Vous êtes sur la page 1sur 8

DUPLEX

1400 to 10100 Basic

DUPLEX 140010100 Basic is a new generation


of all-purpose ventilation units with cross-flow heat recovery
exchangers.
The indoor version of compact DUPLEX 140010100 Basic
units are used for comfort ventilation, hot-air heating and
cooling in small facilities, shop floors, stores, schools,
restaurants, shops, sports and industrial halls and swimming
pools. The units are intended for indoor operation in covered
and dry areas with temperatures between 5 and 40 C and
relative humidity up to 90 %. They are suitable wherever
efficient ventilation and possibly hot-air circulation ventilation
and cooling must be provided at minimum running cost, i.e.
the highest efficiency of heat recovery and low power input
offans.
DUPLEX Basic units are compact appliances containing
inasingle cabinet two independently controlled EC fans with
backward curved blades a heat recovery exchanger with
large heat-transfer surface and high efficiency, slide-out
supply and exhaust air class G4, M5 or F7 filters, drain pans
and possibly also an internal bypass with a servo drive and
acirculation damper with a servo drive.
The cabinet has a sandwich structure and consists
ofpainted sheet and 30 mm of PIR fill with an outstanding
heat transfer coefficient ( = 0,024 W/mK).
DUPLEX Basic ventilation units meet the requirements
of the most stringent European standards:
= Casing properties according to EN 1886
= EC motors according to ErP 2015
3
= SFP < 0,45 W/(m /h) according to PassivHaus*
= Hygienic requests according to VDI6022

AVAILABLE MODIFICATIONS

B
C

14 0 0 t o 10 10 0 B a s i c

All-purpose ventilation units


with cross-flow heat
recovery exchangers

Advantages of DUPLEX Basic units:


= New design of ventilation units with excellent parameters
= Great thermal insulation of the casing (class T2)
= Reduced thermal bridging (class TB1)
= Compact dimensions
= Very flat unit suitable for under ceiling installation
= Ease of installation
= Variable configuration of discharge ports
= Unified dimensions of ports
= Optional versions with a bypass and circulation damper
3
= Horizontal floor-standing up to 10 100 m /h, floorstanding flat or ceiling suspended types up to 8 100 m3/h
3
= High efficiency fans SFP < 0,45 W/(m /h)*
= High heat recovery efficiency of the cross-flow heat
recovery exchanger up to 70 %
= Integrated control system including temperature sensors
= Integrated web server (RD4 regulation only)
= Comfortable unit control with touchscreen CPA controller
= Comprehensive selection software
* in a limited area

(CAN BE COMBINED)

T
CHF
CHW

with in-built bypass damper


with in-built circulation damper

with in-built hot-water heater


with in-built direct chiller
with in-built water-based chiller

Unit ventilators, heat recovery issue 02/2014

OPERATING MODES OF DUPLEX BASIC UNIT S

e2

i2

e2

i2

e2

i2

i1

e1

i1

e1

i1

e1

e1 ... Fresh outdoor air suction


e2 ... Fresh filtered air outlet

Ventilation without heat recovery


(via bypass)

Circulation heating
or cooling

Ventilation with heat recovery


with re-heating (with cooling)

i1
i2

T ... Central heating connection


CH ... Cooling connection

... Exhaust air suction


... Exhaust air outlet

SELECTION SOFTWARE

s a v e

y o u r

e n e r g y

For the detailed design of DUPLEX series


units, accessories and control systems
werecommend using our dedicated design
software. You can find it on our website
atwww.atrea.cz or request a CD at our
office.

N I T

V E N T I L A T O R S

&

H E A T

ATREA s.r.o., V Aleji 20


466 01 Jablonec n. N.
Czech Republic

R E C O V E R Y

Phone: +420 483 368 111


Fax: +420 483 368 112
E - m a i l : atr ea@ a t r e a . c z
www.atrea.cz

PERFORMANCE GRAPHS
DUPLEX BASIC

DUPLEX Basic
Supply air max. 1)
m3h-1
1)
Extraction air max.
m3h-1
Heat recovery efficiency 2)
%
Number of versions and positions

Weight 3)
kg
Max. power input
kW
Voltage
V
Frequency
Hz
min-1
Revolutions max.
4)
Heating output T max.
kW
Cooling output CHW max. 4)
kW
Cooling output CHF max. 4)
kW
1)
2)

1400
1 650
1 660

2400
2 800
2 780

180260
0,7
230

190270
1,4
230

3 350
20
12
11

2 900
27
18
15

5400
7100
5 740
7 750
5 800
7 580
up to 70 %
see table Mounting positions, page 4
280360
310380
360440
2,7
4,8
6,1
400
400
400
50
2 980
2 960
2 700
34
51
64
25
35
51
18
31
48

8100
8 600
8 500

10100
11 000
11 100

470550
7,4
400

570660
10,3
400

2 800
76
60
58

2 570
94
68
65

3400
3 970
4 200

3)

Maximum flow rate through units at zero external pressure


According to air volume

4)

Depending on equipment
Depending on register type, liquid and flow rates

Pressure reserve pst (Pa)

PERFORMANCE SUMMARY

1 000
Supply section (G4)
Supply section with T.3+CHW.5+G4
Supply section with T.3+CHW.5+F7
Exhaust section (G4)

900
800
700
600
500

EX
M

0
10
10113

100

sic

Ba

ic

ic
8 000

Bas

Bas

7 000

PL

X 8112
M

6 000

DU

PLE

asic

5 000

DU

0
710
LEX M111

0B
540
LEX M110

4 000

3 000

DUP

DUP

2 000

asic

1 000

asic

0 Basic

100

0B
340
LEX M109

200

DUP

M1

X 1400
7

0B
240
LEX M108

DUPLE

300

0
0

DUP

400

9 000

10 000 11 000 12 000


Air volume (m3/h)

Heat recovery efficiency (%)

HEAT RECOVERY EFFICIENCY

80

Low limit is without condensation and equal air volume flow (Me = Mi)

1400, 24
70
00 Basic

54
3400 Basic 00 Basic

8100
7100 BasicBasic

10100 Basic

60
50
40
0

1400, 2400 Ba

sic 3400 Basic 5400 Basic

1 000

2 000

4 000

3 000

5 000

8100
7100 Basic Basic
6 000

7 000

10100 Basic

8 000

9 000

K750.G
K750.F
10 000 11 000 12 000
Air volume (m3/h)

Heating / cooling capacity QT/CH (kW)

HEATING AND COOLING PERFORMANCES

100
80
60
40
20
0
0

sic
10100 Ba

Max. heating capacity data T are valid for


70/50 C water temperature dropand +10
C, r.h. 10 % supply air (after recovery)
Max. cooling capacity data CHW are valid for
30 % water/ethylene-glycol mixture, 6/12 C
temperature drop, +30 C, r.h. 50 % supply air

,
1400
1 000

2400

0
340
Basic

2 000

asic

Basic
7100

8100 Basic

B
5400
c

Basi

maximum heating capacity for T.5


maximum cooling capacity for CHF.5 and CHW.6

3 000

4 000

5 000

6 000

7 000

8 000

9 000

10 000 11 000 12 000


Air volume (m3/h)

DIMENSIONS
BASIC DIMENSIONS

UNDERCEILING (top view)


Basic 1400 to 8100

FLOOR-STANDING FLAT (top view)


Basic 1400 to 8100

alternative spigot position


(configuration 31/5)

alternative spigot position


(configuration 41/5)
door

mm
mm
mm
mm
mm
mm
mm

Y2

Y1

Y1

Y1

X1 ( D)
door

X1 ( D)

X1 ( D)

Y2

Y2

150

door
X2 ( D)
X2 ( D)
alternative spigot position
(configuration 31/10)

alternative spigot position


(configuration 11/10)

X2

L
405 x 305

X1 ( D)
door

Y2

Y2

L2

X2 ( D)

DUPLEX Basic
Dimension H
Dimension B
Length L
Length L2
Condensate drain line
Connecting ports
Dimension X1 x Y1 (standard e, i)
Dimension X2 x Y2 (atypical e, i)

200

X1 ( D)

Y2

Y2

200

Y1

H + 50

Y1

X1 ( D)
door

door
X2 ( D)

X2

L
405 x 305

Y1

B
100

L
405 x 305

X2

100

X2

Y2

Y2

Y2

door

100

FLOOR-STANDING (front view)


Basic 1400 to 10100

door
X2 ( D)
X2 ( D)
alternative spigot position
(configuration 41/10)

1 400
1 300
455
2 100
2 070

2 400
1 300
455
2 100
2 070

3 400
1 450
580
2 300
2 270

5 400
1 600
665
2 300
2 270
32

7 100
1 600
885
2 500
2 470

8 100
1600
1 065
2 500
2 470

10 100
1 600
1 295
2 500
2 470

315
315*

315
315*

300 x 400
400 x 300

400 x 400
400 x 400

500 x 500
500 x 500

500 x 500
500 x 500

700 x 500
500 x700

* Dimension X2 x Y2 (port e1, i1) for non-standard configuration: 400 x 200 mm. For detailed design and technical data we recommend using
our dedicated selection software.

TYPES AND DIMENSIONS OF CONNECTING PORTS

RECTANGULAR

Basic port
(inlet, outlet)

X + 20

Port with flexible


flange
(inlet outle)

Port with damper


(inlet outlet)

Port with damper


and flexible flange
(inlet only)

CIRCULAR

150
Y+20

door

door

Port with flexible


flange
(inlet outle)
215

80

260

alter.

alter.

Basic port
(inlet, outlet)

110

alter.

Note: For detailed design and technical data we recommend using our dedicated selection software.

Port with damper


(inlet outlet)

80

Port with damper


and flexible flange
(inlet only)
215

INSTALLATION AND VERSIONS


INSTALLATION VERSIONS AND CONNECTING PORTS

DUPLEX 1400 to 10100 Basic units are available in a range


ofversions to facilitate their installation in the machine room. This
significantly increases options to install DUPLEX Basic units in
cramped spaces.
For structural reasons and to ensure condensate drain it is not
possible to have all units available in all mounting positions. Detailed
drawings are shown in the summary table Mounting positions.

DUPLEX Basic units are characterised by a wide range


of accessories the ports may be optionally fitted with flexible
flanges and inlet ports may have shut-off dampers if required.

MOUNTING POSITIONS
F L O O R - S TA N D I N G
H O R I Z O N TA L P O S I T I O N
Basic 1400 to 10100

configuration 10/0 to 11/10 door-side view (up to 8 configurations in total)

i2

e2

i2

e2

10

11

e1

i1

i1

e1

i1

e2

e2

i1

12

13
i2

e1

CEILING-SUSPENDED
POSITION
Basic 1400 to 8100

i2

configuration 30/0 to 31/15 top view (up to 32 configurations in total)

i2

e2

i2

30

e2
31

i1

e1

e1

i1

e2

i1

i1

e2
33

32
i2

F L O O R - S TA N D I N G
F L AT P O S I T I O N
Basic 1400 to 8100

e1

e1

i2

e1

configuration 40/0 to 41/15 top view (up to 32 configurations in total)

i2

e2

i2

e2

40

41

e1

i1

i1

e1

i1

e2

e2

i1
43

42
e1

i2

i2

Note: For detailed design and technical data we recommend using our dedicated selection software.

e1

HANDLING SPACE
HANDLING SPACE

DUPLEX units must be installed with the prescribed handling


space around the unit in mind.
Below the unit at least 150 mm must be left to install the DN 32
condensate drain line. This line must run through a U-bend at least
150 mm high into a sewer. This space is easily provided when the
steel supporting feet supplied as standard are used. Handling
space in front of the unit must be maintained for opening the front
door, replacing filters and providing servicing and installation
access to each unit part.

Each drawing shows the minimum handling space.


In addition, each unit must have the minimum handling space
of600 mm from the side of the control system electric
switchboard according to CSN.
Units with a heating or cooling control manifold must have free
space from the side of the manifold, too.

Handling space in front of the door


Ceiling- suspended

Floor-standing horizontal

Handling space for accessories


Floor-standing flat

Control modules
min. 600
120

min. T

CPA
RD4

200

min. T

panty

min. 80

ceiling

floor
Control manifolds
min.
600

min. 30

wall

200

RE-TPO4 / RE-TPO3
R-CHW

min. T

Type
DUPLEX 1400 Basic
DUPLEX 2400 Basic
DUPLEX 3400 Basic
DUPLEX 5400 Basic
DUPLEX 7100 Basic
DUPLEX 8100 Basic
DUPLEX 10100 Basic

standard door T (mm)


1 000
1 000
1 200
1 200
1 300
1 300
1 500

hingeless door T (mm)


500
500
600
700
900
1 100
1 300

ACOUSTIC POWER LW AND ACOUSTIC PRESSURE LD1

Type
DUPLEX 1400 Basic
DUPLEX 2400 Basic
DUPLEX 3400 Basic
DUPLEX 5400 Basic
DUPLEX 7100 Basic
DUPLEX 8100 Basic
DUPLEX 10100 Basic

Working point
1 000 m3/h (200 Pa)
2 000 m3/h (200 Pa)
3 000 m3/h (200 Pa)
4 500 m3/h (200 Pa)
6 000 m3/h (200 Pa)
7 500 m3/h (200 Pa)
9 500 m3/h (200 Pa)

inlet e1
51
55
73
77
62
71
83

Acoustic power Lw [dB(A)]


inlet i1
outlet e2 outlet i2
55
77
76
65
86
88
69
95
88
64
98
85
63
87
85
64
95
88
80
89
93

unit
50
56
67
64
63
64
62

Acoustic pressure Lp [dB(A)]


at distance of 3 m
30
35
47
43
43
44
41

MODIFICATIONS
DUPLEX BASIC BASIC UNIT

DUPLEX xxxx Basic


Basic configuration
The compact unit consists of supply and exhaust centrifugal fans with electric motors in anti-vibration mounting,
removable cross-flow air-to-air heat recovery core assembled from thin plastic plates, removable G4, M5 or F7 supply
andexhaust air filters, and a condensate pan with flexible hose. Afront door enables easy access to all built-in
components and filters.
Me.xxx; Mi.xxx
Fans
All units are equipped with high-efficiency fans (ebm-papst and Ziehl Abegg) with free-running impellers and backward
curved blades. Whole range of DUPLEX 1400 to 10100 Basic units meets the requirements of the European
directive ErP 2015.
Heat recovery core
For every single unit size are two heat recovery exchangers available (K750.F and K750.G),
that differs in heat recovery efficiency and pressure loss.

K750.x

DUPLEX BASIC MODIFICATION DESCRIPTION

B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
andanactuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

C.x
Mixing damper (C)
The mixing damper is used to mix exhaust and supply air. Circulation valve consists of an opposed-blade damper and
actuator. It is fitted next to the recovery core inside the unit, it does not increase the size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.

T.x
H o t w a t e r h e a t i n g c o i l ( T )
Built-in water-to-air three-row (possibly multi-row) heating coil; made of copper pipes and aluminum fins. Designed
forsystems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function is reccommended. A coil hydraulic kitforheating capacity
control of RE-TPO4 or RE-TPO3 type can be supplied with the coil upon request.

CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Three- or multi-row coils with various evaporate temperature are chosen
depending on capacity required, refrigerant type and air parameters. Optionally it is possible to deliver double-circuit
evaporator in division 1:1 or 1:2, or completely atypical with needed capacity.

Chilled water cooling coil (CHW)

CHW.x

A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage.
Three- ormulti-row coils are chosen depending on capacity required, cooling medium type and air parameters.
The cooling coil can be equipped with the R-CHW2 or R-CHW3 hydraulic kit on request.

Individual modifications can be freely combined


Example:
DUPLEX-TC (unit with a hot-water heating coil and a mixing damper)
DUPLEX-T-CHF (unit with a hot-water heating coil and a DX coil)

ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)

Ke.xxx; Ki.xxx
Shutoff damper e1; i1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
-- fresh air damper e1 - mandatory for C
modification (with mixing damper) and
Tmodification (with heating coil)
-- exhaust air damper i1

Fe.xxx; Fi.xxx
Air filtration
All DUPLEX Basic units can be equipped with
supply or exhaust air filtration of M5 or F7 class
instead of standard G4 class. Pressure drop of
the filter is then 50 to100 Pa (clean filter)
depending on air flow rate, unit type and dirt
accumulated.

RE-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity
ofaheating coil. It consists of a three-speed
pump, two globe shutoff valves and connection
pipes. Further equipment depends on the type:
RE-TPO4 four-way mixing valve with
anactuator for digital control system
RE-TPO3 three-way mixing valve with
anactuator for digital control system

R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity of
achilled-water cooling coil. It always consists
oftwo globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-CHW3 three-way mixing valve with
anactuator
R-CHW2 throttling valve with an actuator for
digital control system

MFF
Tu b e m a n o m e t e r s
Accessory for filters for simple view of current
pressure drop. The tube manometers are
obligatory for hygienic unit design in accordance
with the VDI 6022.

FK.x
Spare cartride
filters
Replacement filter cartridges in different sizes
based on the unit type. Available in G4, M5 and
F7 filtration class.

Delivery of diassembled unit


All units can be delivered dismantled on request.
The unit is to be assembled by rivets and bolts
directly on site, therefore the unit can be
installed in inaccessible location.
Casing insulation class T3, thermal bridging
class TB2.

H.P
Flexible
connections
Round and rectangular ports can be equipped
with flexible connections upon request.

TPO
Hot water heating
coil (TPO)
Separately supplied coil for installation into
round duct.
It is suitable for cramped locations, where
itisimpossible to put the coil inside the unit,
aswell as for rooftop units.
The coil is standardly equipment with the steamgas capillary thermostat.
Capacities and diameters canbefound
inrespective catalogue sheets.

EPO-V
Electric heating coil
(EPO-V)
Separately supplied heating coil to be fitted
into round or rectangular duct. Capacities and
diameters canbefound in respective
catalogue sheets.

CF.XXX
Constant air flow
and pressure
Manometers reading fan pressure together
with controls, enables intelligent fan control of
preselected airflow. This accessory assumes
the unit is equipped with digital controls of DC or
RD4 type. Using a second manometer (optional
accessory) in the supply air duct enables the
user to control constant pressure in the supply
duct.

EPO-V
Electric preheaters
EPO-V
EPO-V electric heating coils to provide the
antifreeze protection of the heat recovery
exchanger when equal-pressure ventilation is
continuously required. It is installed inside a duct
on the outdoor supply air side of the unit (e1).
Control is provided through the DUPLEX (RD4
or DC) unit control system.

Hingeless door
When needed it is possible to deliver door
without standard hinges than necessary
manipulation space is reduced.

CONTROLS
DUPLEX Basic units are delivered with basic control
components or with complete control systems.
There are three types ofcontrol systems available (electric,
digital and control for kitchens) according tocustomer needs
and an application. The systems also include variety of
sensors (temperature, humidity, air quality, CO2) for effective
operation control.

Features of the control systems


selection of the most suitable and efficient control
system atthe lowest cost, depending on the application
control system is integrated with the unit, most
components arealready wired and checked in factory,
thus reducing the risk of incorect wiring
no control system project documentation is necessary
forstandard cases, standardized solutions can be used
simple wiring, system simplicity, error indication
qualified technical support and consulting

SUMMARY OF DUPLEX BASIC CONTROL SYSTEMS

Type

Use

Basic controls

all electrical components are wired to a junction box


terminal strip inside or outside the unit
standard components are fans, damper actuators,
capillary freeze protection thermostat of hot water
heating coil
more components is included upon customer's
request (exact actuator type, sensors, thermostats,
pressure switches etc.)
suitable for applications with separate delivery of
control system; e.g. large buildings with central control
system etc.

CP controls

RD4 controls

Standard functions
EC fan speed control (stepless)
automatic by-pass damper position
frost protection of heat exchanger
switching of external electric or built-in water heater
input for external switch
inlet and outlet shut-off damper control
minimum and maximum fan speed preselection
analogue input (010 V) for air quality sensor (CO2, RH)
Controller CPA
fully graphic touchscreen
weekly program
party mode
holiday mode
filter change notice
automatic operation based on constant signal
e.g.constant pressure
Controller CPB
rotable controller
switch for heating allowance
Standard functions
EC fan speed control (based on selected mode)
automatic by-pass damper position (heat and cool
recovery)
evaluates and prevents emergency limits based on
measured temperature
ventilation and temperature weekly program setting
A web server and an Ethernet interface built in as
standard connection for remote internet
communication
inputs for switching using 230 V
(4 inputs 3delayed, 1instantenious) switch e.g.
from bathrooms etc.
optional connection of CO2 or RH sensor
max. 2 sensors with a switch or 010 V output
outputs for electric preheater and heater control
(pulse 10 V) or hot-water control (010 V)
Additional RD4-IO module
optional manometer connection to ensure constant
airflow control (see Constant airflow and pressure
control on previous page)
constant pressure control
cooling control outputs (DX- or chilled-water cooling)

Controller

basic version
(fans, actuators, thermostats,
pressure switches
and others on request)

Supervisory control system

Controller CPA
with touchscreen

Controller CPB
rotable controller

CP 18 RD
installation in the standard recessed dual box on the wall

CP 19 RD
installation on wall

Web server
(Standard)

Smartphones Application

Vous aimerez peut-être aussi