ResponsestoFAQsarepreparedbyNFPAtechnicalstafftoassistusersinreadingandunderstandingNFPAcodesand
standards.Theresponses,however,arenotFormalInterpretationsissuedpursuanttoNFPARegulations.Anyopinions
expressedarethepersonalopinionsoftheauthor(s),anddonotnecessarilyrepresenttheofficialpositionoftheNFPAor
itsTechnicalCommittees.Inaddition,theresponsesareneitherintended,norshouldbereliedupon,toprovide
professionalconsultationorservices.
1. DoIneedsprinklersinmybuilding?
NFPA13istheNFPAdocumentthatspecifiestheminimumrequirementsfordesigningand
installingsprinklersystems.Itdoesnotspecifywhichbuildingsrequireasprinklersystem.
TherequirementtoinstallasprinklersystemcomplyingwithNFPA13canusuallybefoundin
oneofthefollowingsources:buildingcode;federal,stateorlocalregulations;insurer's
requirements;accreditationrequirements;orowner'srequest.
2. IfIhaveadrypipesprinklersystemunderapitchedroofexceedingaslopeof16.7%,doI
applybothareaincreasesfromSection52.3.2.5andSection52.3.2.6?
Yes,bothsectionswouldbeappliedcumulativelytothedesignareachosenfromFigure5
2.3.Thisisshowninthefollowingexample:TheapplicationareadeterminedfromFigure5
2.3is1500squarefeet.AsrequiredbySection52.3.2.5,1500squarefeetisincreasedby
30%to1950squarefeetforthesteeplypitchedroof.AsrequiredbySection52.3.2.6,the
1950squarefeetisincreasedby30%forthedrypipesystem.Therefore,theoriginaldensity
chosenfromFigure52.3mustbeappliedover2535squarefeet.Ensurethatthereareno
otherdesignareamodificationsrequiredforthesystembeinginstalled.
3. CanplasticpipebeusedonasprinklersystemcomplyingwithNFPA13?
Section23.5allowstheuseofplasticpipethathasbeenspecificallylistedforfireprotection
use.Thispipemustbeinstalledinaccordancewithitslistinglimitations,includinginstallation
instructions.
4. Whatisthelimitforthecalculatedwatervelocityinasprinklersystemcomplyingwith
NFPA13?
NFPA13doesnotspecifyamaximumlimitforthecalculatedwatervelocity.
5. Dowalkintypefreezers,coolers,vaultsandsafesrequiresprinklers?
Yes.AsexplainedbyFormalInterpretation786,theseareasrequiresprinklersbecausethey
arepartofthepremises.NFPA13requiresthatsprinklersbeinstalledthroughoutthe
premisesinaccordancewithSection41.1.Therearenoexceptionsprovidedwhichallowfor
sprinkleromissionintheseareas.
6. Inapplyingthe'ThreeTimesRule'forsprinklerobstructions(i.e.Section46.5.2.2),what
dimensionisthe24inchmaximumreferringto?
Thismaximumdimensionisthedimensionmeasuredfromthesprinklertothenearestedge
oftheobstruction.Isolatedobstructionsthataremorethan24inchesawayfromstandard
uprightandpendentsprinklersdonotgenerallycreateasignificantobstruction.
7. Aresprinklersrequiredinclosets?
Yes.TherearelimitedexceptionsspecifiedinSection413.8.2forcertainsmallclosetsinthe
dwellingunitsofhotelsandmotels.
8. Canasupplycontrolvalvebeinstalleddownstreamofthefiredepartmentconnection?
TheconfusionthatbringsaboutthisquestionisusuallycausedbySection415.2.4.2,the
ExceptiontoSection414.1.1.2,andExceptionNo.1toSection414.1.1.8.Thesesectionsare
necessarytodifferentiatethefiredepartmentconnectionfromothertypesofwater
supplies.Normally,acontrolvalveisrequiredbeforeandaftereachcheckvalveinasource
ofsupply.Thevalvesarerequiredsothatthecheckvalvecanbeisolatedandserviced.As
well,acontrolvalveisnormallyrequiredineachautomaticsourceofsupplyinaccordance
withSection414.1.1.1.However,thesecontrolvalvesarenotnecessary,norallowed,inthe
firedepartmentconnectionpiping.Whilethecontrolvalvesarenotallowedinthefire
departmentconnectionpipingitself,controlvalvescanbeinstalleddownstreamfromthe
firedepartmentconnectionpipinginaccordancewith414.1.1.Itwouldbeimpracticalto
requireafiredepartmentconnectionafterallcontrolvalvesinamultizoneormultisystem
arrangement.Furthermore,Section414.1.1.3ofNFPA13requiresthatallvalvescontrolling
watersuppliesbesupervisedintheopenposition.Inallcases,thearrangementforthefire
departmentconnectionmustcomplywithSection415.2.3.
9. Ifawatercurtainisinstalled,whatistheequivalentfireseparationrating?
NFPA13doesnotspecifyanequivalentfireseparationratingforwatercurtainsinstalledin
accordancewithSection413.3.4anddesignedinaccordancewithSection53.7.
10. Whatistheallowablereductioninfireseparationratingsinabuildingwhereasprinkler
systemisinstalled?
NFPA13doesnotaddresssuchreductions.Somebuilding/firecodeswillspecifyanallowable
reductioninfireseparationratingsforcertainbuildingswheresprinklersareprovidedin
accordancewithNFPA13.Youwouldneedtoconsultwiththeapplicablebuilding/firecode
foryourparticularprojecttodetermineifthereareanyallowablereductions.
11. Aresprinklersrequiredintheupperportionofanarchitecturalceilingfeature,evenwhen
therearenoopeningstoaboveandthesprinklersatthelowerportiondonotexceedarea
NFPA 13-1996 FAQs
ofcoveragelimitations?
Thisquestionusuallyariseswitharchitecturalfeaturessuchasskylightsandroomswith
multilevelceilings.Thegeneralconcernwiththesetypesoffeaturesisthepotentialforheat
to'pocket'andthenegativeimpacttotheoperationofthesprinklers.Thiscouldbetrueeven
ifsprinklersarespacedwithintheirlimitationsforallowableareaofprotection.NFPA13does
notspecificallyaddressthesprinklerrequirementsforthesearchitecturalfeatures.However,
theapplicablesectionsofChapter4doaddressthedistancebelowtheceilingthatsprinklers
mustbepositioned.Theneedforsprinklersintheupperportioncanbedeterminedbasedon
thedistancefromtheupperleveltothepositionatwhichthesprinklerswouldbeinstalled
onthelowerlevel.IfthisdistanceexceedstheallowabledistancesspecifiedinChapter4,
thensprinklerswouldberequiredattheupperlevel.ObstructionsspecifiedbyChapter4to
anyofthesprinklerswouldalsoneedtobeexaminedandaccountedfor.
12. Aresprinklersrequiredwithinfurniture?
No.Sprinklersarerequiredwithinallpermanentspacesofthestructure,suchasclosets,in
accordancewithSection41.1.Moveablefurnitureitems,suchasdesks,dressersand
wardrobes,donotrequiresprinklerswithinthemevenwhentheyareaffixedtothe
permanentstructureofthebuilding.
13. MustIdesignthesprinklersystemtoprotectthesamehazardthroughoutthestructure?
No.NFPA13doesnotrequirethattheentirestructurebeprotectedasasinglehazard
classification.Therearetwoimportantthingstokeepinmind,however,whendesigninga
systemwithmultiplehazardclassifications.Thefirstisthatyouwilllockthebuildinguseinto
thehazardconfigurationthatthesprinklersystemisdesignedfor.Iftheentirespacewas
protectedforthehighesthazard,however,thebuildinguserwouldnothavetoworryabout
thegenerallocationsofthedifferenthazards.Additionally,thehydrauliccalculation
procedurebecomesmorecomplexwithmultiplehazardclassificationsthanwherethe
highesthazardisusedthroughout.
14. IftherearenohoseconnectionsinabuildingsprinkleredtoNFPA13,willthewater
demandneedtoincludeahosestreamallowance?
Yes.AnoutsidehosestreamdemandwouldberequiredinaccordancewithSection52.3.1.1.
15. DoesSection52.3.2.5applytoquickresponsesprinklers?
Yes.Thissectionappliestospraysprinklersincludingquickresponsesprinklersandextended
coveragesprinklersusedinaccordancewithExceptionNo.3toSection44.3.Theadditional
designareaisrequiredbecauseafireunderaslopedceilingconditionwillcausemore
sprinklerstooperatethaniftheceilingwerehorizontal.