49 2-111/49 2-169 2-71/49
1
3-9 /49
3-149
1-111/49
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-111/49+
2-9 1/49
1288
1-117/89+ 1-149+
2-91/49 2-111/49 2-149
3-91/49 3-117/89
1-149+
2-91/29 2-111/49 2-149
3-91/49 3-91/29
1-149+
2-111/49 2-117/89 2-169
3-91/49 3-111/49 3-149
1-117/89+
2-9 1/49 2-111/49 2-14 2-169+
3-91/49 3-111/49 3-149
688
1-71/49 1-91/49
2-71/49
1-71/49
1-71/49
1-71/49
1-71/49
2-9 1/49
20 psf LL + 15 psf DL
888
988
1088
1288
1-91/29
2-91/49
3-71/49
1-111/49
2-91/49
3-71/49
1-111/49
2-91/49
3-71/49
1-111/49
2-91/49
1-111/49 1-149
2-91/49 2-111/49
3-91/29
1-91/49
1-117/89
2-71/49
2-91/49 2-117/89
3-111/49
1
1-9 /49
1-149
2-71/49
2-91/29 2-149
3-91/49 3-111/49
1-91/29
1-149
2-91/49
2-111/49 2-149
3-71/49
3-91/49 3-111/49
1-111/49 1-117/89 1-149+
2-91/49 2-91/49 2-111/49 2-149
3-71/49
3-91/49 3-117/89
20 psf LL + 25 psf DL
1088
888
988
688
1-71/49
1-91/49
2-71/49
1-71/49
1-91/29
2-9149
3-71/49
1-111/49
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-71/49
1-71/49
1-91/49
2-71/49
1288
1-111/49 1-149
1
2-91/49 2-9 /29 2-149
1
1
3-71/49 3-9 /49 3-11 /49
1-111/49 1-149
1
2-91/49 2-11 /49 2-149
3-91/49 3-111/49
1-117/89+ 1-149+
1
2-91/49 2-11 /49 2-149
3-91/49 3-117/89
1-149+
1
2-91/29 2-11 /49 2-149
1
3-91/49 3-9 /29
1-149+
2-111/49 2-111/49 2-169
3-91/49
3-149
+ See note 1.
NOTES:
1. Required bearing length (based on 625 psi) is 3.09 unless the subscript + is shown.
In that case, 4.59 is required.
2. Headers require full width bearing. Minimum cripple size for 5 1/4 9 thick beams is 2x6.
3. Deflection is limited to L/240 at live load and the lesser of L/180 or 5/16 9 at total load.
4. Roof live and dead loads shown are applied vertically to the horizontal projection.
Roof Truss
Span
Rough
Opening
288 Soffit
Assumed
25 psf LL + 20 psf DL
988399
1688399
1888399
Snow (115%)
30 psf LL + 20 psf DL
988399 1688399
1888399
208
1-9 /49
2-71/49
1-9 /49
2-71/49
248
1-91/29
2-7149
Roof Loading
Rough Opening
Roof
Truss
Span
with
288
Soffit
Assumed
1-11 /49+
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-117/89+
2-91/49
3-71/49
2-117/89
3-111/49
2-149
3-111/49
2-149
3-111/49
2-149
3-117/89
288
328
368
1-111/49+
2-7149
1-11 /49+
2-91/49
3-71/49
1-117/89+
2-169+ 2-91/49
3-149
3-71/49
1-149+
2-169+ 2-91/49
3-149
3-71/49
2-149+
3-117/89
2-169+
3-149
2-169+
3-149
1-11 /49+
2-9149
3-71/49
1-111/49+
2-9149
3-71/49
1-117/89+
2-91/49
3-71/49
1
2-149
3-111/49
2-149
3-117/89
2-149
3-111/49
2-169+
3-149
2-149
3-111/49
40 psf LL + 20 psf DL
988399
1688399
1888399
2-149+
3-117/89
2-169+
3-149
20 psf LL + 15 psf DL
988399
1688399 1888399
Non-Snow (125%)
20 psf LL + 20 psf DL
988399
1688399 1888399
20 psf LL + 25 psf DL
988399
1688399 1888399
1-9 /49
2-71/49
1-9 /49
2-71/49
1-91/49
2-71/49
2-149
3-111/49
2-169+
3-149
2-149+
3-117/89
2-169+
3-149
1-91/49
2-71/49
1-9 /49
2-71/49
1-149+
2-111/49
3-91/49
2-111/49
2-169+
3-149
2-169+
3-149
2-189+
3-149
2-91/49
2-117/89
3-111/49
2-149
3-111/49
2-169+
3-149
2-189+
3-149
2-169+
3-149
1-9 /49
2-71/49
3-169+
1-91/29+
2-71/49
2-91/49
3-149+
3-169+
1-91/49
2-71/49
1-9 /49
2-71/49
2-111/49
2-149
3-111/49
2-117/89
3-111/49
2-149
3-117/89
2-117/89
3-111/49
2-169+
3-149
2-149
3-117/89
2-149
3-111/49
1-11 /49+
2-91/49
2-149
3-71/49 3-111/49
1-111/49+
2-169+ 2-91/49 2-149+
3-149
3-71/49 3-117/89
2-149
3-111/49
2-149
3-117/89
1-11 /49+
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
1-111/49+
2-91/49
3-71/49
2-149
2-149
3-111/49 3-117/89
2-149
3-117/89
2-149
3-111/49
1-91/49
2-71/49
2-117/89 2-149
3-111/49 3-111/49
2-169+
3-149
2-169+
3-149
2-149
3-111/49
2-169+
3-149
2-149+
3-117/89
2-169+
3-149
2-149+
2-169+
3-149
+ See note 1.
NOTES:
1. Required end bearing length (based on 625 psi) is 3.0" unless the subscript + is shown.
In that case, 4.5" is required.
2. Headers require full width bearing. Minimum cripple size for 5 1/4 9 thick beams is 2 x6.
37
Reaction B
128
148
168
188
208
228
248
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
Hip Beam
Depth
Order Length (ft)
React. A (lbs)
React. B (lbs)
up to 4/12
1 11149
2 9149
3 9149
22
1,745
895
1 149
2 9129
3 9149
26
2,380
1,225
2 11789
3 11149
4 9149
28
3,150
1,640
2 149
3 11789
4 11149
32
3,995
2,080
2 169
3 149
4 149
34
4,960
2,600
2 189
3 169
4 149
38
6,110
3,250
3 189
4 169
40
7,370
3,970
20 psf LL + 13 psf DL
Roof Slope
up to 8/12
1 11149
2 9149
3 9149
24
1,805
925
1 149
2 11149
3 9149
28
2,460
1,265
2 11789
3 11149
4 9129
30
3,285
1,720
2 149
3 149
4 11149
34
4,160
2,180
2 169
3 149
4 149
36
5,135
2,695
2 189
3 169
4 169
40
6,465
3,515
3 189
4 189
42
7,640
4,130
up to 12/12
1 11149
2 9149
3 9149
26
1,895
975
1 149
2 11149
3 9149
30
2,585
1,330
2 149
3 11149
4 11149
34
3,450
1,815
2 169
3 149
4 11149
36
4,400
2,330
2 189
3 169
4 149
40
5,540
2,985
3 189
4 169
44
6,815
3,720
4 189
46
8,050
4,365
up to 4/12
1 11149
2 9149
3 9149
22
2,225
1,135
1 149
2 11149
3 9149
26
3,035
1,550
2 149
3 11149
4 11149
28
4,025
2,085
2 169
3 149
4 11789
32
5,100
2,645
2 189
3 169
4 149
34
6,375
3,350
3 189
4 169
38
7,850
4,190
4 189
40
9,290
4,930
3 189
3 189
4 169
4 189
40
44
8,080
8,430
4,325
4,530
4 189
42
9,560
5,090
up to 4/12
1 11149
2 9149
3 9149
22
2,705
1,375
1 149
2 11149
3 11149
26
3,690
1,875
2 149
3 11789
4 11149
28
4,880
2,515
2 169
3 149
4 149
32
6,200
3,210
2 189
3 169
4 169
34
7,745
4,050
3 189
4 189
38
9,465
4,995
40 psf LL + 13 psf DL
Roof Slope
up to 8/12
1 11789
2 9149
3 9149
24
2,770
1,410
2 11789
3 11149
4 9149
28
3,820
1,970
2 149
3 11789
4 11149
30
5,015
2,600
2 169
3 149
4 149
34
6,345
3,290
3 169
4 169
36
7,930
4,160
4 189
40
9,695
5,130
up to 12/12
1 149
2 11149
3 9149
26
2,870
1,470
2 11789
3 11149
4 9149
30
3,820
1,970
2 169
3 149
4 11789
34
5,185
2,695
2 189
3 169
4 149
36
6,690
3,535
3 189
4 169
40
8,350
4,460
4 189
44
10,040
5,335
NOTES:
1. 28-09 maximum roof overhang assumed for order length.
2. Provide posts at both high end and low end to support Reactions A and B. Provide 3 1/2 9 minimum bearing at each end based on Douglas Fir-Larch or
Southern Pine post or plate material.
3. The building designer must consider thrust resistant connections at bearing locations.
4. For non-equal roof slopes, use the greatest roof slope and the longest L distance.
5. Chart is based on triangular loading applied to the hip member. Live load is calculated as applied vertically to the horizontal projection of the rafter
and dead load is calculated along the rafter length.
6. Size based on Roof Snow applications with a load duration factor of 115% and deflection criterion of L/240 live load and L/180 total load.
7. Refer to page 49 Fastening Recommendations for Side-Loaded, Multiple-Piece Members. Use L distance to determine span-carried length or uniform loading.
8. Reactions include heaviest beam weight.
9. A structural ridge beam is assumed.
38
Reaction C
128
148
168
188
208
228
248
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
Valley Beam
Depth
Order Length (ft)
React. C (lbs)
React. D (lbs)
up to 4/12
1 11149
2 9149
3 9149
22
1,745
895
1 149
2 9129
3 9149
26
2,380
1,225
2 117 8 9
3 11149
4 9149
28
3,150
1,640
2 149
3 117 8 9
4 11149
32
3,995
2,080
2 169
3 149
4 149
34
4,960
2,600
2 189
3 169
4 149
38
6,110
3,250
3 189
4 169
40
7,370
3,970
20 psf LL + 13 psf DL
Roof Slope
up to 8/12
1 11149
2 9149
3 9149
24
1,805
925
1 149
2 11149
3 9149
28
2,460
1,265
2 117 8 9
3 11149
4 9129
30
3,285
1,720
2 149
3 149
4 11149
34
4,160
2,180
2 169
3 149
4 149
36
5,135
2,695
2 189
3 169
4 169
40
6,465
3,515
3 189
4 189
42
7,640
4,130
up to 12/12
1 11149
2 9149
3 9149
26
1,895
975
1 149
2 11149
3 9149
30
2,585
1,330
2 149
3 11149
4 11149
34
3,450
1,815
2 169
3 149
4 11149
36
4,400
2,330
2 189
3 169
4 149
40
5,540
2,985
3 189
4 169
44
6,815
3,720
4 189
46
8,050
4,365
3 189
3 189
3 189
4 169
4 169
4 189
38
40
44
7,850
8,080
8,430
4,190
4,325
4,530
4 189
4 189
40
42
9,290
9,560
4,930
5,090
up to 4/12
1 11149
2 9149
3 9149
22
2,705
1,375
1 149
2 11149
3 11149
26
3,690
1,875
2 149
3 1178 9
4 11149
28
4,880
2,515
2 169
3 149
4 149
32
6,200
3,210
2 189
3 169
4 169
34
7,745
4,050
3 189
4 189
38
9,465
4,995
40 psf LL + 13 psf DL
Roof Slope
up to 8/12
1 1178 9
2 9149
3 9149
24
2,770
1,410
2 1178 9
3 11149
4 9149
28
3,820
1,970
2 149
3 1178 9
4 11149
30
5,015
2,600
2 169
3 149
4 149
34
6,345
3,290
3 169
4 169
36
7,930
4,160
4 189
40
9,695
5,130
NOTES:
1. 28-09 maximum roof overhang assumed for order length.
2. Provide posts at both high end and low end to support Reactions C and D. Provide 3 1/2 9 minimum bearing at each end based on Douglas Fir-Larch or
Southern Pine post or plate material.
3. The building designer must consider thrust resistant connections at bearing locations.
4. For non-equal roof slopes, use the greatest roof slope and the longest L distance.
5. Chart is based on triangular loading applied to the valley member. Live load is calculated as applied vertically to the horizontal projection of the rafter
and dead load is calculated along the rafter length.
6. Size based on Roof Snow applications with a load duration factor of 115% and deflection criterion of L/240 live load and L/180 total load.
7. Refer to page 49 Fastening Recommendations for Side-Loaded, Multiple-Piece Members. Use L distance to determine span-carried length or uniform loading.
8. Reactions include heaviest beam weight.
9. A structural ridge beam is assumed.
Georgia-Pacific Corporation, June 2006
up to 12/12
1 149
2 11149
3 9149
26
2,870
1,470
2 1178 9
3 11149
4 9149
30
3,820
1,970
2 169
3 149
4 1178 9
34
5,185
2,695
2 189
3 169
4 149
36
6,690
3,535
3 189
4 169
40
8,350
4,460
4 189
44
10,040
5,335
39
Beam Thickness
Reaction
(lbs)
1 49
3 29
5 49
1,000
1 4
2,000
Beam Thickness
79
1 49
3 29
5 49
1 2
1 2
1 2
1 2
312
134
112
112
3,000
5 4
2 4
1 4
4,000
312
5,000
834
Beam Thickness
79
1 49
3 29
5 49
1 2
1 2
1 2
1 2
112
112
112
1 2
4 4
2 4
1 2
212
134
534
412
214
714
6,000
514
312
234
812
7,000
8,000
9,000
10,000
Beam Thickness
79
1 49
3129
5149
79
1 2
1 2
1 2
1 2
1 2
1 2
112
214
112
112
112
134
112
112
112
1 2
3 4
1 4
1 2
1 2
2 2
1 2
1 2
112
112
414
214
112
112
314
134
112
112
334
212
514
234
134
112
112
112
414
214
614
314
214
134
434
212
134
112
3 2
2 2
7 4
3 4
2 2
5 2
2 4
112
434
312
534
814
414
234
214
614
314
214
134
734
514
612
414
314
914
434
314
212
312
212
134
834
534
412
714
434
334
514
312
234
734
234
11,000
6 2
4 4
5 4
5 4
3 4
8 2
4 4
214
12,000
514
812
534
414
614
414
314
914
434
314
212
13,000
712
534
914
614
434
634
412
312
312
212
14,000
634
714
434
334
512
334
234
15,000
8 4
6 2
7 4
5 2
7 4
5 4
5 4
16,000
9 /4
7 4
5 4
8 4
5 2
4 4
6 4
4 4
314
17,000
714
834
534
412
612
412
314
18,000
734
812
612
914
19,000
8 4
20,000
21,000
614
434
434
312
6 4
6 2
7 4
334
834
714
634
514
734
514
7 2
7 4
5 2
22,000
712
534
23,000
814
24,000
812
814
5 2
812
534
414
412
614
914
614
434
40
and dry-use conditions. For other loads or span configurations, use FASTBeam analysis & selection software or
contact your BlueLinx representative.
12. Beam thickness is the net thickness of the beam. For multiple-piece members beam thickness may be achieved by
properly connecting multiple plies of GP Lam LVL lumber beams. See page 49 for connection details.
13. To size a beam it is necessary to check both live load and total load. Selected beam must work in both rows. When no live
load is shown, total load will control, unless floor live load deflections other than L/360 are checked per note 4.
14. For floor live load deflection limits of L/480 or L/600, multiply the value in the floor LL row (or TL when LL is not
shown) by .75 or .60 respectively.
15. To size a member for a span not shown, use capacities for the next larger span shown (example: for 78 span, use
values shown for 88 span).
16. Verify deflection limits with local building code requirements.
17. Bearing across full width of beam is assumed.
18. Assumes 565 psi bearing stress limited by douglas fir, southern yellow pine or other dense supporting material. For
SPF or other less dense materials, either double the bearing length shown or refer to Bearing Length Requirements
on page 40.
19. Bearing length may be adjusted if a beam is not fully loaded. For example, if 4.29 of bearing is required for a beam
with maximum total load capacity of 1000 PLF yet the total design load is only 700 PLF the bearing length may be
adjusted as follows: 700/1000 x 4.2 = 2.949 minimum (use 2 cripples for 3 9). In no case may end bearing length be less
than 1 12 9 or intermediate bearing length be less than 39.
10. Provide lateral support at bearing points, and continuous lateral support along the top edge of beam.
11. 1349 thick beams with depth greater than 149 must only be used in multiple-piece members.
12. For 3 ply or 4 ply 7 14 9 GP Lam LVL, use 1 34 9 table and multiply by 3 or 4 respectively.
13. Roof members must slope for drainage.
EXAMPLE:
Select a GP Lam LVL beam to carry 520 PLF live load + 200 PLF dead load. Beam supports both floor and roof, and
spans 108.
When a beam carries floor and roof, use tables for floor loads; these tables are based on more stringent criteria than
those used for roof loads. Use the table titled Floor 100%, on page 42. Adding 520 PLF and 200 PLF gives a total load
of 720 PLF. Find 108in the left most column. To the right are three rows showing Live Load L/360, Total Load and
Minimum End and Minimum Interior Bearing requirements in inches. In the row marked Total Load, move to the right
to locate a total load of at least 720 PLF. 1 34 9 x 11 78 9 GP Lam LVL Beam can carry 745 PLF total load. Check live load
capacity. 1 34 9 x 11 78 9 can carry 629 PLF live load, so live load capacity is also adequate. Note required end bearing
length is 3.89 and 9.59 for interior bearing of multiple spans. (See Note 9 above)
If less bearing length or a depth less than 11 78 9 is desired, check the capacity of 3 12 9 LVL beams. In the row marked
Total Load, move farther to the right to locate a total load of at least 720 PLF. A 3 12 9 wide x 9 14 9 deep member can carry
932 PLF total load. Check that live load capacity is at least 520 PLF. 3 12 9 x 9149 beams can carry 627 PLF, which is
sufficient. Use 3 12 9 x 9 14 9 deep. Required end bearing is 2.49 and 5.9 9 is required for interior bearing of multiple
spans.
41
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
7149
660
763
2.3 / 5.8
296
440
1.8 / 4.5
156
230
1.5 / 3.0
118
174
1.5 / 3.0
92
134
1.5 / 3.0
73
105
1.5 / 3.0
58
84
1.5 / 3.0
48
68
1.5 / 3.0
1063
3.2 / 8.1
629
746
3.0 / 7.6
338
503
2.6 / 6.4
258
382
2.2 / 5.4
201
297
1.8 / 4.6
160
235
1.6 / 3.9
129
189
1.5 / 3.4
105
153
1.5 / 3.0
87
126
1.5 / 3.0
73
105
1.5 / 3.0
62
88
1.5 / 3.0
53
75
1.5 / 3.0
45
63
1.5 / 3.0
1499
1325
1425
1576
4.0 / 10.1 4.3 / 10.8 4.8 / 12.0
916
3.7 / 9.3
542
699
3.6 / 8.9
416
589
3.3 / 8.3
326
483
3.0 / 7.4
259
384
2.6 / 6.4
210
309
2.2 / 5.6
172
253
2.0 / 4.9
143
209
1.7 / 4.3
120
174
1.5 / 3.9
101
147
1.5 / 3.5
86
124
1.5 / 3.1
74
106
1.5 / 3.0
56
79
1.5 / 3.0
43
60
1.5 / 3.0
979
4.0 / 10.0
629
745
3.8 / 9.5
484
652
3.7 / 9.1
379
547
3.4 / 8.4
302
448
3.0 / 7.5
245
362
2.6 / 6.5
201
296
2.3 / 5.7
167
245
2.0 / 5.1
140
204
1.8 / 4.5
119
172
1.6 / 4.0
101
146
1.5 / 3.6
87
125
1.5 / 3.3
66
93
1.5 / 3.0
51
71
1.5 / 3.0
40
55
1.5 / 3.0
1180
4.8 / 12.0
909
4.6 / 11.6
760
809
4.5 / 11.3
599
729
4.5 / 11.2
480
636
4.2 / 10.6
390
548
3.9 / 9.8
321
476
3.7 / 9.1
268
395
3.2 / 8.1
225
331
2.9 / 7.3
191
280
2.6 / 6.5
163
239
2.4 / 5.9
141
205
2.1 / 5.3
107
154
1.8 / 4.5
83
118
1.5 / 3.8
65
92
1.5 / 3.2
53
72
1.5 / 3.0
7149
1319
1526
2.3 / 5.8
591
880
1.8 / 4.5
312
461
1.5 / 3.0
236
348
1.5 / 3.0
183
268
1.5 / 3.0
145
211
1.5 / 3.0
117
168
1.5 / 3.0
95
136
1.5 / 3.0
79
111
1.5 / 3.0
66
92
1.5 / 3.0
56
76
1.5 / 3.0
47
64
1.5 / 3.0
41
54
1.5 / 3.0
9149
2056
3.1 / 7.8
1169
1446
2.9 / 7.4
627
932
2.4 / 5.9
478
708
2.0 / 5.0
372
550
1.7 / 4.2
295
434
1.5 / 3.6
238
349
1.5 / 3.2
195
284
1.5 / 3.0
161
233
1.5 / 3.0
135
194
1.5 / 3.0
114
162
1.5 / 3.0
97
137
1.5 / 3.0
84
117
1.5 / 3.0
63
86
1.5 / 3.0
49
64
1.5 / 3.0
9129
2127
2650
3.2 / 8.1 4.0 / 10.1
1258
1493
1831
3.0 / 7.6 3.7 / 9.3
676
1084
1005
1398
2.6 / 6.4 3.6 / 8.9
516
832
765
1178
2.2 / 5.4 3.3 / 8.3
402
651
594
966
1.8 / 4.6 3.0 / 7.4
319
519
470
768
1.6 / 3.9 2.6 / 6.4
257
420
377
619
1.5 / 3.4 2.2 / 5.6
211
344
307
506
1.5 / 3.0 2.0 / 4.9
174
285
253
418
1.5 / 3.0 1.7 / 4.3
146
239
210
349
1.5 / 3.0 1.5 / 3.9
123
203
176
293
1.5 / 3.0 1.5 / 3.5
105
173
149
249
1.5 / 3.0 1.5 / 3.1
90
149
127
213
1.5 / 3.0 1.5 / 3.0
68
112
94
158
1.5 / 3.0 1.5 / 3.0
53
87
70
120
1.5 / 3.0 1.5 / 3.0
42
69
54
93
1.5 / 3.0 1.5 / 3.0
55
72
1.5 / 3.0
1699
1899
23789
2849
3151
3149
4.3 / 10.8 4.8 / 12.0 4.8 / 12.0
3147
3142
4.8 / 12.0 4.8 / 12.0
1958
4.0 / 10.0
1258
1490
3.8 / 9.5
967
1305
3.7 / 9.1
758
1095
3.4 / 8.4
605
896
3.0 / 7.5
490
724
2.6 / 6.5
402
592
2.3 / 5.7
334
490
2.0 / 5.1
280
409
1.8 / 4.5
237
345
1.6 / 4.0
203
293
1.5 / 3.6
174
251
1.5 / 3.3
132
187
1.5 / 3.0
102
142
1.5 / 3.0
81
110
1.5 / 3.0
65
86
1.5 / 3.0
2360
2358
4.8 / 12.0 4.8 / 12.0
2356
2351
4.8 / 12.0 4.8 / 12.0
1818
4.6 / 11.6
1519
1618
4.5 / 11.3
1198
1457
4.5 / 11.2
961
1273
4.2 / 10.6
781
1096
3.9 / 9.8
643
951
3.7 / 9.1
535
790
3.2 / 8.1
450
662
2.9 / 7.3
382
560
2.6 / 6.5
327
477
2.4 / 5.9
282
410
2.1 / 5.3
213
307
1.8 / 4.5
166
235
1.5 / 3.8
131
183
1.5 / 3.2
105
145
1.5 / 3.0
1884
4.8 / 12.0
1882
1876
4.8 / 12.0 4.8 / 12.0
1711
4.8 / 12.0
1709
1704
4.8 / 12.0 4.8 / 12.0
1567
4.8 / 12.0
1387
1446
4.8 / 12.0
1132
1341
4.8 / 12.0
935
1228
4.7 / 11.8
781
1078
4.4 / 11.0
658
953
4.2 / 10.4
560
825
3.8 / 9.6
480
705
3.5 / 8.6
414
606
3.1 / 7.9
315
457
2.6 / 6.6
244
352
2.2 / 5.6
194
276
1.9 / 4.8
156
219
1.7 / 4.1
1565
1560
4.8 / 12.0 4.8 / 12.0
1444
1438
4.8 / 12.0 4.8 / 12.0
1339
1334
4.8 / 12.0 4.8 / 12.0
1249
4.8 / 12.0
1084
1170
4.8 / 12.0
916
1100
4.8 / 12.0
781
1038
4.8 / 12.0
671
951
4.6 / 11.6
580
853
4.4 / 11.0
442
646
3.7 / 9.2
344
499
3.1 / 7.8
273
392
2.7 / 6.7
220
313
2.3 / 5.8
1243
4.8 / 12.0
1164
4.8 / 12.0
1095
4.8 / 12.0
1032
4.8 / 12.0
977
4.8 / 12.0
927
4.8 / 12.0
841
4.8 / 12.0
769
4.8 / 12.0
614
708
4.8 / 12.0
497
656
4.8 / 12.0
KEY TO TABLES
Live Load L/360 = Maximum live load limits deflection to L/360
Total Load = Maximum total load limits deflection to L/240
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
42
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
Condition
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
Live Load L/360
Total Load
End / Int. Bearing
9149
3085
3.1 / 7.8
1754
2169
2.9 / 7.4
940
1397
2.4 / 5.9
717
1062
2.0 / 5.0
558
825
1.7 / 4.2
443
652
1.5 / 3.6
357
523
1.5 / 3.2
292
425
1.5 / 3.0
242
350
1.5 / 3.0
202
291
1.5 / 3.0
171
244
1.5 / 3.0
146
206
1.5 / 3.0
125
175
1.5 / 3.0
95
129
1.5 / 3.0
73
97
1.5 / 3.0
58
73
1.5 / 3.0
46
56
1.5 / 3.0
9129
3190
3.2 / 8.1
1887
2239
3.0 / 7.6
1014
1508
2.6 / 6.4
773
1147
2.2 / 5.4
603
891
1.8 / 4.6
479
705
1.6 / 3.9
386
566
1.5 / 3.4
316
460
1.5 / 3.0
262
379
1.5 / 3.0
219
315
1.5 / 3.0
185
264
1.5 / 3.0
158
224
1.5 / 3.0
136
190
1.5 / 3.0
102
140
1.5 / 3.0
79
105
1.5 / 3.0
62
80
1.5 / 3.0
50
62
1.5 / 3.0
4254
3.2 / 8.1
2516
2986
3.0 / 7.6
1352
2010
2.6 / 6.4
1032
1530
2.2 / 5.4
804
1188
1.8 / 4.6
638
940
1.6 / 3.9
514
754
1.5 / 3.4
422
614
1.5 / 3.0
348
506
1.5 / 3.0
292
420
1.5 / 3.0
246
352
1.5 / 3.0
210
298
1.5 / 3.0
180
254
1.5 / 3.0
136
188
1.5 / 3.0
106
140
1.5 / 3.0
84
108
1.5 / 3.0
66
82
1.5 / 3.0
1699
1899
23789
5300
5698
6302
6298
6294
6284
4.0 / 10.1 4.3 / 10.8 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3662
3916
4720
4716
4712
4702
3.7 / 9.3 4.0 / 10.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2168
2516
2796
2980
3636
3768
3764
3752
3.6 / 8.9 3.8 / 9.5 4.6 / 11.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1664
1934
3038
2356
2610
3236
3422
3418
3408
3.3 / 8.3 3.7 / 9.1 4.5 / 11.3 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1302
1516
2396
1932
2190
2914
3134
3130
3120
3.0 / 7.4 3.4 / 8.4 4.5 / 11.2 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1038
1210
1922
2774
1536
1792
2546
2892
2888
2876
2.6 / 6.4 3.0 / 7.5 4.2 / 10.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
840
980
1562
2264
1238
1448
2192
2682
2678
2668
2.2 / 5.6 2.6 / 6.5 3.9 / 9.8 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
688
804
1286
1870
1012
1184
1902
2456
2498
2486
2.0 / 4.9 2.3 / 5.7 3.7 / 9.1 4.7 / 11.8 4.8 / 12.0 4.8 / 12.0
570
668
1070
1562
2168
836
980
1580
2156
2340
2328
1.7 / 4.3 2.0 / 5.1 3.2 / 8.1 4.4 / 11.0 4.8 / 12.0 4.8 / 12.0
478
560
900
1316
1832
698
818
1324
1906
2200
2190
1.5 / 3.9 1.8 / 4.5 2.9 / 7.3 4.2 / 10.4 4.8 / 12.0 4.8 / 12.0
406
474
764
1120
1562
586
690
1120
1650
2076
2064
1.5 / 3.5 1.6 / 4.0 2.6 / 6.5 3.8 / 9.6 4.8 / 12.0 4.8 / 12.0
346
406
654
960
1342
498
586
954
1410
1902
1954
1.5 / 3.1 1.5 / 3.6 2.4 / 5.9 3.5 / 8.6 4.6 / 11.6 4.8 / 12.0
298
348
564
828
1160
426
502
820
1212
1706
1854
1.5 / 3.0 1.5 / 3.3 2.1 / 5.3 3.1 / 7.9 4.4 / 11.0 4.8 / 12.0
224
264
426
630
884
316
374
614
914
1292
1682
1.5 / 3.0 1.5 / 3.0 1.8 / 4.5 2.6 / 6.6 3.7 / 9.2 4.8 / 12.0
174
204
332
488
688
240
284
470
704
998
1538
1.5 / 3.0 1.5 / 3.0 1.5 / 3.8 2.2 / 5.6 3.1 / 7.8 4.8 / 12.0
138
162
262
388
546
1228
186
220
366
552
784
1416
1.5 / 3.0 1.5 / 3.0 1.5 / 3.2 1.9 / 4.8 2.7 / 6.7 4.8 / 12.0
110
130
210
312
440
994
144
172
290
438
626
1312
1.5 / 3.0 1.5 / 3.0 1.5 / 3.0 1.7 / 4.1 2.3 / 5.8 4.8 / 12.0
KEY TO TABLES
Live Load L/360 = Maximum live load limits deflection to L/360
Total Load = Maximum total load limits deflection to L/240
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
43
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
Condition
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
7149
878
2.7 / 6.7
444
560
2.3 / 5.7
234
308
1.6 / 3.9
177
233
1.5 / 3.3
138
180
1.5 / 3.0
109
142
1.5 / 3.0
88
113
1.5 / 3.0
71
92
1.5 / 3.0
59
75
1.5 / 3.0
49
62
1.5 / 3.0
42
52
1.5 / 3.0
1224
3.7 / 9.3
832
3.4 / 8.5
470
567
2.9 / 7.2
358
468
2.6 / 6.6
279
368
2.3 / 5.6
222
291
1.9 / 4.9
179
234
1.7 / 4.2
146
190
1.5 / 3.7
121
157
1.5 / 3.3
101
131
1.5 / 3.0
86
110
1.5 / 3.0
73
93
1.5 / 3.0
63
79
1.5 / 3.0
47
59
1.5 / 3.0
859
3.5 / 8.7
507
596
3.0 / 7.6
387
492
2.8 / 6.9
301
398
2.4 / 6.1
239
315
2.1 / 5.2
193
253
1.8 / 4.6
158
206
1.6 / 4.0
131
170
1.5 / 3.5
109
142
1.5 / 3.1
93
119
1.5 / 3.0
79
101
1.5 / 3.0
68
86
1.5 / 3.0
51
64
1.5 / 3.0
1524
1577
1576
1756
4.6 / 11.6 4.8 / 12.0 4.8 / 12.0 2.7 / 6.7
887
1054
1127
1180
1120
4.3 / 10.7 4.6 / 11.4 4.8 / 12.0 2.3 / 5.7
468
805
858
943
617
4.1 / 10.2 4.4 / 10.9 4.8 / 12.0 1.6 / 3.9
624
725
355
678
751
856
466
3.8 / 9.5 4.2 / 10.5 4.8 / 12.0 1.5 / 3.3
488
569
275
569
630
785
360
3.5 / 8.7 3.9 / 9.6 4.8 / 12.0 1.5 / 3.0
389
454
720
218
484
536
724
283
3.2 / 8.0 3.6 / 8.9 4.8 / 12.0 1.5 / 3.0
315
367
586
175
414
462
631
227
3.0 / 7.4 3.3 / 8.3 4.5 / 11.3 1.5 / 3.0
258
301
482
143
339
396
549
184
2.6 / 6.5 3.0 / 7.6 4.2 / 10.5 1.5 / 3.0
214
250
401
118
280
328
482
151
2.3 / 5.8 2.7 / 6.7 3.9 / 9.9 1.5 / 3.0
179
210
338
99
234
274
426
125
2.1 / 5.1 2.4 / 6.0 3.7 / 9.3 1.5 / 3.0
152
178
286
83
197
232
375
104
1.8 / 4.6 2.2 / 5.4 3.5 / 8.7 1.5 / 3.0
130
152
245
71
168
197
320
88
1.7 / 4.2 1.9 / 4.9 3.1 / 7.8 1.5 / 3.0
112
131
211
61
144
169
275
74
1.5 / 3.8 1.8 / 4.4 2.8 / 7.1 1.5 / 3.0
84
99
160
46
107
126
207
54
1.5 / 3.1 1.5 / 3.7 2.4 / 5.9 1.5 / 3.0
65
77
124
82
97
159
1.5 / 3.0 1.5 / 3.1 2.0 / 5.0
51
60
98
63
75
124
1.5 / 3.0 1.5 / 3.0 1.7 / 4.3
41
49
79
50
59
99
1.5 / 3.0 1.5 / 3.0 1.5 / 3.7
1499
1699
1899
23789
2366
3.6 / 9.0
2447
3.7 / 9.3
3049
3153
3151
3149
4.6 / 11.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3147
3142
4.8 / 12.0 4.8 / 12.0
1664
3.4 / 8.5
940
1134
2.9 / 7.2
717
935
2.6 / 6.6
558
736
2.3 / 5.6
443
582
1.9 / 4.9
357
468
1.7 / 4.2
292
381
1.5 / 3.7
242
314
1.5 / 3.3
202
261
1.5 / 3.0
171
220
1.5 / 3.0
146
186
1.5 / 3.0
125
159
1.5 / 3.0
95
117
1.5 / 3.0
73
89
1.5 / 3.0
58
68
1.5 / 3.0
46
53
1.5 / 3.0
1718
3.5 / 8.7
1014
1193
3.0 / 7.6
773
984
2.8 / 6.9
603
795
2.4 / 6.1
479
629
2.1 / 5.2
386
506
1.8 / 4.6
316
412
1.6 / 4.0
262
340
1.5 / 3.5
219
283
1.5 / 3.1
185
238
1.5 / 3.0
158
202
1.5 / 3.0
136
172
1.5 / 3.0
102
128
1.5 / 3.0
79
97
1.5 / 3.0
62
74
1.5 / 3.0
50
58
1.5 / 3.0
2108
2253
2360
2358
4.3 / 10.7 4.6 / 11.4 4.8 / 12.0 4.8 / 12.0
2356
2351
4.8 / 12.0 4.8 / 12.0
1609
1715
4.1 / 10.2 4.4 / 10.9
1248
1451
1356
1502
3.8 / 9.5 4.2 / 10.5
977
1137
1138
1261
3.5 / 8.7 3.9 / 9.6
778
907
968
1072
3.2 / 8.0 3.6 / 8.9
629
735
829
923
3.0 / 7.4 3.3 / 8.3
516
603
677
793
2.6 / 6.5 3.0 / 7.6
428
501
560
656
2.3 / 5.8 2.7 / 6.7
359
420
468
549
2.1 / 5.1 2.4 / 6.0
304
356
395
463
1.8 / 4.6 2.2 / 5.4
259
304
335
394
1.7 / 4.2 1.9 / 4.9
223
262
287
338
1.5 / 3.8 1.8 / 4.4
169
198
214
253
1.5 / 3.1 1.5 / 3.7
130
153
164
193
1.5 / 3.0 1.5 / 3.1
103
121
127
150
1.5 / 3.0 1.5 / 3.0
83
97
100
118
1.5 / 3.0 1.5 / 3.0
1885
1884
4.8 / 12.0 4.8 / 12.0
1882
1876
4.8 / 12.0 4.8 / 12.0
1713
1711
4.8 / 12.0 4.8 / 12.0
1709
1704
4.8 / 12.0 4.8 / 12.0
1569
4.8 / 12.0
1441
1447
4.8 / 12.0
1171
1262
4.5 / 11.3
964
1098
4.2 / 10.5
803
963
3.9 / 9.9
675
852
3.7 / 9.3
573
751
3.5 / 8.7
490
641
3.1 / 7.8
423
550
2.8 / 7.1
320
414
2.4 / 5.9
248
318
2.0 / 5.0
196
249
1.7 / 4.3
158
197
1.5 / 3.7
1567
4.8 / 12.0
1565
1560
4.8 / 12.0 4.8 / 12.0
1446
4.8 / 12.0
1444
1438
4.8 / 12.0 4.8 / 12.0
1341
4.8 / 12.0
1339
1334
4.8 / 12.0 4.8 / 12.0
1251
4.8 / 12.0
1171
1172
4.8 / 12.0
987
1102
4.8 / 12.0
840
978
4.5 / 11.3
720
876
4.3 / 10.7
621
789
4.1 / 10.2
472
615
3.5 / 8.8
367
474
3.0 / 7.4
290
372
2.5 / 6.4
234
297
2.2 / 5.5
1249
1243
4.8 / 12.0 4.8 / 12.0
1170
1164
4.8 / 12.0 4.8 / 12.0
1100
1095
4.8 / 12.0 4.8 / 12.0
1038
1032
4.8 / 12.0 4.8 / 12.0
982
4.8 / 12.0
870
932
4.8 / 12.0
663
813
4.6 / 11.5
516
671
4.2 / 10.4
409
529
3.6 / 9.0
330
423
3.1 / 7.8
977
4.8 / 12.0
927
4.8 / 12.0
841
4.8 / 12.0
769
4.8 / 12.0
708
4.8 / 12.0
656
4.8 / 12.0
KEY TO TABLES
Live Load L/240 = Maximum live load limits deflection to L/240
Total Load = Maximum total load limits deflection to L/180
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
44
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
9149
9129
1899
23789
9149
9129
1899
23789
3549
3.6 / 9.0
3671
4573
4730
4727
4724
4721
4713
4732
3.7 / 9.3 4.6 / 11.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 3.6 / 9.0
4894
6098
6306
6302
6298
6294
6284
3.7 / 9.3 4.6 / 11.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2496
3.4 / 8.5
1410
1701
2.9 / 7.2
1075
1403
2.6 / 6.6
838
1104
2.3 / 5.6
665
873
1.9 / 4.9
536
702
1.7 / 4.2
438
571
1.5 / 3.7
363
471
1.5 / 3.3
304
392
1.5 / 3.0
257
329
1.5 / 3.0
219
279
1.5 / 3.0
188
238
1.5 / 3.0
142
176
1.5 / 3.0
110
133
1.5 / 3.0
86
102
1.5 / 3.0
69
79
1.5 / 3.0
2577
3.5 / 8.7
1521
1789
3.0 / 7.6
1160
1476
2.8 / 6.9
904
1193
2.4 / 6.1
718
944
2.1 / 5.2
579
759
1.8 / 4.6
474
618
1.6 / 4.0
392
510
1.5 / 3.5
328
425
1.5 / 3.1
278
357
1.5 / 3.0
237
302
1.5 / 3.0
203
258
1.5 / 3.0
154
191
1.5 / 3.0
119
145
1.5 / 3.0
94
111
1.5 / 3.0
75
87
1.5 / 3.0
3436
4216
3.5 / 8.7 4.3 / 10.7
2028
2386
3218
3.0 / 7.6 4.1 / 10.2
1546
2496
1968
2712
2.8 / 6.9 3.8 / 9.5
1206
1954
1590
2276
2.4 / 6.1 3.5 / 8.7
958
1556
1258
1936
2.1 / 5.2 3.2 / 8.0
772
1258
1012
1658
1.8 / 4.6 3.0 / 7.4
632
1032
824
1354
1.6 / 4.0 2.6 / 6.5
524
856
680
1120
1.5 / 3.5 2.3 / 5.8
438
718
566
936
1.5 / 3.1 2.1 / 5.1
370
608
476
790
1.5 / 3.0 1.8 / 4.6
316
518
404
670
1.5 / 3.0 1.7 / 4.2
272
446
344
574
1.5 / 3.0 1.5 / 3.8
204
338
256
428
1.5 / 3.0 1.5 / 3.1
158
260
194
328
1.5 / 3.0 1.5 / 3.0
124
206
148
254
1.5 / 3.0 1.5 / 3.0
100
166
116
200
1.5 / 3.0 1.5 / 3.0
3161
3380
3540
3537
3534
3526
3328
4.3 / 10.7 4.6 / 11.4 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 3.4 / 8.5
1880
2414
2573
2828
2825
2822
2814
2268
4.1 / 10.2 4.4 / 10.9 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 2.9 / 7.2
1871
2176
1434
2034
2253
2569
2567
2564
2555
1870
3.8 / 9.5 4.2 / 10.5 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 2.6 / 6.6
1465
1706
1116
1707
1891
2354
2351
2348
2340
1472
3.5 / 8.7 3.9 / 9.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 2.3 / 5.6
1167
1361
2161
886
1452
1609
2171
2168
2165
2157
1164
3.2 / 8.0 3.6 / 8.9 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.9 / 4.9
944
1102
1757
714
1243
1385
1893
2012
2009
2001
936
3.0 / 7.4 3.3 / 8.3 4.5 / 11.3 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.7 / 4.2
774
904
1446
584
1016
1189
1646
1876
1873
1865
762
2.6 / 6.5 3.0 / 7.6 4.2 / 10.5 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.7
642
751
1204
1757
484
840
985
1445
1758
1755
1746
628
2.3 / 5.8 2.7 / 6.7 3.9 / 9.9 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.3
538
630
1013
1481
404
702
823
1278
1653
1650
1642
522
2.1 / 5.1 2.4 / 6.0 3.7 / 9.3 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0
456
534
859
1259
342
592
695
1126
1467
1557
1549
440
1.8 / 4.6 2.2 / 5.4 3.5 / 8.7 4.5 / 11.3 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0
389
456
735
1080
292
503
591
961
1314
1474
1465
372
1.7 / 4.2 1.9 / 4.9 3.1 / 7.8 4.3 / 10.7 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0
335
392
634
932
1305
250
431
507
826
1184
1399
1391
318
1.5 / 3.8 1.8 / 4.4 2.8 / 7.1 4.1 / 10.2 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0
253
297
480
708
994
190
322
379
621
922
1220
1261
234
1.5 / 3.1 1.5 / 3.7 2.4 / 5.9 3.5 / 8.8 4.6 / 11.5 4.8 / 12.0 1.5 / 3.0
196
230
372
550
774
146
245
290
477
711
1007
1153
178
1.5 / 3.0 1.5 / 3.1 2.0 / 5.0 3.0 / 7.4 4.2 / 10.4 4.8 / 12.0 1.5 / 3.0
154
181
294
436
614
116
190
225
373
559
793
1062
136
1.5 / 3.0 1.5 / 3.0 1.7 / 4.3 2.5 / 6.4 3.6 / 9.0 4.8 / 12.0 1.5 / 3.0
124
146
237
351
495
92
150
178
296
445
634
984
106
1.5 / 3.0 1.5 / 3.0 1.5 / 3.7 2.2 / 5.5 3.1 / 7.8 4.8 / 12.0 1.5 / 3.0
4506
4720
4716
4712
4702
4.6 / 11.4 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3430
4.4 / 10.9
2902
3004
4.2 / 10.5
2274
2522
3.9 / 9.6
1814
2144
3.6 / 8.9
1470
1846
3.3 / 8.3
1206
1586
3.0 / 7.6
1002
1312
2.7 / 6.7
840
1098
2.4 / 6.0
712
926
2.2 / 5.4
608
788
1.9 / 4.9
524
676
1.8 / 4.4
396
506
1.5 / 3.7
306
386
1.5 / 3.1
242
300
1.5 / 3.0
194
236
1.5 / 3.0
3770
3768
3764
3752
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3426
3422
3418
3408
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3138
4.8 / 12.0
2882
2894
4.8 / 12.0
2342
2524
4.5 / 11.3
1928
2196
4.2 / 10.5
1606
1926
3.9 / 9.9
1350
1704
3.7 / 9.3
1146
1502
3.5 / 8.7
980
1282
3.1 / 7.8
846
1100
2.8 / 7.1
640
828
2.4 / 5.9
496
636
2.0 / 5.0
392
498
1.7 / 4.3
316
394
1.5 / 3.7
3134
3130
3120
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2892
2888
2876
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2682
2678
2668
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2502
4.8 / 12.0
2342
2344
4.8 / 12.0
1974
2204
4.8 / 12.0
1680
1956
4.5 / 11.3
1440
1752
4.3 / 10.7
1242
1578
4.1 / 10.2
944
1230
3.5 / 8.8
734
948
3.0 / 7.4
580
744
2.5 / 6.4
468
594
2.2 / 5.5
2498
2486
4.8 / 12.0 4.8 / 12.0
2340
2328
4.8 / 12.0 4.8 / 12.0
2200
2190
4.8 / 12.0 4.8 / 12.0
2076
2064
4.8 / 12.0 4.8 / 12.0
1964
4.8 / 12.0
1740
1864
4.8 / 12.0
1326
1626
4.6 / 11.5
1032
1342
4.2 / 10.4
818
1058
3.6 / 9.0
660
846
3.1 / 7.8
1954
4.8 / 12.0
1854
4.8 / 12.0
1682
4.8 / 12.0
1538
4.8 / 12.0
1416
4.8 / 12.0
1312
4.8 / 12.0
KEY TO TABLES
Live Load L/240 = Maximum live load limits deflection to L/240
Total Load = Maximum total load limits deflection to L/180
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
45
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
Condition
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
Live Load L/240
Total Load
End / Int. Bearing
7149
955
2.9 / 7.3
444
588
2.4 / 6.0
234
308
1.6 / 3.9
177
233
1.5 / 3.3
138
180
1.5 / 3.0
109
142
1.5 / 3.0
88
113
1.5 / 3.0
71
92
1.5 / 3.0
59
75
1.5 / 3.0
49
62
1.5 / 3.0
42
52
1.5 / 3.0
1330
1577
1577
1576
4.0 / 10.1 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
934
3.8 / 9.5
507
649
3.3 / 8.3
387
511
2.9 / 7.2
301
398
2.4 / 6.1
239
315
2.1 / 5.2
193
253
1.8 / 4.6
158
206
1.6 / 4.0
131
170
1.5 / 3.5
109
142
1.5 / 3.1
93
119
1.5 / 3.0
79
101
1.5 / 3.0
68
86
1.5 / 3.0
51
64
1.5 / 3.0
1146
4.7 / 11.6
813
875
4.5 / 11.1
624
737
4.1 / 10.3
488
619
3.8 / 9.5
389
513
3.4 / 8.5
315
414
3.0 / 7.4
258
339
2.6 / 6.5
214
280
2.3 / 5.8
179
234
2.1 / 5.1
152
197
1.8 / 4.6
130
168
1.7 / 4.2
112
144
1.5 / 3.8
84
107
1.5 / 3.1
65
82
1.5 / 3.0
51
63
1.5 / 3.0
41
50
1.5 / 3.0
1181
1180
4.8 / 12.0 4.8 / 12.0
933
4.7 / 11.9
725
817
4.6 / 11.4
569
686
4.2 / 10.5
454
583
3.9 / 9.7
367
484
3.5 / 8.7
301
396
3.0 / 7.6
250
328
2.7 / 6.7
210
274
2.4 / 6.0
178
232
2.2 / 5.4
152
197
1.9 / 4.9
131
169
1.8 / 4.4
99
126
1.5 / 3.7
77
97
1.5 / 3.1
60
75
1.5 / 3.0
49
59
1.5 / 3.0
943
4.8 / 12.0
856
4.8 / 12.0
785
4.8 / 12.0
720
724
4.8 / 12.0
586
672
4.8 / 12.0
482
597
4.6 / 11.4
401
524
4.3 / 10.7
338
444
3.9 / 9.7
286
375
3.5 / 8.7
245
320
3.1 / 7.8
211
275
2.8 / 7.1
160
207
2.4 / 5.9
124
159
2.0 / 5.0
98
124
1.7 / 4.3
79
99
1.5 / 3.7
1909
2.9 / 7.3
887
1176
2.4 / 6.0
468
617
1.6 / 3.9
355
466
1.5 / 3.3
275
360
1.5 / 3.0
218
283
1.5 / 3.0
175
227
1.5 / 3.0
143
184
1.5 / 3.0
118
151
1.5 / 3.0
99
125
1.5 / 3.0
83
104
1.5 / 3.0
71
88
1.5 / 3.0
61
74
1.5 / 3.0
46
54
1.5 / 3.0
2573
3.9 / 9.8
1754
1810
3.7 / 9.2
940
1233
3.1 / 7.8
717
947
2.7 / 6.6
558
736
2.3 / 5.6
443
582
1.9 / 4.9
357
468
1.7 / 4.2
292
381
1.5 / 3.7
242
314
1.5 / 3.3
202
261
1.5 / 3.0
171
220
1.5 / 3.0
146
186
1.5 / 3.0
125
159
1.5 / 3.0
95
117
1.5 / 3.0
73
89
1.5 / 3.0
58
68
1.5 / 3.0
46
53
1.5 / 3.0
1699
1899
23789
2661
3154
3153
3151
3149
3147
3142
4.0 / 10.1 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1868
3.8 / 9.5
1014
1297
3.3 / 8.3
773
1023
2.9 / 7.2
603
795
2.4 / 6.1
479
629
2.1 / 5.2
386
506
1.8 / 4.6
316
412
1.6 / 4.0
262
340
1.5 / 3.5
219
283
1.5 / 3.1
185
238
1.5 / 3.0
158
202
1.5 / 3.0
136
172
1.5 / 3.0
102
128
1.5 / 3.0
79
97
1.5 / 3.0
62
74
1.5 / 3.0
50
58
1.5 / 3.0
2292
4.7 / 11.6
1626
1750
4.5 / 11.1
1248
1475
4.1 / 10.3
977
1238
3.8 / 9.5
778
1027
3.4 / 8.5
629
829
3.0 / 7.4
516
677
2.6 / 6.5
428
560
2.3 / 5.8
359
468
2.1 / 5.1
304
395
1.8 / 4.6
259
335
1.7 / 4.2
223
287
1.5 / 3.8
169
214
1.5 / 3.1
130
164
1.5 / 3.0
103
127
1.5 / 3.0
83
100
1.5 / 3.0
2362
2360
2358
2356
2351
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1865
4.7 / 11.9
1451
1634
4.6 / 11.4
1137
1371
4.2 / 10.5
907
1167
3.9 / 9.7
735
969
3.5 / 8.7
603
793
3.0 / 7.6
501
656
2.7 / 6.7
420
549
2.4 / 6.0
356
463
2.2 / 5.4
304
394
1.9 / 4.9
262
338
1.8 / 4.4
198
253
1.5 / 3.7
153
193
1.5 / 3.1
121
150
1.5 / 3.0
97
118
1.5 / 3.0
1885
1884
1882
1876
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1713
1711
1709
1704
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1569
4.8 / 12.0
1441
1447
4.8 / 12.0
1171
1343
4.8 / 12.0
964
1194
4.6 / 11.4
803
1048
4.3 / 10.7
675
887
3.9 / 9.7
573
751
3.5 / 8.7
490
641
3.1 / 7.8
423
550
2.8 / 7.1
320
414
2.4 / 5.9
248
318
2.0 / 5.0
196
249
1.7 / 4.3
158
197
1.5 / 3.7
1567
1565
1560
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1446
1444
1438
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1341
1339
1334
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
1251
4.8 / 12.0
1171
1172
4.8 / 12.0
987
1102
4.8 / 12.0
840
1040
4.8 / 12.0
720
945
4.6 / 11.5
621
814
4.2 / 10.5
472
615
3.5 / 8.8
367
474
3.0 / 7.4
290
372
2.5 / 6.4
234
297
2.2 / 5.5
1249
1243
4.8 / 12.0 4.8 / 12.0
1170
1164
4.8 / 12.0 4.8 / 12.0
1100
1095
4.8 / 12.0 4.8 / 12.0
1038
1032
4.8 / 12.0 4.8 / 12.0
982
4.8 / 12.0
870
932
4.8 / 12.0
663
846
4.8 / 12.0
516
671
4.2 / 10.4
409
529
3.6 / 9.0
330
423
3.1 / 7.8
977
4.8 / 12.0
927
4.8 / 12.0
841
4.8 / 12.0
769
4.8 / 12.0
708
4.8 / 12.0
656
4.8 / 12.0
KEY TO TABLES
Live Load L/240 = Maximum live load limits deflection to L/240
Total Load = Maximum total load limits deflection to L/180
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
46
Span
(Ft)
68
88
108
118
128
138
148
158
168
178
188
198
208
228
248
268
288
9149
3859
3.9 / 9.8
2631
2715
3.7 / 9.2
1410
1850
3.1 / 7.8
1075
1421
2.7 / 6.6
838
1104
2.3 / 5.6
665
873
1.9 / 4.9
536
702
1.7 / 4.2
438
571
1.5 / 3.7
363
471
1.5 / 3.3
304
392
1.5 / 3.0
257
329
1.5 / 3.0
219
279
1.5 / 3.0
188
238
1.5 / 3.0
142
176
1.5 / 3.0
110
133
1.5 / 3.0
86
102
1.5 / 3.0
69
79
1.5 / 3.0
9129
1899
23789
9149
9129
3991
4730
4730
4727
4724
4721
4713
5146
5322
6308
4.0 / 10.1 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 3.9 / 9.8 4.0 / 10.1 4.8 / 12.0
3508
2802
3438
3543
3540
3537
3534
3526
3620
3736
4584
3.8 / 9.5 4.7 / 11.6 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 3.7 / 9.2 3.8 / 9.5 4.7 / 11.6
1521
2439
1880
2028
3252
1946
2625
2798
2828
2825
2822
2814
2466
2594
3500
3.3 / 8.3 4.5 / 11.1 4.7 / 11.9 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 3.1 / 7.8 3.3 / 8.3 4.5 / 11.1
1160
1871
2176
1434
1546
2496
1534
2212
2451
2569
2567
2564
2555
1894
2046
2950
2.9 / 7.2 4.1 / 10.3 4.6 / 11.4 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 2.7 / 6.6 2.9 / 7.2 4.1 / 10.3
904
1465
1706
1116
1206
1954
1193
1856
2057
2354
2351
2348
2340
1472
1590
2476
2.4 / 6.1 3.8 / 9.5 4.2 / 10.5 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 2.3 / 5.6 2.4 / 6.1 3.8 / 9.5
718
1167
1361
2161
886
958
1556
944
1540
1750
2171
2168
2165
2157
1164
1258
2054
2.1 / 5.2 3.4 / 8.5 3.9 / 9.7 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.9 / 4.9 2.1 / 5.2 3.4 / 8.5
579
944
1102
1757
714
772
1258
759
1243
1453
2015
2012
2009
2001
936
1012
1658
1.8 / 4.6 3.0 / 7.4 3.5 / 8.7 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.7 / 4.2 1.8 / 4.6 3.0 / 7.4
474
774
904
1446
584
632
1032
618
1016
1189
1791
1876
1873
1865
762
824
1354
1.6 / 4.0 2.6 / 6.5 3.0 / 7.6 4.6 / 11.4 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.7 1.6 / 4.0 2.6 / 6.5
392
642
751
1204
1757
484
524
856
510
840
985
1572
1758
1755
1746
628
680
1120
1.5 / 3.5 2.3 / 5.8 2.7 / 6.7 4.3 / 10.7 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.3 1.5 / 3.5 2.3 / 5.8
328
538
630
1013
1481
404
438
718
425
702
823
1331
1653
1650
1642
522
566
936
1.5 / 3.1 2.1 / 5.1 2.4 / 6.0 3.9 / 9.7 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.1 2.1 / 5.1
278
456
534
859
1259
342
370
608
357
592
695
1126
1560
1557
1549
440
476
790
1.5 / 3.0 1.8 / 4.6 2.2 / 5.4 3.5 / 8.7 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.8 / 4.6
237
389
456
735
1080
292
316
518
302
503
591
961
1417
1474
1465
372
404
670
1.5 / 3.0 1.7 / 4.2 1.9 / 4.9 3.1 / 7.8 4.6 / 11.5 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.7 / 4.2
203
335
392
634
932
1305
250
272
446
258
431
507
826
1220
1399
1391
318
344
574
1.5 / 3.0 1.5 / 3.8 1.8 / 4.4 2.8 / 7.1 4.2 / 10.5 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.8
154
253
297
480
708
994
190
204
338
191
322
379
621
922
1269
1261
234
256
428
1.5 / 3.0 1.5 / 3.1 1.5 / 3.7 2.4 / 5.9 3.5 / 8.8 4.8 / 12.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.1
119
196
230
372
550
774
146
158
260
145
245
290
477
711
1007
1153
178
194
328
1.5 / 3.0 1.5 / 3.0 1.5 / 3.1 2.0 / 5.0 3.0 / 7.4 4.2 / 10.4 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.0
94
154
181
294
436
614
116
124
206
111
190
225
373
559
793
1062
136
148
254
1.5 / 3.0 1.5 / 3.0 1.5 / 3.0 1.7 / 4.3 2.5 / 6.4 3.6 / 9.0 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.0
75
124
146
237
351
495
92
100
166
87
150
178
296
445
634
984
106
116
200
1.5 / 3.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.7 2.2 / 5.5 3.1 / 7.8 4.8 / 12.0 1.5 / 3.0 1.5 / 3.0 1.5 / 3.0
1899
23789
6306
6302
6298
6294
6284
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
4724
4720
4716
4712
4702
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3730
4.7 / 11.9
2902
3268
4.6 / 11.4
2274
2742
4.2 / 10.5
1814
2334
3.9 / 9.7
1470
1938
3.5 / 8.7
1206
1586
3.0 / 7.6
1002
1312
2.7 / 6.7
840
1098
2.4 / 6.0
712
926
2.2 / 5.4
608
788
1.9 / 4.9
524
676
1.8 / 4.4
396
506
1.5 / 3.7
306
386
1.5 / 3.1
242
300
1.5 / 3.0
194
236
1.5 / 3.0
3770
3768
3764
3752
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3426
3422
3418
3408
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
3138
4.8 / 12.0
2882
2894
4.8 / 12.0
2342
2686
4.8 / 12.0
1928
2388
4.6 / 11.4
1606
2096
4.3 / 10.7
1350
1774
3.9 / 9.7
1146
1502
3.5 / 8.7
980
1282
3.1 / 7.8
846
1100
2.8 / 7.1
640
828
2.4 / 5.9
496
636
2.0 / 5.0
392
498
1.7 / 4.3
316
394
1.5 / 3.7
3134
3130
3120
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2892
2888
2876
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2682
2678
2668
4.8 / 12.0 4.8 / 12.0 4.8 / 12.0
2502
4.8 / 12.0
2342
2344
4.8 / 12.0
1974
2204
4.8 / 12.0
1680
2080
4.8 / 12.0
1440
1890
4.6 / 11.5
1242
1628
4.2 / 10.5
944
1230
3.5 / 8.8
734
948
3.0 / 7.4
580
744
2.5 / 6.4
468
594
2.2 / 5.5
2498
2486
4.8 / 12.0 4.8 / 12.0
2340
2328
4.8 / 12.0 4.8 / 12.0
2200
2190
4.8 / 12.0 4.8 / 12.0
2076
2064
4.8 / 12.0 4.8 / 12.0
1964
4.8 / 12.0
1740
1864
4.8 / 12.0
1326
1692
4.8 / 12.0
1032
1342
4.2 / 10.4
818
1058
3.6 / 9.0
660
846
3.1 / 7.8
1954
4.8 / 12.0
1854
4.8 / 12.0
1682
4.8 / 12.0
1538
4.8 / 12.0
1416
4.8 / 12.0
1312
4.8 / 12.0
KEY TO TABLES
Live Load L/240 = Maximum live load limits deflection to L/240
Total Load = Maximum total load limits deflection to L/180
End / Int. Bearing = Required minimum end bearing (inches) for simple or multiple span beams and
minimum interior bearing (inches) for multiple span beams based on plate bearing
stress of 565 psi. See note 9 page 41.
47
Member Depth
2-Ply
3-Ply
4-Ply
71/49-11 7/8 9
149-23 7/8 9
1. See page 49 for diagrams corresponding to these fastening patterns. For top-loaded nailed multiple-piece members, nails can be 16d box, 16d sinkers, or
16d commons.
2. Stagger each row of fasteners by 12(.
3. Specified attachment is from each side.
4. United Steel Products WS series or Simpson Strong-Tie SDS series screws installed per manufacturers recommendations.
5. FastenMaster TrussLok screws installed per manufacturers recommendations. Do not overtighten screws in an attempt to countersink them.
Top-loaded conditions may result from I-joist details similar to F9, F10 and R3.
In details F9 and F10, the supporting wall may be replaced with properly sized multiple-piece GP Lam LVL.
48
1. Values for connections may be factored for spacings other than 12( o.c., double for 6( o.c., triple for 4( o.c., divide by 1.33 for 16( o.c., divide by 2 for 24( o.c.
(Maximum spacing not to exceed 24( o.c. for screws and bolts or 16( o.c. for nails.)
2. Stagger each row of fasteners by 12(.
3. Screws are United Steel Products WS Series or Simpson Strong-Tie SDS Series installed per manufacturers recommendations.
4. For 4-ply members, screws must be 6( long and applied from both sides.
5. Use FastenMaster TrussLok screws 3 38 ( long for 2-ply, 5( long for 3-ply, or 6 34( long for 4-ply. Connection values may be doubled for 12( on-center
spacing. Install per manufacturers recommendations. Do not overtighten screws in an attempt to countersink them.
49
7 149
2x6
2x4
9 149
or 9 129
2x6
2x4
11 149
or 11 789
2x6
2x4
149
169
189
23 789
2x6
2x6
2x6
2x6
3 29
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
1
4/12
6/12
Truss Slope
8/12
Doutside
Reaction
Doutside
Reaction
Doutside
Reaction
(lbs)
(inches)
(lbs)
(inches)
(lbs)
4790
OK
OK
OK
5238
5941
6151
OK
4515
5972
6921
7405
6803
8034
6114
7577
6114
6890
13
OK
OK
OK
OK
5910
6151
OK
OK
6115
7109
6921
7896
5136
7291
6921
8978
6921
9437
6867
9354
OK
OK
OK
OK
6128
OK
OK
OK
6921
7440
6921
OK
6921
8508
6921
9284
6921
10269
6921
10382
6921
8830
Doutside
Reaction
Doutside
Reaction
(inches)
(lbs)
(inches)
(lbs)
(inches)
3395
3967
4821
OK
3395
3783
4873
5576
4797
5185
4797
5185
4797
5185
4797
5185
4419
4779
OK
OK
3932
4877
5953
6144
3932
4514
5631
6699
5419
6001
5419
6001
5419
6001
15
3 16
3 1516
6 116
6 116
3 1516
3 1516
6 116
6 116
3 1516
3 1516
6 116
6 116
3 1516
3 1516
6 116
6 116
6 116
6 116
6 116
6 116
6 116
6 116
4 16
4 316
6 38
6 38
4 316
4 316
6 38
6 38
4 316
4 316
6 38
6 38
4 316
4 316
6 38
6 38
6 38
6 38
6 38
6 38
6 38
6 38
4 16
4 716
6 78
6 78
4 716
4 716
6 78
6 78
4 716
4 716
6 78
6 78
4 716
4 716
6 78
6 78
6 78
6 78
6 78
6 78
6 78
6 78
10/12
4 16
4 1316
7 14
7 14
4 1316
4 1316
7 716
7 716
4 1316
4 1316
7 716
7 716
4 1316
4 1316
7 716
7 716
7 716
7 716
7 716
7 716
7 716
7 716
12/12
5 16
5 316
7 14
7 14
5 316
5 316
8
8
5 316
5 316
8
8
5 316
5 316
8
8
8
8
8
8
8
8
NOTES:
1. Prior to using this chart, beam size must be checked by tables or FASTBeam software.
2. Chart can also be used for 134 9, 5 1 49 and 79 thick GP Lam LVL beams
For 1349 thick beam: 12 x allowable reaction (lbs)
For 5 149 thick beam: 112 x allowable reaction (lbs)
For 79 thick beam: 2 x allowable reaction (lbs)
3. Provide lateral support at bearing points, and continuous lateral support along top edge of beam.
4. Special consideration is required for uplift reactions.
5. Concentrated loads are not allowed in the tapered cut region.
6. Southern Pine bearing plate assumed. (Allowable bearing stress 565 psi).
Roof
slope
12
10. If no allowable reaction is shown, beam will not work with current input; try using
a shallower beam with additional plies.
Doutside (in.)
Beam
bearing
length
50
Rafter
Size
2x6
7 14 9
2x8
2x6
9 14 9
or 9 12 9
2x8
2x10
2x6
2x8
11 14 9
or 11 78 9
2x10
2x12
2x8
149
2x10
2x12
2x8
169
2x10
2x12
2x8
189
2x10
2x12
2x8
2x10
23 789
2x12
Beam Bearing
Length
1
3 29
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
3 129
5 149
4/12
6/12
Rafter Slope
8/12
D outside
Reaction
D outside
Reaction
D outside
Reaction
(inches)
(lbs)
(inches)
(lbs)
(inches)
4095
4095
OK
OK
3855
3855
5416
5416
OK
OK
3855
3855
5082
5082
6921
6973
6921
7897
5082
5082
6484
6484
6921
8539
5082
5082
6484
6484
6921
7886
5082
6484
6484
6921
7886
6484
6484
6921
7886
4559
4559
OK
OK
4089
4089
5936
5936
OK
OK
4089
5566
5566
6921
7375
OK
OK
5390
5390
6921
7589
6921
9096
5390
5390
6877
6877
6921
9402
5390
6877
6877
6921
8861
6877
6921
8364
4 8
4 116
6 12
5 78
4 58
4 116
6 12
5 78
8 916
8
4 58
4 116
6 12
5 78
8 916
8
10 1116
10 18
6 12
5 78
8 916
8
10 1116
10 18
6 12
5 78
8 916
8
10 1116
10 18
6 12
5 78
8 916
8
10 1116
10 18
6 12
5 78
8 916
8
10 1116
10 18
4 8
3 12
6 38
5 12
4 38
3 12
6 38
5 12
8 916
7 1116
4 38
3 12
6 38
5 12
8 916
7 1116
10 1316
9 1516
6 38
5 12
8 916
7 1116
10 1316
9 1516
6 38
5 12
8 916
7 1116
10 1316
9 1516
6 38
5 12
8 916
7 1116
10 1316
9 1516
6 38
5 12
8 916
7 1116
10 1316
9 1516
4 4
3 18
6 38
5 316
4 14
3 18
6 38
5 316
8 1316
7 58
4 14
3 18
6 38
5 316
8 1316
7 58
11 316
10
6 38
5 316
8 1316
7 58
11 316
10
6 38
5 316
8 1316
7 58
11 316
10
6 38
5 316
8 1316
7 58
11 316
10
6 38
5 316
8 1316
7 58
11 316
10
10/12
12/12
D outside
Reaction
D outside
Reaction
(lbs)
(inches)
(lbs)
(inches)
(lbs)
4759
4759
OK
OK
5057
6118
6118
OK
OK
4396
6745
6745
6921
7480
OK
OK
6111
6111
6921
8564
6921
9293
5794
6921
8501
6921
10187
5794
6921
7719
6921
10382
6921
6921
8991
4820
4820
OK
OK
5664
6317
6317
OK
OK
5418
6921
7203
OK
OK
OK
OK
6921
7550
6921
9056
OK
OK
6276
6921
9601
6921
10382
6276
6921
9616
6921
10382
6921
6921
10382
OK
OK
OK
OK
5966
OK
OK
OK
OK
6451
6921
7417
OK
OK
OK
OK
6921
8399
6921
9267
OK
OK
6921
6921
10207
6921
10382
6818
6921
10382
6921
10382
6921
6921
10382
4 4
2 1316
6 12
5 116
4 14
2 1316
6 12
5 116
9 18
7 1116
4 14
2 1316
6 12
5 116
9 18
7 1116
11 14
10 14
6 12
5 116
9 18
7 1116
11 34
10 14
6 12
5 116
9 18
7 1116
11 34
10 14
6 12
5 116
9 18
7 1116
11 34
10 14
6 12
5 116
9 18
7 1116
11 34
10 14
4 4
2 12
6 34
5
4 14
2 12
6 34
5
9 14
7 1316
4 14
2 12
6 34
5
9 916
7 1316
11 14
10 1116
6 34
5
9 916
13
7 16
12 716
10 1116
6 34
5
9 916
7 1316
12 716
10 1116
6 34
5
9 916
13
7 16
12 716
10 1116
6 34
5
9 916
7 1316
12 716
10 1116
NOTES:
1. Prior to using this chart, beam size must be checked by tables or FASTBeam software.
2. Chart can also be used for 13/49, 5 1/49 and 79 thick GP Lam LVL beams
Roof
slope
12
Rafter size
Ceiling joist
Doutside (in.)
Beam
bearing
length
51
Top Mount
PHXU17725
BPH17925
BPH1795
BPH17112
BPH17118
BPH1714
Capacity 100%
(lbs)
4155
3395
3395
3395
3395
3395
Face Mount
HD1770
THD179
THD179
THD179
THD179
THD179
Capacity 100%
(lbs)
1905
5170
5170
5170
5170
5170
LBH35925
LBH3595
LBH35112
LBH35118
HLBH3514
HLBH3516
HLBH3518
HLBH3524
6500
6500
6500
6500
10620
10620
10620
10620
THDH410
THDH410
THDH412
THDH412
THDH414
THDH414
THDH414
7910
7910
9475
9475
10990
10990
10990
HLBH52925
HLBH5295
HLBH52112
HLBH52118
HLBH5214
HLBH5216
HLBH5218
10620
10620
10620
10620
10620
10620
10620
THDH610
THDH610
THDH612
THDH612
THDH614
THDH614
THDH614
7840
7840
9475
9475
11105
11105
11105
HLBH71925
HLBH7195
HLBH71112
HLBH71118
HLBH7114
HLBH7116
HLBH7118
HLBH7124
10620
10620
10620
10620
10620
10620
10620
10620
THDH7210
THDH7210
THDH7212
THDH7212
THDH7214
THDH7214
THDH7214
7840
7840
9475
9475
11105
11105
11105
1. Capacity is for the stated duration of load100% floor loading. Hanger capacity depends on the hanger selected, quantity and size of nails used, and the size and type of support to
which it is fastened. Hanger capacities shown are based on attachment to LVL header material using the hanger manufacturers recommended nailing. Minimum header thickness is
3 12 (. Some hanger/header/fastener combinations may not meet maximum beam capacities and a qualified engineer should be consulted. Before selecting hangers, please refer to the
appropriate reference/design guide from the hanger manufacturer for expanded design information. Many other designs are available for specialized applications.
2. Hanger model numbers quoted are for United Steel Products Company, Inc. and Simpson Strong-Tie hangers. Some suppliers carry similar products produced by other manufacturers.
Contact your local building material retailer or BlueLinx for conversion information and details.
3. Special consideration is required with top mount hangers on nailers. Refer to the hanger manufacturers catalog for reduced capacity.
52
Capacity 100%
(lbs)
3635
3635
3635
3570
3635
3635
4700
6335
6335
6335
6335
6335
6335
6335
5100
4700
7500
10500
7500
10500
10500
10500
10500
Top Mount
WP1.81/7.25
WP9.25
WP9
LBV1.81/11.25
WP11
WP14
WPU3.56/7.25
HWU3.56/9.25
HWU3.56/9.5
HWU3.56/11.25
HWU3.56/11.88
HWU3.56/14
HWU3.56/16
HWU3.56/18
HWI424
WPU5.50/7.25
GLTV5.50/9.25
HGLTV5.59
GLTV5.50/11.25
HGLTV5.511
HGLTV5.514
HGLTV5.516
HGLTV5.518
Face Mount
HU7
HUS1.81/10
HUS1.81/10
HUS1.81/10
HUS1.81/10
HUS1.81/10
HGUS48
HGUS410
HGUS410
HGUS412
HGUS412
HGUS414
HGUS414
HGUS414
Capacity 100%
(lbs)
2145
4900
4900
4900
4900
4900
6805
7890
7890
9205
9205
9745
9745
9745
HGUS5.50/10
HGUS5.50/10
HGUS5.50/12
HGUS5.50/12
HGUS5.50/14
HGUS5.50/14
HGUS5.50/14
7890
7890
9205
9205
9745
9745
9745
GLTV49.25-2
HGLTV49.5-2
GLTV411.25-2
HGLTV411.88-2
HGLTV414-2
HGLTV416-2
HGLTV418-2
HGLTV7.12/24
7500
7500
7500
10500
10500
10500
10500
10500
HGUS7.25/10
HGUS7.25/10
HGUS7.25/12
HGUS7.25/12
HGUS7.25/14
HGUS7.25/14
HGUS7.25/14
7890
7890
9205
9205
9665
9665
9665
Capacity1
100% (lbs)
Total
Beam Width
Column 2
KCC44
15315
3 29
KCC46
24065
3 129
KCC48
24065
KCC64
4 x __Wood
3 89
79
49
6 x __Wood
5 129
119
6 129
3 129
8 x __Wood
7 129
119
6 129
37815
5 149
4 x __Wood
3 589
119
6 129
KCC66
37815
5 49
6 x __Wood
5 29
119
6 129
KCC68
37815
5 49
8 x __Wood
7 29
119
6 129
KCC84
60940
79
4 x __Wood
3 89
139
89
KCC86
60940
79
6 x __Wood
5 129
139
89
KCC88
60940
79
8 x __Wood
7 29
139
89
KLCC35-4
21000
3 129
49 dia. steel
11 129
49
KLCC525-4
21000
5 149
49 dia. steel
11 129
49
79
49 dia. steel
11 129
49
KLCC7-4
21000
KCC
KLCC
53
EI
(106 inch2 lbs)
7 14 9
9 14 9
9 129
11 14 9
11 789
149
169
189
23 789
111
231
250
415
488
800
1195
1701
3969
100%
3918
6208
6529
8985
9951
13581
17477
21831
37222
125%
3014
3845
3949
4676
4935
5819
6650
7481
9923
Weight
(lbs/ft)
3.4
4.3
4.4
5.2
5.5
6.5
7.4
8.4
11.1
a. Table assumes beam has lateral support at bearing points and continuous lateral support along the compression edge of the beam.
b. 13/49 x 169 and deeper beams must only be used in multiple-piece members.
E
G
Fb
Fv
Fc
Fc||
=
=
=
=
=
=
1/2 depth
1/2 depth
1/3 span
1/3 span
NOTES:
1. Hole(s) must be located at mid-depth and within the middle 1/3 span.
2. 19 maximum round hole diameter. No rectangular holes are allowed.
3. Use a minimum 89 spacing between holes and no more than three
holes per span.
4. Chart is valid for single and multiple span uniformly loaded beams
only. Chart is not valid for cantilever sections.
5. Minimum beam depth 7 1/49.
6. Hole location, clearance and the effects of beam deflection should
be considered to avoid problems with piping.
54
Part 2.0Products
2.1Prefabricated wood beams and headers:
A. Acceptable products:
1. Georgia-Pacific Corporation, GP Lam LVL floor
and roof beams.
2. Georgia-Pacific Corporation, GP Lam LVL window
and door headers.
B. Characteristics:
1. Construction:
1349 thick pressure bonded, lap-jointed wood veneers,
with grain of veneers running parallel in the long direction.
2. Beam depths:
71 49, 9149, 9129, 111 49, 117 8 9, 149, 169, 189 and 23 7 89 as
required for loading, deflection and span.
3. Beam length:
As required for span and bearing.
2.2Accessories:
A. Fasteners:
16d common nails, approved screws or 129 bolts.
B. Hangers:
1. Contact BlueLinx or an engineer for acceptable
connectors.
Part 3Execution
3.0General:
A. Provide GP Lam LVL beams and headers where indicated on
drawings using hangers and accessories specified.
B. Install GP Lam LVL beams and headers in accordance with
manufacturers recommendations.
3.2Accessories:
Install accessories where indicated and in accordance with
beam and header manufacturers instructions.
NOTE:
GP engineered lumber products may support mold growth if exposed to certain conditions, including moisture, dampness, condensation,
humidity, water or wet conditions. Mold, mildew, fungi, algae, moss, bacterial growth, decay, rot or similar conditions are not manufacturing or
product defects and Georgia-Pacific and BlueLinx assume no responsibility or liability for such conditions, regardless of cause.
The user is responsible for proper installation of GP engineered lumber products. The products must be installed in strict conformity with
Georgia-Pacifics instructions and all applicable building code requirements and other regulations. In addition, if not specifically covered by
Georgia-Pacifics installation instructions or construction detail illustrations, the products must be installed in accordance with generally
accepted design and construction practices. When installing engineered lumber products, the user should also consider the effects of local
climate and geography. Georgia-Pacific and BlueLinx do not warrant and are not responsible for any finished structure or system that
GP engineered lumber products may be incorporated into or other building components that may be used with these products.
55
BlueLinx Corporation
4300 Wildwood Parkway
Atlanta, GA 30339
1-888-502-BLUE www.bluelinxco.com
* See manufacturers warranty for terms, conditions and limitations. To receive a copy of the manufacturers warranty call 1-888-502-BLUE.
SIMPSON STRONG-TIE is a registered trademark of Simpson Strong-Tie Company, Inc. USP STRUCTURAL CONNECTORS is a trademark of
United Steel Products Company. WOOD I BEAM, FIBERGUARD, PLYTANIUM and FASTSUITE are trademarks and the ENGINEERED LUMBER
logo, the WOOD I BEAM logo, FASTBEAM, FIBERSTRONG, GP LAM and TOUGH-PLY are registered trademarks of Georgia-Pacific Corporation.
TRUSSLOK is a trademark and FASTENMASTER is a registered trademark of Olympic Manufacturing Group, Inc. GEORGIA-PACIFIC, GP and
the GP symbol are trademarks of Georgia-Pacific Corporation and used under license or otherwise with permission. APA and STURD-I-FLOOR are
registered trademarks of APA The Engineered Wood Association. BLUELINX and the BLUELINX design are trademarks and registered servicemarks of BlueLinx Corporation.
2006 Georgia-Pacific Corporation. All rights reserved. Printed in the U.S.A. 7/06 PDI Lit. Item #123040.