Académique Documents
Professionnel Documents
Culture Documents
422-C240-FD-E-RPT-00012-A
ATK002-422-C240-FD-E-RPT-00012
Notice
This document and its contents have been prepared and are intended solely for Saudi Binladin Groups
information and use in relation to King Abdulaziz International Airport.
Atkins assumes no responsibility to any other party in respect of or arising out of or in connection with this
document and/or its contents.
Document History
Status
Originated
Checked
Reviewed
Authorised
Date
HNM
BG
MH
MH
01/06/12
ATK002-422-C240-FD-E-RPT-00012
Table of Contents
Contents
1.1. Abbreviations
1.2. References
2.0 Introduction
10
10
11
11
11
13
13
14
15
15
15
16
17
18
21
21
22
22
22
22
23
ATK002-422-C240-FD-E-RPT-00012
18
19
19
19
19
20
20
21
21
4.2.3. Transformers
4.2.4. Automatic Transfer and Static Switches
4.2.5. Fire Suppression
23
23
23
24
24
24
24
24
25
26
26
27
27
27
29
30
31
32
32
ATK002-422-C240-FD-E-RPT-00012
1.1. Abbreviations
CT Current Transformer
DG Diesel Generator
IP Ingress Protection
LV Low Voltage
MV Medium Voltage
ATK002-422-C240-FD-E-RPT-00012
VT Voltage Transformer
1.2. References
BS 7671 Requirements for Electrical Installations (IEE Wiring Regulations 17th including
Amendment No. 1).
NFPA: National Fire Prevention Association Codes.
Chapter 10 Electrical code
Chapter 70 Electrical Code
Chapter 72 Fire Alarm code
Chapter 780 Lightning protection code
The equipment/systems comply with all related International standards as required in the Contract.
This generally includes the following standards where applicable:
ATK002-422-C240-FD-E-RPT-00012
Standards: equipment and component parts are to comply with the following Standards:
ATK002-422-C240-FD-E-RPT-00012
ATK002-000-A000-FD-M-RPT-00001
ATK002-000-C100-DF-E-RPT-0003
ATK002-422-C240-FD-E-RPT-0010
ATK002-422-C240-FD-E-RPT-0009
ATK002-422-C240-FD-E-RPT-00012
2.0 Introduction
The King Abdul-Aziz International Airport (KAIA) is expanding its runway and passenger
capability. To facilitate this expansion, a new Air Traffic Control tower, a new Passenger
Terminal, Transport Facilities and supporting buildings will be constructed. The new airport
will be constructed in three phases.
Ultimate Phase 3 will have a capacity of 80 million passengers per year. This is
provided by the additional passenger terminal building (PTB3).
The purpose of this document is to define the design principles and criteria of the
proposed Outdoor Package Substation Auxiliary Electrical Substations for the expansion
of the King Abdul-Aziz International Airport in Jeddah. The basis for the design proposal is
covered in this report. This report contains the electrical design criteria of the Auxiliary
Electrical Substations and the basic design requirement for the electrical
equipment/system. The Substations are required provide LV supply to various facilities
being constructed under contracts 422. The Electrical and Building Services designs and
installations shall generally conform to normally accepted design criteria, standards and
regulations as identified within this document. The Outdoor Package Substations are
provided with dual (A and B) 13.8kV incoming supply from the Airport Load Centres.
A single ended package substation combines a single power transformer, MV switchgear
and LV distribution board in a single transportable unit ready for operational on being fixed
position on prepared concrete foundation (SLAB) and connected to the airport load centre.
A double ended substation combines two transformers, two MV switchgears and a LV
distribution board.
Auxiliary Electrical Substation 1, 2, 3, 4, 5, 7 & 8 will be double ended substations.
Auxiliary Electrical Substation 6 will be single ended substation.
The document has been produced on information gained from the Outdoor Package
Substation Specification 261116, dated July 2011. Please refer to associated design
guides below and the associated outdoor substation drawings list in Appendix A.
ATK002-422-C240-FD-E-RPT-00012
This document has been compiled to be a central reference for the basis of design for the
entire Electrical System requirement for Auxiliary Electrical substations facilities within the
422 packages of the overall project.
It should be noted that the client, Saudi Bin Laden Group (SBG), tendered and were
awarded this project on the basis of contract documentation. Contractor to abide by the
Tender Number, J-1X-422-PF-0, Exhibit D Special Specifications, Part D1 and Tender
Number, J-1X-422-PF-0, Exhibit D Special Specifications, Part D2 for the design of
the equipment/system covered in this report.
The Total Normal and Emergency maximum electrical power demand loads of each
Outdoor package substation shall be provided in the Appendices and the calculated
transformer rating. The contractor should verify the normal and emergency loads during
final construction.
The Project requires both single ended and double ended package substations, where the
MV switchgears are fed by 13.8kV dual radial feeders from the utilities distribution Network
coming from the respective load centres.
Outdoor unit substations shall be designed to IEC Standards.
All outdoor substations shall have three separate compartments to accommodate MV
switchgear, Transformer, and LVAC switchgear. A separate battery room with airconditioning shall also be provided for the single ended substation.
The Layout of the plant within the outdoor substation is based on the clearance and
spacing requirements constraints applied on this project.
Transformers shall be of oil type design with suitable oil bund to be designed by the
contractor. The transformers shall be designed for 100% capacity where double ended
configuration is applied so one transformer can assume the total load in the event of a
single transformer failure, including 30% spare capacity.
Outdoor Substations components electrical/mechanical services shall interface through the
BMS panel, Comms Panel, NAC Panel for control and monitoring (locally/remotely)
through the BMS SCADA panel.
The Contractor shall source Equipment and plant based on the KAIA project approved list
of suppliers.
ATK002-422-C240-FD-E-RPT-00012
10
Location
Design Ambient temperature
Altitude
Rainfall
Relative Humidity
Pollution level
Wind speed
ATK002-422-C240-FD-E-RPT-00012
11
Normal power supply will be arranged through SEC (Saudi Electric Company) supply at
13.8kV to the load centre. Power supply at 13.8kV level from load centre is distributed in
the airport and is further stepped down to Low Voltage 400V power supply to meet the
requirements for various facilities.
Emergency power supply is secured from the central diesel MV generators located in the
Load Centre normally supplying the Auxiliary Electrical Substations. Local LV DG set shall
not be provided for the Auxiliary Electrical Substations.
Upon failure of normal utility supply, central generators shall operate and provide essential
supply to the essential loads (breakers controlled by the SCADA system) and once the
normal conditions are restored, the load shall be transferred back to normal power supply.
LV Cable Sizing and Protection Coordination Studies
Local feeders and branch circuits are sized for a total maximum volt drop of 5% of the
nominal voltage from the point of supply during running condition as per requirements;
typically 3% for feeders and 2% for branch circuits. All settings and CB ratings are
indicative and need to be verified as part of a LV protection coordination study relevant to
each package substation. The LVAC cable feeder size, relay settings and LV Protection
coordination studies shall be detailed in a separate report.
Outdoor feeder MV and LV cables (including communications cables) are to be run in
concrete enchased duct banks. No direct buried cables are to be used.
Spare Capacity:
A spare capacity of 30% shall be considered for equipment sizing (e.g. transformer, etc)
30% spare breakers are provided in the distribution levels starting from the main
LV switchboard (MDB), sub distribution boards SDB, etc.
MV - bulk supply
LV - general supply
TN-S
MV Neutral
Resistive Earth
LV Neutral
Solidly Earthed
ATK002-422-C240-FD-E-RPT-00012
12
3.1.4. MV Switchgear
The MV Switchgear shall comprise of two electrically interlocked, arc resistant, vacuum
circuit breakers (VCBs) of the withdrawable type. The Circuit breaker shall be floor
mounted with bottom entry incoming cables.
The MV circuit breakers shall be monitored and controlled locally/remotely from the
SCADA Panel via the BMS System.
The interconnection between the MV switchgear and the Transformer shall be via a MV
power cable of XLPE insulation (to be provided by contractor).
In the event of loss of supply on one feeder (A or B) the MV Switchgear will changeover to
re-supply the transformer from the other circuit.
In the event of loss of supply for both the A and B feeders the generation at load centres
shall start and commence to re-supply the essential loads under the control of BMS
System.
13
Low voltage supplies from the essential and non essential sections of each switchboard
shall be run to the various external loads located outside the package substation and also
internal load requirements of the package substation.
The Sub-distribution board (SDB) maximum number of outgoing ways shall be 14.
The LVAC Board automation shall be achieved via PLC panel mounted to either end for
the LV feeder panels to control and monitor the whole LVAC switchboard through interface
with the SCADA Panel. LVAC Board PLC designed around IEC 60870-5-101 is a standard
for power system monitoring, control & associated communications for telecontrol,
teleprotection, and associated telecommunications for electric power systems.
The LVAC PLC shall interface with LV breakers, including interface elements such as
relays, transducers, etc. as specified and /or as required. The main incoming and outgoing
circuit breakers of the main distribution board shall be monitored and controlled
locally/remotely from the BMS system.
Circuit breakers 800A and above shall be withdrawable ACBs (3 pole type for outgoing
feeders or 4 pole type for incomers and bus-section).
LV Cables shall be XLPE Single core only and shall be specified in mm square.
Transient Voltage Surge Suppression TVSS devices are to be provided in compliance with
Section 264313.
Low voltage supply outlets at 230 Volts, 60 Hz, shall be installed within each compartment
of the substation.
The LV compartment main circuit breaker shall have solid state trip unit with long-time,
short time and ground-fault pick up and time- delay adjustments and with high
instantaneous over-current trip, to correspond with transformer rating and LV interrupting
capacity at location. This shall be time and current coordinated with MV protection on
primary side circuit breakers and protective devices downstream as required shall be
provided in a separate report as mentioned previously.
Voltmeters shall be of Moving iron type, range 1.25 times nominal system voltage, 90
degree angle, size 76 x 76 mm. Voltmeter Selector Switch shall be of 7-position rotary
type.
Ammeters shall be of Moving iron type, range 2 times nominal circuit amperage, 90 degree
angle, size 76 x 76 mm.
Provide Current Transformer (CT) dry type, rated secondary current 5A. Rated primary
current, core size and accuracy are to be determined in accordance with nominal current
of plant protected, short-circuit level and burden.
Provide Voltage Transformer (VT) complete with primary and secondary fuses and
disconnecting device.
ATK002-422-C240-FD-E-RPT-00012
15
The final circuits for the emergency lights shall be fire resistant multi core cables, installed
within the cable trays / cable ladder.
All wiring/cables are to be routed in rigid steel conduits where exposed installations are
subject to mechanical damage or in plenum spaces.
LSZH cables are to be routed cable trays /ladder/rack where Cables are in return air
plenums.
Rigid heavy gauge PVC conduit (of the type detailed below) concrete encased shall be
applied for outdoors Underground Conduit:
Underground duct type: Type EPC-40-PVC rated for 90 C conductors for both in
underground and above ground applications.
For underground duct accessories, duct separators shall be Factory Fabricated rigid PVC
interlocking spacers including Warning tape.
Ducts for MV shall be NEMA Type EPC-40 PVC, in concrete encased duct bank.
Ducts size to be cast in substation base slab for incoming concrete encased duct banks:
160mm OD MV Cables
100mm OD - LV Cables
100mm OD Comms Cables
3.1.10.
The package substation shall comply with following EMI disturbance and interference
practices and standards:
Separation from EMI Sources Shall comply with BICSI TDMM and TIA/EIA-569-A
recommendations. Exhibit D2 : CONTROL-VOLTAGE
ELECTRICAL POWER CABLES 260523
Filters
Luminaires
ATK002-422-C240-FD-E-RPT-00012
16
Induced voltages
Screening
Cable screens
Lightning Protection
The housing enclosure for the Outdoor substation shall be of a single integrated metal
housing type, comprising three totally segregated compartments, accommodating MV
switch- gear, transformer and LV switchgear. The Degree of protection shall be IP 54 for
switchgear (MV or LV) enclosures and IP 23 for transformer housing.
MV and LV connections to corresponding transformer terminals are to be insulated and
inaccessible without the use of tools.
Housing shall be weatherproof, suitable for outdoor installation at particular location,
rodent and vermin proof, high quality hot-dip galvanized sheet steel. Alternative housing
materials shall be submitted for approval by the contractor.
The roof and walls of housing shall be thermally insulated to maintain temperature inside
enclosure within acceptable limits.
The transformer Compartments within the substation shall be naturally ventilated through
sand trap louvred openings of size appropriate to vent the heat dissipated by equipment or
transmitted by outside radiation.
The Transformer compartment shall have Lockable double swing doors. Access to
transformer shall be through demountable bolted panels. It shall be impossible to reach
equipment or live parts from outside the housing. Refer to SAS report for door security and
other substation facilities provided by SAS.
The metal parts of housing shall be cleaned, primed with rust inhibiting and waterproofing
primer and finished with corrosion and weather-resistant enamel and final coat of air drying
enamel. Alternative finish may be used subject to approval.
ATK002-422-C240-FD-E-RPT-00012
17
Identification and danger signs shall be made of heavy cast metal, each not less than 200
x 300 mm and installed on all sides of the substation.
Permanent fungicidal treatment shall be provided for switchgear interiors, transformer coils
and cores, over current protective devices, instruments and instrument transformers and
fungus inserts for cable ties etc.
BMS Panel
NAC Panel
Comms Panel/SAS System
SCADA Panel
Battery & Charger system
Air Conditioning
ATK002-422-C240-FD-E-RPT-00012
18
300
300
300
Over each of the exit doors (both emergency and normal), a compact fluorescent,
bulkhead luminaire shall be installed, via a fused circuit.
The luminaires shall be controlled with a manual switch located within the substation.
Exterior Luminaires shall be selected as not to fail in materials or workmanship, corrode,
fade, stain, perforate, erode, or chalk due to effects of weather or solar radiation within
specified warranty period.
ATK002-422-C240-FD-E-RPT-00012
19
Emergency exit lighting shall be provided to highlight the emergency exit routes.
Emergency exit luminaires shall be located above each emergency exit door and along the
exit route to provide safe means of escape from the substation housing.
ATK002-422-C240-FD-E-RPT-00012
20
3.1.21. Testing
All installations throughout outdoor package substation will be tested to ensure compliance
with BS7671. The Substation shall then be issued with a Test Certificate fully in
accordance with BS7671.
This will include compliance with regard to volt drop current carrying capacity of cables
and equipment, insulation resistance, operation of RCDs, earth electrode resistance,
isolation and switching, protection by barriers or enclosures, shock protection earth loop
impedance, earth continuity and short circuit fault rating.
In addition Test Certificates shall be issued for the Emergency Lighting, Fire Alarm, and
lightning protection systems, all in accordance with their respective standards.
21
26 2
26 2
26 2
The humidity control to rooms without specified levels will be via dehumidification of the
air supply.
22
Control systems shall maintain comfort conditions to those areas requiring a controlled
environment, ensure safe operation of plant and systems, provide flexible timed operation
of plant, optimise running costs and maximise energy efficiency.
Building Management Systems (BMS) will be provided, and BMS outstation panel will be
located within the LVAC Switchroom. The systems will have the capability to self learn
optimum starting and stopping times for minimising energy wastage.
The BMS will be networked within the outdoor substation and be capable of connection to
the site wide BMS network infrastructure by means of connection to a communications
node. The Outdoor Package Substation BMS network shall be run on a BACNet or
LONWorks protocol.
The BMS graphics and alarms software shall be generated as part of the building
installation design and will be installed in the site wide monitoring head-end.
Refer to the project report BMS Design Report ATK002-000-A000-FD-M-RPT-00001A.
4.2.3. Transformers
The SCADA shall monitor temperature and status of the Transformers. Monitoring shall
alarm any critical or maintenance conditions.
ATK002-422-C240-FD-E-RPT-00012
23
5.1.2.1 MV Compartments
Refer to Atkins General Arrangement drawing for MV compartment layout and position of
MV switchgear. The items to be installed;
1 No. MV Transformer oil type, 13.8kV/.042kV DYn11, ONAN, with Off load tap
links +5% to -5% @ 2.5% steps on MV side. WTI indication with Alarm and trip.
Interconnection between Transformer LV side and LVAC Board shall via a Busduct
arrangement (using Busbars, 3 phase and neutral)
Transformer Standards shall comply with IEC 60076-1, 60156, 60296 and 60404-2.
The transformer Noise Level shall conform to general A-weighted sound pressure
level measured at 1 m at any direction from transformer has to be less than 56 dBA.
The Transformer Bushings shall be of porcelain type, tank-cover mounted, or tankside mounted to manufacturer's standard, and as approved, with plug-in or bolt-on
arrangements.
Transformer finish surfaces shall be to be steel grit blasted, caustic washed and
phosphatized, primed with waterproof primer and finished with weather-resistant
enamel and final coat of air- drying enamel. Alternative finish may be used subject
to approval.
LVAC Switchboard including the PLC Panel section. 400V indoor Panel, 3 phase,
50Hz, 50kA 1sec. The LVAC Incomer and bus-section are ACB type.
SCADA Panel - Refer Title Load Centres SCADA PANELS FOR INSTALLATION
AT PLANT LOCATIONS SHEET 3 OF 4, drawing number 422-C100-FD-X03XX00- 003004
ATK002-422-C240-FD-E-RPT-00012
25
LV compartment main circuit breaker shall have a solid state trip unit with long-time,
short time and ground-fault pick up and time- delay adjustments and with high
instantaneous over-current trip, to correspond with transformer rating and LV
interrupting capacity at location, time and current coordinated with MV protection on
primary side and circuit breakers or protective devices downstream, as required.
The dimensions of the LVAC Switchgear shall change according to the type of
switchgear and number of outgoing feeders shown on the GA layout drawing for
each substation.
110V DC Battery and Charger are located in the Battery Room for the single ended
substation.
The Battery and Charger are located in the LVAC Switchroom for the Double ended
substations.
ATK002-422-C240-FD-E-RPT-00012
26
Incomer
The circuit breakers shall be monitored and controlled locally via the SCADA system.
MV Transformer
MV Switchgear
LVAC main distribution boards /PLC Panel
BMS systems
ATK002-422-C240-FD-E-RPT-00012
27
NAC Panel
Comms Panel/SAS System
SCADA Panel
Battery & Charger system
Interior Lighting systems
External lighting
Outdoor CCTV
Door Security System
General small power system
Emergency lighting systemGeneral services/systems containment
Lightning protection systems
Earthing systems
Exact locations and physical layout of equipment and components may be varied as
required to suit manufacturer's design and as approved, provided the required functions
and operations are accomplished.
Contractor to ensure that concrete bases and foundations provided for installation of
equipment are constructed in accordance with approved shop and construction drawings
and equipment manufacturers' drawings and that holes for fixing bolts and provisions for
passage of cables etc. are provided as required.
Contractor to ensure that trench construction and covers provided for installation of power
and control cables are in accordance with approved shop and construction drawings.
Contractor to ensure that equipment supports, fixings and the like, and sleeves for
passage of feeders and cables which are to be built into concrete foundations, bases,
cable trenches or building structure are provided as and when required and that they are
properly installed.
Equipment to be installed on concrete bases etc. and assembled completely plumb and
level, before grouting in holding-down bolts.
Supports and terminations of all installed incoming and outgoing cable supports, cable
ends and termination fittings required for MV, LV and control cables.
Any relays should be set in accordance with manufacturer's instructions and the Local
Power Authorities requirements.
The earthing installation shall be as described in Atkins report Grounding General
Requirements report.
Remove temporary lifting eyes, channels, brackets, and temporary blocking of moving
parts from the switchgear units and other equipment where temporary lifting provisions are
provided.
ATK002-422-C240-FD-E-RPT-00012
28
ATK002-422-C240-FD-E-RPT-00012
29
The main MV earth bar and the main LV earth bar shall not be connected together. MV
and LV earth rods groups shall be connected together via test links.
Separate communications shall be Clean Earth < 1 Ohms
The Earth rods shall be 16mm diameter and 2.4m long.
Bonding connections between down conductors and building re-bars at upper and
lower level of the building when re-bars are used as down conductors.
Perimeter conductor electrically linking all lightning protection earth pits together.
Any cross bonding conductor that may be required by pylon installation contractor.
The entire Lightning system earth resistance shall be not exceed 10 ohms. The lightning
protection system (LPS) earth pits shall be distinctively identified from earthing system
earth pits while maintaining a suitable clearance allowed by the code.
All LPS earth pits shall be lined by a tinned copper ground ring conductor directly buried at
a minimum depth of 600mm. The metallic enclosures of mechanical equipment and steel
cable containment at roof top are cross bonded to the lightning protection system to avoid
side flashing during a lightning discharge.
ATK002-422-C240-FD-E-RPT-00012
30
Estimated
Load
KVA
Transformer
Size kVA
Supply
Load
Centre
AES 1
DOUBLE
328
426.4
500
AES 2
DOUBLE
990
1287
1500
AES 3
DOUBLE
144
187.2
500
AES 4
DOUBLE
137
178.1
500
AES 5
DOUBLE
840
1092
1500
AES 6
SINGLE
49
63.7
500
AES 7
DOUBLE
175
227.5
500
AES 8
DOUBLE
175
227.5
500
Package
Substation
The normal supply loads are those that will usually operate during normal operation of the
Load Centres. The emergency/standby supply loads are those which shall be backed up
by the MV generators located in the Load Centres in the event of loss of normal supplies
feeding the Package Stations. The standby loads include:
ATK002-422-C240-FD-E-RPT-00012
31
A. Appendix
A.1 Auxiliary Electrical Substation Drawing list
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-001100
422-C240-FD-E-03XX07-001100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
ATK002-422-C240-FD-E-RPT-00012
32
422-C240-FD-E-01XX07-002100
422-C240-FD-E-03XX07-002100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-004100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-003100
422-C240-FD-E-03XX07-003100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
ATK002-422-C240-FD-E-RPT-00012
33
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-004100
422-C240-FD-E-03XX07-004100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-005100
422-C240-FD-E-03XX07-005100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
ATK002-422-C240-FD-E-RPT-00012
34
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-006100
422-C240-FD-E-03XX07-006100
422-C240-FD-E-03XX07-030100
422-C240-FD-E-03XX07-040100
422-C240-FD-E-10XX07-001100
422-C240-FD-E-11XX07-001100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-001100
MV PROTECTION DRAWING
422-C240-FD-X-15XX07-030100
422-C240-FD-X-15XX07-031100
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-001100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-007100
422-C240-FD-E-03XX07-007100
ATK002-422-C240-FD-E-RPT-00012
35
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
Drawing No.
Title
Rev
422-C240-FD-E-00XX07-002100
422-C240-FD-E-01XX07-008100
422-C240-FD-E-03XX07-008100
422-C240-FD-E-03XX07-031100
422-C240-FD-E-03XX07-041100
422-C240-FD-E-10XX07-002100
422-C240-FD-E-11XX07-002100
LIGHTNING PROTECTION
422-C240-FD-E-15XX07-002100
MV PROTECTION DRAWING
422-C240-FD-X-15XX00-002003
422-C240-FD-X-15XX00-003003
422-C240-FD-E-19XX07-001100
STANDARD DETAIL
422-C240-FD-C-19XX07-002100
ATK002-422-C240-FD-E-RPT-00012
36
Address
Email:
Telephone:
Direct telephone:
Fax:
ATK002-422-C240-FD-E-RPT-00012
37