Department Of Electrical And Electronics Engineering

EE2402 -PROTECTION AND SWITCHGEAR

UNIT I

INTRODUCTION

UNIT II

OPERATING PRINCIPLES AND RELAY CHARACTERISTICS

UNIT III

APPARATUS PROTECTION

UNIT IV

THEORY OF CIRCUIT INTERRUPTION

UNIT V

CIRCUIT BREAKERS

AIM:
To introduce the students to the various abnormal operating conditions in power system and
describe the apparatus and system protection schemes. Also to describe the phenomena of current interruption to study the
various switchgears.
OBJECTIVES:
i. To discuss the causes of abnormal operating conditions (faults, lightning and switching
surges) of the apparatus and system.
ii. To understand the characteristics and functions of relays and protection schemes.
iii. To understand the problems associated with circuit interruption by a circuit breaker.
UNIT I
INTRODUCTION
9
Importance of protective schemes for electrical apparatus and power system. Qualitative review of faults and fault
currents - relay terminology definitions - and essential qualities of protection. Protection against over voltages due to
lightning and switching - arcing grounds - Peterson Coil - ground wires - surge absorber and diverters
Power System earthing neutral Earthing - basic ideas of insulation coordination.
UNIT II
OPERATING PRINCIPLES AND RELAY CHARACTERISTICS
9
Electromagnetic relays over current, directional and non-directional, distance, negative sequence, differential and under
frequency relays Introduction to static relays.
UNIT III
APPARATUS PROTECTION
9
Main considerations in apparatus protection - transformer, generator and motor protection protection of bus bars. Transmission line protection - zones of protection. CTs and PTs and their applications in protection
schemes.
UNIT IV
THEORY OF CIRCUIT INTERRUPTION
9
Physics of arc phenomena and arc interruption. DC and AC circuit breaking - restriking voltage and recovery voltage rate of rise of recovery voltage - resistance switching - current chopping - interruption of capacitive current.
UNIT V
CIRCUIT BREAKERS
9
Types of circuit breakers air blast, air break, oil, SF6 and vacuum circuit breakers comparative merits of different
circuit breakers testing of circuit breakers.
TOTAL : 45 PERIODS
TEXT BOOKS:
1. M.L. Soni, P.V. Gupta, V.S. Bhatnagar, A. Chakrabarti, A Text Book on Power System
Engineering, Dhanpat Rai & Co., 1998. (For All Chapters 1, 2, 3, 4 and 5).
2. R.K.Rajput, A Tex book of Power System Engineering. Laxmi Publications, First
Edition Reprint 2007.
REFERENCES:
1. Sunil S. Rao, Switchgear and Protection, Khanna publishers, New Delhi, 1986.
2. C.L. Wadhwa, Electrical Power Systems, Newage International (P) Ltd., 2000.
3. B. Ravindranath, and N. Chander, Power System Protection & Switchgear, Wiley Eastern Ltd.,1977.
4. Badri Ram, Vishwakarma, Power System Protection and Switchgear, Tata McGraw Hill, 2001.
5. Y.G. Paithankar and S.R. Bhide, Fundamentals of Power System Protection, Prentice Hall of India Pvt. Ltd., New
Delhi110001, 2003.

UNIT I

INTRODUCTION

Importance of protective schemes for electrical apparatus and power system. Qualitative review of faults and
fault currents - relay terminology definitions - and essential qualities of protection. Protection against over
2

voltages due to lightning and switching - arcing grounds - Peterson Coil - ground wires - surge absorber and
diverters Power System earthing neutral Earthing - basic ideas of insulation coordination.
1] Discuss and compare the various methods of neutral earthing.
[Any two type may ask each carries 8marks or brief all the five divisions]
[16]
Types of Neutral Earthing in Power Distribution:
Introduction:
In the early power systems were mainly Neutral ungrounded due to the fact that the first ground fault did
not require the tripping of the system. An unscheduled shutdown on the first ground fault was particularly
undesirable for continuous process industries. These power systems required ground detection systems, but
locating the fault often proved difficult. Although achieving the initial goal, the ungrounded system provided no
control of transient over-voltages.
A capacitive coupling exists between the system conductors and ground in a typical distribution system.
As a result, this series resonant L-C circuit can create over-voltages well in excess of line-to-line voltage when
subjected to repetitive re-strikes of one phase to ground. This in turn, reduces insulation life resulting in
possible equipment failure.
Neutral grounding systems are similar to fuses in that they do nothing until something in the system
goes wrong. Then, like fuses, they protect personnel and equipment from damage. Damage comes from
two factors, how long the fault lasts and how large the fault current is. Ground relays trip breakers and limit
how long a fault lasts and Neutral grounding resistors limit how large the fault current is.
Importance of Neutral Grounding:
[seven points alone 2marks]
There are many neutral grounding options available for both Low and Medium voltage power systems. The
neutral points of transformers, generators and rotating machinery to the earth ground network provides a
reference point of zero volts. This protective measure offers many advantages over an ungrounded system, like,
1. Reduced magnitude of transient over voltages
2. Simplified ground fault location
3. Improved system and equipment fault protection
4. Reduced maintenance time and expense
5. Greater safety for personnel
6. Improved lightning protection
7. Reduction in frequency of faults.
Method of Neutral Earthing:
There are five methods for Neutral earthing.
1. Unearthed Neutral System
2. Solid Neutral Earthed System.
3. Resistance Neutral Earthing System.
1. Low Resistance Earthing.
2. High Resistance Earthing.
4. Resonant Neutral Earthing System.
5. Earthing Transformer Earthing.
(1) Ungrounded Neutral Systems:

In ungrounded system there is no internal connection between the conductors and earth. However, as
system, a capacitive coupling exists between the system conductors and the adjacent grounded surfaces.
Consequently, the ungrounded system is, in reality, a capacitive grounded system by virtue of the
distributed capacitance.
Under normal operating conditions, this distributed capacitance causes no problems. In fact, it is
beneficial because it establishes, in effect, a neutral point for the system; As a result, the phase
conductors are stressed at only line-to-neutral voltage above ground.
But problems can rise in ground fault conditions. A ground fault on one line results in full line-to-line
voltage appearing throughout the system. Thus, a voltage 1.73 times the normal voltage is present on all
3

insulation in the system. This situation can often cause failures in older motors and transformers, due to
insulation breakdown.

Advantage:
1. After the first ground fault, assuming it remains as a single fault, the circuit may continue in operation,
permitting continued production until a convenient shut down for maintenance can be scheduled.
Disadvantages:
1. The interaction between the faulted system and its distributed capacitance may cause transient overvoltages (several times normal) to appear from line to ground during normal switching of a circuit
having a line-to ground fault (short). These over voltages may cause insulation failures at points other
than the original fault.
2. A second fault on another phase may occur before the first fault can be cleared. This can result in very
high line-to-line fault currents, equipment damage and disruption of both circuits.
3. The cost of equipment damage.
4. Complicate for locating fault(s), involving a tedious process of trial and error: first isolating the correct
feeder, then the branch, and finally, the equipment at fault. The result is unnecessarily lengthy and
expensive down downtime.
(2) Solidly Neutral Grounded Systems:
Solidly grounded systems are usually used in low voltage applications at 600 volts or less.

In solidly grounded system, the neutral point is connected to earth.


Solidly Neutral Grounding slightly reduces the problem of transient over voltages found on the
ungrounded system and provided path for the ground fault current is in the range of 25 to 100% of the
system three phase fault current. However, if the reactance of the generator or transformer is too great,
the problem of transient over voltages will not be solved.
While solidly grounded systems are an improvement over ungrounded systems, and speed up the
location of faults, they lack the current limiting ability of resistance grounding and the extra protection
this provides.
To maintain systems health and safe, Transformer neutral is grounded and grounding conductor must be
extend from the source to the furthest point of the system within the same raceway or conduit. Its
purpose is to maintain very low impedance to ground faults so that a relatively high fault current will
flow thus insuring that circuit breakers or fuses will clear the fault quickly and therefore minimize
4

damage. It also greatly reduces the shock hazard to personnel

1.

1.
2.
3.

If the system is not solidly grounded, the neutral point of the system would float with respect to
ground as a function of load subjecting the line-to-neutral loads to voltage unbalances and instability.
The single-phase earth fault current in a solidly earthed system may exceed the three phase fault current.
The magnitude of the current depends on the fault location and the fault resistance. One way to reduce
the earth fault current is to leave some of the transformer neutrals unearthed.
Advantage:
The main advantage of solidly earthed systems is low over voltages, which makes the earthing design
common at high voltage levels (HV).
Disadvantage:
This system involves all the drawbacks and hazards of high earth fault current: maximum damage and
disturbances.
There is no service continuity on the faulty feeder.
The danger for personnel is high during the fault since the touch voltages created are high.

Applications:
1. Distributed neutral conductor.
2. 3-phase + neutral distribution.
3. Used when the short-circuit power of the source is low.
3) Resistance earthed systems:
Resistance grounding has been used in three-phase industrial applications for many years and it resolves
many of the problems associated with solidly grounded and ungrounded systems.
Resistance Grounding Systems limits the phase-to-ground fault currents. The reasons for limiting the
Phase to ground Fault current by resistance grounding are:
1. To reduce burning and melting effects in faulted electrical equipment like switchgear, transformers,
5

2.
3.
4.
5.
6.
7.

cables, and rotating machines.


To reduce mechanical stresses in circuits/Equipments carrying fault currents.
To reduce electrical-shock hazards to personnel caused by stray ground fault.
To reduce the arc blast or flash hazard.
To reduce the momentary line-voltage dip.
To secure control of the transient over-voltages while at the same time.
To improve the detection of the earth fault in a power system.

Grounding Resistors are generally connected between ground and neutral of transformers, generators
and grounding transformers to limit maximum fault current as per Ohms Law to a value which will not
damage the equipment in the power system and allow sufficient flow of fault current to detect and
operate Earth protective relays to clear the fault.
Therefore, it is the most common application to limit single phase fault currents with low resistance
Neutral Grounding Resistors to approximately rated current of transformer and / or generator.
In addition, limiting fault currents to predetermined maximum values permits the designer to selectively
coordinate the operation of protective devices, which minimizes system disruption and allows for quick
location of the fault.
There are two categories of resistance grounding:
(1) Low resistance Grounding. (2) High resistance Grounding.

Ground fault current flowing through either type of resistor when a single phase faults to ground will
increase the phase-to-ground voltage of the remaining two phases. As a result, conductor insulation and
surge arrestor ratings must be based on line-to-line voltage. This temporary increase in phase-toground voltage should also be considered when selecting two and three pole breakers installed on

resistance grounded low voltage systems.

Neither of these grounding systems (low or high resistance) reduces arc-flash hazards associated with
phase-to-phase faults, but both systems significantly reduce or essentially eliminate the arc-flash hazards
associated with phase-to-ground faults. Both types of grounding systems limit mechanical stresses and
reduce thermal damage to electrical equipment, circuits, and apparatus carrying faulted current.
The difference between Low Resistance Grounding and High Resistance Grounding is a matter of
perception and, therefore, is not well defined. Generally speaking high-resistance grounding refers to a
system in which the NGR let-through current is less than 50 to 100 A. Low resistance grounding
indicates that NGR current would be above 100 A.
A better distinction between the two levels might be alarm only and tripping. An alarm-only system
continues to operate with a single ground fault on the system for an unspecified amount of time. In a
tripping system a ground fault is automatically removed by protective relaying and circuit interrupting
devices. Alarm-only systems usually limit NGR current to 10 A or less.
6

Rating of The Neutral grounding resistor:


1.
2.
3.

Voltage: Line-to-neutral voltage of the system to which it is connected.


Initial Current: The initial current which will flow through the resistor with rated voltage applied.
Time: The on time for which the resistor can operate without exceeding the allowable temperature
rise.

(A).Low Resistance Grounded:

Low Resistance Grounding is used for large electrical systems where there is a high investment in
capital equipment or prolonged loss of service of equipment has a significant economic impact and it is
not commonly used in low voltage systems because the limited ground fault current is too low to
reliably operate breaker trip units or fuses. This makes system selectivity hard to achieve. Moreover, low
resistance grounded systems are not suitable for 4-wire loads and hence have not been used in
commercial market applications
A resistor is connected from the system neutral point to ground and generally sized to permit only 200A
to 1200 amps of ground fault current to flow. Enough current must flow such that protective devices can
fault point.

Since the grounding impedance is in the form of resistance, any transient over voltages are quickly
damped out and the whole transient overvoltage phenomena is no longer applicable. Although
theoretically possible to be applied in low voltage systems (e.g. 480V),significant amount of the system
voltage dropped across the grounding resistor, there is not enough voltage across the arc forcing current
to flow, for the fault to be reliably detected. For this reason, low resistance grounding is not used for
low voltage systems (under 1000 volts line to-line).

Advantages:
1. Limits phase-to-ground currents to 200-400A.
2. Reduces arcing current and, to some extent, limits arc-flash hazards associated with phase-to-ground
arcing current conditions only.
3. May limit the mechanical damage and thermal damage to shorted transformer and rotating machinery
windings.
Disadvantages:
1.
2.
3.
4.

Does not prevent operation of over current devices.


Does not require a ground fault detection system.
May be utilized on medium or high voltage systems.
Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral
loads must be served through an isolation transformer.

Used: Up to 400 amps for 10 sec are commonly found on medium voltage systems.

(B).High Resistance Grounded:

High resistance grounding is almost identical to low resistance grounding except that the ground fault
current magnitude is typically limited to 10 amperes or less. High resistance grounding accomplishes
7

two things.
The first is that the ground fault current magnitude is sufficiently low enough such that no appreciable
damage is done at the fault point. This means that the faulted circuit need not be tripped off-line when
the fault first occurs. Means that once a fault does occur, we do not know where the fault is located. In
this respect, it performs just like an ungrounded system.
The second point is it can control the transient overvoltage phenomenon present on ungrounded
systems if engineered properly.
Under earth fault conditions, the resistance must dominate over the system charging capacitance but not
to the point of permitting excessive current to flow and thereby excluding continuous operation

High Resistance Grounding (HRG) systems limit the fault current when one phase of the system shorts
or arcs to ground, but at lower levels than low resistance systems.
In the event that a ground fault condition exists, the HRG typically limits the current to 5-10A.
HRGs are continuous current rated, so the description of a particular unit does not include a time rating.
Unlike NGRs, ground fault current flowing through a HRG is usually not of significant magnitude to
result in the operation of an over current device. Since the ground fault current is not interrupted, a
ground fault detection system must be installed.
These systems include a bypass contactor tapped across a portion of the resistor that pulses (periodically
opens and closes). When the contactor is open, ground fault current flows through the entire resistor.
When the contactor is closed a portion of the resistor is bypassed resulting in slightly lower resistance
and slightly higher ground fault current.
To avoid transient over-voltages, an HRG resistor must be sized so that the amount of ground
fault current the unit will allow to flow exceeds the electrical systems charging current. As a rule of
thumb, charging current is estimated at 1A per 2000KVA of system capacity for low voltage systems
and 2A per 2000KVA of system capacity at 4.16kV.
These estimated charging currents increase if surge suppressors are present. Each set of suppressors
installed on a low voltage system results in approximately 0.5A of additional charging current and each
set of suppressors installed on a 4.16kV system adds 1.5A of additional charging current.
A system with 3000KVA of capacity at 480 volts would have an estimated charging current of
1.5A.Add one set of surge suppressors and the total charging current increases by 0.5A to 2.0A. A
standard 5A resistor could be used on this system. Most resistor manufacturers publish detailed
estimation tables that can be used to more closely estimate an electrical systems charging current.

Advantages:
1. Enables high impedance fault detection in systems with weak capacitive connection to earth
2. Some phase-to-earth faults are self-cleared.
3. The neutral point resistance can be chosen to limit the possible over voltage transients to 2.5 times the
8

fundamental frequency maximum voltage.


4. Limits phase-to-ground currents to 5-10A.
5. Reduces arcing current and essentially eliminates arc-flash hazards associated with phase-to-ground
arcing current conditions only.
6. Will eliminate the mechanical damage and may limit thermal damage to shorted transformer and
rotating machinery windings.
7. Prevents operation of over current devices until the fault can be located (when only one phase faults to
ground).
8. May be utilized on low voltage systems or medium voltage systems up to 5kV. IEEE Standard 141-1993
states that high resistance grounding should be restricted to 5kV class or lower systems with charging
currents of about 5.5A or less and should not be attempted on 15kV systems, unless proper grounding
relaying is employed.
9. Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral
loads must be served through an isolation transformer.
Disadvantages:
1. Generates extensive earth fault currents when combined with strong or moderate capacitive connection
to earth Cost involved.
2. Requires a ground fault detection system to notify the facility engineer that a ground fault condition has
occurred.
(4) Resonant earthed system:

Adding inductive reactance from the system neutral point to ground is an easy method of limiting the
available ground fault from something near the maximum 3 phase short circuit capacity (thousands of
amperes) to a relatively low value (200 to 800 amperes).
To limit the reactive part of the earth fault current in a power system a neutral point reactor can be
connected between the transformer neutral and the station earthing system.
A system in which at least one of the neutrals is connected to earth through an

1. Inductive reactance.
2. Petersen coil / Arc Suppression Coil / Earth Fault Neutralizer.

The current generated by the reactance during an earth fault approximately compensates the capacitive
component of the single phase earth fault current, is called a resonant earthed system.
The system is hardly ever exactly tuned, i.e. the reactive current does not exactly equal the capacitive
earth fault current of the system.
A system in which the inductive current is slightly larger than the capacitive earth fault current is over
compensated. A system in which the induced earth fault current is slightly smaller than the
capacitiveearth fault current is under compensated
However, experience indicated that this inductive reactance to ground resonates with the system shunt
capacitance to ground under arcing ground fault conditions and creates very high transient over voltages
on the system.
To control the transient over voltages, the design must permit at least 60% of the 3 phase short circuit
current to flow underground fault conditions.
Example. A 6000 amp grounding reactor for a system having 10,000 amps 3 phase short circuit capacity
available. Due to the high magnitude of ground fault current required to control transient over voltages,
inductance grounding is rarely used within industry.
9

Petersen Coils:

A Petersen Coil is connected between the neutral point of the system and earth, and is rated so that the
capacitive current in the earth fault is compensated by an inductive current passed by the Petersen
Coil. A small residual current will remain, but this is so small that any arc between the faulted phase and
earth will not be maintained and the fault will extinguish. Minor earth faults such as a broken pin
insulator, could be held on the system without the supply being interrupted. Transient faults would not
result in supply interruptions.
Although the standard Peterson coil does not compensate the entire earth fault current in a network due
to the presence of resistive losses in the lines and coil, it is now possible to apply residual current
compensation by injecting an additional 180 out of phase current into the neutral via the Peterson coil.
The fault current is thereby reduced to practically zero. Such systems are known as Resonant earthing
with residual compensation, and can be considered as a special case of reactive earthing.
Resonant earthing can reduce EPR to a safe level. This is because the Petersen coil can often effectively
act as a high impedance NER, which will substantially reduce any earth fault currents, and hence also
any corresponding EPR hazards (e.g. touch voltages, step voltages and transferred voltages, including
any EPR hazards impressed onto nearby telecommunication networks).

Advantages:
1. Small reactive earth fault current independent of the phase to earth capacitance of the system.
2. Enables high impedance fault detection.
Disadvantages:
1. Risk of extensive active earth fault losses.
2. High costs associated.

(5) Earthing Transformers:


For cases where there is no neutral point available for Neutral Earthing (e.g. for a delta winding), an earthing
transformer may be used to provide a return path for single phase fault currents

1
0

In such cases the impedance of the earthing transformer may be sufficient to act as effective earthing
impedance. Additional impedance can be added in series if required. A special zig-zag transformer is
sometimes used for earthing delta windings to provide a low zero-sequence impedance and high positive
and negative sequence impedance to fault currents.

Conclusion:
Resistance Grounding Systems have many advantages over solidly grounded systems including arc-flash hazard
reduction, limiting mechanical and thermal damage associated with faults, and controlling transient over
voltages.

High resistance grounding systems may also be employed to maintain service continuity and assist with
locating the source of a fault.
When designing a system with resistors, the design/consulting engineer must consider the specific
requirements for conductor insulation ratings, surge arrestor ratings, breaker single-pole duty ratings,
and method of serving phase-to-neutral loads.

2] Discuss the essential qualities of protective relaying.

16

Protective Relaying (Part11)


A protective relaying scheme should have certain important qualities. Such an essential qualities of
protective relaying are,
1. Reliability
2. Selectivity and Discrimination
3. Speed and Time
4. Sensitivity
5. Stability
6. Adequateness
7. Simplicity and Economy

1
1

1.1 Reliability
A protective relaying should be reliable is its basic quality. It indicates the ability of the relay system to
operate under the predetermined conditions. There are various components which go into the operation before a
relay operates. Therefore every component and circuit which is involved in the operation of a relay plays an
important role. The reliability of a protection system depends on the reliability of various components like
circuit breakers, relays, current transformers (C.T.s), potential transformers (P.T.s), cables, trip circuits etc. The
proper maintenance also plays an important role in improving the reliable operation of the system. The
reliability can not be expressed in the mathematical expressions but can be adjusted from the statistical data.
The statistical survey and records give good idea about the reliability of the protective system. The inherent
reliability is based on the design which is based on the long experience. This can be achieved by the factors like,
i) Simplicity
ii) Robustness
iii) High contact pressure
iv) Dust free enclosure
iv) Good contact material
vi) Good workmanship and
vii) Careful Maintenance
1.2 Selectivity and Discrimination
The selectivity id the ability of the protective system to identify the faulty part correctly and disconnect that
part without affecting the rest of the healthy part of system. The discrimination means to distinguish between.
The discrimination quality of the protective system is the ability to distinguish between normal condition and
abnormal condition and also between abnormal condition within protective zone and elsewhere. The protective
system should operate only at the time of abnormal condition and not at the time of normal condition. Hence it
must clearly discriminate between normal and abnormal condition. Thus the protective system should select the
fault part and disconnect only the faulty part without disturbing the healthy part of the system.
The protective system should not operate for the faults beyond its protective zone. For example, consider
the portion of a typical power system shown in the Fig. 1.

Fig. 1
It is clear from the Fig. 1 that if fault F2 occurs on transmission line then the circuit breakers 2 and 3 should
operate and disconnect the line from the remaining system. The protective system should be selective in
selecting faulty transmission line only for the fault and it should isolate it without tripping the adjacent
transmission line breakers or the transformer.
If the protective system is not selective then it operates for the fault beyond its protective zones and
unnecessary the large part of the system gets isolated. This causes a lot of inconvenience to the supplier and
users.
1.3 Speed and Time
a protective system must disconnect the faulty system as fast as possible. If the faulty system is not
disconnect for a long time then,
1. The devices carrying fault currents may get damaged.
2. The failure leads to the reduction in system voltage. Such low voltage may affect the motors and generators
running on the consumer sude.
17

The total time required between the instant of fault and the instant of final arc interruption in the circuit
breaker is called fault clearing time. It is the sum of relay time and circuit breaker time. The relay time is the
time between the instant of fault occurrence and the instant of closure of relay contacts. The circuit breaker
times is the time taken by the circuit breaker to operate to open the contacts and to extinguish the arc
completely. The fault clearing time should be as small as possible to have high speed operation of the protective
system.
Though the small fault clearing time is preferred, in practice certain time lag is provided. This is because,
1. To have clear discrimination between primary and backup protection
2. To prevent unnecessary operation of relay under the conditions such as transient, starting inrush of current
etc.
Thus fast protective system is an important quality which minimises the damage and it improves the overall
stability of the power system.
1.4 Sensitivity
The protective system should be sufficiently sensitive so that it can operate reliably when required. The
sensitivity of the system is the ability of the relay system to operate with low value of actuating quantity.
It indicates the smallest value of the actuating quantity at which the protection starts operating in relation
with the minimum value of the fault current in the protected zone.
The relay sensitivity is the function of the volt-amperes input to the relay coil necessary to cause its
operation. Smaller the value of volt-ampere input, more sensitive is the relay. Thus 1 VA input relay is more
sensitive than the 5VA input relay.
Mathematically the sensitivity is expressed by a factor called sensitivity factor . It is the ratio of minimum
short circuit current in the protected zone to the minimum operating current required for the protection to start.
Ks = Is/Io
where Ks = sensitivity factor
Is = minimum short circuit current in the zone
Io= minimum operating current for the protection
1.5 Stability
The stability is the quality of the protective system due to which the system remains inoperative and stable
under certain specified conditions such as transients, disturbance, through faults etc. For providing the stability,
certain modifications are required in the system design. In most of the cases time delays, filter circuits,
mechanical and electrical bias are provided to achieve stable operation during the disturbances.
1.6 Adequateness
There are variety of faults and disturbance those may practically exists in a power system. It is impossible
to provide protection against each and every abnormal condition which may exist in practice, due to economical
reasons. But the protective system must provide adequate protection for any element of the system. The
adequateness of the system can be assessed by considering following factors,
1. Ratings of various equipments
2. Cost of the equipments
3. Locations of the equipments
4. Probability of abnormal condition due to internal and external causes.
5. Discontinuity of supply due to the failure of the equipment
1.7 Simplicity and Economy
In addition to all the important qualities, it is necessary that the cost of the system should be well within
limits. In practice sometimes it is not necessary to use ideal protection scheme which is economically
unjustified. In such cases compromise is done. As a rule, the protection cost should not be more than 5% of the
total cost. But if the equipments to be protected are very important, the economic constrains can be relaxed.
18

The protective system should be as simple as possible so that it can be easily


maintained. The complex system are difficult from the maintenance point of view.
The simplicity and reliability are closely related to each other. The simpler system are
always more reliable.
3] Discuss the nature and causes of different faults in a power system.
(16)

Nature and causes of Faults: Any faults in electrical apparatus are nothing

but the defect in its electrical


circuit which makes current path directed from its intended path. Normally due to
breaking of conductors or failure of insulation, these faults occur. The other reasons for
occurrence of fault include mechanical failure, accidents. Excessive internal and
external stresses. The impedance of the path in the fault is low and the fault currents are
comparatively large. The induction of insulation is not considered as a fault until it
shows some effect sucj as excessive current flow or reduction of impedance between
conductors or between conductors and earth.
When a fault occurs on a system, the voltage of the three phases become unbalanced.
As the fault currents are large, the apparatus may get damaged. The flow of power is
diverted towards the fault which affects the supply to the neighboring zone.
A power system consists of generators, transformers, switchgear, transmission and
distribution circuits. There is always a possibility in such a large network that some fault
will occur in some part of the system. The maximum possibility of fault occurrence is on
the transmission lines due to their greater lengths and exposure to atmospheric
conditions.
The faults cannot be classified according to the causes of their incidence. The
breakdown may occur at normal voltage due to deterioration of insulation. The
breakdown may also occur due to damage on account of unpredictable causes which
include perching of birds, accidental short circuiting by snakes, kite strings, three
branches etc. The breakdown may occur at abnormal voltages due to switching surges
or surges caused by lighting.
4] List the types of faults in power system
Active Faults
The Active fault is when actual current flows from one phase conductor to another
(phase-to-phase) or alternatively from one phase conductor to
earth (phase-to-earth). This type of fault can also be further
classified into two areas, namely the solid fault and the
incipient fault.
Passive Faults
Passive faults are not real faults in the true sense of the word but are rather conditions
that are stressing the system beyond its design
19

capacity, so that ultimately


active faults will occur.
Typical examples are:
Overloading - leading to overheating of
insulation (deteriorating quality,
reduced life and ultimate failure).
under frequency - causing plant to behave
incorrectly.
Power swings - generators going out-of-step or synchronism with each other
Transient & Permanent Faults
Transient faults are faults which do not damage the insulation permanently and allow
the circuit to be safely re-energized after a short period of time. A typical example
would be an insulator flashover following a lightning strike, which would be
successfully cleared on opening of the circuit breaker, which could then be
automatically reclosed.
Transient faults occur mainly on outdoor equipment where air is the main insulating
medium.
Permanent faults, as the name implies, are the result of permanent damage to the
insulation. In this case, the equipment has to be repaired and reclosing must not be
entertained.
Symmetrical & Asymmetrical Faults
A symmetrical fault is a balanced fault with the sinusoidal waves being equal about their
axes, and represents a
steady state condition.
An asymmetrical fault displays a d.c. offset, transient in nature and decaying
to the steady state of the symmetrical fault after a period of time:
Faults on a Three Phase System
The types of faults that can occur on a three phase A.C. system are as follows:
Types of Faults
on a Three Phase
System. (A) Phase-toearth fault
(B) Phase-to-phase fault
(C) Phase-to-phase-to-earth fault
(D) Three phase fault
(E) Three phase-to-earth fault
5] What is a surge absorber? Write a short note on Ferranti surge absorber.
[8] Surge absorbers are protective devices used to absorb the complete surge i,e.
due to lightening surge or any transient surge in the system..........unlike the
lightening arrestor in which a non-linear resistor is provided which provides a
low resistance path to the dangerously high voltages on the system to the
earth...
Ferranti surge absorber
20

6. What are the causes of over voltage on a power system?


(8)

Overvoltage - Causes and Protection


Over voltages occur in a system when the system voltage rises over 110% of the
nominal rated voltage. Overvoltage can be caused by a number of reasons, sudden
reduction in loads, switching of transient loads, lightning strikes, failure of control
equipment such as voltage regulators, neutral displacement,. Overvoltage can cause
damage to components connected to the power supply and lead to insulation failure,
damage to electronic components, heating, flashovers, etc.
Overvoltage relays can be used to identify overvoltages and isolate equipment.
These relays operate when the measured voltage exceeds a predetermined set-point.
The voltage is usually measured using a Potential Transformers. The details of the
21

ratio of the potential transformer are also entered into the relay. These relays are
usually provided with a time delay. The time delay can be either instantaneous, fixed
time or for IDMT (inverse definite minimum time) curves.
Generally, overvoltage relays are provided with sufficient time delay in order to
avoid unwanted trippings due to transients (See article on Transients).
These relays can be used to isolate feeders and other equipment connected to the network.
In the case of
generators, these relay also switch off the excitation system to the generators thereby
preventing voltage build- up.
ii) Rod gap
(4)
It is a very simple type of diverter and consists of two 1.5 cm rods, which are bent at
right angles with a gap in
between as shown in Fig 8. One rod is connected to the line circuit and the other
rod is connected to earth. The distance between gap and insulator (i.e. distance P)
must not be less than one third of the gap length so that the arc may not reach the
insulator and damage it. Generally, the gap length is so adjusted that breakdown should
occur at 80% of spark-voltage in order to avoid cascading of very steep wave fronts
across the insulators. The string of insulators for an overhead line on the bushing of
transformer has frequently a rod gap across it. Fig 8 shows the rod gap across the
bushing of a transformer. Under normal operating conditions, the gap remains nonconducting. On the occurrence of a high voltage surge on the line, the gap sparks
over and the surge current is conducted to earth. In this way excess charge on the line
due to the surge is harmlessly conducted to earth
Limitations:
(i) After the surge is over, the arc n the gap is maintained by the normal supply voltage,
leading to short-circuit
on the system.
(ii) The rods may melt or get damaged due to excessive heat produced by the arc.
(iii) The climatic conditions (e.g. rain, humidity, temperature etc.) affect the
performance of rod gap arrester. (iv) The polarity of the f the surge also affects the
performance of this arrester.
Due to the above limitations, the rod gap arrester is only used as a back-up
protection in case of main arresters.
It is a very simple type of diverter and consists of two 1.5 cm rods, which are bent at
right angles with a gap in between as shown in Fig 8. One rod is connected to the
line circuit and the other rod is connected to earth. The distance between gap and
insulator (i.e. distance P) must not be less than one third of the gap length so that the
arc may not reach the insulator and damage it. Generally, the gap length is so adjusted
that breakdown should occur at 80% of spark-voltage in order to avoid cascading of
very steep wave fronts across the insulators. The string of insulators for an overhead
line on the bushing of transformer has frequently a rod gap across it. Fig 8 shows the
22

rod gap across the bushing of a transformer. Under normal operating conditions, the
gap remains non-conducting. On the occurrence of a high voltage surge on the line,
the gap sparks over and
the surge current is conducted to earth. In this way excess charge on the line due to
the conducted to earth surge is harmlessly

(iii) Arcing horns


(4)
Transmission and other electrical equipment can be exposed to overvoltages.
Overvoltages can be caused by a number of reasons such as lightning strikes, transient
surges, sudden load fluctuation, etc. In the event of an overvoltage, the insulating
equipment such as the insulators on a transmission line or bushings in a transformer
can be exposed to high voltages which may lead to their failure.
Arcing horns are protective devices that are constructed in the form of
projections in the conducting materials on both sides of an insulator. Arcing horns
are fitted in pairs. Thus in transmission lines they are found on the conducting line
and the transmission tower across the insulators. In transmission lines, in the
event of a lightning strike on the tower, the tower potential rises to dangerous levels and
can result in flashovers across the insulators causing their failure. Arcing horns prevent
this by conducting the arc across the air gap across them.
Arcing horns function by bypassing the high voltage across the insulator using
air as a conductive medium. The small gap between the horns ensures that the air
between them breaks down resulting in a flashover and conducts the voltage surge
rather than cause damage to the insulator.The horns are constructed in pair so that one
horn is on the line side and the other is on the ground side.

23

Arcing Horns are also used along with air insulated switchgear equipment. Air
insulated switchgear are vulnerable to damage due to arcing. Arcing horns serve to
divert the arc towards themselves thus protecting the switching equipment. The arcing
horns serve to move the arc away from the bushings or the insulators.
Figure shows the horn gap arrester. It consists of a horn shaped metal rods A and B
separated by a small air gap. The horns are so constructed that distance between them
gradually increases towards the top as shown. The horns are mounted on porcelain
insulators. One end of horn is connected to the line through a resistance and choke coil L
while the other end is effectively grounded. The resistance R helps in limiting the follow
current to a small value. The choke coil is so designed that it offers small reactance at
normal power frequency but a very high reactance at transient frequency. Thus the choke
does not allow the transients to enter the apparatus to be protected. The gap between the
horns is so adjusted that normal supply voltage is not enough to cause an arc across the

24

gap.

Under normal conditions, the gap is non-conducting i.e. normal supply voltage is
insufficient to initiate the arc between the gap. On the occurrence of an over voltage,
spark-over takes place across the small gap G. The heated air around the arc and the
magnetic effect of the arc cause the arc to travel up the gap. The arc moves progressively
into positions 1,2 and 3. At some position of the arc (position 3), the distance may be too
great for the voltage to maintain the arc; consequently, the arc is extinguished. The
excess charge on the line is thus conducted through the arrester to the ground.

(iv) Basic impulse insulation level


(4)

25

BIL or basic impulse insulation level is the dielectric insulation gradient of a material
tested to withstand the voltage stress at a voltage impressed between the material and
a conductive surface beyond the BIL rating, an electric tracking starts to occur which
will then result into an arcing flashover to the conductive surface. In
addition it is the capacity of an equipment to withstand mechanical stress like
lightning strike without causing any damage to the equipment...

11. What is Peterson coil? What protective functions are performed by this
device?

(16) [Ref Q.No 1 IN 16 MARKS]

Types of Faults on
a Three Phase
System. (A)
Phase-to-earth
fault
(B) Phase-to-phase fault
(C) Phase-to-phase-to-earth fault
(D) Three phase fault
(E) Three phase-to-earth fault
(F) Phase-to-pilot fault * (G) Pilot-to-earth fault *
2] What is the need for protection zones in the tem?
Any fault occurring within the given zone will provide necessary tripping of relays or
disconnecting or opening of circuit breakers and thus the healthy section is safe
guarded.
If a fault occurs in the overlapping zone in a proper protected scheme, more circuit
breakers than the minimum necessary to isolate the faulty part of the system would
trip.
3] what is surge absorber? How do they differ from surge diverter?
Surge Absorber: it is a protective device used to reduce the steepness of the
wave front of a surge and absorbs energy contained in the travelling wave.
Surge Diverter
It will divert excess voltages from an electrical surge to earth. It measures the
volts coming in and once it gets above a set amount (normally 260 volts), will divert
the excess volts to earth equipment. Unlike the more common Surge Protector
Powerboards that simply switch off if there is spike in volts, a Surge Diverter will
just divert the excess volts away. It is also installed on your main switchboard,
thereby protecting all powerpoints.
26

4] Define the term Insulation Coordination.


Insulation Coordination is the process of determining the proper insulation
levels of various components in a power system as well as their arrangements. It is the
selection of an insulation structure that will withstand voltage stresses to which the
system, or equipment will be subjected to, together with the proper surge arrester. The
process is determined from the known characteristics of voltage surges and the
characteristics of surge arresters.

5] Write any two functions of protective relaying?


(i) The function of a protective relay is to detect and locate a fault and issue
a command to the circuit breaker to disconnect the faulty element.
(ii)It is a device which senses abnormal conditions on a power system
by constantly monitoring electrical quantities of the system which differ under
normal and abnormal conditions.
6] What are the desirable qualities of protective relaying? Or Mention the
essential features of the power system protection. Or List the essential features of
switchgear.
1. Selectivity

2. Speed & time

3. Sensitivity

4. Reliability

5. Simplicity

6. Economy

7] What is meant by switchgear?


The apparatus used for switching, controlling and protecting the electrical
circuits and equipment is known as switchgear.
8] What are the functions of protection relaying?
The principal function of protective relaying is to cause the prompt removal
from service of any element of the power system when it starts to operate in an
abnormal manner or interface with the operation of rest of
the system.
9] What are the causes of faults in power system?
(ii) Heavy short circuit current may cause damage to damage equipment or
other element of the system of the system due to overheating and high mechanical
forces set up due to heavy current.

27

(iii) Arc associated with short circuits may cause fire hazards. Such fires
resulting from arcing may destroy the fault element of the system. There is also
possibility of firing spreading to the other devices if the fault is not isolated quickly.

10] What are the different types of fault in power system transmission lines?
1. Symmetrical faults 3 phase faults
2. Unsymmetrical faults Single phase to ground, single phase to open circuit,
Two phase to groundfault; phase to phase short circuit.
11] List out the types of faults in power system
A].Single phase to ground B] phase to phase faults C] Two phase to ground
fault and D] Three phase short circuit faults.
12] Explain the need for overlapping the zones of protection.
1. The circuit breakers are located in the connection to each power element.
2. This provision makes it possible to disconnect only the faulty element from the
system.

13] Differentiate between primary and back up protection.


No
1
2
3

Primary protection
It is designed to protect the components
of the power system. [main protection]

Back Up Protection
It is second line of protection in case main
protection fails.

It is for instantaneous protection

It is designed to operate with enough time


delay

Only faulty element will be removed.

Larger part of the power system is removed.

14] What are the causes of faults in power system?


1. Internal causes of the equipment.
2. Heavy short circuit current may cause s damage the equipment or other
element of the system due to overheating and high mechanical forces set up
due to heavy current.
3. Deterioration of insulation.
15] What are the functions of protective relays
To detect the fault and initiate the operation of the circuit breaker to isolate
the defective element from the rest of the system, thereby protecting the system from
28

damages consequent to the fault.


16. Give the consequences of short circuit.
Whenever a short-circuit occurs, the current flowing through the coil increases
to an enormous value. If protective relays are present , a heavy current also flows
through the relay coil, causing it to operate by closing its contacts. The trip circuit is
then closed , the circuit breaker opens and the fault is isolated from the rest of the
system. Also, a low voltage may be created which may damage systems connected to
the supply.
17. Define protected zone.
Are those which are directly protected by a protective system such as relays, fuses
or switchgears. If a fault occurring in a zone can be immediately detected and or
isolated by a protection scheme dedicated to that particular zone.
18. What are unit system and non-unit system?
A unit protective system is one in which only faults occurring within its
protected zone are isolated. Faults occurring elsewhere in the system have no
influence on the operation of a unit system.
A non-unit system is a protective system which is activated even when
the faults are external to its protected zone.

19.What is primary protection?


Is the protection in which the fault occurring in a line will be cleared by
its own relay and circuit breaker. It serves as the first line of defence.
20. What is back up protection?
Is the second line of defence, which operates if the primary protection fails to
activate within a definite time delay.
21. Name the different kinds of over current relays.
Induction type non-directional over current relay, Induction type directional
over current relay & current differential relay.
22. Define energizing quantity.
It refers to the current or voltage which is used to activate the relay into operation.

29

23. Define operating time of a relay.


It is defined as the time period extendind from the occurrence of the fault
through the relay detecting the fault to the operation of the relay.
24. Define resetting time of a relay.
It is defined as the time taken by the relay from the instant of isolating the fault
to the moment when the fault is removed and the relay can be reset.
25. What are over and under current relays?
Overcurrent relays are those that operate when the current in a line exceeds a
predetermined value. (eg: Induction type non-directional/directional overcurrent relay,
differential overcurrent relay)whereas undercurrent relays are those which operate
whenever the current in a circuit/line drops below a predetermined
value.(eg:differential over-voltage relay)
26. Mention any two applications of differential relay.
Protection of generator & generator transformer unit; protection of large motors and
busbars .
27. What is biased differential bus zone reduction?
The biased beam relay is designed to respond to the differential current in terms
of its fractional relation to the current flowing through the protected zone. It is
essentially an over-current balanced beam relay type with an additional restraining coil.
The restraining coil produces a bias force in the opposite direction to the operating
force.

30