Académique Documents
Professionnel Documents
Culture Documents
EARTHING
1.0
INTRODUCTION
Earthing means a connection to the general mass of earth. The use of
earthing is so widespread in an electric system that at practically every
point in the system, from the generating system to the consumers
equipment, earth connections are made.
Earthing is divided into two main categories:
Neutral Earthing
General Earthing
2.0
OBJECTS OF EARTHING
2.1
Neutral Earthing
This is the earthing of the star or neutral point of power system lines
and apparatus.
The objects of neutral earthing are:
a) To reduce the voltage stress due to switching and lightning surges and
to discharge safely into the ground over voltages occurring in the
system.
b) To permit the use of graded insulation in H.V. and E.H.V systems with
consequent reduction in weight, size and cost.
c) To control the fault currents to satisfactory values.
d) To ensure the operation of ground or earth fault relays.
82
2.2
General Earthing
This is a term applied to all earthing of metal parts of lines and
apparatus used in electrical systems and equipment used in the
utilisation of electrical energy other than neutral earthing.
The objects of general earthing are:
NEUTRAL EARTHING
The various methods of neutral earthing are:
83
3.1
Each line conductor has a capacitance to the earth and the magnitude
of this capacitance is the same in a perfectly transposed three phase
line. With balanced voltages applied to such a line, the capacitance
currents will be equal in magnitude as shown above. Assume an earth
fault in conductor B.
But the voltage across the other two phases rises to phase to phase
voltage, as shown.
84
The fault phase B supplied the currents ICGR and ICGY. These being
capacitive
currents, no current flows when the line capacitance is charged.
Hence, an arcing takes place at the faulted point. During this period,
the line capacitance discharges and capacitive current once again
flows.
intermittent arcing at the point of fault and also gives rise to abnormal
voltages across the healthy phases due to the capacitance effect. In
practice, voltages of 3 to 4 times the system phase voltage may occur
thereby causing damage to the system insulation.
Hence isolated
Solid Earthing
In solid earthing a direct metallic connection is made between the
system neutral and the ground. The ground electrode resistance will
be very small usually less than one ohm.
85
consists of two components IFBG which flows into the system neutral
and ICBG = ICGR + ICGY the capacitive currents. IFBG is a very large
component compared to ICBG.
The potentials VRN and VYN will still be the phase to ground voltages
as the neutral is not displaced from the ground potential as it is held at
ground potential.
3.21 The Main Advantages are:
a) There is no abnormal voltage rise on the other healthy phases.
b) Permits the use of discriminative protective gear.
c) No voltage stress on the system insulation.
86
In such cases
increased
ground
fault
currents
affect
neighboring
telecommunication circuits.
Most of the adverse effects have been overcome nowadays by the use
of high rupturing capacity, high speed circuit breaker and fast acting
protective relays. Hence in the world over, it is the practice to adopt
solid earthing for the neutrals of power systems.
3.3
Resistance Earthing
This is one form of impedance earthing and introduced when it
becomes necessary to limit the earth fault current.
The resistance
87
88
Where
Vph
I
resistance in ohms
Vph
89
Reactance Earthing
This is another form of impedance earthing also called `Peferson Coil
Earthing' after the name of the inventor.
90
and in any case inadequate to maintain the arc. Hence the name `arc
suppression coil'
It can be seen from the phasor diagram that:
a) Voltage of the faulted phase at the point of fault is zero.
b) Voltage of the healthy phases rises to 3 times the phase voltage.
c) A resultant capacity current ICBG equal to 3 times the line to neutral
charging current flows through the fault, leading the voltage of the
faulty phase by 900.
d) Voltages of the faulty phase i.e. the phase voltage is impressed across
the arc
suppression coil and a fault current IFBG restricted in magnitude by the
impedance of the coil flows, lagging the voltage of the faulty phase by
900.
e) The capacity current ICBG and the fault current IFBG are in direct
phase opposition. By suitably adjusting the value of the reactance with
the help of tappings provided on such coils, IFBG can be made equal to
the capacity current ICBG so that the resultant fault current is
practically limited to zero.
In actual practice, however, there will always be a small residual
current present in the fault due to the effect of resistance in the arc
suppression coil. But the current is too small to maintain an arc.
A system earthed through an arc suppression coil is similar to an
isolated earth system except for the arcing grounds. Since the voltage
91
92
ICBG =
Also IFBC =
Where
3 Vph
Xc
Vph
Xl
Vph
Xl
Xl
Xc
3
1__
3c
1 __ Henries
3 2 c
ohms
ICBG =
3Vph
Xc
4.0
EARTHING TRANSFORMERS
4.1
93
The earth fault current flowing in the earth returns to the power system
by way of the earthed star point of the earthing transformer.
This
current gets equally, divided in all opposite direction to the source and
to the fault as shown.
94
current is 1000 Amps and line to line voltage is 11KV, then KVA rating
of the earthing transformer is:
=
11 x 1000
3
6350 KVA
This
95
5.1
5.2
5.3
In less densely populated regions where loads are small but distances
are long, only single circuit lines are justified. Such systems are good
fields for the application of arc suppression coils.
The number of
96
97
98
6.1
a) High conductivity
b) Low rate of corrosion by soil
c) Low rate of corrosion due to galvanic action.
6.2
Copper fulfills all these requirements and at one time used to be the
only material for grounding systems. No doubt, it creates galvanic cell
with other dissimilar metals i.e. zinc, lead, iron etc buried in the
vicinity. Yet it is cathodic with respect to all these metals. This causes
the corrosion of other buried materials like steel pipes, conduits, cable
sheaths etc, and keeps the copper
earthing materials intact. However, scarcity and high cost of this metal
prompted research in the use of other materials for the grounding
systems. The knowledge gained has brought forth steel and to some
extent aluminium in to use. Steel has the following advantages as a
grounding material:
1) It is available in plenty
99
6.3
Depending upon
resistivity of soils (low resistivity soil are generally more corrosive), the
zinc coating may be destroyed within 2 to 20 years. Galvanized steel
in ground corrodes at a slow rate in the beginning but the rate of
corrosion increases once the coating is destroyed.
Therefore,
6.4
Size of Conductor:
While deciding the size of grounding material, the following factors
should be kept in view:
100
3. That it will last for at least 50 years without causing a break in the
grounding circuit due to corrosion.
4. That it has sufficient conductivity so that it does not contribute
substantially to local potential gradients.
It is a common practice to allow for 50% margin to cover excessive
corrosion in certain soils particularly those of low resistivity because
such soils by virtue of free salts and moisture cause heavy corrosion.
7.0
EARTHING SYSTEM
7.1
1) All parts of apparatus (other than live parts) connected to the earthing
system through earthing conductors shall be at ground potential.
2) Operators and attendants shall be at ground potential at all times.
Also by providing such a ground surface of uniform potential under and
surrounding the station, there can exist no difference of potential in a
short distance great enough to shock or injure an attendant when short
circuits or
other abnormal occurrences take place.
7.2
101
keep grounding potential within safe limits even though the earth
resistance may be kept low.
As a
CONDUCTOR MESH
It may be mentioned here that these electrodes may or may not be
used depending upon the design of the earthing grid.
All metal
7.3
Step
Potential,
Touch
Potential
and
Transfer
Potential
Definitions
The flow of ground fault current results in voltage gradients on the
surface of the earth in the vicinity of the grounding system.
The
102
voltage that exists between the two feet of a person standing on such
a ground is called Step Potential as shown in fig. 7.1 below whereas the
voltage that exists between the hand and both feet of a person is
called Touch Potential as shown in fig. 7.2
0.165/t
where `t' is time duration of shock in seconds and is less than 3
seconds.
103
E step (tolerable)
9 + 0.054 Ps volts
-1
-2
For grounding to be safe, for step contact, under fault conditions the
voltage gradient in volts per meter (assuming distance of one pace to
be one meter) on the surface of the ground should not exceed the
value given by equation (1) or (2) as the case may be.
Similarly, from Fig. 7.2, the tolerable potential difference between any
point on the ground where a man may stand and any point on the
structures or equipment frames which can be touched simultaneously
by either hand is given by:
E touch (tolerable)
(Rk + Rf/2) Ik
104
E touch (tolerable)
-3
-4
8.0
105
8.1
Trenches dug for burying the grounding conductor should be filled with
earth free of stones. The filling should be carefully rammed.
8.2
Where copper
8.4
For protection against rust of buried welded joints, located in soil, the
weld should be coated with molten bitumen and covered with bitumen
impregnated tape. In case of copper conductor the joint faces should
be tinned.
8.5
8.6
Where the diameter of the bolt for connecting the earth bar to
apparatus exceeds one quarter of the width of the earth bar, the
connection to the bolt shall be made with a wider piece or flag of metal
jointed to the earth bar. If of copper the earth bars or flags shall be
106
8.8
All the area over which the ground grid is spread should be covered by
7.5 cm thick crushed rock which should also be spread 1 to 1.5 meters
from the periphery grounding system. Crushed rock should be placed
outside along the periphery of the fencing.
8.9
107