with counterflow
heat exchangers
DUPLEX 5008000 Multi is a new generation
of all-purpose ventilation units with counterflow heat recovery
exchangers.
The indoor version of compact DUPLEX 5008000 Multi
units are used for comfort ventilation, hot-air heating and
cooling in small facilities, shop floors, stores, schools,
restaurants, shops, sports and industrial halls and swimming
pools. The units are intended for indoor operation in covered
and dry areas with temperatures between 5 and 40 C and
relative humidity up to 90 %. They are suitable wherever
efficient ventilation and possibly hot-air circulation ventilation
and cooling must be provided at minimum running cost, i.e.
the highest efficiency of heat recovery, low power input of
fans and as little noise as possible.
DUPLEX Multi units are compact appliances containing
inasingle cabinet two independently controlled EC fans with
backward curved blades a heat recovery exchanger with
large heat-transfer surface and high efficiency, slide-out
supply and exhaust air class G4, M5 or F7 filters, drain pans
and possibly also an internal bypass with a servo drive and
acirculation damper with a servo drive.
The cabinet has a sandwich structure and consists
ofaluminium sheet and 30 mm of PIR fill with an outstanding
heat transfer coefficient ( = 0,024 W/mK).
DUPLEX Multi ventilation units meet the requirements
of the most stringent European standards:
= Casing properties according to EN 1886
= EC motors according to ErP 2015
3
= SFP < 0,45 W/(m /h) according to PassivHaus*
= Hygienic requests according to VDI6022
AVAILABLE MODIFICATIONS
B
C
(CAN BE COMBINED)
T
CHF
CHW
O P E R AT I N G M O D E S O F D U P L E X M U LT I U N I T S
T CH
e2
i1
T CH
i2
e2
i2
e1
i1
i1
e1
Circulation heating
or cooling
T CH
e2
i1
i2
SELECTION SOFTWARE
s a v e
y o u r
e n e r g y
N I T
V E N T I L A T O R S
&
H E A T
R E C O V E R Y
DUPLEX
500 to 8000 Multi
PERFORMANCE GRAPHS
DUPLEX MULTI
DUPLEX Multi
Supply air max. 1)
Extraction air max. 1)
Heat recovery efficiency 2)
Number of versions and
Weight 3)
Max. power input
Voltage
Frequency
Revolutions max.
Heating output T max. 4)
Cooling output CHW max. 4)
Cooling output CHF max. 4)
1)
2)
m3h-1
m3h-1
%
kg
kW
V
Hz
min-1
kW
kW
kW
500
660
670
1000
1 200
1 150
80 110
0,3
230
95 130
0,7
230
4 300
5
4
3
3 350
14
8
6
1500
2 200
1 800
2500
3500
5000
6500
8000
3 400
4 600
5 750
7 100
9 600
3 200
4 200
5 500
7 050
9 100
to 93 %
see table Mounting positions, page 4
200 280 290 370 320 390 370 450 480 560 580 670
1,2
2,6
4,5
4,6
7,3
9,3
230
400
400
400
400
400
50
2 920
3 000
2 980
2 400
2 820
2 560
22
30
42
51
71
88
16
22
30
42
56
62
10
13
25
32
41
50
3)
4)
Depending on equipment
Depending on register type, liquid and flow rates
PERFORMANCE SUMMARY
1 000
Supply section (G4)
Supply section with T.3+CHW.5+G4
Supply section with T.3+CHW.5+F7
Exhaust section (G4)
900
800
700
600
500
00
80 3
EX M11
500
X 6112
Mu
lti
lti
lti
6 000
Mu
Mu
5 000
PL
PLE
00
50
EX M111
lti
4 000
DU
DU
PL
Mu
3 000
DU
0
350
LEX M110
lti
2 000
DUP
Mu
ulti
i
1 000
0
250
LEX M109
0M
150
LEX M108
0 Mult
0
0
DUP
DUP
M1
Multi
100
X 1000
7
200
DUPLE
300
00
DUPLEXM5
106
400
7 000
8 000
9 000
10 000
Air volume (m3/h)
100
1
95 500 Mu 500 Mu
lti
lti
90
85
80
75
1000 Multi
70
0
1 000
2 000
3500 Mu
6500 Multi
lti
2500 Multi
3 000
8000 Multi
5000 Multi
4 000
5 000
6 000
7 000
8 000
9 000
10 000
Air volume (m3/h)
100
80
60
Max. heating
capacity
data uvdny
T are valid
forvodu
Max.
topn vkony
T jsou
pro
70/50
C water
temperature
dropand
sespdem
70/50
C; vstupn
vzduch+10 C,
r.h.
10 % supply air
(after recovery)
(porekuperaci)
+10C,
rh 10 %.
Max. cooling
chladiccapacity
vkony CHW
jsou are
uvdny
Max.
data CHW
valid for
provodu
s 30 % etylenglykolu
a se 6/12
spdem
30
% water/ethylene-glycol
mixture,
C
temperature
drop,vzduch
+30 C,30
r.h.C,
50rh
% 50
supply
6/12 C; vstupn
%. air
40
6500 Mult
8000 Mult
5000 Mult
1500 Mult
20
0
0
ulti
M
500
1000 Multi
1 000
2 000
2500 Multi
3 000
3500 Multi
4 000
5 000
6 000
7 000
8 000
9 000
10 000
Air volume (m3/h)
DIMENSIONS
BASIC DIMENSIONS
L
405 x 305
X3 ( D)
Y2
door
Y3
door
B
X3 ( D)
L2
X1 ( D)
Y1
L
405 x 305
X3 ( D)
Y1
K K
Y1
X2
1 650
Y3
door
200
X2
Y3
B
100
L
405 x 305
X2
100
X2
Y2
Y2
door
Y2
door
100
X1 ( D)
X1 ( D)
door
X4 ( D)
X4 ( D)
alternative spigot position
(configuration 11/10)
500
765
384
1 600
1 652
mm
mm
mm
mm
mm
1000
970
384
1 800
1 852
Y4
Y4
door
X4 ( D)
X4 ( D)
alternative spigot position
(configuration 30/10)
DUPLEX Multi
Dimension H
Dimension B
Length L
Length L2
Condensate drain line
Connecting ports
Circular diameter D 1)
Dimension X1 x Y1 (standard e1, i1)
Dimension X2 x Y2 (atypical e1, i1)
Dimension X3 x Y3 (standard e2, i2)
Dimension X4 x Y4 (atypical e2, i2)
1)
Y4
Y4
Y4
Y4
150
door
X4 ( D)
X4 ( D)
alternative spigot position
(configuration 41/10)
1500
1 600
455
2 300
2 270
2500
1 600
580
2 300
2 270
3500
1 600
665
2 300
2 270
5000
1 600
885
2 500
2 470
22
mm
mm
mm
mm
mm
200
200 2)
2)
250
250 2)
6500
1 600
1 065
2 500
2 470
8000
1 600
1 290
2 500
2 470
32
315
400 x 200
300 x 400
300 x 400
450 x 710
250 x 355
400 x 400
400 x 400
500 x 710
250 x 400
500 x 500
500 x 500
710 x 710
355 x 630
... for DUPLEX Multi 500 and 1000 only in ceiling suspended version
RECTANGULAR
Basic port
(inlet, outlet)
X + 20
150
CIRCULAR
door
Basic port
(inlet, outlet)
215
80
alter.
Note: For detailed design and technical data we recommend using our dedicated design software.
80
260
alter.
alter.
110
Y+20
door
150
MOUNTING POSITIONS
F L O O R - S TA N D I N G
H O R I Z O N TA L P O S I T I O N
Multi 500 to 8000
e2
i2
e2
i2
10
11
e1
CEILING-SUSPENDED
POSITION
Multi 500 to 6500
i1
e2
i2
31
e1
i1
e2
i2
30
F L O O R - S TA N D I N G
F L AT P O S I T I O N
Multi 1500 to 6500
e1
i1
e1
i1
e2
i2
e2
40
e1
i2
41
i1
i1
e1
HANDLING SPACE
HANDLING SPACE
Floor-standing horizontal
Control modules
min. 600
120
min. T
DC
RD4
200
min. T
hinges
min. 80
ceiling
floor
Control manifolds
min.
600
min. 30
wall
200
RE-TPO4 / RE-TPO3
R-CHW
min. T
Typ
DUPLEX 500 Multi
DUPLEX 1000 Multi
DUPLEX 1500 Multi
DUPLEX 2500 Multi
DUPLEX 3500 Multi
DUPLEX 5000 Multi
DUPLEX 6500 Multi
DUPLEX 8000 Multi
Type
DUPLEX 500 Multi
DUPLEX 1000 Multi
DUPLEX 1500 Multi
DUPLEX 2500 Multi
DUPLEX 3500 Multi
DUPLEX 5000 Multi
DUPLEX 6500 Multi
DUPLEX 8000 Multi
Working point
500 m3/h (200 Pa)
1 000 m3/h (200 Pa)
1 500 m3/h (200 Pa)
2 500 m3/h (200 Pa)
3 500 m3/h (200 Pa)
5 000 m3/h (200 Pa)
6 500 m3/h (200 Pa)
8 000 m3/h (200 Pa)
inlet e1
53
66
58
59
61
64
70
76
unit
59
63
64
70
70
73
76
70
MODIFICATIONS
DUPLEX MULTI BASIC UNIT
Me.xxx; Mi.xxx
Fans
All units are equipped with high-efficiency fans (ebm-papst and Ziehl Abegg) with free-running impellers and backward
curved blades. Whole range of DUPLEX Multi 500 to 8000 units meets the requirements of the European directive
ErP 2015.
Heat recovery core
The only heat recovery core type S7 or S3 made of plastic in counterflow arrangement with high
efficiency up to 93 %.
S7.C
B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
andanactuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.
C.x
Mixing damper (C)
The mixing damper is used to mix exhaust and supply air. Circulation valve consists of an opposed-blade damper and
actuator. It is fitted next to the recovery core inside the unit, it does not increase the size of the unit.
The standard actuator is BELIMO 24 V; other types are available upon request.
T.x
H o t w a t e r h e a t i n g c o i l ( T )
Built-in water-to-air three-row (possibly five-row) heating coil; made of copper pipes and aluminum fins. Designed
forsystems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function is reccommended. A coil hydraulic kitforheating capacity
control of RE-TPO4 or RE-TPO3 type can be supplied with the coil upon request.
CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Three- or four-row coils with various evaporate temperature are chosen
depending on capacity required, refrigerant type and air parameters. Optionally it is possible to deliver double-circuit
evaporator in division 1:1 or 1:2, or completely atypical with needed capacity.
CHW.x
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage.
Three- orfive-row coils are chosen depending on capacity required, cooling medium type and air parameters.
The cooling coil can be equipped with the R-CHW2 or R-CHW3 hydraulic kit on request.
ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)
CHF
A
B,C D
Ke.xxx; Ki.xxx
Shutoff damper e1; i1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
-- fresh air damper e1 - mandatory for C
modification (with mixing damper) and
Tmodification (with heating coil)
-- exhaust air damper i1
Fe.xxx; Fi.xxx
Air filtration
All DUPLEX Multi units can be equipped with
supply or exhaust air filtration of M5 or F7 class
instead of standard G4 class. Pressure drop of
the filter is then 50 to100 Pa (clean filter)
depending on air flow rate, unit type and dirt
accumulated.
RE-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity
ofaheating coil. It consists of a three-speed
pump, two globe shutoff valves and connection
pipes. Further equipment depends on the type:
RE-TPO4 four-way mixing valve with
anactuator for digital control system
RE-TPO3 three-way mixing valve with
anactuator for digital control system
R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity of
achilled-water cooling coil. It always consists
oftwo globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-CHW3 three-way mixing valve with
anactuator
R-CHW2 throttling valve with an actuator for
digital control system
RCHF.x
Accessories
for DX coil
It is possible to equip the DX coils with
refrigeration circle components: expansion valve
with an orifice (A), solenoid valve (B, C),
sightglass(D), filter-drier (E), eventually
withanevaporator pressure regulator.
FK.x
Spare cartride
filters
Replacement filter cartridges in different sizes
based on the unit type. Available in G4, M5 and
F7 filtration class.
H.P
Flexible
connections
Round and rectangular ports can be equipped
with flexible connections upon request.
CF.XXX
Constant air flow
and pressure
Manometers reading fan pressure together
with controls, enables intelligent fan control of
preselected airflow. This accessory assumes
the unit is equipped with digital controls of DC or
RD4 type. Using a second manometer (optional
accessory) in the supply air duct enables the
user to control constant pressure in the supply
duct.
EPO-V
Electric preheaters
EPO-V
EPO-V electric heating coils to provide the
antifreeze protection of the heat recovery
exchanger when equal-pressure ventilation is
continuously required. It is installed inside a duct
on the outdoor supply air side of the unit (e1).
Control is provided through the DUPLEX (RD4
or DC) unit control system.
MFF
Tu b e m a n o m e t e r s
Accessory for filters for simple view of current
pressure drop. The tube manometers are
obligatory for hygienic unit design in accordance
with the VDI 6022.
Hingeless door
When needed it is possible to deliver door
without standard hinges than necessary
manipulation space is reduced.
CONTROLS
DUPLEX Multi units are delivered with basic control
components or with complete control systems.
There are three types ofcontrol systems available (electric,
digital and control for kitchens) according tocustomer needs
and an application. The systems also include variety of
sensors (temperature, humidity, air quality, CO2) for effective
operation control.
Type
Use
basic
RD4 controls
DC controls
Controller
basic version
(fans, actuators, thermostats,
pressure switches
and others on request)
CP 18 RD
installation in the standard
recessed dual box on the wall
CP 19 RD
installation on wall
Web server
(Standard)
Application for
Smartphones
Controllers
DC-p1, DC-p2
DUPLEX
DC control
(module DC-XS)
(module DC EXPc)
Communication
protocols
KNX, Modbus,
TCP/IP
External
components