PERFORMANCE SUMMARY UMA # 38

Untitled SOTANO OFICINAS MANTO


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.10

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,191

Liners
Pressure drop (in w.g.)

Solid
0.61

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (alternate)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
2.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
2,280
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
0.71

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 1 of 159

1.71
1.53
1,553
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 38

Untitled SOTANO OFICINAS MANTO


Air Handler Coils
Coil Tag
#1

Model #
5 W H 6 C - 14T x 44 LH Q

Qty Location
1
Section B - Coil A

Footnotes
A,B

#1
Coil
102.6
Total capacity (MBH)
65.3
Sensible capacity (MBH)
Air Properties
2,280
Air flow (ft/min)
0
Altitude (ft)
334
Face velocity (ft/min)
0.47
Air pressure drop (in w.g.)
77.2 / 65.8
Entering air DB / WB (F)
50.6 / 50.4
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
17.0
Fluid flow rate (gal/min)
2.6
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
56.1
Leaving fluid temp. (F)
5.7
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
44.0
Finned length (in)
6.8
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
7
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.
B. Fin material - 0.008 Polycoat

Tuesday, January 21, 2003

Page 2 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 38

Untitled SOTANO OFICINAS MANTO


Supply Fan Specification
Air handler model
AHD2 FS 040 V M
Fan type
Forward curved (alternate/9-9)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

2,280
1.71
1,553
1.53
54.0

1,600

3.60
3.20
2.80
1.60
1.20
0.80

0.25

0.50

0.75

2.00
2.40
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.00
1.25

1.50

1.75

2.00

Fan Curve

2,000

Tuesday, January 21, 2003

2,400

2,800
3,200
Air flow (ft/min)
Page 3 of 159

3,600

4,000

4,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 4 of 159

Leaving air view

60.0 in
60.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

3.0 in

37.5 in/1,057 lb

78.0 in

54.0 in

Entering air view

15.0 in

65.0 in/775 lb

1.0 in

Contact factory for fan dimensionals.

Side view - AHD2 FS 040 V M

DRAWING UMA # 38

Untitled SOTANO OFICINAS MANTO

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 37

Untitled SOTANO COMEDOR


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.11

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,191

Liners
Pressure drop (in w.g.)

Solid
0.89

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (alternate)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
3.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
2,520
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.00

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 5 of 159

2.00
2.01
1,688
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 37

Untitled SOTANO COMEDOR


Air Handler Coils
Coil Tag
#1

Model #
5 W P 8 C - 14T x 44 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
184.2
Total capacity (MBH)
91.4
Sensible capacity (MBH)
Air Properties
2,520
Air flow (ft/min)
0
Altitude (ft)
370
Face velocity (ft/min)
0.71
Air pressure drop (in w.g.)
82.3 / 72.0
Entering air DB / WB (F)
48.4 / 48.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
35.5
Fluid flow rate (gal/min)
4.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.4
Leaving fluid temp. (F)
13.6
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
44.0
Finned length (in)
6.8
Face area (ft)
8 / 12
Rows / fin spacing (fins/in)
9
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 6 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 37

Untitled SOTANO COMEDOR


Supply Fan Specification
Air handler model
AHD2 FS 040 V M
Fan type
Forward curved (alternate/9-9)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

2,520
2.00
1,688
2.01
54.0

1,600

4.00
3.60
3.20
2.00
1.60
1.20

0.50

0.75

1.00

2.40
2.80
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.25
1.50

1.75

2.00

2.25

Fan Curve

2,000

Tuesday, January 21, 2003

2,400

2,800
3,200
Air flow (ft/min)
Page 7 of 159

3,600

4,000

4,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 8 of 159

Leaving air view

60.0 in
60.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

3.0 in

37.5 in/1,084 lb

78.0 in

54.0 in

Entering air view

15.0 in

65.0 in/845 lb

1.0 in

Contact factory for fan dimensionals.

Side view - AHD2 FS 040 V M

DRAWING UMA # 37

Untitled SOTANO COMEDOR

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 36

Untitled SOTANO OFICINAS DIETISTA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 048 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.15

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,689

Liners
Pressure drop (in w.g.)

Solid
1.12

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
4,040
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.27

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 9 of 159

2.27
3.15
1,259
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 36

Untitled SOTANO OFICINAS DIETISTA


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 C - 14T x 54 LH Q

Qty Location
1
Section B - Coil A

Footnotes
A,B

#1
Coil
149.3
Total capacity (MBH)
105.5
Sensible capacity (MBH)
Air Properties
4,040
Air flow (ft/min)
0
Altitude (ft)
483
Face velocity (ft/min)
0.82
Air pressure drop (in w.g.)
76.4 / 64.7
Entering air DB / WB (F)
52.2 / 52.2
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
26.1
Fluid flow rate (gal/min)
2.8
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.5
Leaving fluid temp. (F)
5.1
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
54.0
Finned length (in)
8.4
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
10
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.
B. Fin material - 0.008 Polycoat

Tuesday, January 21, 2003

Page 10 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 36

Untitled SOTANO OFICINAS DIETISTA


Supply Fan Specification
Air handler model
AHD2 FS 048 V M
Fan type
Forward curved (standard/12-12)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

4,040
2.27
1,259
3.15
54.0

2,400

7.20
6.40
5.60
3.20
2.40
1.60

1.00

1.20

1.40

4.00
4.80
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.60
1.80

2.00

2.20

2.40

Fan Curve

3,200

Tuesday, January 21, 2003

4,000

4,800
5,600
Air flow (ft/min)
Page 11 of 159

6,400

7,200

8,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 12 of 159
26.6 in

70.0 in

15.8 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

70.0 in

3.0 in

37.5 in/1,204 lb

12.4 in

80.0 in

64.0 in

Entering air view

15.0 in

65.0 in/871 lb

1.0 in

13.6 in

Side view - AHD2 FS 048 V M

DRAWING UMA # 36

Untitled SOTANO OFICINAS DIETISTA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 35

Untitled P.BAJA AUTOPSIA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 080 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.14

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
5,146

Liners
Pressure drop (in w.g.)

Solid
0.98

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
5,979
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.12

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 13 of 159

2.12
4.34
1,014
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 35

Untitled P.BAJA AUTOPSIA


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 C - 18T x 62 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
231.8
Total capacity (MBH)
152.9
Sensible capacity (MBH)
Air Properties
5,979
Air flow (ft/min)
0
Altitude (ft)
484
Face velocity (ft/min)
0.68
Air pressure drop (in w.g.)
77.4 / 66.0
Entering air DB / WB (F)
53.7 / 52.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
45.4
Fluid flow rate (gal/min)
3.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.2
Leaving fluid temp. (F)
5.5
Fluid pressure drop (ft w.g.)
Construction
5 / 18
Type / tubes in face
28.7
Finned height (in)
62.0
Finned length (in)
12.4
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
15
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 14 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 35

Untitled P.BAJA AUTOPSIA


Supply Fan Specification
Air handler model
AHD2 FS 080 V M
Fan type
Forward curved (standard/15-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

5,979
2.12
1,014
4.34
54.0

4,000

9.60
8.40
4.80
3.60
2.40

0.75

1.00

1.25

6.00
7.20
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.50
1.75

2.00

2.25

2.50

10.80

Fan Curve

4,800

Tuesday, January 21, 2003

5,600

6,400
7,200
Air flow (ft/min)
Page 15 of 159

8,000

8,800

9,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

21.0 in

26.5 in

51.0 in

Page 16 of 159

This drawing is not to scale; it is to be used for dimensional purposes only.

78.0 in

18.8 in

Leaving air view

37.0 in

51.0 in

78.0 in

3.0 in

43.5 in/1,834 lb

15.8 in

90.5 in

72.0 in

Entering air view

21.0 in

69.0 in/1,190 lb

2.0 in

16.0 in

Side view - AHD2 FS 080 V M

DRAWING UMA # 35

Untitled P.BAJA AUTOPSIA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 34

Untitled P.BAJA CIRCULA Y ESPERA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 180 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.13

B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
11,422

Liners
Pressure drop (in w.g.)

Solid
0.87

Refer to attached pages for coil performance.


D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
Fixed
Air flow (ft/min)
11,820
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
0.99

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 17 of 159

1.99
7.91
659
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 34

Untitled P.BAJA CIRCULA Y ESPERA


Air Handler Coils
Coil Tag
#1

Model #
5 W F 6 C - 30T x 86 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
650.1
Total capacity (MBH)
373.2
Sensible capacity (MBH)
Air Properties
11,820
Air flow (ft/min)
0
Altitude (ft)
414
Face velocity (ft/min)
0.65
Air pressure drop (in w.g.)
80.2 / 68.9
Entering air DB / WB (F)
50.8 / 50.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
120.0
Fluid flow rate (gal/min)
4.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.8
Leaving fluid temp. (F)
11.4
Fluid pressure drop (ft w.g.)
Construction
5 / 30
Type / tubes in face
47.8
Finned height (in)
86.0
Finned length (in)
28.6
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
30
Number of feeds
Air handler
Casing construction
1@2
Supply connections (qty@in)
1@2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 18 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 34

Untitled P.BAJA CIRCULA Y ESPERA


Supply Fan Specification
Air handler model
AHD2 FS 180 V M
Fan type
Forward curved (standard/22-22)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

11,820
1.99
659
7.91
54.0

8,000

8.00
6.00

0.50

0.75

1.00

10.00

12.00
14.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.25
1.50

1.75

16.00

2.00

18.00

2.25

20.00

Fan Curve

10,000

Tuesday, January 21, 2003

12,000

14,000
16,000
Air flow (ft/min)
Page 19 of 159

18,000

20,000

22,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


74.0 in
61.8 in/4,026 lb

Page 20 of 159

104.0 in

27.4 in

Leaving air view

45.4 in

74.0 in

This drawing is not to scale; it is to be used for dimensional purposes only.

32.0 in/1,546 lb

17.8 in

146.5 in

104.0 in

Entering air view

10.0 in/613 lb

27.4 in

Side view - AHD2 FS 180 V M

DRAWING UMA # 34

Untitled P.BAJA CIRCULA Y ESPERA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 33

Untitled P.BAJA LABORATORIO


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 100 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.14

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
6,176

Liners
Pressure drop (in w.g.)

Solid
0.97

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
7,259
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.11

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 21 of 159

2.11
5.27
864
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 33

Untitled P.BAJA LABORATORIO


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 C - 22T x 62 LH Q

Qty Location
1
Section B - Coil A

Footnotes
A,B

#1
Coil
288.0
Total capacity (MBH)
189.9
Sensible capacity (MBH)
Air Properties
7,259
Air flow (ft/min)
0
Altitude (ft)
481
Face velocity (ft/min)
0.67
Air pressure drop (in w.g.)
77.8 / 66.5
Entering air DB / WB (F)
53.5 / 53.4
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
54.3
Fluid flow rate (gal/min)
3.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.6
Leaving fluid temp. (F)
5.5
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
62.0
Finned length (in)
15.1
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
18
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.
B. Fin material - 0.008 Polycoat

Tuesday, January 21, 2003

Page 22 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 33

Untitled P.BAJA LABORATORIO


Supply Fan Specification
Air handler model
AHD2 FS 100 V M
Fan type
Forward curved (standard/18-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

7,259
2.11
864
5.27
54.0

4,500

6.00
4.50
3.00

1.00

1.20

1.40

7.50
9.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.60
1.80

2.00

10.50

2.20

12.00

2.40

13.50

Fan Curve

6,000

Tuesday, January 21, 2003

7,500

9,000
10,500
Air flow (ft/min)
Page 23 of 159

12,000

13,500

15,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

26.5 in

28.0 in

58.0 in

Page 24 of 159

This drawing is not to scale; it is to be used for dimensional purposes only.

78.0 in

22.0 in

Leaving air view

36.0 in

58.0 in

78.0 in

3.0 in

51.0 in/2,420 lb

16.4 in

114.5 in

72.0 in

Entering air view

26.5 in

73.0 in/1,334 lb

2.0 in

19.0 in

Side view - AHD2 FS 100 V M

DRAWING UMA # 33

Untitled P.BAJA LABORATORIO

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 32

Untitled P.BAJA DIAGNOSTICO


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 080 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Throw away

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.11

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
5,146

Liners
Pressure drop (in w.g.)

Solid
0.90

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
5,660
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.01

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 25 of 159

2.01
3.82
982
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 32

Untitled P.BAJA DIAGNOSTICO


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 18T x 62 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
208.4
Total capacity (MBH)
147.6
Sensible capacity (MBH)
Air Properties
5,660
Air flow (ft/min)
0
Altitude (ft)
458
Face velocity (ft/min)
0.63
Air pressure drop (in w.g.)
76.0 / 64.2
Entering air DB / WB (F)
51.9 / 51.4
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
38.1
Fluid flow rate (gal/min)
4.6
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.9
Leaving fluid temp. (F)
16.1
Fluid pressure drop (ft w.g.)
Construction
5 / 18
Type / tubes in face
28.7
Finned height (in)
62.0
Finned length (in)
12.4
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
9
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 26 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 32

Untitled P.BAJA DIAGNOSTICO


Supply Fan Specification
Air handler model
AHD2 FS 080 V M
Fan type
Forward curved (standard/15-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

5,660
2.01
982
3.82
54.0

4,000

9.00
8.00
7.00
4.00
3.00
2.00

0.80

1.00

1.20

5.00
6.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.40
1.60

1.80

2.00

2.20

Fan Curve

4,800

Tuesday, January 21, 2003

5,600

6,400
7,200
Air flow (ft/min)
Page 27 of 159

8,000

8,800

9,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

21.0 in

26.5 in

51.0 in

Page 28 of 159

This drawing is not to scale; it is to be used for dimensional purposes only.

78.0 in

18.8 in

Leaving air view

37.0 in

51.0 in

78.0 in

3.0 in

43.5 in/1,834 lb

15.8 in

90.5 in

72.0 in

Entering air view

21.0 in

69.0 in/1,190 lb

2.0 in

16.0 in

Side view - AHD2 FS 080 V M

DRAWING UMA # 32

Untitled P.BAJA DIAGNOSTICO

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 31

Untitled P.BAJA URGENCIA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 240 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.11

B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
14,078

Liners
Pressure drop (in w.g.)

Solid
0.73

Refer to attached pages for coil performance.


D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
15.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
14,849
External static @ Actual (in w.g.)
1.10
Internal static @ Actual (in w.g.)
0.84

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 29 of 159

1.94
8.79
553
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 31

Untitled P.BAJA URGENCIA


Air Handler Coils
Coil Tag
#1

Model #
5 W F 6 C - 34T x 106 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
757.9
Total capacity (MBH)
448.4
Sensible capacity (MBH)
Air Properties
14,849
Air flow (ft/min)
0
Altitude (ft)
372
Face velocity (ft/min)
0.55
Air pressure drop (in w.g.)
78.6 / 67.5
Entering air DB / WB (F)
50.5 / 50.5
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
126.3
Fluid flow rate (gal/min)
4.0
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
56.0
Leaving fluid temp. (F)
11.6
Fluid pressure drop (ft w.g.)
Construction
5 / 34
Type / tubes in face
54.2
Finned height (in)
106.0
Finned length (in)
39.9
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
34
Number of feeds
Air handler
Casing construction
1@2
Supply connections (qty@in)
1@2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 30 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 31

Untitled P.BAJA URGENCIA


Supply Fan Specification
Air handler model
AHD2 FS 240 V M
Fan type
Forward curved (standard/25-25)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

14,849
1.94
553
8.79
54.0

12,500

7.50

0.80

1.00

10.00

1.20

12.50

15.00
17.50
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.40
1.60

1.80

20.00

2.00

22.50

2.20

25.00

Fan Curve

15,000

Tuesday, January 21, 2003

17,500

20,000
22,500
Air flow (ft/min)
Page 31 of 159

25,000

27,500

30,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

38.0 in

40.0 in

82.5 in

Page 32 of 159
45.4 in

122.0 in

31.3 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

122.0 in

70.0 in/4,845 lb

82.5 in

3.0 in

34.0 in/1,973 lb

18.4 in

162.5 in

116.0 in

Entering air view

38.0 in

49.0 in/1,103 lb

2.0 in

31.3 in

Side view - AHD2 FS 240 V M

DRAWING UMA # 31

Untitled P.BAJA URGENCIA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 30

Untitled P.BAJA QQUIROFANO 1-4


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 064 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.17

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.68

Refer to attached pages for coil performance.


D. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
Fixed
Air flow (ft/min)
5,900
External static @ Actual (in w.g.)
2.50

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

1.03
3.53
6.88
1,288
0
54.0
One
Left
Solid

E. Shipping split

Tuesday, January 21, 2003

Page 33 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 30

Untitled P.BAJA QQUIROFANO 1-4


F. Section 27 Diffuser section
Liners

Solid

Pressure drop (in w.g.)

0.19

G. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 34 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 30

Untitled P.BAJA QQUIROFANO 1-4


Air Handler Coils
Coil Tag
#1

Model #
5 W P 8 A - 21T x 60 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
239.2
Total capacity (MBH)
158.6
Sensible capacity (MBH)
Air Properties
5,900
Air flow (ft/min)
0
Altitude (ft)
423
Face velocity (ft/min)
0.68
Air pressure drop (in w.g.)
74.8 / 64.0
Entering air DB / WB (F)
50.0 / 50.0
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
47.6
Fluid flow rate (gal/min)
3.7
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.1
Leaving fluid temp. (F)
12.8
Fluid pressure drop (ft w.g.)
Construction
5 / 21
Type / tubes in face
33.5
Finned height (in)
60.0
Finned length (in)
13.9
Face area (ft)
8/8
Rows / fin spacing (fins/in)
14
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 35 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 30

Untitled P.BAJA QQUIROFANO 1-4


Supply Fan Specification
Air handler model
AHD2 FS 064 H M
Fan type
Forward curved (standard/15-11)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

5,900
3.53
1,288
6.87
54.0

4,000

8.00
6.00
4.00

1.20

1.60

2.00

10.00
12.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


2.40
2.80

3.20

14.00

3.60

16.00

4.00

18.00

Fan Curve

5,000

Tuesday, January 21, 2003

6,000

7,000
8,000
Air flow (ft/min)
Page 36 of 159

9,000

10,000

11,000

Version 3.70 - Released 5/13/2002 - VA01

21.0 in
20.5 in
45.0 in

Tuesday, January 21, 2003

3.0 in

2.0 in

Page 37 of 159

Leaving air view

52.0 in/563 lb

76.0 in
76.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

70.0 in
3.0 in

134.5 in/2,357 lb

Entering air view

21.0 in

Side view - AHD2 FS 064 H M

DRAWING UMA # 30

Untitled P.BAJA QQUIROFANO 1-4

45.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 29

Untitled P.BAJA RECOBRO


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.13

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.81

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
10,170
External static @ Actual (in w.g.)
2.00
Internal static @ Actual (in w.g.)
0.94

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 38 of 159

2.94
9.08
785
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 29

Untitled P.BAJA RECOBRO


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
396.9
Total capacity (MBH)
267.9
Sensible capacity (MBH)
Air Properties
10,170
Air flow (ft/min)
0
Altitude (ft)
432
Face velocity (ft/min)
0.57
Air pressure drop (in w.g.)
77.1 / 65.6
Entering air DB / WB (F)
52.7 / 52.6
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
72.0
Fluid flow rate (gal/min)
3.4
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.0
Leaving fluid temp. (F)
6.7
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
23
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 39 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 29

Untitled P.BAJA RECOBRO


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

10,170
2.94
785
9.08
54.0

9,000

7.50

0.90

1.20

10.00

1.50

12.50

15.00
17.50
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.80
2.10

2.40

20.00

2.70

22.50

3.00

25.00

Fan Curve

10,500

Tuesday, January 21, 2003

12,000

13,500
15,000
Air flow (ft/min)
Page 40 of 159

16,500

18,000

19,500

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

26.5 in

42.0 in

72.0 in

Page 41 of 159

This drawing is not to scale; it is to be used for dimensional purposes only.

94.0 in

20.4 in

Leaving air view

39.0 in

72.0 in

94.0 in

3.0 in

56.0 in/3,162 lb

16.5 in

142.5 in

88.0 in

Entering air view

26.5 in

77.0 in/1,967 lb

2.0 in

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 29

Untitled P.BAJA RECOBRO

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 28

Untitled P.BAJA QUIROFANO ORTOP.


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.24

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
1.15

Refer to attached pages for coil performance.


D. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
Fixed
Air flow (ft/min)
4,120
External static @ Actual (in w.g.)
2.50

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

1.64
4.14
5.16
1,664
0
54.0
One
Left
Solid

E. Shipping split

Tuesday, January 21, 2003

Page 42 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 28

Untitled P.BAJA QUIROFANO ORTOP.


F. Section 27 Diffuser section
Liners

Solid

Pressure drop (in w.g.)

0.26

G. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 43 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 28

Untitled P.BAJA QUIROFANO ORTOP.


Air Handler Coils
Coil Tag
#1

Model #
5 W H 8 C - 17T x 44 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
173.4
Total capacity (MBH)
114.3
Sensible capacity (MBH)
Air Properties
4,120
Air flow (ft/min)
0
Altitude (ft)
498
Face velocity (ft/min)
1.15
Air pressure drop (in w.g.)
74.5 / 63.8
Entering air DB / WB (F)
48.9 / 48.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
32.6
Fluid flow rate (gal/min)
4.4
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.6
Leaving fluid temp. (F)
19.0
Fluid pressure drop (ft w.g.)
Construction
5 / 17
Type / tubes in face
27.1
Finned height (in)
44.0
Finned length (in)
8.3
Face area (ft)
8 / 12
Rows / fin spacing (fins/in)
8
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 44 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 28

Untitled P.BAJA QUIROFANO ORTOP.


Supply Fan Specification
Air handler model
AHD2 FS 040 H M
Fan type
Forward curved (standard/12-12)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

4,120
4.14
1,664
5.16
54.0

3,200

7.50
6.00
4.50

2.40

2.70

3.00

9.00
10.50
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


3.30
3.60

3.90

12.00

4.20

13.50

4.50

15.00

Fan Curve

4,000

Tuesday, January 21, 2003

4,800

5,600
6,400
Air flow (ft/min)
Page 45 of 159

7,200

8,000

8,800

Version 3.70 - Released 5/13/2002 - VA01

15.0 in
23.5 in
42.0 in

Tuesday, January 21, 2003

3.0 in

1.0 in

Page 46 of 159

Leaving air view

52.0 in/479 lb

60.0 in
60.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

54.0 in
3.0 in

124.5 in/1,960 lb

Entering air view

15.0 in

Side view - AHD2 FS 040 H M

DRAWING UMA # 28

Untitled P.BAJA QUIROFANO ORTOP.

42.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 27

Untitled P.BAJA QUIROF. 5


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 048 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.18

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.86

Refer to attached pages for coil performance.


D. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
4,550
External static @ Actual (in w.g.)
2.50

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

1.25
3.75
5.46
1,595
0
54.0
One
Left
Solid

E. Shipping split

Tuesday, January 21, 2003

Page 47 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 27

Untitled P.BAJA QUIROF. 5


F. Section 27 Diffuser section
Liners

Solid

Pressure drop (in w.g.)

0.21

G. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 48 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 27

Untitled P.BAJA QUIROF. 5


Air Handler Coils
Coil Tag
#1

Model #
5 W P 8 B - 17T x 54 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
203.2
Total capacity (MBH)
128.9
Sensible capacity (MBH)
Air Properties
4,550
Air flow (ft/min)
0
Altitude (ft)
448
Face velocity (ft/min)
0.86
Air pressure drop (in w.g.)
75.5 / 64.9
Entering air DB / WB (F)
49.3 / 49.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
39.6
Fluid flow rate (gal/min)
3.9
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.3
Leaving fluid temp. (F)
13.2
Fluid pressure drop (ft w.g.)
Construction
5 / 17
Type / tubes in face
27.1
Finned height (in)
54.0
Finned length (in)
10.2
Face area (ft)
8 / 10
Rows / fin spacing (fins/in)
11
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 49 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 27

Untitled P.BAJA QUIROF. 5


Supply Fan Specification
Air handler model
AHD2 FS 048 H M
Fan type
Forward curved (standard/12-12)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

4,550
3.75
1,595
5.46
54.0

3,200

8.00
6.00
4.00

1.20

1.60

2.00

10.00
12.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


2.40
2.80

3.20

14.00

3.60

16.00

4.00

18.00

Fan Curve

4,000

Tuesday, January 21, 2003

4,800

5,600
6,400
Air flow (ft/min)
Page 50 of 159

7,200

8,000

8,800

Version 3.70 - Released 5/13/2002 - VA01

15.0 in
25.5 in
44.0 in

Tuesday, January 21, 2003

3.0 in

1.0 in

Page 51 of 159

Leaving air view

52.0 in/534 lb

70.0 in
70.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

64.0 in
3.0 in

124.5 in/2,074 lb

Entering air view

15.0 in

Side view - AHD2 FS 048 H M

DRAWING UMA # 27

Untitled P.BAJA QUIROF. 5

44.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 26

Untitled P.BAJA ESTERILIZACION


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.14

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,191

Liners
Pressure drop (in w.g.)

Solid
0.84

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
3.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
3,000
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
0.98

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 52 of 159

1.98
1.83
1,153
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 26

Untitled P.BAJA ESTERILIZACION


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 14T x 44 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
128.7
Total capacity (MBH)
82.5
Sensible capacity (MBH)
Air Properties
3,000
Air flow (ft/min)
0
Altitude (ft)
440
Face velocity (ft/min)
0.59
Air pressure drop (in w.g.)
77.7 / 66.4
Entering air DB / WB (F)
52.2 / 52.1
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
25.7
Fluid flow rate (gal/min)
4.0
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.0
Leaving fluid temp. (F)
10.0
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
44.0
Finned length (in)
6.8
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
7
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 53 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 26

Untitled P.BAJA ESTERILIZACION


Supply Fan Specification
Air handler model
AHD2 FS 040 V M
Fan type
Forward curved (standard/12-12)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

3,000
1.98
1,153
1.83
54.0

2,500

5.00
4.50
4.00
2.50
2.00
1.50

1.05

1.20

1.35

3.00
3.50
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.50
1.65

1.80

1.95

2.10

Fan Curve

3,000

Tuesday, January 21, 2003

3,500

4,000
4,500
Air flow (ft/min)
Page 54 of 159

5,000

5,500

6,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 55 of 159
25.6 in

60.0 in

15.8 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

60.0 in

3.0 in

37.5 in/1,084 lb

12.4 in

78.0 in

54.0 in

Entering air view

15.0 in

65.0 in/740 lb

1.0 in

13.6 in

Side view - AHD2 FS 040 V M

DRAWING UMA # 26

Untitled P.BAJA ESTERILIZACION

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 25

Untitled P.BAJA LABOR EXPULSION


CS Air Handler
Model #
Quantity
Environment

AHD2 AF 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.13

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Shipping split
D. Section 18 Internal face & bypass short coil section
Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
0.96

Refer to attached pages for coil performance.


E. Shipping split

Tuesday, January 21, 2003

Page 56 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 25

Untitled P.BAJA LABOR EXPULSION


F. Section 3 Vertical draw-thru fan section
Fan type
Airfoil (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
8,590
External static @ Actual (in w.g.)
2.50
Internal static @ Actual (in w.g.)
1.09

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 57 of 159

3.59
7.54
1,894
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 25

Untitled P.BAJA LABOR EXPULSION


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section D - Coil A

Footnotes
A

#1
Coil
331.2
Total capacity (MBH)
225.0
Sensible capacity (MBH)
Air Properties
8,590
Air flow (ft/min)
0
Altitude (ft)
464
Face velocity (ft/min)
0.68
Air pressure drop (in w.g.)
76.7 / 65.2
Entering air DB / WB (F)
52.4 / 52.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
58.4
Fluid flow rate (gal/min)
3.9
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.4
Leaving fluid temp. (F)
11.6
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 58 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 25

Untitled P.BAJA LABOR EXPULSION


Supply Fan Specification
Air handler model
Fan type
Style
Inlet vanes
Altitude (ft)

AHD2 AF 120 V M
Airfoil (standard/201)
Draw-thru
No
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

8,590
3.59
1,894
7.54
54.0

6,400

7.80
7.65
7.50
7.05
6.90
6.75

1.50

2.00

2.50

7.20
7.35
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


3.00
3.50

4.00

4.50

5.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,000

8,800
9,600
Air flow (ft/min)
Page 59 of 159

10,400

11,200

12,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

26.5 in

28.0 in

58.0 in

Page 60 of 159

94.0 in

27.0 in

This drawing is not to scale; it is to be used for dimensional purposes only.

94.0 in

42.0 in

Leaving air view

51.0 in/3,079 lb

22.9 in

58.0 in

3.0 in

32.0 in/951 lb

22.3 in

114.5 in

88.0 in

Entering air view

26.5 in

73.0 in/1,048 lb

2.0 in

Side view - AHD2 AF 120 V M

DRAWING UMA # 25

Untitled P.BAJA LABOR EXPULSION

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 24

Untitled P.BAJA SEMI. INTENS.


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.14

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.17

D. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.45

Refer to attached pages for coil performance.


E. Shipping split

Tuesday, January 21, 2003

Page 61 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 24

Untitled P.BAJA SEMI. INTENS.


F. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (alternate)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
3,050
External static @ Actual (in w.g.)
2.50

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

0.91
3.41
3.93
2,170
0
54.0
One
Left
Solid

G. Section 27 Diffuser section


Liners

Solid

Pressure drop (in w.g.)

0.14

H. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 62 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 24

Untitled P.BAJA SEMI. INTENS.


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 17T x 44 LH

Qty Location
1
Section D - Coil A

Footnotes
A

#1
Coil
113.6
Total capacity (MBH)
79.8
Sensible capacity (MBH)
Air Properties
3,050
Air flow (ft/min)
0
Altitude (ft)
368
Face velocity (ft/min)
0.45
Air pressure drop (in w.g.)
76.7 / 64.8
Entering air DB / WB (F)
52.5 / 52.2
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
20.2
Fluid flow rate (gal/min)
2.7
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.3
Leaving fluid temp. (F)
5.2
Fluid pressure drop (ft w.g.)
Construction
5 / 17
Type / tubes in face
27.1
Finned height (in)
44.0
Finned length (in)
8.3
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
8
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 63 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 24

Untitled P.BAJA SEMI. INTENS.


Supply Fan Specification
Air handler model
AHD2 FS 040 H M
Fan type
Forward curved (alternate/9-9)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

3,050
3.41
2,170
3.93
54.0

2,000

9.00
8.00
7.00
4.00
3.00
2.00

0.50

1.00

1.50

5.00
6.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


2.00
2.50

3.00

3.50

4.00

Fan Curve

2,500

Tuesday, January 21, 2003

3,000

3,500
4,000
Air flow (ft/min)
Page 64 of 159

4,500

5,000

5,500

Version 3.70 - Released 5/13/2002 - VA01

3.0 in

1.0 in

Tuesday, January 21, 2003


107.0 in/1,135 lb

Page 65 of 159
3.0 in

60.0 in

Leaving air view

89.5 in/1,194 lb

This drawing is not to scale; it is to be used for dimensional purposes only.

60.0 in

54.0 in

Entering air view

15.0 in

Side view - AHD2 FS 040 H M

DRAWING UMA # 24

Untitled P.BAJA SEMI. INTENS.

42.0 in

23.5 in

15.0 in

42.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 23

Untitled P.BAJA QUEMADOS


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 022 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.14

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.20

D. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.51

Refer to attached pages for coil performance.


E. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (alternate)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
3.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
1,830
External static @ Actual (in w.g.)
2.50
Tuesday, January 21, 2003

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

Page 66 of 159

1.02
3.52
2.32
2,110
0
54.0
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 23

Untitled P.BAJA QUEMADOS


F. Shipping split
G. Section 27 Diffuser section
Liners

Solid

Pressure drop (in w.g.)

0.16

H. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 67 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 23

Untitled P.BAJA QUEMADOS


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 13T x 32 LH

Qty Location
1
Section D - Coil A

Footnotes
A

#1
Coil
59.4
Total capacity (MBH)
45.7
Sensible capacity (MBH)
Air Properties
1,830
Air flow (ft/min)
0
Altitude (ft)
397
Face velocity (ft/min)
0.51
Air pressure drop (in w.g.)
76.4 / 64.0
Entering air DB / WB (F)
53.3 / 53.0
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
11.1
Fluid flow rate (gal/min)
2.0
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.7
Leaving fluid temp. (F)
2.5
Fluid pressure drop (ft w.g.)
Construction
5 / 13
Type / tubes in face
20.7
Finned height (in)
32.0
Finned length (in)
4.6
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
6
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 68 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 23

Untitled P.BAJA QUEMADOS


Supply Fan Specification
Air handler model
AHD2 FS 022 H M
Fan type
Forward curved (alternate/9-6)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

1,830
3.52
2,110
2.32
54.0

1,500

6.00
5.40
4.80
3.00
2.40
1.80

1.20

1.60

2.00

3.60
4.20
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


2.40
2.80

3.20

3.60

4.00

Fan Curve

1,800

Tuesday, January 21, 2003

2,100

2,400
2,700
Air flow (ft/min)
Page 69 of 159

3,000

3,300

3,600

Version 3.70 - Released 5/13/2002 - VA01

3.0 in

1.0 in

Tuesday, January 21, 2003

Page 70 of 159
3.0 in

128.0 in/1,275 lb

48.0 in

Leaving air view

46.0 in/343 lb

This drawing is not to scale; it is to be used for dimensional purposes only.

48.0 in

42.0 in

Entering air view

15.0 in

Side view - AHD2 FS 022 H M

DRAWING UMA # 23

Untitled P.BAJA QUEMADOS

34.0 in

15.5 in

15.0 in

34.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 22

Untitled P.BAJA INTENS.


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 048 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.21

B. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Left
Solid

C. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.31

D. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.70

Refer to attached pages for coil performance.


E. Shipping split

Tuesday, January 21, 2003

Page 71 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 22

Untitled P.BAJA INTENS.


F. Section 2 Horizontal blow-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
4,991
External static @ Actual (in w.g.)
2.50

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

1.47
3.97
6.54
1,650
0
54.0
One
Left
Solid

G. Section 27 Diffuser section


Liners

Solid

Pressure drop (in w.g.)

0.25

H. Section 13 Cartridge/bag
Filter depth
Filter media
Access panels

Tuesday, January 21, 2003

12" (30.48 cm)


Supplied by other
One

Panel hand
Liners

Page 72 of 159

Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 22

Untitled P.BAJA INTENS.


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 17T x 54 LH

Qty Location
1
Section D - Coil A

Footnotes
A

#1
Coil
195.8
Total capacity (MBH)
130.6
Sensible capacity (MBH)
Air Properties
4,991
Air flow (ft/min)
0
Altitude (ft)
491
Face velocity (ft/min)
0.70
Air pressure drop (in w.g.)
77.3 / 65.9
Entering air DB / WB (F)
53.0 / 52.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
35.9
Fluid flow rate (gal/min)
4.9
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.9
Leaving fluid temp. (F)
16.3
Fluid pressure drop (ft w.g.)
Construction
5 / 17
Type / tubes in face
27.1
Finned height (in)
54.0
Finned length (in)
10.2
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
8
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 73 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 22

Untitled P.BAJA INTENS.


Supply Fan Specification
Air handler model
AHD2 FS 048 H M
Fan type
Forward curved (standard/12-12)
Style
Blow-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

4,991
3.97
1,650
6.54
54.0

3,000

8.00
6.00
4.00

1.60

2.00

2.40

10.00
12.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


2.80
3.20

3.60

14.00

4.00

16.00

4.40

18.00

Fan Curve

4,000

Tuesday, January 21, 2003

5,000

6,000
7,000
Air flow (ft/min)
Page 74 of 159

8,000

9,000

10,000

Version 3.70 - Released 5/13/2002 - VA01

3.0 in

1.0 in

Tuesday, January 21, 2003


107.0 in/1,265 lb

Page 75 of 159
3.0 in

70.0 in

Leaving air view

89.5 in/1,345 lb

This drawing is not to scale; it is to be used for dimensional purposes only.

70.0 in

64.0 in

Entering air view

15.0 in

Side view - AHD2 FS 048 H M

DRAWING UMA # 22

Untitled P.BAJA INTENS.

44.0 in

25.5 in

15.0 in

44.0 in

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 21

Untitled P.BAJA MED.FIS. Y REHAB.


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.16

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,191

Liners
Pressure drop (in w.g.)

Solid
1.05

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
3.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
3,350
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
1.22

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 76 of 159

2.21
2.33
1,223
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 21

Untitled P.BAJA MED.FIS. Y REHAB.


Air Handler Coils
Coil Tag
#1

Model #
5 W H 6 B - 14T x 44 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
134.6
Total capacity (MBH)
89.1
Sensible capacity (MBH)
Air Properties
3,350
Air flow (ft/min)
0
Altitude (ft)
491
Face velocity (ft/min)
0.74
Air pressure drop (in w.g.)
76.8 / 65.5
Entering air DB / WB (F)
52.2 / 51.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
26.6
Fluid flow rate (gal/min)
4.1
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.1
Leaving fluid temp. (F)
12.7
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
44.0
Finned length (in)
6.8
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
7
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 77 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 21

Untitled P.BAJA MED.FIS. Y REHAB.


Supply Fan Specification
Air handler model
AHD2 FS 040 V M
Fan type
Forward curved (standard/12-12)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

3,350
2.21
1,223
2.33
54.0

2,400

6.00
5.40
4.80
3.00
2.40
1.80

1.20

1.35

1.50

3.60
4.20
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.65
1.80

1.95

2.10

2.25

Fan Curve

3,000

Tuesday, January 21, 2003

3,600

4,200
4,800
Air flow (ft/min)
Page 78 of 159

5,400

6,000

6,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 79 of 159
25.6 in

60.0 in

15.8 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

60.0 in

3.0 in

37.5 in/1,084 lb

12.4 in

78.0 in

54.0 in

Entering air view

15.0 in

65.0 in/761 lb

1.0 in

13.6 in

Side view - AHD2 FS 040 V M

DRAWING UMA # 21

Untitled P.BAJA MED.FIS. Y REHAB.

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 20

Untitled P.BAJA ADMIN.


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.16

B. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.19

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.49

Refer to attached pages for coil performance.


D. Shipping split
E. Section 1 Horizontal draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
11,780
External static @ Actual (in w.g.)
1.00

Tuesday, January 21, 2003

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

Page 80 of 159

0.84
1.84
8.60
677
0
54.0
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 20

Untitled P.BAJA ADMIN.


Air Handler Coils
Coil Tag
#1

Model #
5 W Q 5 C - 36T x 76 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
517.7
Total capacity (MBH)
319.5
Sensible capacity (MBH)
Air Properties
11,780
Air flow (ft/min)
0
Altitude (ft)
389
Face velocity (ft/min)
0.49
Air pressure drop (in w.g.)
78.7 / 67.4
Entering air DB / WB (F)
53.5 / 52.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
102.2
Fluid flow rate (gal/min)
2.5
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.1
Leaving fluid temp. (F)
2.6
Fluid pressure drop (ft w.g.)
Construction
5 / 36
Type / tubes in face
57.4
Finned height (in)
76.0
Finned length (in)
30.3
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
45
Number of feeds
Air handler
Casing construction
1@2 1/2
Supply connections (qty@in)
1@2 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 81 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 20

Untitled P.BAJA ADMIN.


Supply Fan Specification
Air handler model
AHD2 FS 150 H M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

11,780
1.84
677
8.61
54.0

7,500

7.50
6.00
4.50

0.50

0.75

1.00

9.00
10.50
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.25
1.50

1.75

12.00

2.00

13.50

2.25

15.00

Fan Curve

9,000

Tuesday, January 21, 2003

10,500

12,000
13,500
Air flow (ft/min)
Page 82 of 159

15,000

16,500

18,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

26.5 in
42.0 in
72.0 in

Page 83 of 159
39.0 in

20.4 in

94.0 in
94.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

3.0 in

12.8 in

Leaving air view

56.0 in/2,130 lb

72.0 in
27.4 in

88.0 in

Entering air view

26.5 in

101.0 in/2,342 lb

2.0 in

Side view - AHD2 FS 150 H M

DRAWING UMA # 20

Untitled P.BAJA ADMIN.

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 19

Untitled P.BAJA FARMACIA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 040 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.13

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
2,191

Liners
Pressure drop (in w.g.)

Solid
0.76

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
2.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
2,824
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
0.88

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 84 of 159

1.88
1.62
1,124
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 19

Untitled P.BAJA FARMACIA


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 C - 14T x 44 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
188.3
Total capacity (MBH)
90.9
Sensible capacity (MBH)
Air Properties
2,824
Air flow (ft/min)
0
Altitude (ft)
414
Face velocity (ft/min)
0.53
Air pressure drop (in w.g.)
83.1 / 73.3
Entering air DB / WB (F)
52.9 / 52.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
36.4
Fluid flow rate (gal/min)
5.6
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.4
Leaving fluid temp. (F)
18.6
Fluid pressure drop (ft w.g.)
Construction
5 / 14
Type / tubes in face
22.3
Finned height (in)
44.0
Finned length (in)
6.8
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
7
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 85 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 19

Untitled P.BAJA FARMACIA


Supply Fan Specification
Air handler model
AHD2 FS 040 V M
Fan type
Forward curved (standard/12-12)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

2,824
1.88
1,124
1.62
54.0

2,500

4.50
4.00
3.50
2.00
1.50
1.00

1.05

1.20

1.35

2.50
3.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.50
1.65

1.80

1.95

2.10

Fan Curve

3,000

Tuesday, January 21, 2003

3,500

4,000
4,500
Air flow (ft/min)
Page 86 of 159

5,000

5,500

6,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

15.0 in

20.0 in

38.5 in

Page 87 of 159
25.6 in

60.0 in

15.8 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

60.0 in

3.0 in

37.5 in/1,057 lb

12.4 in

78.0 in

54.0 in

Entering air view

15.0 in

65.0 in/740 lb

1.0 in

13.6 in

Side view - AHD2 FS 040 V M

DRAWING UMA # 19

Untitled P.BAJA FARMACIA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 18

Untitled P.BAJA CONSULTA


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 240 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s)
Top dampers
Back dampers
Filter media

Top and back


Standard
Standard
2" Pleated 35% eff.

Access panels
Panel hand
Liners
Pressure drop (in w.g.)

One
Left
Solid
0.12

B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
14,078

Liners
Pressure drop (in w.g.)

Solid
0.68

Refer to attached pages for coil performance.


D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
10.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
15,507
External static @ Actual (in w.g.)
1.00
Internal static @ Actual (in w.g.)
0.80

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 88 of 159

1.80
8.80
537
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 18

Untitled P.BAJA CONSULTA


Air Handler Coils
Coil Tag
#1

Model #
5 W Q 5 C - 34T x 106 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
749.2
Total capacity (MBH)
455.1
Sensible capacity (MBH)
Air Properties
15,507
Air flow (ft/min)
0
Altitude (ft)
389
Face velocity (ft/min)
0.49
Air pressure drop (in w.g.)
79.6 / 68.1
Entering air DB / WB (F)
52.3 / 52.2
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
140.6
Fluid flow rate (gal/min)
3.6
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.7
Leaving fluid temp. (F)
6.6
Fluid pressure drop (ft w.g.)
Construction
5 / 34
Type / tubes in face
54.2
Finned height (in)
106.0
Finned length (in)
39.9
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
42
Number of feeds
Air handler
Casing construction
1@2 1/2
Supply connections (qty@in)
1@2 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 89 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 18

Untitled P.BAJA CONSULTA


Supply Fan Specification
Air handler model
AHD2 FS 240 V M
Fan type
Forward curved (standard/25-25)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

15,507
1.80
537
8.80
54.0

12,500

7.50
5.00

0.60

0.80

1.00

10.00

12.50
15.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.40

1.60

17.50

1.80

20.00

2.00

22.50

Fan Curve

15,000

Tuesday, January 21, 2003

17,500

20,000
22,500
Air flow (ft/min)
Page 90 of 159

25,000

27,500

30,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

3.0 in

38.0 in

40.0 in

82.5 in

Page 91 of 159
45.4 in

122.0 in

31.3 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

122.0 in

70.0 in/4,785 lb

82.5 in

3.0 in

34.0 in/1,797 lb

18.4 in

162.5 in

116.0 in

Entering air view

38.0 in

49.0 in/1,103 lb

2.0 in

31.3 in

Side view - AHD2 FS 240 V M

DRAWING UMA # 18

Untitled P.BAJA CONSULTA

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 17

Untitled E.P.3-ESTE
CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.13

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
0.90

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
7,860
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.03

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 92 of 159

1.53
3.80
636
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 17

Untitled E.P.3-ESTE
Air Handler Coils
Coil Tag
#1

Model #
5 W F 6 C - 22T x 76 LH Q

Qty Location
1
Section B - Coil A

Footnotes
A,B

#1
Coil
394.8
Total capacity (MBH)
238.0
Sensible capacity (MBH)
Air Properties
7,860
Air flow (ft/min)
0
Altitude (ft)
425
Face velocity (ft/min)
0.67
Air pressure drop (in w.g.)
79.4 / 67.9
Entering air DB / WB (F)
51.2 / 51.2
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
71.3
Fluid flow rate (gal/min)
3.5
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.1
Leaving fluid temp. (F)
7.2
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
22
Number of feeds
Air handler
Casing construction
1@2
Supply connections (qty@in)
1@2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.
B. Fin material - 0.008 Polycoat

Tuesday, January 21, 2003

Page 93 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 17

Untitled E.P.3-ESTE
Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

7,860
1.53
636
3.80
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.75

0.90

1.05

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.35

1.50

1.65

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 94 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 95 of 159
39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,789 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,458 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 17

Untitled E.P.3-ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 16

Untitled E.P.3-OESTE
CS Air Handler
Model #
Quantity
Environment

AHD2 FS 100 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 13 Cartridge/bag
Filter depth
Filter media
Pre-filter media
Access panels

12" (30.48 cm)


Supplied by other
2" Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.18

B. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.23

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.42

Refer to attached pages for coil performance.


D. Section 1 Horizontal draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
Fixed
Air flow (ft/min)
8,070
External static @ Actual (in w.g.)
1.00

Tuesday, January 21, 2003

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

Page 96 of 159

0.83
1.83
5.65
825
0
54.0
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 16

Untitled E.P.3-OESTE
Air Handler Coils
Coil Tag
#1

Model #
5 W H 4 C - 28T x 62 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
354.2
Total capacity (MBH)
215.0
Sensible capacity (MBH)
Air Properties
8,070
Air flow (ft/min)
0
Altitude (ft)
420
Face velocity (ft/min)
0.42
Air pressure drop (in w.g.)
78.6 / 67.6
Entering air DB / WB (F)
53.8 / 53.4
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
70.8
Fluid flow rate (gal/min)
5.5
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.0
Leaving fluid temp. (F)
17.9
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
62.0
Finned length (in)
19.2
Face area (ft)
4 / 12
Rows / fin spacing (fins/in)
14
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 97 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 16

Untitled E.P.3-OESTE
Supply Fan Specification
Air handler model
AHD2 FS 100 H M
Fan type
Forward curved (standard/18-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

8,070
1.83
825
5.65
54.0

4,800

6.00
4.50
3.00

1.00

1.20

1.40

7.50
9.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.60
1.80

2.00

10.50

2.20

12.00

2.40

13.50

Fan Curve

6,000

Tuesday, January 21, 2003

7,200

8,400
9,600
Air flow (ft/min)
Page 98 of 159

10,800

12,000

13,200

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

8.6 in

Page 99 of 159
36.0 in

22.0 in

Leaving air view

58.0 in
19.0 in

78.0 in
78.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

Entering air view

133.0 in/2,931 lb

Side view - AHD2 FS 100 H M

DRAWING UMA # 16

Untitled E.P.3-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 15

Untitled E.P.2-AUDIT.
CS Air Handler
Model #
Quantity
Environment

AHD2 FS 100 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.18

B. Shipping split
C. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
Fixed
Air flow (ft/min)
8,175
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.78

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners
Pressure drop (in w.g.)

1.28
4.66
719
0
54.0
Large
Standard
One
Left
Solid
0.60

Refer to attached pages for coil performance.

Tuesday, January 21, 2003

Page 100 of 159

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 15

Untitled E.P.2-AUDIT.
Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 28T x 62 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
389.9
Total capacity (MBH)
234.4
Sensible capacity (MBH)
Air Properties
8,175
Air flow (ft/min)
0
Altitude (ft)
425
Face velocity (ft/min)
0.60
Air pressure drop (in w.g.)
78.6 / 67.6
Entering air DB / WB (F)
52.0 / 51.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
76.0
Fluid flow rate (gal/min)
3.9
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.3
Leaving fluid temp. (F)
9.9
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
62.0
Finned length (in)
19.2
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
21
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 101 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 15

Untitled E.P.2-AUDIT.
Supply Fan Specification
Air handler model
AHD2 FS 100 V M
Fan type
Forward curved (standard/18-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

8,175
1.28
719
4.66
54.0

3,600

9.00
8.00
7.00
4.00
3.00
2.00

0.72

0.84

0.96

5.00
6.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.08
1.20

1.32

1.44

1.56

Fan Curve

4,800

Tuesday, January 21, 2003

6,000

7,200
8,400
Air flow (ft/min)
Page 102 of 159

9,600

10,800

12,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003

Page 103 of 159


51.0 in/2,915 lb

16.4 in

114.5 in
58.0 in

58.0 in
36.0 in

78.0 in

22.0 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

78.0 in

Entering air view

10.0 in/441 lb

19.0 in

Side view - AHD2 FS 100 V M

DRAWING UMA # 15

Untitled E.P.2-AUDIT.

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 14

Untitled E.P.2-ESTE
CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.13

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
0.84

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
7,975
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.98

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 104 of 159

1.48
3.79
626
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 14

Untitled E.P.2-ESTE
Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
381.4
Total capacity (MBH)
232.6
Sensible capacity (MBH)
Air Properties
7,975
Air flow (ft/min)
0
Altitude (ft)
431
Face velocity (ft/min)
0.61
Air pressure drop (in w.g.)
79.2 / 67.7
Entering air DB / WB (F)
52.1 / 51.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
70.4
Fluid flow rate (gal/min)
4.8
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.8
Leaving fluid temp. (F)
16.1
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 105 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 14

Untitled E.P.2-ESTE
Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

7,975
1.48
626
3.79
54.0

6,000

9.00
8.00
7.00
4.00
3.00
2.00

0.72

0.84

0.96

5.00
6.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.08
1.20

1.32

1.44

1.56

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 106 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 107 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,789 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,425 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 14

Untitled E.P.2-ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 13

Untitled E.P.2-OESTE
CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.16

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
1.05

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,100
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.22

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 108 of 159

1.72
5.20
681
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 13

Untitled E.P.2-OESTE
Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
333.2
Total capacity (MBH)
232.5
Sensible capacity (MBH)
Air Properties
9,100
Air flow (ft/min)
0
Altitude (ft)
492
Face velocity (ft/min)
0.74
Air pressure drop (in w.g.)
76.3 / 64.7
Entering air DB / WB (F)
52.7 / 52.4
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
59.3
Fluid flow rate (gal/min)
4.0
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.3
Leaving fluid temp. (F)
11.9
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 109 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 13

Untitled E.P.2-OESTE
Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,100
1.72
681
5.20
54.0

6,000

9.60
6.00
4.80
3.60

0.75

0.90

1.05

7.20
8.40
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.35

1.50

1.65

10.80

1.80

12.00

Fan Curve

7,500

Tuesday, January 21, 2003

9,000

10,500
12,000
Air flow (ft/min)
Page 110 of 159

13,500

15,000

16,500

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 111 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,856 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,425 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 13

Untitled E.P.2-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 12

Untitled PISO 6-ESTE(FUTURO)


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.12

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.84

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,560
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.97

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 112 of 159

1.47
5.09
586
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 12

Untitled PISO 6-ESTE(FUTURO)


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
377.2
Total capacity (MBH)
262.1
Sensible capacity (MBH)
Air Properties
9,560
Air flow (ft/min)
0
Altitude (ft)
406
Face velocity (ft/min)
0.63
Air pressure drop (in w.g.)
76.2 / 64.5
Entering air DB / WB (F)
50.8 / 50.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
61.3
Fluid flow rate (gal/min)
3.2
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
56.3
Leaving fluid temp. (F)
7.8
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
21
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 113 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 12

Untitled PISO 6-ESTE(FUTURO)


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,560
1.47
586
5.09
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.40

0.60

0.80

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.00
1.20

1.40

1.60

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 114 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 115 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,141 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,849 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 12

Untitled PISO 6-ESTE(FUTURO)

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 11

Untitled PISO 6-OESTE ( FUTURO )


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.13

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.81

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
10,160
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.95

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 116 of 159

1.45
5.68
594
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 11

Untitled PISO 6-OESTE ( FUTURO )


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
347.8
Total capacity (MBH)
256.2
Sensible capacity (MBH)
Air Properties
10,160
Air flow (ft/min)
0
Altitude (ft)
431
Face velocity (ft/min)
0.58
Air pressure drop (in w.g.)
75.9 / 64.1
Entering air DB / WB (F)
52.6 / 52.5
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
61.4
Fluid flow rate (gal/min)
2.9
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.3
Leaving fluid temp. (F)
5.1
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
23
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 117 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 11

Untitled PISO 6-OESTE ( FUTURO )


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

10,160
1.45
594
5.68
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.40

0.60

0.80

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.00
1.20

1.40

1.60

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 118 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 119 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,141 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,746 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 11

Untitled PISO 6-OESTE ( FUTURO )

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 10

Untitled PISO 5-ESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.17

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
1.08

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,250
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.25

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 120 of 159

1.75
5.41
688
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 10

Untitled PISO 5-ESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
342.1
Total capacity (MBH)
239.1
Sensible capacity (MBH)
Air Properties
9,250
Air flow (ft/min)
0
Altitude (ft)
500
Face velocity (ft/min)
0.76
Air pressure drop (in w.g.)
76.7 / 64.8
Entering air DB / WB (F)
52.8 / 52.5
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
61.7
Fluid flow rate (gal/min)
4.2
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.1
Leaving fluid temp. (F)
12.8
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 121 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 10

Untitled PISO 5-ESTE


Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,250
1.75
688
5.42
54.0

7,200

9.60
6.00
4.80
3.60

0.90

1.05

1.20

7.20
8.40
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.35
1.50

1.65

1.80

10.80

1.95

12.00

Fan Curve

8,400

Tuesday, January 21, 2003

9,600

10,800
12,000
Air flow (ft/min)
Page 122 of 159

13,200

14,400

15,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 123 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,856 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,425 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 10

Untitled PISO 5-ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 9

Untitled PISO 5-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.16

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
1.16

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,130
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.32

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 124 of 159

1.82
5.45
699
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 9

Untitled PISO 5-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 C - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
347.9
Total capacity (MBH)
243.8
Sensible capacity (MBH)
Air Properties
9,130
Air flow (ft/min)
0
Altitude (ft)
493
Face velocity (ft/min)
0.85
Air pressure drop (in w.g.)
76.3 / 64.6
Entering air DB / WB (F)
51.6 / 51.6
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
58.6
Fluid flow rate (gal/min)
4.0
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.9
Leaving fluid temp. (F)
11.6
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 125 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 9

Untitled PISO 5-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,130
1.82
699
5.45
54.0

7,200

6.00
4.50
3.00

0.90

1.05

1.20

7.50
9.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.35
1.50

1.65

10.50

1.80

12.00

1.95

13.50

Fan Curve

8,400

Tuesday, January 21, 2003

9,600

10,800
12,000
Air flow (ft/min)
Page 126 of 159

13,200

14,400

15,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 127 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,856 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,458 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 9

Untitled PISO 5-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 8

Untitled PISO 4-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.15

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.94

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
11,080
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.09

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 128 of 159

1.59
7.07
632
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 8

Untitled PISO 4-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
406.6
Total capacity (MBH)
287.7
Sensible capacity (MBH)
Air Properties
11,080
Air flow (ft/min)
0
Altitude (ft)
470
Face velocity (ft/min)
0.65
Air pressure drop (in w.g.)
76.9 / 65.0
Entering air DB / WB (F)
52.8 / 52.7
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
75.2
Fluid flow rate (gal/min)
3.5
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.8
Leaving fluid temp. (F)
7.3
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
5 / 12
Rows / fin spacing (fins/in)
23
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 129 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 8

Untitled PISO 4-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

11,080
1.59
632
7.07
54.0

7,200

9.60
6.00
4.80
3.60

0.60

0.80

1.00

7.20
8.40
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.40

1.60

1.80

10.80

2.00

12.00

Fan Curve

8,400

Tuesday, January 21, 2003

9,600

10,800
12,000
Air flow (ft/min)
Page 130 of 159

13,200

14,400

15,600

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 131 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,141 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,746 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 8

Untitled PISO 4-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 7

Untitled PISO 4-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 080 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 13 Cartridge/bag
Filter depth
Filter media
Pre-filter media
Access panels

12" (30.48 cm)


Supplied by other
2" Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.24

B. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.30

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.96

Refer to attached pages for coil performance.


D. Section 1 Horizontal draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
7,680
External static @ Actual (in w.g.)
1.00

Tuesday, January 21, 2003

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

Page 132 of 159

1.50
2.50
7.47
1,134
0
54.0
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 7

Untitled PISO 4-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W F 8 B - 23T x 62 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
616.7
Total capacity (MBH)
281.6
Sensible capacity (MBH)
Air Properties
7,680
Air flow (ft/min)
0
Altitude (ft)
487
Face velocity (ft/min)
0.96
Air pressure drop (in w.g.)
85.8 / 75.7
Entering air DB / WB (F)
51.3 / 51.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
112.9
Fluid flow rate (gal/min)
5.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.9
Leaving fluid temp. (F)
17.0
Fluid pressure drop (ft w.g.)
Construction
5 / 23
Type / tubes in face
36.7
Finned height (in)
62.0
Finned length (in)
15.8
Face area (ft)
8 / 10
Rows / fin spacing (fins/in)
23
Number of feeds
Air handler
Casing construction
1@2
Supply connections (qty@in)
1@2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 133 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 7

Untitled PISO 4-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 080 H M
Fan type
Forward curved (standard/15-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

7,680
2.50
1,134
7.47
54.0

4,000

6.00
4.50
3.00

0.90

1.20

1.50

7.50
9.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.80
2.10

2.40

10.50

2.70

12.00

3.00

13.50

Fan Curve

5,000

Tuesday, January 21, 2003

6,000

7,000
8,000
Air flow (ft/min)
Page 134 of 159

9,000

10,000

11,000

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


51.0 in

5.2 in

Page 135 of 159


37.0 in

18.8 in

Leaving air view

51.0 in
16.0 in

78.0 in
78.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

Entering air view

123.5 in/2,705 lb

Side view - AHD2 FS 080 H M

DRAWING UMA # 7

Untitled PISO 4-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 6

Untitled PISO 3-ESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.12

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.87

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,730
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.99

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 136 of 159

1.49
5.31
592
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 6

Untitled PISO 3-ESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W F 6 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
463.5
Total capacity (MBH)
288.3
Sensible capacity (MBH)
Air Properties
9,730
Air flow (ft/min)
0
Altitude (ft)
413
Face velocity (ft/min)
0.65
Air pressure drop (in w.g.)
78.8 / 67.2
Entering air DB / WB (F)
51.3 / 51.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
82.9
Fluid flow rate (gal/min)
3.2
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.2
Leaving fluid temp. (F)
6.1
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
28
Number of feeds
Air handler
Casing construction
1@2
Supply connections (qty@in)
1@2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 137 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 6

Untitled PISO 3-ESTE


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,730
1.49
592
5.31
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.40

0.60

0.80

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.00
1.20

1.40

1.60

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 138 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 139 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,141 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,849 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 6

Untitled PISO 3-ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 5

Untitled PISO 3-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.15

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
0.97

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
8,680
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.12

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 140 of 159

1.62
4.64
660
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 5

Untitled PISO 3-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
336.1
Total capacity (MBH)
228.2
Sensible capacity (MBH)
Air Properties
8,680
Air flow (ft/min)
0
Altitude (ft)
469
Face velocity (ft/min)
0.69
Air pressure drop (in w.g.)
76.8 / 65.2
Entering air DB / WB (F)
52.5 / 52.3
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
60.2
Fluid flow rate (gal/min)
4.1
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.2
Leaving fluid temp. (F)
12.2
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 141 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 5

Untitled PISO 3-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

8,680
1.62
660
4.64
54.0

6,000

9.60
8.40
4.80
3.60
2.40

0.75

0.90

1.05

6.00
7.20
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.35

1.50

1.65

1.80

10.80

Fan Curve

7,500

Tuesday, January 21, 2003

9,000

10,500
12,000
Air flow (ft/min)
Page 142 of 159

13,500

15,000

16,500

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 143 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,789 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,425 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 5

Untitled PISO 3-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 4

Untitled PISO 2-ESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 100 H M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.22

B. Section 20 External face & bypass section


Liners

Solid

Pressure drop (in w.g.)

0.28

C. Section 7 Short cooling coil section


Coil size
Drain pan

Large
Standard

Liners
Pressure drop (in w.g.)

Solid
0.59

Refer to attached pages for coil performance.


D. Section 1 Horizontal draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
7.50
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,155
External static @ Actual (in w.g.)
0.50

Tuesday, January 21, 2003

Internal static @ Actual (in w.g.)


Total static @ Actual (in w.g.)
Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Access panels
Panel hand
Liners

Page 144 of 159

1.09
1.59
6.42
812
0
70.0
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 4

Untitled PISO 2-ESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W H 5 B - 28T x 62 LH

Qty Location
1
Section C - Coil A

Footnotes
A

#1
Coil
325.2
Total capacity (MBH)
232.1
Sensible capacity (MBH)
Air Properties
9,155
Air flow (ft/min)
0
Altitude (ft)
476
Face velocity (ft/min)
0.59
Air pressure drop (in w.g.)
76.8 / 64.8
Entering air DB / WB (F)
53.3 / 52.8
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
61.3
Fluid flow rate (gal/min)
4.7
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.6
Leaving fluid temp. (F)
17.1
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
62.0
Finned length (in)
19.2
Face area (ft)
5 / 10
Rows / fin spacing (fins/in)
14
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 145 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 4

Untitled PISO 2-ESTE


Supply Fan Specification
Air handler model
AHD2 FS 100 H M
Fan type
Forward curved (standard/18-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,155
1.59
812
6.42
70.0

4,800

9.60
8.40
4.80
3.60
2.40

0.90

1.05

1.20

6.00
7.20
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.35
1.50

1.65

1.80

1.95

10.80

Fan Curve

6,000

Tuesday, January 21, 2003

7,200

8,400
9,600
Air flow (ft/min)
Page 146 of 159

10,800

12,000

13,200

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

8.6 in

Page 147 of 159


36.0 in

22.0 in

Leaving air view

58.0 in
19.0 in

78.0 in
78.0 in
This drawing is not to scale; it is to be used for dimensional purposes only.

Entering air view

113.0 in/2,993 lb

Side view - AHD2 FS 100 H M

DRAWING UMA # 4

Untitled PISO 2-ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 3

Untitled PISO 2-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 120 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.14

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
7,570

Liners
Pressure drop (in w.g.)

Solid
0.93

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
8,430
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
1.07

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 148 of 159

1.57
4.32
648
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 3

Untitled PISO 2-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 B - 22T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
360.1
Total capacity (MBH)
231.3
Sensible capacity (MBH)
Air Properties
8,430
Air flow (ft/min)
0
Altitude (ft)
456
Face velocity (ft/min)
0.66
Air pressure drop (in w.g.)
77.7 / 66.4
Entering air DB / WB (F)
52.2 / 52.1
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
65.0
Fluid flow rate (gal/min)
4.4
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
55.1
Leaving fluid temp. (F)
14.0
Fluid pressure drop (ft w.g.)
Construction
5 / 22
Type / tubes in face
35.1
Finned height (in)
76.0
Finned length (in)
18.5
Face area (ft)
6 / 10
Rows / fin spacing (fins/in)
16
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 149 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 3

Untitled PISO 2-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 120 V M
Fan type
Forward curved (standard/20-18)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

8,430
1.57
648
4.32
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.75

0.90

1.05

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.20
1.35

1.50

1.65

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 150 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


58.0 in

58.0 in

Page 151 of 159


39.6 in

94.0 in

22.9 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

51.0 in/2,789 lb

17.5 in

114.5 in

94.0 in

Entering air view

42.0 in/1,425 lb

24.9 in

Side view - AHD2 FS 120 V M

DRAWING UMA # 3

Untitled PISO 2-OESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 2

Untitled PISO 1- ESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.12

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.82

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,420
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.94

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 152 of 159

1.44
4.91
580
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 2

Untitled PISO 1- ESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 6 C - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
390.3
Total capacity (MBH)
263.9
Sensible capacity (MBH)
Air Properties
9,420
Air flow (ft/min)
0
Altitude (ft)
400
Face velocity (ft/min)
0.62
Air pressure drop (in w.g.)
76.9 / 65.0
Entering air DB / WB (F)
50.9 / 50.9
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
64.2
Fluid flow rate (gal/min)
3.3
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
56.2
Leaving fluid temp. (F)
8.5
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
6 / 12
Rows / fin spacing (fins/in)
21
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 153 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 2

Untitled PISO 1- ESTE


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,420
1.44
580
4.91
54.0

6,000

9.00
8.00
5.00
4.00
3.00

0.40

0.60

0.80

6.00
7.00
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


1.00
1.20

1.40

1.60

1.80

10.00

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 154 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 155 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,074 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,849 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 2

Untitled PISO 1- ESTE

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 1

Untitled PISO 1-OESTE


CS Air Handler
Model #
Quantity
Environment

AHD2 FS 150 V M
1
Indoor

Insulation (entire unit)


Wall thickness
Sealed panels

2.00#
2" (5.08 cm)
Positive pressure only

Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is
based on ARI Standard-430.
- See individual coil ratings for ARI certification information.
- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth
Filter media
Access panels

2" (5.08 cm)


Pleated 35% eff.
One

Panel hand
Liners
Pressure drop (in w.g.)

Left
Solid
0.12

B. Section 18 Internal face & bypass short coil section


Coil size
Drain pan
Maximum bypass air flow (ft/min)

Small
Standard
10,094

Liners
Pressure drop (in w.g.)

Solid
0.66

Refer to attached pages for coil performance.


C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type
Forward curved (standard)
Internal isolation
Spring (standard)
Arrangement
#3
Motor type
High Eff. TEFC
Motor voltage
460V/3/60
Motor power (HP)
5.00
Motor hand
Left
Drive
150% HP Adjustable
Air flow (ft/min)
9,430
External static @ Actual (in w.g.)
0.50
Internal static @ Actual (in w.g.)
0.78

Tuesday, January 21, 2003

Total static @ Actual (in w.g.)


Brake power @ Actual (HP)
Rotations per minute
Altitude (ft)
Coldest dry bulb temp (F)
Coil size
Drain pan
Access panels
Panel hand
Liners

Page 156 of 159

1.28
4.60
557
0
54.0
Large
Standard
One
Left
Solid

Version 3.70 - Released 5/13/2002 - VA01

PERFORMANCE SUMMARY UMA # 1

Untitled PISO 1-OESTE


Air Handler Coils
Coil Tag
#1

Model #
5 W P 5 B - 28T x 76 LH

Qty Location
1
Section B - Coil A

Footnotes
A

#1
Coil
319.8
Total capacity (MBH)
233.4
Sensible capacity (MBH)
Air Properties
9,430
Air flow (ft/min)
0
Altitude (ft)
400
Face velocity (ft/min)
0.45
Air pressure drop (in w.g.)
76.1 / 64.3
Entering air DB / WB (F)
53.2 / 52.7
Leaving air DB / WB (F)
Actual
Air properties measured at
Fluid Properties
Water
Fluid
60.0
Fluid flow rate (gal/min)
2.8
Fluid velocity (ft/s)
44.0
Entering fluid temp. (F)
54.7
Leaving fluid temp. (F)
4.9
Fluid pressure drop (ft w.g.)
Construction
5 / 28
Type / tubes in face
44.6
Finned height (in)
76.0
Finned length (in)
23.6
Face area (ft)
5 / 10
Rows / fin spacing (fins/in)
23
Number of feeds
Air handler
Casing construction
1@1 1/2
Supply connections (qty@in)
1@1 1/2
Return connections (qty@in)
MPT
Connection type
A. Certified in accordance with the ARI
Forced-Circulation Air-Cooling and Air-Heating
Coils Certification Program, which is based on
ARI Standard-410.

Tuesday, January 21, 2003

Page 157 of 159

Version 3.70 - Released 5/13/2002 - VA01

FAN CURVE UMA # 1

Untitled PISO 1-OESTE


Supply Fan Specification
Air handler model
AHD2 FS 150 V M
Fan type
Forward curved (standard/22-15)
Style
Draw-thru
Inlet vanes
No
Altitude (ft)
0

Air flow (ft/min)


Static pressure @ Altitude (in w.g.)
Rotations per minute
Brake power @ Altitude (HP)
Coldest dry bulb (F)

9,430
1.28
557
4.60
54.0

6,000

8.00
7.20
6.40
4.00
3.20
2.40

0.45

0.60

0.75

4.80
5.60
Brake power @ Altitude (HP)

Static pressure @ Altitude (in w.g.)


0.90
1.05

1.20

1.35

1.50

Fan Curve

7,200

Tuesday, January 21, 2003

8,400

9,600
10,800
Air flow (ft/min)
Page 158 of 159

12,000

13,200

14,400

Version 3.70 - Released 5/13/2002 - VA01

Tuesday, January 21, 2003


72.0 in

72.0 in

Page 159 of 159


39.0 in

94.0 in

20.4 in

Leaving air view

This drawing is not to scale; it is to be used for dimensional purposes only.

56.0 in/3,074 lb

16.5 in

142.5 in

94.0 in

Entering air view

42.0 in/1,713 lb

27.4 in

Side view - AHD2 FS 150 V M

DRAWING UMA # 1

Untitled PISO 1-OESTE

Version 3.70 - Released 5/13/2002 - VA01

Vous aimerez peut-être aussi