Contents
1. 650 series overview..............................................3
11. Logic..................................................................26
2. Application...........................................................3
12. Monitoring.........................................................28
3. Available functions...............................................6
13. Metering............................................................30
4. Impedance protection........................................17
5. Current protection..............................................19
6. Voltage protection..............................................21
7. Frequency protection.........................................22
9. Control................................................................23
20. Ordering............................................................88
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes
no responsibility for any errors that may appear in this document.
Copyright 2011 ABB AB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
ABB
2. Application
REL650 is used for the protection, control
and monitoring of overhead lines and cables
in solidly or impedance earthed networks.
The IED can be used up to the high voltage
levels. It is suitable for the protection of
heavily loaded lines and multi-terminal lines
where the requirement for fast three-phase
tripping is wanted.
The full scheme distance protection provides
protection of power lines with high
sensitivity and low requirement on remote
ABB
WA1
WA2
132kV/
110V
132kV/
110V
QB2
QB1
79
QC1
QA1
Meter.
C MMXU
52PD
QC2
50BF 3I> BF
1000/1
CC RBRF
QB9
0->1
SMB RREC
37
PD
50STB
STB PTOC
50
50N
3I>>
P<
32
Meter.
CV MMXN
P>
IN>>
51/67
GOP PDOP
3I>
OC4 PTOC
68
21
ZM RPSB
ZDN RDIR
1->0
25
SYNC
SES RSYN
Meter.
C MSQI
46
26
q>
L PTTR
51N/67N
Cond
S SCBR
67N
Ph Sel
FDPS PDIS
IN<->
SDEPSDE
SOTF
IN>
EF4 PTOC
Z<->
SDD RFUF
Iub
BRC PTOC
EF PIOC
PH PIOC
GUP PDUP
I>
CC RPLD
94
SMP PTRC
ZCV PSOF
21
Z<
ZQD PDIS
Monit.
Wh<->
LMB RFLO
ETP MMTR
QC9
59
U>
OV2 PTOV
27
U<
UV2 PTUV
27
Meter.
U<
LOV PTUV
V MMXU
Meter.
Meter.
VNMMXU
V MSQI
132kV/110V
Line data
Line length: 50km
Positive sequence line impedance: 0.195+j*0.410 Ohms-Primary/km
Zero sequence line impedance: 0.400+j*1.310 Ohms-Primary/km
Function Enabled
in Settings
85
ZC PSCH
Cond
TCS SCBR
85
ZCRW PSCH
EC PSCH
85
ECRW PSCH
Mont.
DRP RDRE
Cond
ANSI
IEC
IEC61850
IEC
DNP
ANSI
IEC
IEC60870-5-103
IEC09000653-2-en.vsd
SPVN ZBAT
IEC09000653 V2 EN
Figure 1. A typical protection application for quadrilateral distance zones in a single breaker
arrangement
ABB
132 kV Bus
WA1
WA2
132kV/
110V
132kV/
110V
QB2
QB1
79
QC1
QA1
Meter.
52PD
QC2
50BF 3I> BF
CC RBRF
QB9
37
PD
50STB
STB PTOC
50
50N
3I>>
P<
32
Meter.
CV MMXN
P>
IN>>
C MSQI
46
51/67
GOP PDOP
3I>
OC4 PTOC
68
21
ZM RPSB
ZDN RDIR
1->0
25
SYNC
SES RSYN
26
q>
L PTTR
51N/67N
Cond
S SCBR
67N
IN<->
SDEPSDE
SOTF
IN>
EF4 PTOC
Ph Sel
Z<->
SDD RFUF
Iub
BRC PTOC
EF PIOC
PH PIOC
GUP PDUP
I>
CC RPLD
94
SMP PTRC
Meter.
C MMXU
1000/1
0->1
SMB RREC
FMPS PDIS
ZCV PSOF
21
Z<
ZMO PDIS
Monit.
Wh<->
LMB RFLO
ETP MMTR
QC9
59
U>
OV2 PTOV
27
U<
UV2 PTUV
27
Meter.
U<
LOV PTUV
V MMXU
Meter.
Meter.
VNMMXU
V MSQI
132kV/110V
Line data
Line length: 50km
Positive sequence line impedance: 0.195+j*0.410 Ohms-Primary/km
Zero sequence line impedance: 0.400+j*1.310 Ohms-Primary/km
Function Enabled
in Settings
85
ZC PSCH
Cond
TCS SCBR
85
ZCRW PSCH
EC PSCH
85
ECRW PSCH
Mont.
DRP RDRE
Cond
ANSI
IEC
IEC61850
ANSI
IEC
DNP
IEC
IEC60870-5-103
IEC09000654-2-en.vsd
SPVN ZBAT
IEC09000654 V2 EN
Figure 2. A typical protection application for mho distance zones in a single breaker
arrangement
ABB
132 kV Bus
WA1
REL650 A11 Quad Distance Zones,
1PH/3PH Tripping, Single Breaker
10AI (4I+1I+5U)
WA2
132kV/
110V
132kV/
110V
QB2
QB1
79
QC1
QA1
Meter.
C MMXU
52PD
QC2
50BF 3I> BF
1000/1
CSP RBRF
QB9
0->1
94
STB RREC
37
P<
Meter.
CV MMXN
50STB
I>
STB PTOC
50
50N
3I>>
P>
GOP PDOP
IN>>
51/67
3I>
OC4S PTOC
68
21
ZM RPSB
ZDN RDIR
25
SYNC
SES RSYN
Meter.
C MSQI
46
SDD RFUF
Iub
Cond
BRC PTOC
26
EF PIOC
SPT PIOC
32
GUP PDUP
PD
CC RPLD
1->0
STP PTRC
S SCBR
q>
37
51N/67N
SOTF
IN>
ZCV PSOF
EF4 PTOC
Ph Sel
Z<->
2I<
SDE PSDE
L PTTR
FDPS PDIS
21
Z<
ZQD PDIS
Monit.
Wh<->
LMB RFLO
ETP MMTR
QC9
59
U>
OV2 PTOV
27
U<
UV2 PTUV
27
Meter.
U<
LOV PTUV
V MMXU
Meter.
Meter.
V MSQI
VN MMXU
132kV/110V
Line data
Line length: 50km
Positive sequence line impedance: 0.195+j*0.410 Ohms-Primary/km
Zero sequence line impedance: 0.400+j*1.310 Ohms-Primary/km
Function Enabled
in Settings
85
ZC PSCH
Cond
TCS SCBR
85
ZCWS PSCH
EC PSCH
85
ECRW PSCH
Mont.
DRP RDRE
Cond
ANSI
IEC
IEC61850
IEC
DNP
ANSI
IEC
IEC60870-5-103
IEC10000342-1-en.vsd
SPVN ZBAT
IEC10000342 V1 EN
ABB
3. Available functions
Main protection functions
REL650 (A11)
1Ph/1CB
REL650 (A05)
3Ph/1CB, mho
Line Distance
REL650 (A01)
3Ph/1CB, quad
Impedance protection
ZQDPDIS
21
FDPSPDIS
21
ZMOPDIS
21
FMPSPDIS
21
ZDNRDIR
21
PPLPHIZ
ZMRPSB
ZCVPSOF
ABB
68
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
Function description
REL650 (A01)
3Ph/1CB, quad
Current protection
PHPIOC
50
SPTPIOC
50
OC4PTOC
51/67
OC4SPTOC
51/67
EFPIOC
50N
EF4PTOC
51N/
67N
SDEPSDE
67N
UC2PTUC
37
LPTTR
26
CCRBRF
50BF
CSPRBRF
50BF
STBPTOC
50STB
Stub protection
CCRPLD
52PD
BRCPTOC
46
GUPPDUP
37
GOPPDOP
32
DNSPTOC
46
1
1
1
1
ABB
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
Function description
REL650 (A01)
3Ph/1CB, quad
UV2PTUV
27
OV2PTOV
59
ROV2PTOV
59N
LOVPTUV
27
Voltage protection
Frequency protection
ABB
SAPTUF
81
Underfrequency function
SAPTOF
81
Overfrequency function
SAPFRC
81
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
SESRSYN
25
SMBRREC
79
Autorecloser
STBRREC
79
Autorecloser
Control
QCBAY
Bay control
LOCREM
LOCREMCTRL
SLGGIO
15
15
15
VSGGIO
20
20
20
DPGGIO
16
16
16
SPC8GGIO
AUTOBITS
I103CMD
I103IEDCMD
I103USRCMD
I103GENCMD
50
50
50
I103POSCMD
50
50
50
10
ABB
87
REL650 (A11)
1Ph/1CB
CCSRDIF
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
SDDRFUF
TCSSCBR
Logic
ABB
SMPPTRC
94
Tripping logic
SPTPTRC
94
Tripping logic
TMAGGIO
12
12
12
OR
283
283
283
INVERTER
140
140
140
PULSETIMER
40
40
40
GATE
40
40
40
XOR
40
40
40
LOOPDELAY
40
40
40
TIMERSET
40
40
40
AND
280
280
280
SRMEMORY
40
40
40
RSMEMORY
40
40
40
FXDSIGN
B16I
16
16
16
B16IFCVI
16
16
16
11
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
IB16A
16
16
16
IB16FCVB
16
16
16
CVMMXN
Measurements
CMMXU
10
10
10
VMMXU
CMSQI
VMSQI
VNMMXU
CNTGGIO
Event counter
DRPRDRE
Disturbance report
AxRADR
BxRBDR
SPGGIO
64
64
64
SP16GGIO
16
16
16
MVGGIO
16
16
16
MVEXP
66
66
66
LMBRFLO
Fault locator
SPVNZBAT
Monitoring
SSIMG
63
SSIML
71
SSCBR
12
ABB
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
I103MEAS
I103MEASUSR
I103AR
I103EF
I103FLTPROT
I103IED
I103SUPERV
I103USRDEF
20
20
20
PCGGIO
16
16
16
ETPMMTR
Metering
ABB
13
Designed to communicate
REL650 (A11)
1Ph/1CB
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
IEC61870-5-103
IEC60870-5-103 serial
communication via ST
GOOSEINTLKRCV
59
59
59
GOOSEBINRCV
GOOSEDPRCV
32
32
32
GOOSEINTRCV
32
32
32
GOOSEMVRCV
16
16
16
GOOSESPRCV
64
64
64
Station communication
Scheme communication
ZCPSCH
85
ZCRWPSCH
85
ZCWSPSCH
85
14
ABB
ABB
REL650 (A11)
1Ph/1CB
ZCLCPLAL
Line Distance
REL650 (A05)
3Ph/1CB, mho
REL650 (A01)
3Ph/1CB, quad
IEC 61850/
Function block
name
ECPSCH
85
ECRWPSCH
85
15
Function description
SELFSUPEVLST
SNTP
Time synchronization
TIMESYNCHGEN
Time synchronization
DTSBEGIN,
DTSEND,
TIMEZONE
IRIG-B
Time synchronization
SETGRPS
ACTVGRP
TESTMODE
CHNGLCK
TERMINALID
IED identifiers
PRODINF
Product information
PRIMVAL
SMAI_20_1-12
3PHSUM
12
GBASVAL
ATHSTAT
Authority status
ATHCHCK
Authority check
FTPACCS
DOSFRNT
DOSLAN1
DOSSCKT
16
ABB
4. Impedance protection
Five zone distance protection,
quadrilateral characteristic
ZQDPDIS
Five zone distance protection, quadrilateral
characteristic ZQDPDIS is a five zone full
scheme protection with three fault loops for
phase-to-phase faults and three fault loops
for phase-to-earth fault for each of the
independent zones. Individual settings for
each zone in resistive and reactive reach
gives flexibility for use as back-up protection
for transformer connected to overhead lines
and cables of different types and lengths.
ZQDPDIS together with Phase selection with
load encroachment FDPSPDIS has
functionality for load encroachment, which
increases the possibility to detect high
resistive faults on heavily loaded lines, as
shown in figure4.
X
Forward
operation
R
Reverse
operation
ABB
17
Operation area
Operation area
No operation area
en07000117.vsd
IEC07000117 V1 EN
18
No operation area
jX
Operation area
5. Current protection
Instantaneous phase overcurrent
protection PHPIOC
The instantaneous three phase overcurrent
function has a low transient overreach and
short tripping time to allow use as a high set
short-circuit protection function.
ABB
ABB
Directional over/underpower
protection GOPPDOP/GUPPDUP
The directional over-/under-power protection
GOPPDOP/GUPPDUP can be used wherever
ABB
6. Voltage protection
Two step undervoltage protection
UV2PTUV
Undervoltages can occur in the power system
during faults or abnormal conditions. Two
step undervoltage protection (UV2PTUV)
21
7. Frequency protection
22
Rate-of-change frequency
protection SAPFRC
Rate-of-change frequency protection function
(SAPFRC) gives an early indication of a main
disturbance in the system. SAPFRC can be
used for generation shedding, load shedding
and remedial action schemes. SAPFRC can
discriminate between positive or negative
change of frequency.
SAPFRC is provided with an undervoltage
blocking.
ABB
8. Secondary system
supervision
Current circuit supervision
CCSRDIF
Open or short circuited current transformer
cores can cause unwanted operation of many
protection functions such as differential,
earth-fault current and negative-sequence
current functions.
It must be remembered that a blocking of
protection functions at an occurrence of open
CT circuit will mean that the situation will
remain and extremely high voltages will
stress the secondary circuit.
Current circuit supervision (CCSRDIF)
compares the residual current from a three
phase set of current transformer cores with
the neutral point current on a separate input
taken from another set of cores on the
current transformer.
A detection of a difference indicates a fault in
the circuit and is used as alarm or to block
protection functions expected to give
unwanted tripping.
ABB
9. Control
Synchrocheck, energizing check,
and synchronizing SESRSYN
The Synchronizing function allows closing of
asynchronous networks at the correct
23
Autorecloser SMBRREC
The autorecloser (SMBRREC) function
provides high-speed and/or delayed autoreclosing for single breaker applications.
Up to five reclosing attempts can be included
by parameter setting.
The autoreclosing function can be configured
to co-operate with a synchrocheck function.
Autorecloser STBRREC
The autoreclosing function provides highspeed and/or delayed auto-reclosing for
single breaker applications.
Up to five reclosing attempts can be included
by parameter setting. The first attempt can be
single- and/or three phase for single-phase or
multi-phase faults respectively.
Multiple autoreclosing functions are provided
for multi-breaker arrangements. A priority
circuit allows one circuit breaker to close first
and the second will only close if the fault
proved to be transient.
24
AutomationBits AUTOBITS
The Automation bits function (AUTOBITS) is
used to configure the DNP3 protocol
command handling.
10. Scheme
communication
Scheme communication logic for
distance or overcurrent protection
ZCPSCH
To achieve instantaneous fault clearance for
all line faults, a scheme communication logic
is provided. All types of communication
schemes for example, permissive
underreaching, permissive overreaching,
blocking, unblocking, intertrip are available.
ABB
25
26
11. Logic
Tripping logic SMPPTRC
A function block for protection tripping is
provided for each circuit breaker involved in
the tripping of the fault. It provides the pulse
prolongation to ensure a trip pulse of
sufficient length, as well as all functionality
necessary for correct co-operation with
autoreclosing functions.
The trip function block includes functionality
for breaker lock-out.
ABB
ABB
27
12. Monitoring
Measurements CVMMXN, CMMXU,
VNMMXU, VMMXU, CMSQI, VMSQI
The measurement functions are used to get online information from the IED. These service
values make it possible to display on-line
information on the local HMI and on the
Substation automation system about:
measured voltages, currents, frequency,
active, reactive and apparent power and
power factor
primary and secondary phasors
current sequence components
voltage sequence components
28
Indications DRPRDRE
To get fast, condensed and reliable
information about disturbances in the
primary and/or in the secondary system it is
important to know, for example binary
signals that have changed status during a
disturbance. This information is used in the
short perspective to get information via the
local HMI in a straightforward way.
There are three LEDs on the local HMI
(green, yellow and red), which will display
status information about the IED and the
Disturbance report function (trigged).
The Indication list function shows all selected
binary input signals connected to the
Disturbance report function that have
changed status during a disturbance.
29
13. Metering
Pulse counter logic PCGGIO
Pulse counter (PCGGIO) function counts
externally generated binary pulses, for
instance pulses coming from an external
energy meter, for calculation of energy
consumption values. The pulses are captured
by the BIO (binary input/output) module
and then read by the PCGGIO function. A
scaled service value is available over the
station bus.
ABB
ABB
Time synchronization
Use time synchronization to achieve a
common time base for the IEDs in a
protection and control system. This makes
comparison of events and disturbance data
between all IEDs in the system possible.
Time-tagging of internal events and
disturbances are an excellent help when
evaluating faults. Without time
synchronization, only the events within the
IED can be compared to one another. With
time synchronization, events and
disturbances within the entire station, and
even between line ends, can be compared at
evaluation.
In the IED, the internal time can be
synchronized from a number of sources:
31
SNTP
IRIG-B
DNP
IEC60870-5-103
32
16. Station
communication
IEC 61850-8-1 communication
protocol
The IED supports the communication
protocols IEC 61850-8-1 and DNP3 over TCP/
IP. All operational information and controls
are available through these protocols.
However, some communication functionality,
for example, horizontal communication
(GOOSE) between the IEDs, is only enabled
by the IEC 61850-8-1 communication protocol.
The IED is equipped with an optical Ethernet
rear port for the substation communication
standard IEC 61850-8-1. IEC 61850-8-1
protocol allows intelligent electrical devices
(IEDs) from different vendors to exchange
information and simplifies system
engineering. Peer-to-peer communication
according to GOOSE is part of the standard.
Disturbance files uploading is provided.
Disturbance files are accessed using the IEC
61850-8-1 protocol. Disturbance files are
available to any Ethernet based application
via FTP in the standard Comtrade format.
Further, the IED can send and receive binary
values, double point values and measured
values (for example from MMXU functions),
together with their quality, using the IEC
61850-8-1 GOOSE profile. The IED meets the
GOOSE performance requirements for
ABB
DNP3 protocol
Ethernet
100BASEFX LC
IEC
61850-8-1
DNP3
IEC
60870-5-103
ST
connector
= Supported
33
K
A
H
B
D
IJ
E
E
G
IEC09000672.ai
IEC09000672 V1 EN
240 mm
21.55 mm
21.55 mm
220 mm
227 mm
265.9 mm
228.9 mm
300 mm
272 mm
254 mm
6 mm
IEC09000676.ai
IEC09000676 V1 EN
25.5 mm
482.6 mm (19")
265.9 mm (6U)
13 mm
B
E
C
IEC09000677.ai
IEC09000677 V1 EN
25.5 mm
482.6 mm (19")
222 mm
13 mm
27 mm
265.9 mm (6U)
13 mm
34
ABB
D E
IEC09000678.ai
IEC09000678 V1 EN
ABB
270 mm
190.5 mm
252.5 mm
296 mm
6.8 mm
13 mm
268.9 mm
GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN
25.5 mm
258.6 mm
220 mm
265.9 mm
13 mm
224 mm
265.9 mm
35
Slot
Rear Position
COM
pCOM
PSM
pPSM
TRM
p2
X101, X102
BIO
p3
X321, X324
BIO
p4
X326, X329
BIO
p5
X331, X334
BIO
p6
X336, X339
36
ABB
ABB
37
38
ABB
ABB
39
40
ABB
ABB
41
Nominal
range
Operative
range
The range of values of a given energizing quantity for which the equipment,
under specified conditions, is able to perform its intended functions
according to the specified requirements
42
ABB
Analog inputs
Table 2. Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Operating range
Rated frequency 5 Hz
Current inputs
Rated current, In
0.1/0.5 A1)
1/5 A2)
Continuously
4A
20 A
For 1 s
100 A
500 A
For 10 s
20 A
100 A
Half-wave value
250 A
1250 A
Input impedance
<100 m
<20 m
Rated voltage, Un
Thermal withstand
capability:
Dynamic current
withstand:
Voltage inputs
Voltage withstand:
Continuous
420 V rms
For 10 s
450 V rms
<0.05 VA
1) Residual current
2) Phase currents or residual current
ABB
43
Auxiliary DC voltage
Table 3. Power supply
Description
Type 1
Type 2
Uauxnominal
85...110% of Un (85...264 V
AC)
80...120% of Un (38.4...150 V
DC)
80...120% of Un (88...300 V
DC)
Maximum load of auxiliary
voltage supply
35 W
50 ms at Uaux
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.3 W
Threshold voltage
44
ABB
Value
Rated voltage
250 V AC/DC
5A
10 A
30 A
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
1 A/0.3 A/0.1 A
ABB
Description
Value
Rated voltage
250 V DC
8A
15 A
30 A
1 A/0.3 A/0.1 A
20...250 V DC
~1.0 mA
20 V DC
45
Protocol
Cable
LAN1 (X1)
TCP/IP protocol
Fibre-optic cable
with LC connector
100 MBits/s
Fibre type
Connector
Permitted path
attenuation1)
Distance
1300 nm
MM 62.5/125
m glass
fibre core
LC
<8 dB
2 km
Protocol
Cable
IRIG-B
Counter connector
Influencing factors
Table 12. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 40
IP 20
Value
IP 42
46
ABB
Value
-25...+55C (continuous)
-40...+70C (<16h)
Note: Degradation in MTBF and HMI
performance outside the temperature range
of -25...+55C
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
up to 2000 m
-40...+85C
Reference
operation
96 h at -25C
16 h at -40C
IEC 60068-2-1
storage
96 h at -40C
Damp heat
tests
ABB
16 h at +70C
IEC 60068-2-2
storage
96 h at +85C
steady state
240 h at +40C
humidity 93%
IEC 60068-2-78
cyclic
IEC 60068-2-30
47
Reference
IEC 61000-4-18
IEC 60255-22-1, level 3
Common mode
2.5 kV
Differential mode
1.0 kV
IEC 61000-4-2
IEC 60255-22-2, level 4
Contact discharge
8 kV
Air discharge
15 kV
IEC 61000-4-6
IEC 60255-22-6, level 3
Radiated, amplitudemodulated
IEC 61000-4-3
IEC 60255-22-3, level 3
IEC 61000-4-4
IEC 60255-22-4, class A
Communication ports
2 kV
Other ports
4 kV
IEC 61000-4-5
IEC 60255-22-5, level 3/2
Communication
1 kV line-to-earth
Other ports
2 kV line-to-earth, 1 kV lineto-line
3s
1000 A/m
Continuous
100 A/m
48
ABB
Reference
300 V rms
150 V rms
Differential mode
Voltage dips and short
interruptions
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0... s : Correct behaviour at
power down
Electromagnetic emission
tests
IEC 60255-11
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
0.5...30 MHz
Radiated RF-emission
ABB
30...230 MHz
230...1000 MHz
49
Dielectric tests:
Test voltage
IEC 60255-5
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min,
communication
IEC 60255-5
5 kV, unipolar impulses,
waveform 1.2/50 s, source
energy 0.5 J
1 kV, unipolar impulses,
waveform 1.2/50 s, source
energy 0.5 J, communication
Insulation resistance
measurements
Isolation resistance
IEC 60255-5
>100 M, 500 V DC
Reference
IEC 60255-27
<0.1 (60 s)
Reference
Requirement
IEC 60255-21-1
Class 2
IEC60255-21-1
Class 1
IEC 60255-21-2
Class 1
IEC 60255-21-2
Class 1
Bump test
IEC 60255-21-2
Class 1
Seismic test
IEC 60255-21-3
Class 2
Product safety
Table 19. Product safety
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
50
ABB
EMC compliance
Table 20. EMC compliance
ABB
Description
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
51
Impedance protection
Table 21. Distance measuring zone, Quad ZQDPDIS
Function
Range or value
Accuracy
Number of zones
5 with selectable
direction
Minimum operate
residual current
(5-30)% of IBase
1,0 % of I
1,0 % of I
Positive sequence
impedance reach for
zones
0.005 - 3000.000
(1.00-9000.00) /
loop
(1.00-3000.00) /
loop
(0 - 180) degrees
0.00 - 3.00
(-180 - 180)
degrees
Dynamic overreach
<5% at 85
degrees
measured with
CVTs and
0.5<SIR<30
(0.000-60.000) s
0.5% 10 ms
Operate time
30 ms typically
Reset ratio
105% typically
Reset time
35 ms typically
52
ABB
Range or value
Accuracy
(5-500)% of IBase
1.0% of Ir
(0.503000.00)
(0.50 - 3000.00)
(1.009000.00) /loop
(0.503000.00) /loop
Load encroachment
criteria:
Load resistance, forward
and reverse
Safety load impedance
angle
ABB
(1.003000.00) /phase
(5-70) degrees
53
Range or value
Accuracy
5 with selectable
direction
2.0% of Ir
Positive sequence
impedance
(0.0053000.000) W/
phase
(0.0053000.000) /
phase
(1090) degrees
(0.003.00)
(-180180) degrees
Dynamic overreach
<5% at 85 degrees
measured with CVTs
and 0.5<SIR<30
Timers
(0.000-60.000) s
0.5% 10 ms
Operate time
30 ms typically
Reset ratio
Range or value
Accuracy
Load encroachment
criteria: Load resistance,
forward and reverse
(1.003000) W/phase
(570) degrees
54
ABB
Range or value
Accuracy
0,5% of Ur
< 105%
0,5% of Ur
> 95%
> 95%
Timers
(0.000 - 60.000) s
0,5% 10 ms
Operating mode
No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a,
231a, 312a, 321a
ABB
Function
Range or value
Accuracy
Reactive reach
(0.10-3000.00) W
Resistive reach
(0.101000.00)W
Timers
(0.000-60.000) s
0.5% 25 ms
(5-30) of IBase
1% of Ir
55
Table 27. Automatic switch onto fault logic, voltage and current based ZCVPSOF
Parameter
Range or
value
Accuracy
(1100)% of
UBase
0.5% of Ur
<105%
(1100)% of
IBase
1.0% of Ir
<105%
(0.000
60.000) s
0.5% 10 ms
(0.000
60.000) s
0.5% 10 ms
Current protection
Table 28. Instantaneous phase overcurrent protection PHPIOC
Function
Range or value
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
> 95%
Operate time
20 ms typically at 0 to 2 x Iset
Reset time
35 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
Operate time
10 ms typically at 0 to 10 x Iset
Reset time
45 ms typically at 10 to 0 x Iset
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at t = 100 ms
56
ABB
Range or value
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
ABB
Reset ratio
> 95%
Operate time
20 ms typically at 0 to 2 x Iset
Reset time
35 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
Operate time
10 ms typically at 0 to 10 x Iset
Reset time
45 ms typically at 10 to 0 x Iset
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at t = 100 ms
57
Setting range
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
> 95%
(1-10000)% of lBase
1.0% of Ir at I Ir 1.0%
of I at I > Ir
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25ms
Inverse characteristics,
see table 84, table 85 and
table 86
17 curve types
Operate time,
nondirectional start
function
20 ms typically at 0 to 2 x Iset
30 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
58
ABB
Setting range
Accuracy
Operate current
(5-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
ABB
Reset ratio
> 95%
(1-10000)% of lBase
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
Inverse characteristics,
17 curve types
see table 84, table 85 and
table 86
Operate time,
nondirectionalstart
function
20 ms typically at 0 to 2 x Iset
30 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
59
Range or value
Accuracy
Operate current
(1-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
> 95%
Operate time
20 ms typically at 0 to 2 x Iset
Reset time
30 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
Operate time
10 ms typically at 0 to 10 x Iset
Reset time
40 ms typically at 10 to 0 x Iset
2 ms typically at 0 to 10 x Iset
Dynamic overreach
< 5% at t = 100 ms
60
ABB
Range or value
Accuracy
Operate current
(1-2500)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
ABB
Reset ratio
> 95%
(1100)% of lBase
1.0% of Ir
(1-10000)% of lBase
1.0% of Ir at I < Ir
1.0% of I at I < Ir
(0.000-60.000) s
0.5% 25 ms
Timers
(0.000-60.000) s
0.5% 25 ms
Inverse characteristics,
see table 84, table 85 and
table 86
17 curve types
Minimum polarizing
voltage
(1100)% of UBase
0.5% of Ur
Minimum polarizing
current
(2-100)% of IBase
1.0% of Ir
(0.50-1000.00) W/phase
(0.503000.00) W/phase
30 ms typically at 0,5 to 2 x IN
30 ms typically at 2 to 0,5 x IN
61
Table 34. Sensitive directional residual overcurrent and power protection SDEPSDE
Function
Range or value
Accuracy
(0.25-200.00)% of lBase
1.0% of Ir at I Ir
At low setting:
(2.5-10) mA
(10-50) mA
(0.25-200.00)% of SBase
At low setting:
(0.25-5.00)% of SBase
(0.25-200.00)% of lBase
At low setting:
(2.5-10) mA
(10-50) mA
(1.00-400.00)% of lBase
At low setting:
(10-50) mA
(1.00-200.00)% of UBase
(0.25-200.00)% of lBase
1.0% of I at I > Ir
0.5 mA
1.0 mA
1.0% of Sr at S Sr
1.0% of S at S > Sr
10% of set value
1.0% of Ir at Ir
1.0% of I at I > Ir
0.5 mA
1.0 mA
1.0% of Ir at I Ir
1.0% of I at I > Ir
1.0 mA
0.5% of Ur at UUr
0.5% of U at U > Ur
At low setting:
(2.5-10) mA
(10-50) mA
1.0% of Ir at I Ir
1.0% of I at I > Ir
0.5 mA
1.0 mA
0.5% of Ur at UUr
Reset ratio
> 95%
Timers
(0.000-60.000) s
0.5% 25 ms
Inverse characteristics,
see table 84, table 85 and
table 86
17 curve types
2.0 degrees
(0-90) degrees
2.0 degrees
62
0.5% of U at U > Ur
ABB
Table 34. Sensitive directional residual overcurrent and power protection SDEPSDE,
continued
Function
Range or value
Accuracy
ABB
Function
Setting range
Accuracy
5.0-100.0% of IBase
in steps of 1.0%
1.0 % of Ir
5.0-100.0% of IBase
in steps of 1.0%
1.0 % of Ir
0.000-60.000 s in
steps of 1 ms
0.5 % 25 ms
0.000-60.000 s in
steps of 1 ms
0.5 % 25 ms
Reset ratio
<105%
63
Range or value
Accuracy
Reference current
(0-400)% of IBase
1.0% of Ir
Reference temperature
(0-600)C
1.0C
Operate time:
Time constant t = (0
1000) minutes
Alarm temperature
(0-200)C
Trip temperature
(0-600)C
(0-600)C
I 2 - I p2
t = t ln 2
I - Ib 2
EQUATION1356 V1 EN
(Equation 1)
I = actual measured
current
Ip = load current before
overload occurs
Ib = base current, IBase
Range or value
Accuracy
(5-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(2-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(5-200)% of lBase
1.0% of Ir at I Ir
Reset ratio
> 95%
Timers
(0.000-60.000) s
0.5% 10 ms
35 ms typically
10 ms maximum
64
1.0% of I at I > Ir
ABB
Range or value
Accuracy
(5-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(2-200)% of lBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
> 95%
(5-200)% of lBase
1.0% of Ir at I Ir
Reset ratio
> 95%
Timers
(0.000-60.000) s
0.5% 10 ms
35 ms typically
10 ms maximum
1.0% of I at I > Ir
Range or value
Accuracy
Operating current
(1-2500)% of IBase
1.0% of Ir at I Ir
1.0% of I at I > Ir
Reset ratio
> 95%
Operating time
20 ms typically at 0 to 2 x Iset
Resetting time
30 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
ABB
Function
Range or value
Accuracy
(0-100) %
1.0% of Ir
Reset ratio
>95%
Time delay
(0.000-60.000) s
0.5% 25 ms
65
Range or value
Accuracy
(5100)% of IBase
1.0% of Ir
(50-90)% of maximum
current
2.0% of Ir
Timer
(0.00-60.000) s
0.5% 25 ms
35 ms typically
30 ms typically
15 ms typically
10 ms typically
Range or value
Accuracy
Power level
(0.0500.0)% of SBase
1.0% of Sr at S < Sr
1.0% of S at S > Sr1)
(1.0-2.0)% of SBase
2)
(2.0-10)% of SBase
3)
Characteristic angle
(-180.0180.0) degrees
2 degrees
Timers
(0.010 - 6000.000) s
0.5% 25 ms
1)
2)
3)
66
ABB
Range or value
Accuracy
Operate current
1.0% of Ir at I <Ir
1.0% of I at I > Ir
Reset ratio
> 95 %
< 0,5% of Ur
2,0 degrees
(1 - 90) degrees
2,0 degrees
Timers
(0.00 - 6000.00) s
0.5% 25 ms
ABB
40 ms typically at 2 to 0 x Iset -
40 ms typically at 2 to 0 x Iset -
15 ms typically
Dynamic overreach
67
Voltage protection
Table 44. Two step undervoltage protection UV2PTUV
Function
Range or value
Accuracy
(1100)% of UBase
0.5% of Ur
Reset ratio
<105%
See table 88
(0.00 - 6000.00) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
(0.00060.000) s
0.5% 25 ms
10 ms typically at 2 to 0 x Uset
15 ms typically
Range or value
Accuracy
(1-200)% of UBase
0.5% of Ur at U < Ur
0.5% of U at U > Ur
Reset ratio
>95%
See table 87
(0.00 - 6000.00) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
30 ms typically at 0 to 2 x Uset
40 ms typically at 2 to 0 x Uset
10 ms typically at 0 to 2 x Uset
15 ms typically
68
ABB
Range or value
Accuracy
(1-200)% of UBase
0.5% of Ur at U < Ur
0.5% of U at U > Ur
(1100)% of UBase
0.5% of Ur at U < Ur
0.5% of U at U > Ur
Reset ratio
>95%
See table 89
(0.006000.00) s
0.5% 25 ms
(0.00060.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
30 ms typically at 0 to 2 x Uset
40 ms typically at 2 to 0 x Uset
10 ms typically at 0 to 2 x Uset
15 ms typically
ABB
Function
Range or value
Accuracy
Operate voltage
(0100)% of UBase
0.5% of Ur
Reset ratio
<105%
Pulse timer
(0.05060.000) s
0.5% 25 ms
Timers
(0.00060.000) s
0.5% 25 ms
69
Frequency protection
Table 48. Under frequency protection SAPTUF
Function
Range or value
Accuracy
(35.00-75.00) Hz
2.0 mHz
(45 - 65) Hz
2.0 mHz
(0.000-60.000)s
<250 ms
(0.000-60.000)s
<150 ms
Range or value
Accuracy
(35.00-75.00) Hz
2.0 mHz at
symmetrical
three-phase
voltage
Timer
(0.000-60.000)s
<250 ms
70
ABB
Range or value
Accuracy
(-10.00-10.00) Hz/s
10.0 mHz/s
(45.00 - 65.00) Hz
2.0 mHz
Timers
(0.000 - 60.000) s
<130 ms
Range or value
Accuracy
Operate current
(5-200)% of Ir
10.0% of Ir at I Ir
10.0% of I at I > Ir
Block current
(5-500)% of Ir
5.0% of Ir at I Ir
5.0% of I at I > Ir
ABB
Function
Range or value
Accuracy
(1-100)% of UBase
1.0% of Ur
(1100)% of IBase
1.0% of Ir
(1100)% of UBase
0.5% of Ur
(1100)% of IBase
1.0% of Ir
(1100)% of UBase
5.0% of Ur
(1100)% of IBase
5.0% of Ir
(1-100)% of UBase
0.5% of Ur
(1-100)% of IBase
1.0% of Ir
(1-100)% of UBase
0.5% of Ur
(1-100)% of IBase
1.0% of Ir
71
Range or value
Accuracy
(0.020 - 300.000) s
0,5% 110 ms
Control
Table 54. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Range or value
Accuracy
0.2 to 5.0
(0.003-1.000) Hz
2.0 mHz
(5.0-90.0) degrees
2.0 degrees
0.5% of Ur
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
72
ABB
Range or value
Accuracy
1-5
(0.000-60.000) s
0.5% 25 ms
shot
shot
shot
shot
ABB
2
3
4
5
t2
t3
t4
t5
3Ph
3Ph
3Ph
3Ph
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
Reclaim time
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
73
Range or value
Accuracy
Number of autoreclosing
shots
1-5
(0.000-60.000) s
0.5% 25 ms
shot
shot
shot
shot
(0.00-6000.00) s
2
3
4
5
t2
t3
t4
t5
3Ph
3Ph
3Ph
3Ph
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
Reclaim time
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
74
ABB
Scheme communication
Table 57. Scheme communication logic for distance or overcurrent protection ZCPSCH
Function
Range or value
Accuracy
Scheme type
Off
Intertrip
Permissive UR
Permissive OR
Blocking
(0.000-60.000) s
0.5% 10 ms
Minimum duration of a
carrier send signal
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
Operation mode of
unblocking logic
Off
NoRestart
Restart
Table 58. Current reversal and weak-end infeed logic for distance protection
ZCRWPSCH
ABB
Function
Range or value
Accuracy
Off
Echo
Echo & Trip
(10-90)% of UBase
0.5% of Ur
Reset ratio
<105%
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
75
Table 59. Current reversal and weak-end infeed logic for distance protection ZCWSPSCH
Function
Range or value
Accuracy
(10-90)% of UBase
0.5% of Ur
Reset ratio
<105%
(0.000-60.000) s
0.5% 10 ms
(0.00-6000.00) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
Range or value
Accuracy
Timers
(0.00060.000) s
0.5% 10 ms
Table 61. Scheme communication logic for residual overcurrent protection ECPSCH
Function
Range or value
Accuracy
Scheme type
Off
Intertrip
Permissive UR
Permissive OR
Blocking
Communication scheme
coordination time
(0.000-60.000) s
0.5% 25 ms
Minimum duration of a
send signal
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
76
ABB
Table 62. Current reversal and weak-end infeed logic for residual overcurrent protection
ECRWPSCH
Function
Range or value
Accuracy
Off
Echo
Echo & Trip
(5-70)% of UBase
1.0% of Ur
(0.000-60.000) s
0.5% 25 ms
(0.000-60.000) s
0.5% 25 ms
(0.00060.000) s
0.5% 25 ms
Logic
Table 63. Tripping logic SMPPTRC
Function
Range or value
Accuracy
Trip action
3-ph
Timers
(0.000-60.000) s
0.5% 10 ms
ABB
Function
Range or value
Accuracy
Trip action
3-Ph, 1/3-Ph
Timers
(0.000-60.000) s
0.5% 10 ms
77
Range or value
Accuracy
5 ms
20 ms
100 ms
AND
60
60
160
OR
60
60
160
XOR
10
10
20
INVERTER
30
30
80
SRMEMORY
10
10
20
RSMEMORY
10
10
20
GATE
10
10
20
PULSETIMER
10
10
20
(0.00090000.000) s
0.5% 25 ms
TIMERSET
10
10
20
(0.00090000.000) s
0.5% 25 ms
LOOPDELAY
10
10
20
Monitoring
Table 66. Measurements CVMMXN
Function
Range or value
Accuracy
Voltage
(0.1-1.5) Ur
0.5% of Ur at UUr
0.5% of U at U > Ur
Connected current
(0.2-4.0) Ir
0.5% of Ir at I Ir
0.5% of I at I > Ir
Active power, P
1.0% of Sr at S Sr
1.0% of S at S > Sr
1)
Reactive power, Q
1.0% of Sr at S Sr
1.0% of S at S > Sr
1)
Apparent power, S
1.0% of Sr at S Sr
1.0% of S at S > Sr
cos phi = 1
0.5% of S at S > Sr
0.5% of Sr at S Sr
< 0.02
1)
2)
78
2)
ABB
ABB
Function
Range or value
Accuracy
Counter value
0-10000
10 pulses/s
79
Range or value
Accuracy
Current recording
1,0% of Ir at I Ir
1,0% of I at I > Ir
Voltage recording
1,0% of Ur at U
Ur
1,0% of U at U >
Ur
Pre-fault time
(0.053.00) s
Post-fault time
(0.110.0) s
Limit time
(0.58.0) s
1 ms
See time
synchronization
technical data
30 + 10 (external +
internally derived)
96
30
96
150
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
Recording bandwidth
(5-300) Hz
80
ABB
Value or range
Accuracy
(0.001-1500.000) /phase
Phase selection
Value
Maximum number of events in
the list
1000
Resolution
1 ms
Accuracy
Depending on time
synchronizing
Value
Maximum number of indications presented
for single disturbance
96
100
Value
Maximum number of events in disturbance report 150
Maximum number of disturbance reports
ABB
100
Resolution
1 ms
Accuracy
Depending on
time
synchronizing
81
Value
Buffer capacity
30
100
Value
Maximum number of analog inputs
40
96
Range or value
Accuracy
(60-140) % of Ubat
<105 %
(60-140) % of Ubat
>95 %
Timers
(0.000-60.000) s
0.5% 110 ms
Range or value
Accuracy
Pressure alarm
0.00-25.00
Pressure lockout
0.00-25.00
Temperature alarm
-40.00-200.00
Temperature lockout
-40.00-200.00
Timers
(0.000-60.000) s
0.5% 110 ms
82
ABB
Range or value
Accuracy
0.00-25.00
0.00-25.00
Temperature alarm
-40.00-200.00
Temperature lockout
-40.00-200.00
Timers
(0.000-60.000) s
0.5% 110 ms
Range or value
Accuracy
(0-200) ms
0.5% 25 ms
(0 - 9999)
(0.00-60.00) s
0.5% 25 ms
(0.00-60.00) s
0.5% 25 ms
(0.00-60.00) s
0.5% 25 ms
Metering
Table 79. Pulse counter PCGGIO
Function
Setting range
Accuracy
(13600) s
Table 80. Function for energy calculation and demand handling ETPMMTR
Function
Range or value
Accuracy
Energy metering
MWh Export/Import,
MVArh Export/Import
Hardware
ABB
83
IED
Table 81. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 40
IP 20
Value
IP 42
Dimensions
Value
Width
220 mm
Height
265.9 mm (6U)
Depth
249.5 mm
Weight box
<10 kg (6U)
Weight LHMI
1.3 kg (6U)
84
ABB
Range or value
Accuracy
Operating characteristic:
ANSI/IEEE C37.112,
class 5 + 40 ms
t =
A
P
( I - 1)
+ B k
EQUATION1249-SMALL V1 EN
I = Imeasured/Iset
Range or value
Accuracy
Operating characteristic:
A=0.14, P=0.02
A=13.5, P=1.0
IEC 60255-151,
class 5 + 40 ms
IEC Inverse
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
t =
A
P
k
( I - 1)
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
ABB
85
Range or value
Accuracy
IEC 60255-151,
class 5 + 40 ms
IEC 60255-151,
class 5 + 40 ms
t =
0.339 -
0.236
I
EQUATION1137-SMALL V1 EN
I = Imeasured/Iset
RD type logarithmic inverse
characteristic
t = 5.8 - 1.35 In
I
k
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
Table 87. Inverse time characteristics for overvoltage protection
Function
Range or value
Accuracy
Type A curve:
k = (0.05-1.10) in steps of
0.01 unless otherwise stated
Class 5 +40 ms
t =
U -U >
U>
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
Type B curve:
t =
k = (0.05-1.10) in steps of
0.01 unless otherwise stated
k 480
32 U - U > - 0.5
U >
2.0
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k = (0.05-1.10) in steps of
0.01 unless otherwise stated
k 480
32 U - U > - 0.5
U >
3.0
- 0.035
EQUATION1438-SMALL V1 EN
86
ABB
Range or value
Accuracy
Type A curve:
k = (0.05-1.10) in steps of
0.01 unless otherwise stated
Class 5 +40 ms
t =
U < -U
U<
EQUATION1431-SMALL V1 EN
U< = Uset
U = UVmeasured
Type B curve:
t =
k = (0.05-1.10) in steps of
0.01 unless otherwise stated
k 480
32 U < -U - 0.5
U <
2.0
+ 0.055
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
ABB
87
Range or value
Accuracy
Type A curve:
k = (0.05-1.10) in
steps of 0.01
Class 5 +40 ms
t =
U -U >
U>
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
Type B curve:
t =
k = (0.05-1.10) in
steps of 0.01
k 480
32 U - U > - 0.5
U >
2.0
- 0.035
EQUATION1437-SMALL V1 EN
Type C curve:
t =
k = (0.05-1.10) in
steps of 0.01
k 480
32 U - U > - 0.5
U >
3.0
- 0.035
EQUATION1438-SMALL V1 EN
88
ABB
20. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Exemple code: REL650*1.1-A01X00-X00-B1A5-B-A-SA-AB1-RA3-AAXX-E. Using the code of each position #1-11
specified as REL650*1-2 2-3-4 4-5-6-7 7-8 8-9 9-10 10 10 10-11
#
- 3
- 4
- 5
- 7
- 8
- 9
- 10
- 1
1
Position
REL650*
- 2
SOFTWARE
#1
Version number
1.1
Version no
Selection for position #1.
Configuration alternatives
1.1
#2
A01
A05
A11
ACT configuration
ABB standard configuration
X00
X00
Software options
#3
No option
X00
Selection for postition #3
X00
#4
English IEC
B1
Selection for position #4.
#4
X0
Chinese
A5
Selection for position #4.
ABB
B1
89
Casing
#5
B
Selection for position #5.
#6
#7
Compression terminals
Ringlug terminals
pPSM
Power supply
Slot position:
100-240V AC, 110-250V DC, 9BO
B
Selection for position #7.
#8
Detached LHMI
No detached mounting of LHMI
X0
B1
B2
B3
B4
B5
90
ABB
#9
Compression terminals
Ringlug terminals
Slot position:
p2
Analog system
A3
p6
p5
p4
#10
p3
A3
A
#11
pCOM
B
Selection for position #11.
Accessories
Rack mounting kit for 2 x 6U 1/2 x 19"
Quantity:
1KHL400240R0001
Quantity:
Quantity:
Quantity:
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual, Communication protocol manual,
DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103,
Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LED
label template is always included for each IED.
ABB
91
Quantity:
IEC
Quantity:
Technical manual
IEC
Quantity:
Commissioning manual
IEC
Quantity:
Application manual
IEC
Quantity:
IEC
Quantity:
IEC
Quantity:
IEC
Quantity:
Engineering manual
IEC
Quantity:
Installation manual
IEC
Quantity:
IEC
Quantity:
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Country:
End user:
Station name:
Voltage level:
92
kV
ABB
Related documents
ABB
Identity number
Application manual
Technical manual
Commissioning manual
Identity number
Engineering manual
Operation manual
Installation manual
93
94
ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone
+46 (0) 21 32 50 00
Fax
+46 (0) 21 14 69 18
www.abb.com/substationautomation
Contact us