Vous êtes sur la page 1sur 70

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

5.2 Centrifugal Fans


Accessories . . . . . . . . . . . . . . . . . . . . . . . . .580

Contents

Introduction. . . . . . . . . . . . . . . . . . . 522
CAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
CNA and CNB . . . . . . . . . . . . . . . . . . . . . . . 523
CND and CNF . . . . . . . . . . . . . . . . . . . . . . . 524
CMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525

Medium-Pressure Centrifugal Fans


CAL . . . . . . . . . . . . . . . . . . . . . . . . . 526
Construction. . . . . . . . . . . . . . . . . . . . . . . . . 526
Materials and Surface Treatment. . . . . . . . . 526
Working Ranges . . . . . . . . . . . . . . . . . . . . . 527
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 528
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 529
Dimensions Shaft Ends for Belt-driven Versions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
Dimensioning . . . . . . . . . . . . . . . . . . . . . . . . 544
Performance Curves . . . . . . . . . . . . . . . . . . 545

Low-Pressure Centrifugal Fans CNA


and CNB. . . . . . . . . . . . . . . . . . . . . . 558

Medium-Pressure Centrifugal Fans


CMP . . . . . . . . . . . . . . . . . . . . . . . . . . 583
Main Characteristics. . . . . . . . . . . . . . . . . . .583
Technical Characteristics . . . . . . . . . . . . . . .583
Surface Treatment and Material. . . . . . . . . .583
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .583
Environment . . . . . . . . . . . . . . . . . . . . . . . . .583
Acoustic Characteristics. . . . . . . . . . . . . . . .584
Accessories . . . . . . . . . . . . . . . . . . . . . . . . .584
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .585
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . .585
Performance Curves . . . . . . . . . . . . . . . . . .586
Position Designations. . . . . . . . . . . . . . . . . .586

Sound Conditions . . . . . . . . . . . . . . 587


Control of Air Volume . . . . . . . . . . . 589
Pole Changing . . . . . . . . . . . . . . . . . . . . . . .589
Inlet Vane Control . . . . . . . . . . . . . . . . . . . .589
Frequency Conversion . . . . . . . . . . . . . . . . .589

Surface Treatment . . . . . . . . . . . . . . . . . . . . 558


Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 558
Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . 559
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 560
Outlet Flanges . . . . . . . . . . . . . . . . . . . . . . . 561
Motor Mounting Arrangements . . . . . . . . . . 561
Base frame for fan and motor . . . . . . . . . . . 562
Position Designations . . . . . . . . . . . . . . . . . 562
Shaft Extension . . . . . . . . . . . . . . . . . . . . . . 562
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 563
Performance Curves . . . . . . . . . . . . . . . . . 565

Low- and Medium-Pressure Centrifugal


Fans CND and CNF. . . . . . . . . . . . . 570
Surface Treatment and Material . . . . . . . . . 570
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570
Environment. . . . . . . . . . . . . . . . . . . . . . . . . 570
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 571
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 572
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . 572
Outlet Flanges . . . . . . . . . . . . . . . . . . . . . . . 573
Motor Sizes and Position Designations . . . . 573
Position Designations for Impeller . . . . . . . . 574
Motor Sizes . . . . . . . . . . . . . . . . . . . . . . . . . 574
Max. RPM . . . . . . . . . . . . . . . . . . . . . . . . . . 574
Motor Installation . . . . . . . . . . . . . . . . . . . . . 575
Low-Mounted Bracket for Large Motors. . . . 575
Shaft End . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
Dimensioning Curves. . . . . . . . . . . . . . . . . . 576

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
MU 14378 0710

521

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Introduction

Materials and Surface Treatment

This chapter describes the centrifugal fans type

Housing

CAL, CNA, CNB, CND, CNF and CMP.

Heavy sheet steel, steel 37-2 or stainless sheet AISI


316L

The introduction of the fans on these first few

Impeller

pages is followed by detailed data on and in-

Corten, DOMEX 500 or SAF-2205 steel qualities,

depth descriptions of each fan type.

or AISI 316L at reduced RPMs

The chapter finishes with descriptions of sound

Bearing bracket

conditions and control of air volumes common to

Galvanised heavy steel sections

all the fans.

Guide vane arrangement


AISI 316L
Surface treatment

CAL
The CAL fans are roboustly built compact centrifugal fans capable of deliverying medium pressures.

Corrosion Classification
The galvanised version meets the requirements
for operation in medium-level corrosive environ-

Application
In aggressive environments and well-suited for
purposes with high physical loads and long life
requirements.

ments in accordance with DS/EN ISO 12944-2,


corrosion category C3.
The stainless steel version meets the requirements
for aggressive corrosive environments category
C5. As standard only parts in the airflow are

Ranges
The CAL standard range comprises 24 sizes in the
belt-driven version (impeller diameters from 315
to 1250 mm) and 19 sizes in the directly coupled
version

Hot-dip galvanised

(impeller

diameters

from

630

to

1250 mm). Directly coupled versions are made


with or without drive-side removable (DSR) impellers.
Air volumes are from 0.3 to 21 m3/s and total
pressures up to 8500 Pa.

made of stainless steel. If required all parts can be


made of stainless steel.
Technical Specification
Technical capacities are in accordance with BS
848:1980 and ISO 5801 1997, installation type D.
Accessories
Flexible connections for inlet and outlet
Mating flange for the outlet

The temperature range runs from 0 - 70 C.

Anti-vibration mountings
Access door on the casing of the fan housing

Construction
The housing, impeller and bearing bracket are
welded.
The fan is available in belt-driven or directly coupled versions.
The fan shaft is supported in two-part steel bearing housings with spherical roller/ball bearings.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
522

Introduction

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CNA and CNB

Corrosion Classification

These are single inlet low pressure fans with back-

Fulfils the following international standard for

ward curved blades.

operation in unheated, low-corrosive environments:

Application

DS/EN ISO 12944-2 corrosivity category C2

In marine ventilating systems for clean and noncorrosive air, max. 70 C, and with requirements

Technical Specification

for a low sound level.

The capacities comply with the requirements according to BS 848, Part 1, arrangement D.

Ranges
The CNA is avaiable in 9 sizes with impeller di-

Accessories

ameters from 250 to 1000 mm.

For installation and service are listed in the fol-

Air volumes from 0.2 to 14 m /s and pressures up

lowing pages.

to 1000 Pa.
Control
The CNB is available in 7 sizes with impeller diameters from 400 to 1000 mm.
Air volumes are from 0.8 to 18 m3/s and pressures

Inlet vane control


Continuously variable speed control (CNA-

up to 1500 Pa.

250 and 315 single phase direct coupled motor)


Three stage controller (CNA-250 and 315 sin-

Construction

gle phase direct coupled motor)

Fan casing with rectangular side plates for univer-

Three phase multi speed motor for 2 speeds

sal mounting.

Frequency converter, three phase motors

The fan is available in direct connected or belt


driven design.

Protection

Materials and Surface Treatment

Wire guard (inlet and outlet)

Casing, CNA/B

Drain connection

Sendzimir-galvanised (hot-dip galvanised) steel

Spark proof inlet cone

sheet, unpainted.
Impeller, CNA 250 to -630
Spot welded, galvanised steel sheet.
Impeller, CNA 710 to -1000
Welded Cor-ten steel sheet, hot-dip galvanised.
Impeller, CNB
Welded Cor-ten steel sheet, hot-dip galvanised.
Inlet Cone CNA/CNB
CNA/B -250 to -630: Hot-dip galvanised deep
drawn sheet, unpainted.
CNA/B -710 to -1000: Cast aluminium, unpainted.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Introduction

523

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CND and CNF

Accessories

These are low- and medium pressure fans with

The following accessories are used during instal-

backward curved blades.

lation and service.

Application

Control

They are suitable for installation in aggressive environments, as they, for example, can withstand

Duct boss - inlet

the effects of seawater.

Flexible connections
Mating flange

Ranges

Inspection hatch

The CND is available in 7 sizes with impeller diameters from 315 mm to 710 mm.

Protection

Air volumes are from 0.2 to 10 m /s and pressures up to approx. 2000 Pa.

Drain plug
Wire guards

The CNF is available in 6 sizes with impeller di-

Anti-vibration mountings

ameters from 400 to 710 mm.

Spark proof inlet funnel

Air volumes are from 0.2 to 11 m3/s and pressures up to approx. 4000 Pa.
Construction
The fan housing is constructed from two rectangular side panels and an all-welded casing.
The fan is available in direct coupled or belt
driven design.
Surface Treatment and Material
All parts of the fans are treated with a 60 m hotdip galvanisation for protection.
Alternatively, by special agreement and at additional cost, the fans can also be made of stainless
steel AISI 316L.
Corrosion Classification
The fans are designed for operation in corrosion
category C5-I (very high), as formulated in DS/
EN ISO 12944-2.
Versions are also available for medium-level corrosive environments in accordance with DS/EN
ISO 12944-2, corrosion category C3.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
524

Introduction

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CMP

Accessories

These are medium pressure fans with multi-blade

The following accessories are used during instal-

impellers.

lation and service.

Application

Control

The design is intended to withstand installation in


aggressive enviroments such as on-board ships.

Duct boss inlets and outlets


Mating flange outlets

Ranges
The CMP fans are available in 5 sizes with impel-

Protection

ler diameters from 140 to 247 mm.


Airflow rates are from 0.13 to 0.54 m3/s and pres-

Wire guards

sures up to approx. 1400 Pa.


Construction
The fan housing is constructed from sheet steel
and receive a corrosion-proof finish in polyester
resin.
The motors are direct coupled to impeller.
Surface Treatment and Material
All parts of the fans are made of sheet steel. The
impeller blades are of galvanised sheet steel.
Stainless steel is available as an option.
The finish is a corrosion-proof polyester resin.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Introduction

525

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Medium-Pressure Centrifugal
Fans CAL

The shaft bushing in the fan housing is either a

Centrifugal fans type CAL are roboust compact

tween shaft and housing) or a double lip seal that

medium pressure fans designed for use in aggres-

prevents aggressive gases and condensate from

sive environments. They are well suited to pur-

leaking out.

simple gap seal (approximately 1 mm gap be-

poses with high physical loads and long life requirements.

The impeller has backward-curved blades.

The CAL is available in 24 sizes in belt-driven ver-

The fan housing is fitted with the following.

sions (impeller diameters from 315 to 1250 mm)


and in 19 sizes in directly coupled versions (impeller diameters from 630 to 1250 mm). Directly

A duct boss and conical inlet funnel on the inlet side

coupled versions are made with or without drive-

A flange on the outlet side

side removable (DSR) impellers for easier service

A discharge boss at the lowest point of the fan

and maintenance. More details on DSR versions

housing in those installation positions where it

are available on request.

is necessary.
3

Air volumes run from 0.3 to 21 m /s and pressure


outputs up to 8500 Pa.
The temperature range runs from 0 - 70 C.

Construction
The fan consists of a robustly welded housing
with angle stiffeners, an impeller, a combined motor and bearing bracket and a support bracket on
the inlet side. The stiffeners and brackets are all
made of strong steel sections.
The base of the brackets forms the base frame of

Centrifugal Fan Type CAL

the fan.
In the belt-driven version, the shaft has spherical
roller or ball bearings in steel bearing housings.
In the directly coupled fan, the impeller is
mounted directly on the motor shaft.

The fan housing and bearing bracket are made of


galvanised heavy sheet steel.
The impeller is made of Corten A and DOMEX

Directly coupled versions with drive-side removable impellers are somewhat different in construction and dimensions compared to those with nonremovable impellers. Exact specifications are
available on request.

Materials and Surface Treatment

500 steel qualities.


The surface is hot-dip galvanised and meets international requirements for operation in mediumlevel corrosive environments in accordance with
the standard DS/EN ISO 12944, part 2, corrosion
category C3.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
526

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Alternatively, the fan housing can also be made in

The impeller is available in two stainless versions,

a stainless version in AISI 316L. This meets the re-

either SAF 2205 or AISI 316L for limited RPMs.

quirements for aggressive environments category

See dimensioning curves on pages 544 to 557.

C5. Only parts in the airflow are made of stainless


steel. If required all parts can be made of stainless

Working Ranges

steel.

The below curves show the working ranges of the


CAL fans. The curves show where the efficiency is
greater than 75% with an indication of the peak ef-

-6
30

CAL 100%
-7
10

630

82
%

5000

82
%

82% 400

82% - 31
5

Total pressure [Pa]

6000

82%
- 500

ficiency of 82%.

710
4000

%
82

-8

00

800
500

400

3000

82%

900

900

82%

0
100

82%

0
- 125
82%

0
112

1000

315

1120

1250

2000
1000
0 0

10

15

20

Air volume [m3/s]


6000
800

%
82

5000

00
-8

%
82

Total pressure [Pa]

900

-9

CAL 85%

00

%
82

4000

0
00
-1

82%

20
- 11
82%

0
125

1120

1000
3000

1250

2000
1000
0

10

15

20

7000

CAL 70%

82%

- 80
0

82%
30
82%
-6

8000

82% 500

82% - 4
00

9000

- 71
0

Air volume [m /s]

800
400

900

630

%
82

6000

Total pressure [Pa]

710
5000

%
82

00
-9

0
00
-1

%
82

1120

1000

500

0
12
-1

%
82

0
25
-1

1250

4000
3000
2000
1000
0 0

10

15

20

Air volume [m /s]


Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

527

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

instructions for further details. The anti-vibration

Accessories

mountings for the suction side of the fans are supFlexible Connections
Flexible connections of flameproof material for
max. 80 C and flexible connections of incombustible material for max. 250 C are available for the
inlet and outlet.

plied unfitted.
Inspection Hatch Position on Casing
The inspection hatch on the casing of the fan
housing is positioned differently depending on
fan size.

Inlet

It is secured with either one or two nuts and has a


rubber seal.
CAL 315 - 500

CAL 630 - 1250

B
56

Motor side

300

200

Inlet side

56

Outlet
100

200

Size of Inspection Hatch

The inspection hatch can be positioned in one of


three positions according to Eurovent. The below
figure shows the possible positions seen from the
Standard Flexible Connections

shaft end.
RD0

Mating Flanges

RD180

RD90
45

RD270
135

45

225

225

135

The mating flange for the outlet is made of flats.


See dimensions on pages 529 - 543.

135

225

225
45

LG270
LG90

LG0

LG180
225

45

Anti-Vibration Mountings

45

135

225

135
135

The sizes and types of anti-vibration mountings


are best calculated by Novenco, as different types
may be required due to load variations at the four

135

225
225

45

135

45

Possible Positions of Inspection Hatch

installation points of the fan.


The fans are supplied with installation instructions that indicate the positions of the anti-vibration mountings.
The following applies to CAL/R with motor sizes
larger than 225. The anti-vibration mountings on
the motor bracket side are factory-fitted. These are
protected against transport damages by protection devices that must be removed before the fan
can be put into operation. Refer to the installation
Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
528

Medium-Pressure Centrifugal Fans CAL

45

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensions
CAL 100% Direct Motor Size 160-280
Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-630
-710
-800
-900
-1000
CAL
-630
-710
-800
-900
-1000

E1
160-180 200-225 250-280

Bu

C1

F1

630

441

449

107

500

584

1019

1199

737

470

710

497

505

121

560

648

1075

1255

831

528

800

560

570

136

630

720

1320

1320

936

600

900

630

640

153

710

800

1390

1390

1560

1053

670

1000

700

710

170

800

880

14604)

1460

1630

1170

754

G1

Pos. 0

Weight 3)
kg

H
J
Pos. 90 Pos. 180 Pos. 270 160-180 200-225 250-280

591

429

630

500

450

800

450

630

64

274

667

483

710

560

500

900

450

630

64

333

752

544

800

630

560

1000

630

630

66

461

845

612

900

710

630

1120

630

630

800

66

578

940

680

1000

800

710

1250

6304)

630

800

66

680

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor.
4) The CAL-1000 is unavailable with motor size 160.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

u x 15

CAL
-630
-710
-800
-900
-1000

65

70.5

680 730 491 541

24

55

98.5

760 810 547 597

26

50

80.0

850 900 610 660

30

50

115.0

950 1000 680 730

32

50

10 100.0

1050 1100 750 800

36

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

529

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 100% Direct Motor Size 250-280


Duct boss

Drain plug 1 RG
Dimensions in mm
CAL
-1120
-1250

Bu

C1

E1

F1

1120

784

796

190

900

996

1796

1310

845

1250

875

887

213

1000

1100

1887

1463

942

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

J
250-280

Weight 2)
kg

1048

762

1120

900

800

1400

850

69

1047

69

1188

H
CAL
-1120
-1250

1169

850

1250

1000

900

1600

850

3)

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor.
3) The CAL-1250 is unavailable with motor size 250.

Outlet Flange
r

CAL
-1120
-1250

r n x 100

T
X

p x 100

S
Y

u x 15

70

11

102

1180 1240 844 904

40

85

12

97.5

1310 1370 935 995

44

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
530

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 100% Belt-driven Motor Size 112-225


Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-315
-400
-500
-630
-710
-800
-900
-1000
CAL
-315
-400
-500
-630
-710
-800
-900
-1000

E1
112-132 160-180 200-225

Bu

C1

F1

315

221

227

54

250

332

797

369

236

400

280

286

68

315

400

856

1036

468

299

500

350

356

85

400

480

926

1106

585

373

630

441

449

107

500

584

1199

1369

737

470

710

497

505

121

560

648

1255

1425

831

528

800

560

570

136

630

720

1320

1490

936

600

900

630

640

153

710

800

1390

1560

1053

670

1000

700

710

170

800

880

1460

1630

1170

754

G1

Pos. 0

H
J
Pos. 90 Pos. 180 Pos. 270 112-132 160-180 200-225

Weight
3)
kg

297

215

315

250

224

450

450

155

62

95

377

272

400

315

280

560

450

630

155

62

158

470

340

500

400

355

710

450

630

155

62

212

591

429

630

500

450

800

630

800

180

64

395

667

483

710

560

500

900

630

800

180

64

460

752

544

800

630

560

1000

630

800

180

66

587

845

612

900

710

630

1120

630

800

180

66

707

940

680

1000

800

710

1250

630

800

180

66

824

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor and belt drive.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

u x 15

CAL
-315
-400
-500
-630
-710
-800
-900
-1000

57.5

110.5

365 415 271 321

12
16

50.0

90.0

450 500 330 380

50.0

75.0

550 600 400 450

20

65.0

70.5

680 730 491 541

24

55.0

98.5

760 810 547 597

26
30

50.0

80.0

850 900 610 660

50.0

115.0

950 1000 680 730

32

50.0

10 100.0

1050 1100 750 800

36

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

531

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 100% Belt-driven Motor Size 225-250


Duct boss

Drain plug 1 RG
Dimensions in mm
CAL
-1120
-1250
CAL
-1120
-1250

Bu

C1

E1

F1

G1

1120

784

796

190

900

996

1871

1310

845

1048

762

1250

875

887

213

1000

1100

1962

1463

942

1169

850

J1

M1

Weight 2)
kg

Pos. 0

H
Pos. 90 Pos. 180 Pos. 270

1120

900

800

1400

925

600

152

69

1870

1320

1450

1250

1000

900

1600

925

600

152

69

1870

1320

1650

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor and belt drive.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-1120
-1250

u x 15

70

11 102.0

1180 1240 844 904

40

85

12

1310 1370 935 995

44

97.5

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
532

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 85% Direct Motor Size 160-280


Duct boss

Drain plug 1 RG
Dimensions in mm
E1
CAL
-800
-900
-1000

Bu

C1

160-225

250-280

F1

800

476

486

136

630

720

1236

1406

936

600

900

536

546

153

710

800

1296

1466

1053

670

1000

595

605

170

800

880

1355

1525

1170

754

Weight 3)
kg

H
CAL
-800
-900
-1000

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

160-225

250-280

752

544

800

630

560

1000

630

800

114

453

845

612

900

710

630

1120

630

800

120

559

940

680

1000

800

710

1250

6304)

800

126

656

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor.
4) The CAL-1000 is unavailable with motor size 160.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-800
-900
-1000

u x 15

50

88

850 900 526 576

28

50

118

950 1000 586 636

30

50

10

97.5

1050 1100 645 695

34

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

533

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 85% Direct Motor Size 250-280


Duct boss

Drain plug 1 RG
Dimensions in mm
CAL
-1120
-1250

Bu

C1

E1

F1

1120

667

679

190

900

996

1679

1310

845

1250

744

756

213

1000

1100

1756

1463

942

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

J
250-280

Weight 2)
kg

1048

762

1120

900

800

1400

850

136

1021

144

1154

H
CAL
-1120
-1250

1169

850

1250

1000

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor.
3) The CAL-1250 is unavailable with motor size 250.

900

1600

850

3)

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100
B

T
X

p x 100

S
Y

CAL
-1120
-1250

u x 15

70

11

93.5

1180 1240 727 787

38

85

12

82.0

1310 1370 804 864

42

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
534

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 85% Belt-driven Motor Size 160-225


Duct boss

Drain plug 1 RG
Dimensions in mm
E1
CAL
-800
-900
-1000
CAL
-800
-900
-1000

Bu

C1

160-180

200-225

F1

800

476

486

136

630

720

1236

1406

936

600

900

536

546

153

710

800

1296

1466

1053

670

1000

595

605

170

800

880

1355

1525

1170

754

H
J
Pos. 90 Pos. 180 Pos. 270 160-180 200-225

Weight 3)
kg

G1

Pos. 0

752

544

800

630

560

1000

630

800

180

114

573

845

612

900

710

630

1120

630

800

180

120

688

940

680

1000

800

710

1250

630

800

180

126

798

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor and belt drive.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-800
-900
-1000

u x 15

50

88

850 900 526 576

28

50

118

950 1000 586 636

30

50

10

97.5

1050 1100 645 695

34

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

535

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 85% Belt-driven Motor Size 250-280


Duct boss
B

50

50

C1

25

25
440

1200

25

100

700

Bu

120

CAL
-800
-900
-1000

100

980

17

17

195

E1

1640

1)

G1

53

F1

L
50

Drain plug 1 RG

Dimensions in mm

6 x 15

Bu

C1

E1

F1

800

476

486

136

630

720

1586

936

600

900

536

546

153

710

800

1646

1053

670

1000

595

605

170

800

880

1705

1170

754

H
CAL
-800
-900
-1000

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

752

544

800

630

560

1000

114

837

845

612

900

710

630

1120

120

947

940

680

1000

800

710

1250

126

1052

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor and belt drive.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-800
-900
-1000

u x 15

50

88

850 900 526 576

28

50

118

950 1000 586 636

30

50

10

97.5

1050 1100 645 695

34

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
536

Weight 2)

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 85% Belt-driven Motor Size 225-315


Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-1120
-1250

E1
225-250 280-315

Bu

C1

F1

G1

1120

667

679

190

900

996

1754

2054

1310

845

1048

762

1250

744

756

213

1000

1100

1831

2131

1463

942

1169

850

H
CAL
-1120
-1250

Pos. 0

Pos. 90

J
Pos. 180

Pos. 270

225-250

J1
280-315

225-250

K
280-315

225-250

280-315

1120

900

800

1400

925

1225

600

875

152

207

1250

1000

900

1600

925

1225

600

875

152

207

M
CAL
-1120
-1250

M1

225-250

280-315

225-250

136

1870

2050

1320

1500

1425

1655

144

1870

2050

1320

1500

1620

1865

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor and belt drive.

280-315

Weight 2) kg
225-250
280-315

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-1120
-1250

u x 15

70

11

93.5

1180 1240 727 787

38

85

12

82.0

1310 1370 804 864

42

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

537

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 70% Direct Motor Size 160-280


Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-630
-710
-800
-900
-1000
CAL
-630
-710
-800
-900
-1000

E1
160-180 200-225 250-280

Bu

C1

F1

630

309

317

107

500

584

887

1067

737

470

710

348

356

121

560

648

926

1106

831

528

800

392

402

136

630

720

1152

1152

1322

936

600

900

441

451

153

710

800

1201

1201

1371

1053

670

1000

490

500

170

800

880

1250

1250

1420

1170

754

G1

Pos. 0

Weight 3)
kg

591

429

630

500

450

140

257

667

483

710

560

313

752

544

800

630

845

612

900

940

680

1000

H
J
Pos. 90 Pos. 180 Pos. 270 160-180 200-225 250-280
800

450

630

500

900

450

630

149

560

1000

630

630

800

162

436

710

630

1120

630

630

800

174

536

800

710

1250

6304)

630

800

186

629

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor.
4) The CAL-1000 is unavailable with motor size 160.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

u x 15

CAL
-630
-710
-800
-900
-1000

65

104.5

55

124.0

50

96.0

50

120.5

950 1000 491 541

28

50

10

95.0

1050 1100 540 590

32

760 810 398 448

22

850 900 442 492

26

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Medium-Pressure Centrifugal Fans CAL

20

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
538

680 730 359 409

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 70% Direct Motor Size 250-315


Duct boss

Drain plug 1 RG
Dimensions in mm
CAL
-1120
-1250

Bu

C1

E1

F1

1120

549

561

190

900

996

1561

1310

845

1250

613

625

213

1000

1100

1625

1463

942

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

J
250-315

Weight 2)
kg

1048

762

1120

900

800

1400

850

203

988

219

1114

H
CAL
-1120
-1250

1169

850

1250

1000

900

1600

850

3)

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor.
3) The CAL-1250 is unavailable with motor size 250.

Outlet Flange
CAL
-1120
-1250

r n x 100

T
X

p x 100

S
Y

70

11

84,5

1180 1240 609 669

36

85

12 116.5

1310 1370 673 733

38

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

u x 15

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

539

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 70% Belt-driven Motor Size 112-225


Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-400
-500
-630
-710
-800
-900
-1000
CAL
-400
-500
-630
-710
-800
-900
-1000

E1
112-132 160-180 200-225

Bu

C1

F1

400

196

202

68

315

400

772

952

468

299

500

245

251

85

400

480

821

1001

585

373

630

309

317

107

500

584

1067

1237

737

470

710

348

356

121

560

648

1106

1276

831

528

800

392

402

136

630

720

1152

1322

936

600

900

441

451

153

710

800

1201

1371

1053

670

1000

490

500

170

800

880

1250

1420

1170

754

G1

Pos. 0

H
J
Pos. 90 Pos. 180 Pos. 270 112-132 160-180 200-225

Weight
3)
kg

377

272

400

315

280

560

450

630

155

110

154

470

340

500

400

355

710

450

630

155

122

198

591

429

630

500

450

800

630

800

180

140

376

667

483

710

560

500

900

630

800

180

149

440

752

544

800

630

560

1000

630

800

180

162

557

845

612

900

710

630

1120

630

800

180

174

668

940

680

1000

800

710

1250

630

800

180

186

774

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Depends on motor size. See dimension table.
3) Weight is excl. motor and belt drive.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

u x 15

CAL
-400
-500
-630
-710
-800
-900
-1000

50

98.0

450 500 246 296

14

50

72.5

550 600 295 345

18

65

104.5

680 730 359 409

20

55

124.0

760 810 398 448

22

50

96.0

850 900 442 492

26

50

120.5

950 1000 491 541

28

50

10

95.0

1050 1100 540 590

32

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
540

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 70% Belt-driven Motor Size 250-280


Duct boss
B

50

50

C1

25

25
440

1200

25

100

700

Bu

120

CAL
-800
-900
-1000

100

980

17

17

195

E1

1640

1)

G1

53

F1

L
50

Drain plug 1 RG

Dimensions in mm

6 x 15

Bu

C1

E1

F1

800

392

402

136

630

720

1502

936

600

900

441

451

153

710

800

1551

1053

670

1000

490

500

170

800

880

1600

1170

754

H
CAL
-800
-900
-1000

G1

Pos. 0

Pos. 90

Pos. 180

Pos. 270

Weight 2)
kg

752

544

800

630

560

1000

162

820

845

612

900

710

630

1120

174

925

940

680

1000

800

710

1250

186

1025

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor and belt drive.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-800
-900
-1000

u x 15

50

96.0

50

120.5

50

10

95.0

850 900 442 492

26

950 1000 491 541

28

1050 1100 540 590

32

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

541

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CAL 70% Belt-driven Motor Size 225-315


Duct boss

Drain plug 1 RG
Dimensions in mm

CAL
-1120
-1250

E1
225-250 280-315

Bu

C1

F1

G1

1120

549

561

190

900

996

1636

1936

1310

845

1048

762

1250

613

625

213

1000

1100

1700

2000

1463

942

1169

850

H
CAL
-1120
-1250

Pos. 0

Pos. 90

J
Pos. 180

Pos. 270

225-250

J1
280-315

225-250

K
280-315

225-250

1120

900

800

1400

925

1225

600

875

152

207

1250

1000

900

1600

925

1225

600

875

152

207

M
CAL
-1120
-1250

M1
280-315

Weight 2) kg
225-250
280-315

225-250

280-315

225-250

203

1870

2050

1320

1500

1390

1620

219

1870

2050

1320

1500

1580

1825

1) Depends on fan position. H is increased by 30 64 mm depending on anti-vibration mountings.


2) Weight is excl. motor and belt drive.

Position of Motor
The position of the motor is in accordance with
Eurovent.

Outlet Flange
r

r n x 100

T
X

p x 100

S
Y

CAL
-1120
-1250

u x 15

70

11

84.5

1180 1240 609 669

36

85

12 116.5

1310 1370 673 733

38

NB On the mating flange;


A and B dimensions are table value +5 mm /
X and Y dimensions are table value -5 mm /
r and q dimensions are table value -2.5 mm.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
542

280-315

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensions Shaft Ends for Beltdriven Versions


Motor Sizes 200 and 225
CAL
630 - 1000

d (h6)

70

140

20

74,5

Motor Sizes 225 and 250

CAL
1120 & 1250

d (h6)

80

110

22

85

Motor Sizes 112 and 132


CAL
315 - 500

d (h6)

40

80

12

43

Motor Sizes 250 and 280


CAL
800 - 1000

d (h6)

80

140

22

85

Motor Sizes 160 and 180


CAL
400 & 500
630 - 1000

d (h6)

50

110

14

53,5

60

110

18

64

Motor Sizes 280 and 315


CAL
1120 & 1250

d (h6)

90

140

25

95

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

543

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning

Example Choice of Motor

The basis for dimensioning is the airflow rate and

The power consumption in the dimensioning

the pressure loss in the ventilation system. This is

curves refers to the fan shaft. To cover the loss in

called the static pressure of the fan and has the

the belt drive and bearing parts, etc., the power

formula ps = ps2 - ps1.

consumption reading is increased by the factor C1.

To establish the total pressure of the fan, pt, add

C1 depends on the fan size.

the air speed pressure, the dynamic pressure pd at

315-630 :

C1 = 1.2

the outlet and the installation loss at the inlet p1

710-1000 :

C1 = 1.1

1120-1250 :

C1 = 1.05

and outlet p2.


These values are stated in connection with the
performance curves on pages 545 to 557.

For arrangement B applies the following.

All curves are plotted for arrangement D.

(free inlet, duct for outlet)

Arrangements

Pressure loss = static pressure = ps = ps2 - ps1 =

p2
p1

p1

p2

p2

p1

p1

p2

Airflow rate qv = 0.9 m3/s

ps2 - ps1

Pa

+ p1

Pa

+ pd + p2

Pa

Total pressure

Pa

2000 Pa
The graph on page 545 reveals that type CAL-315
is best suited.
The total pressure is calculated as follows.
ps2 - ps1

2000

Pa

ps2 - ps1

Pa

+ p1

10

Pa

+ p1

Pa

+ pd

102

Pa

+ pd

Pa

Total pressure

2112

Pa

Total pressure

Pa

ps2 - ps1

Pa

+ pd + p2

Pa

Total pressure

Pa

ps2 - ps1

Pa

+ pd

Pa

Total pressure

Pa

= 1.20 kg/m3

Fan speed: 3822 RPM

Correction:

Efficiency: 81%

2.3 x 1.2 = 2.76 kW

Power demand: 2.3 kW

Motor: 3 kW

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
544

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Performance Curves
Basis for charts
(Arr. D)

Symbols:
pt

total pressure

volume flow

pd

dynamic pressure, outlet n

speed, r.p.m.

p1

connection loss, inlet

efficiency, %

p2

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

qv

Dimensioning Curves 100%


CAL315/100

= 1.20 kg/m3

Moment of inertia,
Iv

0.11 kgm2

Circumferential speed,
u

0.016 x n, m/s

Impeller of DOMEX 500 or SAF-2205


Max. 4940 RPM
Impeller of AISI 316L
Max. 3826 RPM
At 45 C max. 3640 RPM
At 70 C max. 3503 RPM

CAL400/100

= 1.20 kg/m3

Moment of inertia,
Iv

0.38 kgm2

Circumferential speed,
u

0.021 x n, m/s

Impeller of DOMEX 500 or SAF-2205


Max. 3950 RPM
Impeller of AISI 316L
Max. 3088 RPM
At 45 C max. 2937 RPM
At 70 C max. 2827 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

545

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 100%


CAL500/100

= 1.20 kg/m3

Moment of inertia,
Iv

1.17 kgm2

Circumferential speed,
u

0.026 x n, m/s

Impeller of SAF-2205
Max. 3190 RPM
Impeller of AISI 316L
Max. 2470 RPM
At 45 C max. 2350 RPM
At 70 C max. 2261 RPM

CAL630/100

= 1.20 kg/m3

Moment of inertia,
Iv

3.56 kgm2

Circumferential speed,
u

0.033 x n, m/s

Impeller of SAF-2205
Max. 2920 RPM
At 45 C max. 2715 RPM
At 70 C max. 2601 RPM
Impeller of AISI 316L
Max. 1913 RPM
At 45 C max. 1820 RPM
At 70 C max. 1751 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
546

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 100%


CAL710/100

= 1.20 kg/m3

Moment of inertia,
Iv

5.76 kgm2

Circumferential speed,
u

0.037 x n, m/s

Impeller of SAF-2205
Max. 2440 RPM
At 45 C max. 2270 RPM
At 70 C max. 2174 RPM
Impeller of AISI 316L
Max. 1599 RPM
At 45 C max. 1521 RPM
At 70 C max. 1464 RPM
CAL800/100

= 1.20 kg/m3

Moment of inertia,
Iv

9.31 kgm2

Circumferential speed,
u

0.042 x n, m/s

Impeller of SAF-2205
Max. 2040 RPM
At 45 C max. 1898 RPM
At 70 C max. 1817 RPM
Impeller of AISI 316L
Max. 1337 RPM
At 45 C max. 1272 RPM
At 70 C max. 1224 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

547

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 100%


CAL900/100

= 1.20 kg/m3

Moment of inertia,
Iv

15.0 kgm2

Circumferential speed,
u

0.047 x n, m/s

Impeller of SAF-2205
Max. 1712 RPM
At 45 C max. 1590 RPM
At 70 C max. 1523 RPM
Impeller of AISI 316L
Max. 1120 RPM
At 45 C max. 1066 RPM
At 70 C max. 1026 RPM
CAL1000/100

= 1.20 kg/m3

Moment of inertia,
Iv

23.0 kgm2

Circumferential speed,
u

0.052 x n, m/s

Impeller of SAF-2205
Max. 1461 RPM
At 45 C max. 1358 RPM
At 70 C max. 1300 RPM
Impeller of AISI 316L
Max. 957 RPM
At 45 C max. 910 RPM
At 70 C max. 876 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
548

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 100%


CAL1120/100

= 1.20 kg/m3

Moment of inertia,
Iv

35.2 kgm2

Circumferential speed,
u

0.059 x n, m/s

Impeller of SAF-2205
Max. 1233 RPM
At 45 C max. 1146 RPM
At 70 C max. 1097 RPM

CAL1250/100

= 1.20 kg/m3

Moment of inertia,
Iv

54.5 kgm2

Circumferential speed,
u

0.065 x n, m/s

Impeller of SAF-2205
Max. 1046 RPM
At 45 C max. 972 RPM
At 70 C max. 930 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

549

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 85%


CAL800/85

= 1.20 kg/m3

Moment of inertia,
Iv

8.81 kgm2

Circumferential speed,
u

0.042 x n, m/s

Impeller of SAF-2205
Max. 2403 RPM
At 45 C max. 2232 RPM
At 70 C max. 2138 RPM
Impeller of AISI 316L
Max. 1573 RPM
At 45 C max. 1496 RPM
At 70 C max. 1440 RPM
CAL900/85

= 1.20 kg/m3

Moment of inertia,
Iv

14.2 kgm2

Circumferential speed,
u

0.047 x n, m/s

Impeller of SAF-2205
Max. 2016 RPM
At 45 C max. 1871 RPM
At 70 C max. 1792 RPM
Impeller of AISI 316L
Max. 1318 RPM
At 45 C max. 1254 RPM
At 70 C max. 1207 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
550

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 85%


CAL1000/85
Moment of inertia,
Iv

= 1.20 kg/m3

21.7 kgm2

Circumferential speed,
u

0.052 x n, m/s

Impeller of SAF-2205
Max. 1719 RPM
At 45 C max. 1597 RPM
At 70 C max. 1530 RPM
Impeller of AISI 316L
Max. 1126 RPM
At 45 C max. 1071 RPM
At 70 C max. 1030 RPM
CAL1120/85

= 1.20 kg/m3

Moment of inertia,
Iv

33.4 kgm2

Circumferential speed,
u

0.059 x n, m/s

Impeller of SAF-2205
Max. 1450 RPM
At 45 C max. 1348 RPM
At 70 C max. 1291 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

551

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 85%


CAL1250/85

= 1.20 kg/m3

Moment of inertia,
Iv

51.8 kgm2

Circumferential speed,
u

0.065 x n, m/s

Impeller of SAF-2205
Max. 1230 RPM
At 45 C max. 1143 RPM
At 70 C max. 1095 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
552

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 70%


CAL400/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

0.34 kgm2

Circumferential speed,
u

0.021 x n, m/s

Impeller of SAF-2205
Max. 5696 RPM
Impeller of AISI 316L
Max. 4411 RPM
At 45 C max. 4196 RPM
At 70 C max. 4038 RPM

CAL500/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

1.05 kgm2

Circumferential speed,
u

0.026 x n, m/s

Impeller of SAF-2205
Max. 3850 RPM
Impeller of AISI 316L
Max. 3529 RPM
At 45 C max. 3357 RPM
At 70 C max. 3231 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

553

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 70%


CAL630/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

3.20 kgm2

Circumferential speed,
u

0.033 x n, m/s

Max 3200 RPM with belt


drive version
Impeller of SAF-2205
Max. 3600 RPM
Impeller of AISI 316L
Max. 2733 RPM
At 45 C max. 2600 RPM
At 70 C max. 2502 RPM
For fans used in the shaded areas, it
is necessary to consider whether the
required power can be achieved with
the maximum motor size.
CAL710/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

5.20 kgm2

Circumferential speed,
u

0.037 x n, m/s

Impeller of SAF-2205
Max. 3000 RPM
Impeller of AISI 316L
Max. 2284 RPM
At 45 C max. 2173 RPM
At 70 C max. 2091 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
554

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 70%


CAL800/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

8.40 kgm2

Circumferential speed,
u

0.042 x n, m/s

Max 2600 RPM with belt


drive version
Impeller of SAF-2205
Max. 2918 RPM
At 45 C max. 2711 RPM
At 70 C max. 2596 RPM
Impeller of AISI 316L
Max. 1910 RPM
At 45 C max. 1817 RPM
At 70 C max. 1749 RPM
For fans used in the shaded areas, it
is necessary to consider whether the
required power can be achieved with
the maximum motor size.
CAL900/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

13.5 kgm2

Circumferential speed,
u

0.047 x n, m/s

Impeller of SAF-2205
Max. 2445 RPM
At 45 C max. 2272 RPM
At 70 C max. 2176 RPM
Impeller of AISI 316L
Max. 1601 RPM
At 45 C max. 1523 RPM
At 70 C max. 1465 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

555

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 70%


CAL1000/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

20.6 kgm2

Circumferential speed,
u

0.052 x n, m/s

Impeller of SAF-2205
Max. 2088 RPM
At 45 C max. 1940 RPM
At 70 C max. 1858 RPM
Impeller of AISI 316L
Max. 1367 RPM
At 45 C max. 1300 RPM
At 70 C max. 1251 RPM
For fans used in the shaded areas, it
is necessary to consider whether the
required power can be achieved with
the maximum motor size.
CAL1120/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

31.7 kgm2

Circumferential speed,
u

0.059 x n, m/s

Impeller of SAF-2205
Max. 1761 RPM
At 45 C max. 1636 RPM
At 70 C max. 1567 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
556

Medium-Pressure Centrifugal Fans CAL

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves 70%


CAL1250/70

= 1.20 kg/m3

Polar mass moment of inertia,


Iv

49.1 kgm2

Circumferential speed,
u

0.065 x n, m/s

Impeller of SAF-2205
Max. 1494 RPM
At 45 C max. 1388 RPM
At 70 C max. 1329 RPM

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CAL

557

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Low-Pressure Centrifugal Fans


CNA and CNB

Bearing assembly on CNB-500 to - 1000 must be

Centrifugal fans types CNA and CNB are light-

maintenance instructions).

greased, the others are greased for life (please see

weight, compact low pressure fans designed for


universal installation in marine systems.
Type CNA is available in nine sizes with impeller
diameters from 250 mm to 1000 mm, air volumes
from 0.2 m3/s to 14 m3/s and total pressure up to
approx. 1000 Pa.
Type CNB is available in seven sizes with impeller diameters from 400 to 1000 mm and is designed for higher speeds with air volumes from
0.8 m3/s up to 18 m3/s and a total pressure up to
1500 Pa.
Both CNA and CNB comprise the following main
components:
Fan Casing
Fan casing made up of two rectangular side plates
and a scroll plate.
Centrifugal Fan Type CNA/B

Inlet Cone
Inlet cone fitted in the front side plate of the fan
with boss for duct connection. The inlet cone is
specially designed to guide the air to the impeller
without loss in pressure.

All fan parts are protected against ordinary atmospheric corrosion.

Impeller
The impeller is with broad, backward curved
blades.

Accessories
Motor
The motor is according to specification.

Bearing Assembly
Bearing assembly with two dust and waterproof,
totally enclosed deep groove ball bearings in a
flange bearing casing, mounted on the rear side
plate of the fan or two flange bearings mounted in
two covers.

Surface Treatment

Motor Mounting
For mounting of motors not exceeding the sizes
stated on page 561 for the flanges of the fan casing. The mounting plate is adjustable for tensioning of the belts.
Base Frame
Common base frame for mounting of motors
larger than the sizes stated on page 561 beside the
fan.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
558

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

The sizes 250, 315 and 400 are also available


with direct coupled flanged motor mounted on
the rear side plate of the fan.
The sizes 500 and 630 are also available with di-

Positions
Direction of rotation RD or LG.
Motor positions 1, 2, 3 and 4 refer to the location
of the motor in relation to the outlet opening.

rect coupled footmounted motor mounted on


pedestal.
Belt Drive
Belt drive consisting of pulleys, v-belts, and belt
guard.
Flexible Connections
Flexible connections for inlet boss and outlet
flange.
Counter Flange
Counter flange for fan outlet.
Wire Guard
Wire guard for inlet opening.
Anti-vibration mountings
The anti-vibration mountings are of type LYDO.
Inlet Vane Control
Inlet vane control for control of fan capacity.
An inlet flange is required for the mounting of the
inlet vane control on sizes -710 to -1000.
Inlet Flange
Inlet flange for mounting on fan inlet boss. Also
used for attachment of flexible connection to the
inlet vane control.
Inspection Door
Inspection door in fan casing scroll plate.
Drain Connection
Please see page 563.
Spark proof Inlet Cone
Spark proof inlet cone for fans in mechanical ventilation systems of hazardous spaces.
Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

559

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensions

With belt drive

Direct coupled
CNA-250, -315, -400

CNA-500, -600

CNB-400

CNB-500, -630

All sizes

Dimensions in mm
CNA
CNB

F1

-250

250

175

30

250

235

310

250

245

200

-315

315

220

30

315

280

410

280

345

250

-400

400

280

30

400

340

485

315

400

300

-500

500

350

35

500

420

600

400

500

350

-630

630

440

35

630

510

758

488

623

440

-710

710

497

40

710

577

870

535

670

465

-800

800

560

40

800

640

976

604

754

516

-900

900

630

45

900

720

1098

680

847

573

-1000

1000

700

45

1000

790

1215

750

940

640

Dimensions in mm

Weight*, kg

CNA
CNB

H1

CNA

-250

560

445

150

207

60

12

22

-315

690

595

160

252

100

12

35

-400

800

700

145

312

100

12

53

55

-500

1000

850

170

392

125

15

89

98

CNB

-630

1246

1063

250

482

125

15

146

161

-710

1405

1135

260

537

63

15

238

262

-800

1580

1270

280

600

85

15

304

334

-900

1778

1420

300

680

110

15

350

385

-1000

1965

1580

360

750

90

15

487

535

*Weight excl. of motor and belt drive

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
560

G1

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Outlet Flanges
Dimensions in mm
CNA
CNB

-250

207

-315

252

-400

312

85

282

110

110

347

143

140

432

185

-500

386

125

536

155

-630

476

170

666

200

-710

537

150

750

170

-800

600

170

840

175

-900

680

195

950

200

-1000

750

160

1050

180

Counter Flanges
Counter flanges (4 strips) with bolt holes as in the
outlet flanges are available as optional extras.
Ducts
Ducts are made with the same inside dimensions
as the fan outlet opening (A x B).

Motor Mounting Arrangements


The tables shows the maximum motor sizes that
can be mounted direct on the fans
Fan size

Motor size
for direct coupled

Max. motor on side


vertical mounting plate
Type
Weight

Max. motor on top


horizontal mounting plate
Type
Weight

250

71 90

90

20

90

20

315

71 100

112

40

112

40

400

80 100

112

40

112

40

500

112 132

132

70

132

70

630

160 1

132

70

132

70

710

132

70

160

140

800

132

70

160

40

900

132

70

180 2

190

1000

132

70

180

190

1.
2.

CNA max. 132


CNA max. 160

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

561

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Base frame for fan and motor


Motors of larger sizes should be mounted on slide
rails beside the fan.
A common base frame supporting both fan and
motor as illustrated in the sketches can be supplied. Please specify required motor position (pos.
W or Z, please see below).

Position Designations
Position according to EUROVENT
Note
Fan positions for base frame mounting must be in
accordance with EUROVENT

Shaft Extension

CNA

CNB

Fan size

250

24j6

50

27

315

24j6

50

27

400

24j6

50

27

28j6

50

1
41

500

28j6

50

31

38k6

90

10

630

32k6

60

10

35

48k6

90

14

51

710

35h8

100

10

38

55m6

100

16

59

800

40h8

100

12

43

55m6

100

16

59

900

40h8

100

12

43

60m6

115

18

64

1000

55h8

100

16

59

60m6

115

18

64

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
562

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Accessories

Flexible Connection, Inlet

Flexible Connection, Outlet

Drain Connection Inspection Door

Types CNA and CNB are available with inspection door in scroll plate of casing and drain connection.
When ordering please state location of inspection
door and drain connection in ralation to the outlet
direction, e.g.
Inspection door pos. RD 120
Drain connection pos. RD 180

Duct Connection

CNA
CNB

250

310

280

250

10

315

385

355

315

10

400

480

450

400

12

500

590

560

500

12

12

630

720

690

630

12

12

710

790

765

710

10

14

800

880

850

800

10

14

900

1000

970

900

16

14

1000

1080

1050

1000

16

14

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

563

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Conical Inlet Vane Control for Size 250 - 630


The inlet vane control is mounted direct on the inlet boss of the fan.
Use an inlet flange for attachment of flexible connection.
The performance curves beginning on page 565
apply to fans without inlet vane control.
NOTE: Do not forget control.

CNA
CNB

Weight
kg

D1

D2

250

377

355

315

250

150

10

70

10

315

482

450

400

315

190

12

87

12

400

592

560

500

400

215

12

12

111

16

500

722

690

630

500

284

12

12

138

25

630

893

860

800

630

365

16

12

174

45

QBA Inlet Vane Control for Size 710 - 1000


The inlet vane control is mounted on the fan by
means of an inlet flange.
Use an inlet flange for attachment of flexible connection.
The performance curves beginning on page 565
apply to the fans without inlet vane control.

CNA
CNB

710
800

800

765

715

250

10

14

56

880

850

800

250

10

14

74

900

1000

970

900

350

16

15

91

1000

1090

1050

1000

350

16

15

100

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
564

Weight
kg

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

3600 r.p.m. (direct

n=3600

1200

0.025 kgm

3200

1000

95dB

3000

800

2800 92dB

Impeller tip speed


u

65

1.20 kg/m3

60

Iv

pt, Pa

3400

coupled)

max.=

= 65%

1400

71%

3150 r.p.m. (belt driven)

70

max.=

70%

CNA250-D

71%

Performance Curves

50

2600

0.013 x n, m/s

89dB

600

40

2400

220086dB
400

2000

83dB

pd + p 2

p1

0.5

10

20
100
200

300

10

20

m3/s
m/s

200

100

pd

1k

0.
5

0.

0.1

qv

6
0.

0.

4
0.

pd

0.2

0.

200

0.

1800
1600
1400

300
400

Pa
Pa

30

Pa

max.=

3000 r.p.m.

1.20 kg/m3

Iv

0.05 kgm2

Impeller tip speed


u

0.016 x n, m/s

pt, Pa

CNA315

Sound data:

Symbols:

Please see page 587

pt

total pressure

pd

p1

p2

qv

volume flow

dynamic pressure, outlet n

speed, r.p.m.

connection loss, inlet

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

efficiency, %

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

565

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CNA400
max.=

1950 r.p.m.

Iv

0.175 kgm2

max.=

2380 r.p.m.

Iv

0.3 kgm2

pt, Pa

CNB400

Impeller tip speed


u

0.021 x n, m/s

1.20 kg/m3

CNA500
max.=

1575 r.p.m.

Iv

0.55 kgm2

max.=

1925 r.p.m.

Iv

0.75 kgm2

pt, Pa

CNB500

Impeller tip speed


u

0.026 x n, m/s

1.20 kg/m3

Sound data:

Symbols:

Please see page 587

pt

total pressure

pd

p1

p2

qv

volume flow

dynamic pressure, outlet n

speed, r.p.m.

connection loss, inlet

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

efficiency, %

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
566

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CNA630
max.=

1240 r.p.m.

Iv

1.35 kgm2

max.=

1515 r.p.m.

Iv

1.85 kgm2

pt, Pa

CNB630

Impeller tip speed


u

0.033 x n, m/s

1.20 kg/m3

CNA710
max.=

1105 r.p.m.

Iv

3 kgm2

max.=

1350 r.p.m.

Iv

3 kgm2

pt, Pa

CNB710

Impeller tip speed


u

0.037 x n, m/s

1.20 kg/m3

Sound data:

Symbols:

Please see page 587

pt

total pressure

pd

p1

p2

qv

volume flow

dynamic pressure, outlet n

speed, r.p.m.

connection loss, inlet

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

efficiency, %

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

567

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CNA800
max.=

975 r.p.m.

Iv

5 kgm2

max.=

1190 r.p.m.

Iv

5 kgm2

pt, Pa

CNB800

Impeller tip speed


u

0.042 x n, m/s

1.20 kg/m3

CNA900
max.=

870 r.p.m.

Iv

7.75 kgm2

max.=

1065 r.p.m.

Iv

7.75 kgm2

pt, Pa

CNB900

Impeller tip speed


u

0.047 x n, m/s

1.20 kg/m3

Sound data:

Symbols:

Please see page 587

pt

total pressure

pd

p1

p2

qv

volume flow

dynamic pressure, outlet n

speed, r.p.m.

connection loss, inlet

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

efficiency, %

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
568

Low-Pressure Centrifugal Fans CNA and CNB

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CNA1000
max.=

785 r.p.m.

Iv

14 kgm2

max.=

960 r.p.m.

Iv

14 kgm2

pt, Pa

CNB1000

Impeller tip speed


u

0.052 x n, m/s

1.20 kg/m3

Sound data:

Symbols:

Please see page 587

pt

total pressure

pd

p1

p2

qv

volume flow

dynamic pressure, outlet n

speed, r.p.m.

connection loss, inlet

connection loss, outlet

kW =

power required, impeller

air velocity, outlet

dB

sound power level, outlet

efficiency, %

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low-Pressure Centrifugal Fans CNA and CNB

569

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Low- and Medium-Pressure


Centrifugal Fans CND and CNF

Alternatively, by special agreement and at addi-

Centrifugal fans of type CND and CNF are light

steel AISI 316L.

tional cost, the fans can also be made of stainless

and compact low- and medium pressure fans designed for installation in aggressive environments.

Motors

The motors fitted in the CND and CNF are either

The type CND is produced in 7 sizes with impeller diameters from 315 mm to 710 mm, airflow
rates from 0.2 m3/s to 10 m3/s and total pressures
up to approximately 2000 Pa.

direct coupled or belt-driven.


Requirement: B5 flange (large flange) for all motor
sizes for directly coupled motors and B3 (base) for
belt-driven motors.

The type CNF is produced in 6 sizes with impeller

Environment

diameters from 400 mm to 710 mm, airflow rates

Centrifugal fan types CND and CNF are designed

from 0.2 m /s to 11 m /s and total pressures up to

for the temperature range -20C to +70C.

approximately 4000 Pa.


Galvanised versions meet the requirements for
The CND and CNF have both the following main

operation in medium-level corrosive environ-

components.

ments in accordance with DS/EN ISO 12944-2,


corrosion category C3.

Fan housing constructed from two rectan-

The stainless version of the fans is designed, with

gular side panels and an all-welded casing.

regard to materials and finishing, to function in

Inlet funnel mounted in the front side panel

corrosion category C5-I (very high), as formulated

of the fan with a boss for duct connection and

in DS/EN ISO 12944-2.

designed to conduct air to the impeller with as


little loss as possible.
Impeller with 8 backward-curved blades.
The impellers in the CND and CNF share the
same design and are produced with the same
geometry and material. The CND is, however,
partially welded, while the CNF is all-welded.
The CNF is thus designed for operation with
higher RPMs.
Bearing part with two dustproof and waterproof deep groove ball bearings mounted in
flanged bearing housings. The bearings have
lifetime lubrication.
Centrifugal Fan Type CND

Surface Treatment and Material

All parts of the fans are treated with a 60 m hotdip galvanisation for protection.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
570

Low- and Medium-Pressure Centrifugal Fans CND and CNF

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Accessories

Spark proof Inlet Funnel


Spark proof inlet funnels for use in environments

Duct Boss - Inlet


This is fitted as standard on both CND and CNF.
Loose duct bosses are available for connection of

with increased security are available for both the


CND and CNF.

ducts with flexible connections.


Flexible Connections
For duct boss and outlet flange.
Versions (materials) for both circular (inlet) and
square (outlet) connections.
Mating Flange
For installation on the outlet of the fan.
The mating flanges consist of welded steel frames
and are finished with min. 60 m hot-dip galvanisation.
Inspection Hatch
The CND and CNF are available with an inspection hatch located in the casing of the housing.
Inspection hatches are available in 2 sizes, depending on the fan size.
The location of the inspection hatch in relation to
the outlet direction must be stated on order.
Drain Plug
The location of the drain plug in the side panels of
the fan housing in relation to the outlet direction
must be stated on order.
Wire guards
Wire guards are available for the inlet (circular)
and outlet (square), respectively.
Anti-Vibration Mountings
Both the CND and CNF are available with anti-vibration mountings.
The location and choice of anti-vibration mountings are shown in the installation instructions.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

571

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensions
H

45

B1

A1

A
E
G

CND/CNF
Size

1.

For anti-vibration mountings J

A
A1
B
B1
C
D
E
F1
G
H
J
K
L approx.
S
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
[mm]
[mm]

315

690

410

595

345

252

315

280

ML-24

297

525

11.5

335

1,040

100

400

800

485

700

400

312

400

340

ML-24

357

585

11.5

430

1,120

125

450

891

543

760

445

347

450

375

ML-29

392

655

14

480

1,175

125

500

1,000

600

850

500

392

500

420

ML-29

443

690

14

535

1,255

125

560

1,121

673

953

560

437

560

465

ML-29

488

795

14

595

1,440

125

630

1,246

760

1,063

622

482

630

510

ML-26

533

840

14

665

1,525

125

710

1,405

869

1,135

672

537

710

577

ML-31

595

910

14

750

1,620

125

ML in this column means Motor Length.

Weights
CND/CNF
Size
315

Weight, direct coupled, Weight, belt-driven,


excl. motor [kg]
excl. motor [kg]
40

62

400

59

78

450

77

100

500

84

118

560

113

165

630

153

206

710

187

255

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
572

Low- and Medium-Pressure Centrifugal Fans CND and CNF

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Outlet Flanges
Mating flanges with the same size bolt holes as

G
P stk. x R

dimensions as the outlet opening of the fan (A x

NxT

Connection ducts are made with the same internal

the outlet flanges are available as accessories.

MxK

B).
B

CND/CNF
Size

A
[mm]

B
[mm]

C
[mm]

F
[mm]

G
[mm]

K
[mm]

315

315

220

30

347

252

110

400

400

280

30

432

312

140

M
[mm]

N
[mm]

T
[mm]

P
[qty.]

R
[mm]

142,5

10

185

10

450

450

315

30

482

347

125

185

12

500

500

350

35

536

386

125

155

14

560

560

395

35

596

431

125

155

14

630

630

440

35

666

476

170

200

14

710

710

497

40

750

537

150

170

18

10

Motor Sizes and Position Designations


RD 0

RD 90

RD 180

RD 270

Direct coupled and low


motor bracket for belt drive

LG 0

LG 90

LG/1

LG/2

LG 180

LG/3

LG 270

LG/4

Belt

drive

with

motor

mounted on fan housing

RD/1

RD/2

RD/3

RD/4

The positions are according to EUROVENT and seen from the motor side.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

573

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Position Designations for Impeller

Pos. LG

Pos. RD

Motor Sizes
CND/CNF
Size

- 80

- 90

- 100

Motor Size
- 112

315

- 132

400

450

500

- 160

560

630

710

- 180

*
*

Please note that motor flange B5 is a large flange

motor must be coordinated with the motor cover

and for all motor sizes. The junction box of the

of the fan.

Max. RPM
The CND and CNF share the same design and are

Max. RPM

produced with the same geometry and material.

CND/CNF
Size

CND

The CND is, however, partially welded, while the

315

4618

5874

CNF is all-welded. The CNF is thus designed for

400

3426

4090

operation with higher RPMs.

450

2957

3365

500

2592

2927

560

2249

2464

630

2086

2387

710

1797

1994

Steel quality: Domex 500


Surface treatment: Hot-dip galvanisation, approx.
60 m zinc.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
574

Low- and Medium-Pressure Centrifugal Fans CND and CNF

CNF

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Motor Installation
The maximum allowable motor sizes that can be
installed directly on the fans appear from the below tables

Motor on side
- vertical motor panel

Motor Installation Sizes for


Direct Coupled Motors

Belt-driven - motor on side

CND/CNF Motor InstallaSize


tion Size

CND/CNF
Size

Motor on top
- horizontal motor panel

Belt-driven - motor on top

Max. Motor
Type Weight [kg]

CND/CNF
Size

Max. Motor
Type Weight [kg]

315

80 - 112

315

112

40

315

112

40

400

80 - 132

400

112

40

400

112

40

450

80 - 132

450

112

40

450

112

40

500

80 - 132

500

132

70

500

132

70

560

100 - 160

560

132

70

560

132

70

630

100 - 160

630

132

70

630

132

140

710

112 - 180

710

132

70

710

160

140

Low-Mounted Bracket for Large Motors


Large motors are mounted on low motor brackets
that are bolted to the fan housing. The low centre
of gravity and the large distances between the installation points give a stable installation for large
motors.
The required motor and fan positions are shown
to the right.

Shaft End

CND/CNF
Size

315

28h6

30

31

400

28h6

30

31

450

38h6

50

10

41

500

38h6

50

10

41

560

48h6

70

14

51

630

48h6

70

14

51

710

65h6

70

18

69

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

575

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensioning Curves
The shaded areas in the below figures indicate the
maximum working ranges for the standard motor
sizes.

Da

3 x Da

Basis for chart (Arr. D)

D1

1 x D1

CND-315
Max.
Ipt

Symbols
Pt = Total pressure

qv

= Volume flow

Pd = Dynamic pressure, outlet

= RPM

P1 = Connection loss, inlet

= efficiency in %

P2 = Connection loss, outlet

kW = Power demand, impeller

v = air speed, outlet

dB = Sound power level, outlet

6000

= 4,618 RPM
= 0.0951 kg x m

60

70

65

70

74

74

Pt,
Pa

65

5000

2
109 dB

4000

CNF-315
Max.

= 5,874 RPM

Ipt

= 0.0951 kg x m2

= 1.20 kg/m3 (at 20 C)

106 dB

3000

400

103 dB

350
000

2000

100 dB

97 dB

0
250

94 dB
91 dB

Pd

Pd + P2

P1

10

4.5

0.5

qv

2.2

1.5

30

20

40
1000

500
1000

500
50

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

3 m3/s
m/s

2.5

1.5

88 dB

7.5

200

9k

1000

576

60%

Max. speed 618


4
CND

1500
100

Pa
Pa
Pa

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CND-400

CNF

CND

Max.

= 3,426 RPM

Ipt

= 0.2440 kg x m2

5000

60

Pt,
Pa

= 4,090 RPM

Ipt

= 0.2440 kg x m2

= 1.20 kg/m3 (at 20 C)

300

103 dB

2000

100 dB

250

97 dB
200

94 dB
91 dB

Pd + P2

P1

CND-450

20

40

30

200

300

400

500

600

500
20

10

CND

m3/s
m/s

10

800

50

60

65

Max. speed = 33
n
CNF

65 70

60

75

77

70

77

Ipt

= 0.4218 kg x m2

= 1.20 kg/m3 (at 20 C)

Pa

80

90

70

75

65
106 dB

Max. speed 957


2
CND

3000

= 3,365 RPM

Pa

Pa

CNF-450
Max.

900

1000
40

30

700

CNF

4000
pt,
Pa

100

kW

Pd

85
7.
7

qv

Pd

10
9

= 0.4218 kg x m2

60%

106 dB

150

Ipt

70

65

= 2,957 RPM

75

77

Max. speed 426


3
CND

3000

1000

Max.

77

4000

CNF-400
Max.

75

70

65

Max. speed 4090


n=
CNF

60%

260

103 dB

2000
100 dB

220

97 dB
0

180

1000

94 dB
91 dB

10

140

qv

Pd

Pd + P2

P1

kW

3
5 m /s

m/s
10

20
100

200

30
300

10000
10

20

400

500

20000
30

40

40
600

700

30000
50

60

Pa
Pa
Pa

70

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

577

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CND-500

CND

Max.

= 2,592 RPM

Ipt

= 0.6430 kg x m2

pt,
Pa

Max. speed
CNF

Ipt

= 0.6430 kg x m2

= 1.20 kg/m3 (at 20 C)

7
292

60

65

75

70

79

79

75

70

2
Max. speed
259
CND

CNF-500
= 2,927 RPM

n=

106 dB

3000

Max.

CNF

4000

65
103 dB
60%

0
220

2000

100 dB
0
180

97 dB
94 dB

0
150

1000

91 dB
9

k
11

0
120

Pd

Pd + P2

P1

qv

6 m3/s

m/s

CND-560
= 2,249 RPM

Ipt

= 1.0212 kg x m2

Max.

= 2,464 RPM

Ipt

= 1.0212 kg x m2

30

200

300

400

500

Pa
600

500
10

20

700
1000

30

40

50

60

Pa
Pa

70

CNF
60

65

70

80

75

81

81

80

75

Max. speed
4
246
CNF
n=

3000
pt,
Pa

CNF-560

20
100

CND

Max.

10

Max. speed
9
CND
224

70

65

2000

190

60%
106 dB

= 1.20 kg/m (at 20 C)

160

1000

103 dB

0
130

100 dB
97 dB
94 dB

91 dB

Pd + P2

P1

Pd

7
6

qv

k
11
10

100

7 m3/s

m/s
30

20

10
100

200

300

400

20

30

40

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
578

Low- and Medium-Pressure Centrifugal Fans CND and CNF

600 Pa

10000

5000
10

500

Pa

50

Pa
60

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

CND-630

CNF

CND

Max.

= 2,086 RPM

Ipt

= 2.2571 kg x m2

4000

Max. speed
387
n=2
CNF

pt,
Pa

Max.

= 2,387 RPM

Ipt

= 2.2571 kg x m2

= 1.20 kg/m3 (at 20 C)

70

83

80

75

80

83

75

Max. speed
2086
CND

3000

CNF-630

60 65

109 dB

1800

70

65

106 dB

2000

60%

1600

103 dB

1400

1000

100 dB
97 dB

1200
94 dB

1000

18
kW

14

16

12

qv 1

10

m /s

m/s

CND-710

Pd

Pd + P2

P1

CND

Max.

= 1,797 RPM

IVent

= 3.6479 kg x m2

= 1,994 RPM

IVent

= 3.6479 kg x m2

= 1.20 kg/m3 (at 20 C)

10

30

20
100

200

300

10

20

30

400

500

600

40

50

60

500

Pa
700 Pa
1000 Pa

70

CNF

94
Max. speed
19
CNF
n=

60 65

70

75

75

80

84 84

80

3000
pt,
Pa

109 dB

Max. speed 1797


CND

CNF-710
Max.

106 dB

1600

65

2000

60 %
103 dB

1400
100 dB

1200

1000

97 dB

1000

94 dB

kW

18

20

16
14

10

12

8
6

0
0

qv

Pd

Pd + P2

P1

20
100

m /s

10

5
10
200

m/s
30

300

400

500

Pa
600

500
10

20

30

700
1000

40

50

60

Pa
Pa

70

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

579

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Accessories
Duct bosses
These are fitted as standard on both the CND and
CNF.
Loose duct bosses are available for connection of
ducts with flexible connections.
Material: Steel
Surface treatment: Hot-dip galvanised, approx.
60 m
Duct bosses

Flexible Connections
These are for duct bosses and outlet flanges and
available in both flameproof and incombustible
materials.
Material quality: Perl E 6
Temperature range: -30 to +80 C
Material quality: Alpha Maritex
Temperature range: -36 to +260 C
Flexible Connections

Inlet

Outlet

Mating Flanges
These are or installation on the outlet of the fan.
The mating flanges are made of welded steel
frames.
Material: Steel Domex 240
Surface treatment: Hot-dip galvanised, approx.
60 m.
Mating Flanges

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
580

Low- and Medium-Pressure Centrifugal Fans CND and CNF

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Wire guards
These are available for both inlets (circular) and
outlets (square).
Material: Steel wire
Surface treatment: Electrogalvanised, approx.
20 m
Finish treatment: Passivated
Wire guards

Anti-Vibration Mountings
Both the CND and CNF are available with anti-vibration mountings.
Refer to the installation instructions for details on
the different kinds of mountings and their locations.

Anti-Vibration Mountings

Base Plate for Anti-Vibration Mountings


Both the CND and CNF are available with base
plates for fixing anti-vibration mountings to the
foundation.
Material: Domex 240
Surface treatment: Hot-dip galvanised, approx.
60 m
Base Plate for Anti-Vibration Mountings

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Low- and Medium-Pressure Centrifugal Fans CND and CNF

581

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Inspection Hatch
The CND and CNF are both available with an inspection hatch located in the casing of the housInspection hatches are available in 2 sizes, de-

300

200

ing.
pending on the fan size.
Please state the location of the inspection hatch
and drain plug in relation to the outlet direction
on order. See example below.

100
200

Inspection Hatch

Inspection hatch pos. RD 120


Drain plug pos. RD 180
Material: Domex 240
120o
180o

Surface treatment: Hot-dip galvanised, approx.


60 m

Drain Plug

Inspection Hatch

Drain Plug
Please state the location of the drain plug in the
side panels of the fan housing in relation to the
outlet direction on order.
Material: Stainless steel and hot-dip galvanised
fittings respectively.
Connection: 3/4 RG
Drain Plug

Spark proof Inlet Funnels


Spark proof inlet funnels for use in environments
with increased security are available for both the
CND and CNF.
Material: For example hard brass

Brass Inlet Funnels

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
582

Low- and Medium-Pressure Centrifugal Fans CND and CNF

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Medium-Pressure Centrifugal
Fans CMP

Optional Stainless steel fans


Optional ATEX approved construction with
category 2 certification for operation in explosive atmospheres

Technical Characteristics

The specifications of the CMP fans are summed


up below.

Model

Centrifugal Fan Type CMP

Max. current [A] Installed Max.


power airflow
RPMs 230 V 400 V
[kW]
[m3/s]

CMP-512-2T 2850

0.55

0.32

0.08

0.13

CMP-514-2T 2850

1.21

0.70

0.18

0.28

CMP-616-2T 2740

1.73

1.00

0.37

0.40

CMP-718-2T 2855

3.00

1.73

0.75

0.39

CMP-820-2T 2845

4.16

2.40

1.10

0.54

Centrifugal fans type CMP are single-inlet, light


and compact medium pressure fans designed for
installation in aggressive environments.
The multi-blade impeller and the casing are both
made from sheet steel.

Surface Treatment and Material

The CMP fans are made of sheet steel with impeller blades of galvanised sheet steel. Optionally the
fans can also be delivered in stainless steel.

The fans are available as single or two-speed versions in five sizes. Impeller diameters are from

The finish is a corrosion-proof polyester resin


which is polymerised at 190 C, after alkaline degreasing and phosphate-free pre-treatment.

140 to 247 mm, airflow rates from 0.13 to 0.54 m3/


s and total pressures up to approximately 1400 Pa.

Motors

The motors fitted in the CMP are direct coupled


and asynchronous of the squirrel-cage type. Op-

Main Characteristics

All the CMP models share the following main

tionally ATEX approved motors are also availa-

characteristics.

ble.
The motors are class F with ball bearings and have

Fan housing of sheet steel

IP55 protection, except single-phase models

Impeller with forward-facing blades made

which have IP54 protection.

from galvanised sheet steel

Single-phase 230V 50Hz., and three-phase 230/

Corrosion-proof finish in polyester resin

400V 50Hz. (up to 1.1 kW.) and 400/690V 50Hz.

Direct coupled class F motors

(power over 1.1 kW.). Special windings for differ-

Asynchronous motor with squirrel-cage motor

ent voltages are optional.

Optional Special windings for different voltages


Maximum airflow temperature is 120 C.
Optional Maximum airflow temperature of
250 C

Environment
Centrifugal fan types CMP are designed for maximum airflow temperatures up to 120 C. Optionally designs for 250 C are also available.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CMP

583

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Acoustic Characteristics

Guards

The below table shows the sound pressure levels

Guards are available for the inlet. It is made from

emitted by the CMP fans at a distance equivalent


to twice the fan span plus the impeller diameter or
at a minimum of 1.5 m.

Model

Octave band [Hz]


125 250 500 1k 2k

63

4k

sheet steel and is in accordance with the standard


UNE-100250.

8k

CMP-512-2T 37

47

58

65

69

66

64

57

CMP-514-2T 40

50

61

68

72

69

67

60

CMP-616-2T 44

54

65

72

76

73

71

64

CMP-718-2T 45

55

66

73

77

74

72

65

CMP-820-2T 48

58

69

76

80

77

75

68

Guard Type RPA

Accessories
Duct bosses Inlets and Outlets
Adaptor duct bosses for both inlets and outlets
are available for fitting the fans on to ducts.

Duct Boss Type B

Mating Flanges Outlets


An adaptor mating flanges for connecting outlets
to circular ducts is available.

Mating Flange Type BIC

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
584

Medium-Pressure Centrifugal Fans CMP

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Dimensions
d2

C
C1

d2

d1

d1

D1

45
D1

C2

90
d
B1

O k2

O k2

J1

J2

LJ J2
K

CMP
Size

B1

B2

512

182

207

118

514-2

225

254

150

616-2

258

297 173.5

718-2T
820-2T
1.

303.5 348
322

LJ

J1

377

C1

250.5 211.5

I
C

H1

B2

C2

D11 d d1 d2

39

112

140

132

H1

J1

J2

M.4

81

69

106 118

105 75

K k2

86

5.5

91

122 147

64

128 83 105 107

6.5

105.5 153 172

147 103 128 125

85

93

L O

252

207

45

140

169 151.5

M.4

100

295

239

56

160

204

180

M.6

110

201

358

294

64

180

238

210

M.6

129.5

122

169 192

170 115 145 146

223

335.5

267

68.5

200

247

230

M.6

137.5

137

184 213 94.5 189 130 160 156

Recommended nominal duct diameter

Weights
Model

Approx.
weight [kg]

CMP-512-2T

4.0

CMP-514-2T

5.0

CMP-616-2T

8.0

CMP-718-2T

12.5

CMP-820-2T

15.0

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Medium-Pressure Centrifugal Fans CMP

585

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Performance Curves
1400
1200
820
Total pressure [Pa]

1000
718
800
600

616

514
400
512
200

0
0

800

400

0.1

1200

0.2

0.3
Air flow

1600
0.4

[m3/h]

2000

0.6 [m3/s]

0.5

Position Designations
LG 0

LG 45

LG 90

LG 180

LG 270

LG 315

RD 0

RD 45

RD 90

RD 180

RD 270

RD 315

The positions are according to EUROVENT and seen from the motor side.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
586

Medium-Pressure Centrifugal Fans CMP

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Sound Conditions

The sound pressure level often just referred to as

Generation of sound by fans in operation is una-

sound level describes the sound impression per-

voidable. In connection with fans sound is pro-

ceived by the human ear at a given distance from

duced by the passage of air through the fan unit

the fan. It is measured using a sound level meter,

and by moving parts in components such as the

which means a microphone is placed at the point

motor and bearings.

in question.
The sound pressure level depends in other words

The sound can be kept within bounds by careful

on the sound power level, the distance from the

design and construction of fan components. As far

fan, and the sound absorbing properties of the

as sound generated by air in motion is concerned,

surroundings.

it is especially the inlet cone and impeller that add


to the sound level. Here it should be kept in mind

Describing acoustic properties of fans based on

that adverse installation conditions, for instance

sound pressure levels must include an accurate

sharp bends immediately in front of the inlet

description of the conditions under which the

opening, can increase the sound generation con-

sound pressure levels are measured. Furthermore,

siderably.

in order to compare sound pressure levels the


measurement setups have to be identical. For ex-

The sound generated by motor and machinery as

ample with regard to the distances from the fans

well as the sound caused by air in motion which

to sound absorbing surroundings.

escapes through the fan housing, can be dampened by enclosing the fan. This is, for example,

In properly designed fans the sound power levels

done by surrounding the fan with a casing or

depend almost entirely on the supplied air vol-

walls of low-vibration materials.

ume and the total pressure of the fan.

The sound generated by the impeller is transmit-

The sound power levels of the CNA and CNB fans

ted through the fan inlet and outlet to the ducting

appear from the performance curves beginning on

and thence to the ventilated spaces. Any calcula-

page 565. The sound power levels of the CAL, and

tion of sound conditions in the duct system and

CND and CNF fans appear from the dimension-

the ventilated spaces - as well as the design of any

ing curves on pages 545 and 576, respectively.

anti-vibration mountings to be installed in the

The sound power levels are indicated in terms of

system must be based on the sound power level

dB ref. 10-12 W, which apply to the normal field of

in the fan inlet and outlet. In dealing with sound it

operation of the fan and have a tolerance of 5 dB.

is essential to distinguish between sound power

To divide the sound power levels into octaves, the

levels and sound pressure levels they cannot be

sound power level within each octave band is de-

compared.

termined by subtracting the correction values


listed in the below table from the total sound

The sound power level describes the sound en-

power levels.

ergy transmitted through the fan inlet and outlet

The correction values depend on the blade fre-

openings. It forms the basis of all calculations of

quency

sound conditions in the duct systems and the


spaces served by the fan.

given

by

the

equation

z n- , where z is the number of


Blade frequency = ----------60

blades and n the fan speed in r.p.m.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Sound Conditions

587

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

The CAL has 8 blades. The CNA and CNB each


have 12 blades. The CND and CNF each have 8
blades.
Example
A centrifugal fan type CNA-315 delivers 0.6 m3/s
against 300 Pa at 1400 r.p.m. This gives a blade
frequency of 280 Hz (= 12 x 1400 / 60). From the
charts beginning on page 565 the total sound
power level is found to be 85 dB. The correction
value for 250 Hz is 4 dB. See the table below.
Hence, the sound power level of this octave band
is 85 dB 4 dB = 81 dB. The complete octave band
analysis is given in the second table below.
Octave band, Hz
Bladefrequency

63

125

250

500

1k

2k

4k

90-180 Hz

12

17

22

27

8k
32

180-360 Hz

11

12

17

22

27

360-710 Hz

13

11

12

17

22

710-1400 Hz

15

13

10

12

18

63

125

250

500

1k

2k

4k

8k

74

78

81

78

73

68

63

58

Correction Values for CNA, CNB, CND and CNF


Octave band, Hz
Sound power level, dB

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
588

Sound Conditions

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Control of Air Volume

Frequency Conversion

Dependent on operating requirements fan capac-

Used under the same operating conditions as inlet

ity can be controlled in several ways.

vane control, the fan efficiency remain close to unchanged in the entire downwards controlled area

Pole changing between 2 fixed fan speeds in

and less sound is generated during the down-

the proportion 3 : 2 (motor with 2 separate

wards control. Frequency conversion is therefore

windings) or 2 : 1 (motor with Dahlander

a good approach if more than two speeds are

windings)

needed.

Inlet vane control on the inlet side of the fan


Speed control through frequency conversion
A combination of the above methods

Pole Changing

80
%

example if the system is to switch between day to


night operation, it is recommended to provide the
fan with a pole-changeable motor. When changing to another speed the fan efficiency remains

Total pressure [Pa]

In case of varying air volume requirements, for

70
60

50%

40%
30%

unchanged.

60

20%

A timer can be used to control the pole changing.

80

90

50o

10%

40o
30o

If other operating points are required than those

70

20o

Aperture

10o

obtainable by pole changing, then alternative

Air volume, qv [m3/s]

methods of control must be applied.

Principle diagram showing relation between aperture angle


and efficiency when downward controlling with inlet vane

Inlet Vane Control


Control of the inlet vanes is typically used when

control.

requirements for air volume is changing constantly. It is also used in systems where the air
volume must remain constant regardless of outside pressure conditions.
The inlet vane control can be operated by a servomotor controlled by a pressurestat or a flow sensor.
At reduced flow control the fan efficiency drops
as indicated on the performance chart. In case of
large variations in air volume it is therefore recommended to combine the inlet vane control with
pole changing.

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
Control of Air Volume

589

HI-PRES MARINE & OFFSHORE

5.2 Centrifugal Fans

Products

Owing to continued product development Novenco reserves the right to introduce alterations without prior notice
590

Control of Air Volume