SHEET i OF i
30421007-3CL00010-P0D
13.8 kV MV CABLE
SIZING REPORT
DESIGN BASIS
FOR
13.8kV MV CABLE SIZING
DOCUMENT NO : 30421007-3CL-00010-P0D
MARCH 2005
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150
P0D
03.03.2005
P0C
15.12.2004
P0B
30.10.2004
P0A
28.08.2004
REV NO. DATE
276463800.xls
SECTION :cover sheeet
MP
SR
MP
SR
MP
SR
MP
SR
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
SHEET 1 OF 10
276463800.xls
SECTION :cover sheeet
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
SHEET 2 OF 10
CONTENTS
SECTION
DESCRIPTION
1.0
SCOPE
2.0
3.0
GENERAL PARAMETERS
4.0
SIZING CRITERIA
5.0
CONCLUSION
6.0
276463800.xls
SECTION :Index
SHEET 3 OF 10
276463800.xls
SECTION :Index
SHEET 4 OF 10
SCOPE
Scope of this report is to calculate the 13.8kV Cable size (8.7/15kV Grade) from Unit#7 Generator Circuit
Breaker or Unit#8 Generator Circuit Breaker to Unit Auxiliary Transformer of UAT 307 or UAT 308.
2.0
2.1
2.2
2.3
2.4
Key One Line Diagram for Arar Plant Drawing No: KA667481 REV P0E
2.5
2.6
3.0
GENERAL PARAMETERS
- Depth of Burried Cables
- Ground Temperature at a depth of 1 meter
- Average Thermal Soil resistivity
- Ambient air Temperature
- Short Circuit current
4.0
=
=
=
=
=
1 meter
35 Deg C
2 Deg C -m/w
50 Deg C
68.4 kA for 3 second
SIZING CRITERIA
The Power Cable size shall be selected on the basis of :
- Current Carrying Capacity.
- Permissible Voltage Drop.
- Short circuit Rating.
4.1
1250 kVA
=
3 x 13.8 kV
= 52.3 Amps
However, as per the Data Schedule of 13.8kV cable of PTS-1022, the minimum size of
1C x 630 Sqmm/Phase Cu, XLPE Unarmoured cable size has been selected.
According to SAUDI CABLE COMPANY Catalogues for Medium Voltage Cables page 61 of section-6
the nominal current carrying capacities for 1Cx630Sqmm Unarmoured cables are,
276463800.xls
SECTION :Notes and Sizing Cal
Current Carrying
capacity in Amps for 1C
x 630
Sqmm
665
SHEET 5 OF 10
720
Current Carrying
capacity in Amps for 1C
x 630
Sqmm
980
965
276463800.xls
SECTION :Notes and Sizing Cal
SHEET 6 OF 10
The following Derating factors have been considered as per SAUDI CABLE COMPANY Catalogues
for the site conditions specified:
Derating factor Kd for Cable Laid in Duct ways :(for both Flat/trefoil formation)
of Section- 6
- Ground Temperature 35 DegC
K1
=
0.95
Page 69
medium voltage
- Thermal Resistivity of soil 2.0Deg C-m/W K2
=
0.84
Page 70
cables of Saudi
- Depth of Laying 1m
K3
=
0.98
Page 69
cable company
- Group Rating Factor
K4
=
0.80
Page 71
catalogues.
-according to:
- installation system = spacing between two adjacent(center line to center line) ducts equal 0.3m
- No of ducts in ground = 3
Derating Factor Kd
Kd
=
=
K1 x K2 x K3 x K4
0.6256
Derating factor Ka for Cable installed in free air:(for both Flat/trefoil formation)
K5
0.89
0.86
Derating Factor Ka
Ka
=
=
K5 x K6
0.7654
According to the above, the maximum current carrying capacity of the selected 1C x 630Sqmm/phase
cable as follows
Maximum current carrying capacity of Cable Laid in Duct ways(after considering derating factor)
Laying cable in flat formation, current
=
Laying cable in trefoil formation, current =
665 x Kd =
720 x Kd =
416.02 Amps
450.43 Amps
=
=
980 x Ka =
965 x Ka =
750.09 Amps
738.61 Amps
As per above calculation, 1C x 630 Sqmm/Phase cable can carry the required load current of 52.3Amps
under all site conditions.
4.2
VOLTAGE DROP SIZING : From drg no KA-667496 REV P0A, cable length = 30m. Add 10m at each
end, also add another 12m, so total length = 52m.
The Voltage drop check is calculated as follows :
=
V%
3 x(RCOS + XSIN) x I x L x 100 /Un for three phase system
Where,
=
Power Factor
= 0.8
COS
SIN
0.6
26.15
L
Un
Length in Km
0.052
Cable Voltage in V
13800
276463800.xls
SECTION :Notes and Sizing Cal
SHEET 7 OF 10
276463800.xls
SECTION :Notes and Sizing Cal
SHEET 8 OF 10
51.65
kA
The selected 1R x 1C x 630Sqmm/Phase cable size can withstand upto 51.65kA for 3 seconds only.
Whereas, the maximum short circuit current is 68.4kA for 3 seconds.
Therefore, 2R x 1C x 630Sqmm/Phase cable size has been selected for short circuit current carrying
capacity
142 x 2 x 630
I =
3
I
103.30
kA
The selected 2Rx1Cx630Sqmm/Phase cable size can withstand upto 103.3kA for 3 seconds. Whereas, the
maximum short circuit current is 68.4kA for 3 seconds only.
5.0
CONCLUSION
From Unit#7 Generator Circuit Breaker or Unit#8 Generator Circuit Breaker to
Unit Auxiliary Transformer UAT 307 or UAT 308
8.7/15kV Grade, XLPE insulated, Copper Conductor of size 2R x 1C x 630 Sqmm/Phase,
Unarmoured cable has been selected based on the above calculations.
276463800.xls
SECTION :Notes and Sizing Cal
SHEET 9 OF 10
FEEDER DESCRIPTION
LOAD
VOLTAGE
kVA
VOLTS
FULL
LOAD
CURRENT CARRYING CAPACITY OF CABLE (SINGLE
CABLE SIZE SELECTED
CURRENT
RUN)
IFL
AMPS
SQ.MM
IN DUCT
BANKS
1250
13800
276463800.xls
SECTION :Cable Sizing Report Summary
52.30
IN AIR
2 RUN OF 2 RUN OF
1C X 630
1C X
/Phase
630 /Phase
DERATING FACTOR
CABLE LAID IN AIR(CABLE CABLE LAID IN DUCT CABLE LAID IN AIRCABLE LAID IN DUCT
CABLE LAID IN AIR(CABLE
BANKS
CABLE TRAYS
TRAY)
BANKS
TRAY)
(IN BOTH
(IN
FLAT/TREFOIL
BOTH FLAT/TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
IN FLAT
IN TREFOIL
FORMATION)
FORMATION)
FORMATION FORMATION FORMATION FORMATION
FORMATION FORMATION FORMATION FORMATION
CABLE LAID IN DUCT
BANKS
665.00
720.00
980.00
965.00
0.6256
0.7654
416.02
450.43
750.09
738.61
LENGTH
OF
CABLE
% VOLTAGE
DROP
KM
0.052
0.002
SHEET 10 OF 10