Vous êtes sur la page 1sur 38

www.eeecube.blogspot.

com

LABT MANUAL

EE 2305 ELECTRICAL MACHINES LAB II

www.eeecube.blogspot.com

EX.NO.1. LOAD TEST ON 3-PHASE CAGE INDUCTION MOTOR


AIM :
To determine the performance characteristics of 3-phase squirrel cage induction
motor by direct loading.
APPARATUS REQUIRED:
SI NO APPARATUS REQUIRED

TYPE

RANGE QUANTITY

NAME PLATE DETAILS :


FUSE RATING CALCULATION :
125% of rated current.
No-load test - 25% of rated current.
THEORY :
The load test on 3-phase induction motor is performed to obtain its various characteristics
including efficiency. A belt and brake drum arrangement as shown in the circuit diagram
can load the motor. If S1 and S2 are the tensions provided at the two sides of the belt, then
the load torque is given by
T = (S1 - S2) * 9.81 * R

N-m.

Where R is the radius of the brake drum in metre. The mechanical output of the motor is
given by
Pm = 2 * 3.14 * N * T Watt
60

www.eeecube.blogspot.com

Where N is the speed of the motor in, RPM. The power input to the motor
Pi = VLIL watt
The efficiency of the motor is given by
Efficiency = Pm / Pi
FORMULA :
Torque,
T = (S1 S2) * 9.81 * r (Nm)
Input power
(Pi) = (W1 + W2) (Watt)
Output power
(Po) = 2 NT / 60 (Watt)
Efficiency
= Po X 100
Pi
Cos = W/(31/2 VLIL)
Slip = (Ns N) / Ns *100
PRECAUTION:
1.
2.
3.
4.

TPST switch should be at open position.


3-phase autotransformer should be at minimum voltage position.
There should be no-load at the time of starting(Loosen the belt on the brake drum)
Brake drum should be filled with water.

PROCEDURE:
1.
2.
3.
4.
5.
6.
7.

The connections are made as per the circuit diagram.


Power supply is obtained from the
control panel.
The TPST switch is closed.
Rated voltage of 3-phase induction motor, is applied by adjusting autotransformer
The initial readings of ammeter, voltmeter and wattmeter are noted.
By increasing the load step by step, the reading of ammeter, voltmeter and wattmeter
Step1 to 6 is repeated till the ammeter shows the rated current of 3-phase induction
motor.
8. Decrease the load, bring auto-transformer to its minimum voltage position.
9. Switch off the supply.

www.eeecube.blogspot.com

CIRCUIT DIAGRAM
LOAD TEST ON THREE PHASE SQUIRREL CAGE INDUCTION MOTOR:

Fuse

T
P
S
T

ROT

--

( 0 600)V,MI

OR

415V,50Hz,
3
SUPPLY
M
C

STATOR

L
V

BRAKE
DRUM

www.eeecube.blogspot.com

OBSERVATION TABLE :

S.N
O

V (volt)

I (A)

Speed
(rpm)

Spring Balance

Torque
=((S1 S2) *
9.81 * R)
N-m

S1(Kg)

I/P

O/P
2
(V*IL) NT
watt

60
(watt)

S2(Kg)

RESULT :

VIVA QUESTIONS :
induction motor?
1.Explain what is meant by a 3-phase
2.Write the classification of 3-phase induction motor?
3.State the steps to draw the equivalent circuit of 3-phase induction motor?
4.State the condition for maximum torque of 3-phase induction motor?
5.Give the different methods of speed control of I.M.
6.How do you calculate slip speed?
7.State the condition when induction, motor acts as induction generator?
8.Give the other name for induction generator?

Efficiency =
Output Power
Input Power
100
%

%
slip

www.eeecube.blogspot.com

EX.NO.2.NO LOAD AND BLOCKED ROTOR TEST ON 3 SQUIRREL CAGE


INDUCTION MOTOR
AIM
To conduct no load test and blocked rotor test on given 3 squirrel cage
induction motor and to draw the circle diagram..
APPARATUS REQUIRED
S.No

APPARATUS

RANGE

TYPE

QUANTITY

FORMLULAE
Cos o=Wo / 3 VoIo
Cos r=Wbr / 3 VbrIbr
Ibm = Ibr (Vo/Vbr)
Wbm = Wbr (Vo/Vbr)2
Stator copper loss = 3 Ibr2Rs
PRECAUTION
1. The 3 autotransformer should be kept at initial position.
2. Initially the machine should be under no load condition.
PROCEDURE
NO LOAD TEST
1. Connections are made as per the circuit diagram.
2. 3 AC supply is increased gradually using 3 autotransformer till rated voltage
is applied.
3. Readings of voltmeter and wattmeter are noted.

2
0

www.eeecube.blogspot.com

BLOCKED ROTOR TEST


1. Connections are made as per the circuit diagram and rotor is blocked from
rotating.
2. Applied voltage is increased until rated load current flows.
3. Readings of all meters are noted.
MEASUREMENT OF STATOR RESISTANCE
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of voltmeter and ammeter are noted.
4. Stator resistance in ohms is calculated as
Ra/phase = (Vx1.5) /2I
PROCEDURE FOR CONSTRUCTING THE CIRCLE
1. Vector OO is drawn at an angle of phase with respect to OY represents the
output line.
2. OX is drawn parallel to OX.
3. Vector OA is Ibr plotted at an angle of phasor with respect to OY. OA is joined
which represents the output line.
4. A perpendicular bisector from output line which cuts OY at C. With C as centre
and OC as radius draw a semi-circle
passing through A.
Y
5. From A, a perpendicular is drawn meeting OX at E and OD at D.
6. AD represents Wbr in CM.
EF represents stator copper loss in CM.
AD represents rotor copper loss in CM.
7. Join OF which represents the torque line.
8. Line AD is extended and points S is marked, where AS is equal to rated output
power.
9. Line PS is drawn parallel to output line.
10. From P, perpendicular line is drawn meeting OX at y.
11. Join OP.
MEASUREMENT OF PARAMETER AT FULL LOAD
Stator current = OP x X
%
= (PQ/PV)x 100
%Slip = (QR/PR)x 100
Torque = (PRxV/(2NT/60))
Pf
= PV/OP
MAXIMUM OUTPUT
The perpendicular at OA line cuts the circle at P and OA at PQ.
Maximum output = P1Q1x power scale (W)
MAXIMUM TORQUE

www.eeecube.blogspot.com

The perpendicular bisector of line cuts the circle at PR and OF at Q2.


Maximum torque = (PFx power scale)/T
Nm
CIRCUIT DIAGRAM
NO LOAD AND BLOCKED ROTOR TEST ON THREE PHASE SQUIRREL CAGE
INDUCTION MOTOR:

Fuse

ROTOR

R
T
P
S
T

M
C

125% of full load current rating


NAME PLATE DETAILS:

-OR

415V,50Hz,
3
SUPPLY

FUSE RATING CALCULATION:

ROT

R
( 0 600)V,MI

STATOR

L
V

BRAKE
DRUM

www.eeecube.blogspot.com

NO LOAD TEST
S.No

Vo (V)

Io (A)

Wo (W)
W1 W2

Wo=(W1+W2)
W

Wo (W)
W1 W2

Wo=(W1+W2)
W

BLOCKED ROTOR TEST


S.No

Vo (V)

Io (A)

MEASUREMENT OF STATOR RESISTANCE


S.No

RESULT:

Voltage (V)

Current (A)

Rs = (Vx1.5) /2I

www.eeecube.blogspot.com

EX.NO.3 NO LOAD AND BLOCKED ROTOR TEST ON 1-PHASE INDUCTION


MOTOR
AIM :
To obtain the equivalent circuit of the given 1-phase induction motor by no-load test and
blocked rotor test.
APPARATUS REQUIRED:
SI NO

APPARATUS REQUIRED

NAME PLATE DETAILS :


FUSE RATING CALCULATION :

Blocked rotor test -> 125% of rater current.


No-load test -> 25% of rater current.

TYPE

RANGE

QUANTITY

www.eeecube.blogspot.com

CIRCUIT DIAGRAM :
NO-LOAD TEST :

www.eeecube.blogspot.com

BLOCKED ROTOR TEST :

www.eeecube.blogspot.com

FORMULA :
NO-LOAD TEST :
Wo = VoIo Cos 0
Where, Cos 0 = Wo / VoIo
Iw = Io *Cos 0
I = Io *Sin 0
BLOCKED ROTOR TEST :
Z01 = Vsc / Isc
R01 = Wsc / Isc2
X01 = [Z022 - R022]1/2
Xm = [Zm2 - Rm2]1/2 ;
Xs = [Zs2 - Rs2]1/2 ;

R2 = R01 Rm || Rs
X2 = X01 [Xm || (Xs-Xc)]

NO-LOAD TEST :
PRECAUTION :
DPST switch should be at open position.
2. Auto transformer should be at minimum position.
PROCEDURE :
The connections are made as per the circuit diagram.
Get the power supply from the control panel.
Close the DPST switch.
Adjust the auto-transformer to the rated voltage of 1-phase induction motor.
Note the readings of ammeter, voltmeter and wattmeter.
Bring auto-transformer to minimum voltage position. Switch of the supply.

BLOCKED ROTOR TEST :


PRECAUTION :
Keep the DPST switch in open position.
Auto- transformer should be at minimum position.
Before switching on the supply, some load is applied in the brake drum, so that rotor does
not rotate.
PROCEDURE :
Connections are made as per the circuit diagram.
Get the power supply from the control panel.

www.eeecube.blogspot.com

Close the DPST switch.


Auto transformer is adjusted to rated current of 1-phase induction motor.
Readings of ammeter, voltmeter and wattmeter are noted down.
Bring auto-transformer to its minimum voltage position and switch off the supply, after
removing the load.
OBSERVATION TABLE
NO-LOAD TEST :
SI
NO

Voltage
(volt)

Io
(Amp)

Wo (Watt)

BLOCKED ROTOR TEST :


SI
NO

Voltage
(volt)

Io
(Amp)

Wo (Watt)

RESULT :

VIVA QUESTIONS :
What is a 1-phase induction motor?
Write the classification of 1-phase induction motor?
Why do we draw the equivalent circuit of 1-phase induction motor?
What is double-field revolving theory?
Why 1-phase induction, motor is not self starting?

www.eeecube.blogspot.com

EX.NO.4. REGULATION OF 3 ALTERNATOR BY ZPF METHOD


AIM
To predetermine the regulation of a given 3 alternator at full load condition and
different power by ZPF method.
APPARATUS REQUIRED
S.No

APPARATUS

RANGE

TYPE

QUANTITY

PRECAUTIONS
1. Motor field rheostat should be kept at minimum resistance position.
2. Alternator field rheostat should be kept at maximum resistance position.
PROCEDURE
OPEN CIRCUIT TEST
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. DC motor is started and brought to rated speed by adjusting rheostat.
4. Keeping the TPST open, alternator field rheostat is energized.
5. By varying alternator field rheostat, the field (If) current is varied in steps, and E
(internal emf ) is noted.
6. Above procedure is noted till 125% of rated voltage.

www.eeecube.blogspot.com

SHORT CIRCUIT TEST


1. TPST switch is closed.
2. By varying alternator field rheostat, the field current, (If) is varied in steps and
corresponding short current (Isc) is noted.
3. Above procedure is repeated till rated current is reached.
ZPF TEST
1. DC motor is run at rated speed by adjusting motor field rheostat.
2. 3 ZPF load is connected to alternator by closing TPST switch.
3. By alternatively varying field rheostat, ZPF load, alternator is made to deliver
rated current. Readings are noted.
DRAWING ZPF CURVE
1. OCC is drawn.
2. Point A is located such that OA gives If corresponding to Irated. Under short circuit
test.
3. Point B is located such that it gives If to voltage from ZPF test.
4. Points A and B joined by curve parallel to OC called ZPF curve.
5. From the curve, ZPF curve is extended.
6. From H, HD is drawn parallel to OCC line.
7. From B, BH is drawn parallel and equal to OA.
8. Point D is point to B and BHD is tangent is obtained.
9. From D, perpendicular to BH at E is drawn.
10. DE gives Ia XL. BE gives If necessary to overcome demagnetizing effect of
armature resistance. EH gives If necessary for balancing armature leakage
reactance drop DE.
11. Internal emf, E1 is calculated as

www.eeecube.blogspot.com

E1 = ((Vph cos + Ia Ra)2 + (Vph sin + IaXL)2)


+ for lagging pf and
- for leading pf.
12. Find If1 corresponding E1 from OCC.
13. If2 is field current, required to overcome armature reaction (BE)
14. If = (If12+If22-2If1If2 cos(90)) + for lagging pf and
- for leading pf.
15. From internal emf E1, a horizontal line is drawn cutting the OCC.
16. The regulation is calculated as
% regulation = ((Eo Vph)/ Vph)x100.

ZPF
TEST ON THREE PHASE ALTERNATOR:
3 point
(0 10) A,
starter
A
R
MI
LF A

Fus
e
M

220 V
DC
SUPP
LY

D
P
S
T

700

1.5 A

220 V
DC
SUPP
LY

A1
N
F1`
F1

D
P
S
T

Neutral
link

STATO
RR

A2

Fus
e

F2
Neutral
link

300V,10A,U
PF

B
F2

F1

L
O
A
D

1000 ,1.5 A
A
(02)A,
MC

V (0
300)V,MI

I
N
D
U
C
T
I
V
E

ROTO
R

www.eeecube.blogspot.com

FUSE RATING CALCULATION:


125% of the full load current rating.
SHORT CIRCUIT TEST ON THREE PHASE ALTERNATOR:
3 point starter

Fuse

LFA

220 V
DC
F1`
SUPPL
Y

700
1.5 A

D
P
S
T

STATO
R

A1
F1
A2

N
B

F2

F1

F2

Y
Neutral
link
Fus
e

220 V
DC
SUPPL
Y

1000 ,1.5 A
( 0 2 ) A , MC
A
ROTO
R

D
P
S
T

Neutral link
FUSE RATING CALCULATION:
125% of the full load current rating.

( 0 10) A,MI

www.eeecube.blogspot.com

RESULT

EX.NO.5. REGULATION OF 3 ALTERNATOR BY ASA METHOD

www.eeecube.blogspot.com

AIM
To predetermine the regulation of a given 3 alternator at full load condition and
different power by ASA method.
APPARATUS REQUIRED
S.No

APPARATUS

RANGE

TYPE

QUANTITY

PRECAUTIONS
3. Motor field rheostat should be kept at minimum resistance position.
4. Alternator field rheostat should be kept at maximum resistance position.
PROCEDURE
OPEN CIRCUIT TEST
7. Connections are made as per the circuit diagram.
8. Supply is given by closing the DPST switch.
9. DC motor is started and brought to rated speed by adjusting rheostat.
10. Keeping the TPST open, alternator field rheostat is energized.
11. By varying alternator field rheostat, the field (If) current is varied in steps, and E
(internal emf) is noted.
12. Above procedure is noted till 125% of rated voltage.
SHORT CIRCUIT TEST

www.eeecube.blogspot.com

4. TPST switch is closed.


5. By varying alternator field rheostat, the field current, (If) is varied in steps and
corresponding short current (Isc) is noted.
6. Above procedure is repeated till rated current is reached.
ASA TEST
4. DC motor is run at rated speed by adjusting motor field rheostat.
5. 3 ZPF load is connected to alternator by closing TPST switch.
6. By alternatively varying field rheostat, ZPF load, alternator is made to deliver
rated current. Readings are noted.
DRAWING ASA CURVE
12. OCC is drawn.
13. Point A is located such that OA gives If corresponding to Irated. Under short circuit
test.
14. Point B is located such that it gives If to voltage from ZPF test.
15. Points A and B joined by curve parallel to OC called ZPF curve.
16. From the curve, ZPF curve is extended.
17. From H, HD is drawn parallel to OCC line.
18. From B, BH is drawn parallel and equal to OA.
19. Point D is point to B and BHD is tangent is obtained.
20. From D, perpendicular to BH at E is drawn.
21. DE gives Ia XL. BE gives If necessary to overcome demagnetizing effect of
armature resistance. EH gives If necessary for balancing armature leakage
reactance drop DE.
22. Internal emf, E1 is calculated as
E1 = ((Vph cos + Ia Ra)2 + (Vph sin + IaXL)2)
+ for lagging pf and
- for leading pf.
12. Find If1 corresponding E1 from OCC.

www.eeecube.blogspot.com

13. If2 is field current, required to overcome armature reaction (BE)


14. If = (If12+If22-2If1If2 cos(90)) + for lagging pf and
- for leading pf.
15. From internal emf E1, a horizontal line is drawn cutting the OCC. Distance
between tangent to OCC and tangent to OCC measures If3.
This is added with the field current to get final field current.
Ifr = If+If3
16. Eo corresponding to Ifr is found.
17. The regulation is calculated as
% regulation = ((Eo Vph)/ Vph)x100.
ASA
TEST ON THREE PHASE ALTERNATOR:
3 point
(0 10) A,
starter
A
R
MI
LF A

Fus
e
M

220 V
DC
SUPP
LY

D
P
S
T

700

1.5 A

220 V
DC
SUPP
LY

A1

D
P
S
T

STATO
RR

N
F1`
F1

A2

Fus
e

B
F2

F1

1000 ,1.5 A
A
(02)A,
MC

V (0
300)V,MI

I
N
D
U
C
T
I
V
E
L
O
A
D

ROTO
R

FUSE RATING CALCULATION:


125% of the full load current rating.
Neutral
link

F2
Neutral
link

300V,10A,U
PF

www.eeecube.blogspot.com

SHORT CIRCUIT TEST ON THREE PHASE ALTERNATOR:


3 point starter

Fuse

LFA

220 V
DC
F1`
SUPPL
Y

700
1.5 A

D
P
S
T

STATO
R

A1
F1
A2

N
B

F2

F1

F2

Y
Neutral
link
Fus
e

220 V
DC
SUPPL
Y

1000 ,1.5 A
( 0 2 ) A , MC
A
ROTO
R

D
P
S
T

Neutral link

TABULAR COLOUMN
OPEN CIRCUIT TEST
S.No

Field Current If (A)

Induced Voltage Vr (V)

Vph =Vr /3 (V)

( 0 10) A,MI

www.eeecube.blogspot.com

SHORT CIRCUIT TEST


S.No

Field Current If (A)

Short circuit Current IA (A)

ZPF TEST
S.No Voltage Field Current
(V)

If (A)

Armature
Current (A)

RESULT

EX.NO.6 LOAD TEST ON SINGLE PHASE INDUCTION MOTOR


AIM
To conduct load test on single phase induction motor and to draw the performance
characteristics.
APPARATUS REQUIRED
S.NO

APPARATUS

RANGE

TYPE

QUANTITY

www.eeecube.blogspot.com

FORMULA USED
1. Synchronous speed (Ns)=120f/p (rpm)
Where f=frequency in Hz
P=no. of poles, calculated by assuming 5% slip
2. % slip =

( Ns Nr) *100
Ns

Where Ns=synchronous speed in rpm


Nr=speed of the rotor in rpm
3. Torque T = (S1~ S2)*R*9.81 (N-m)
Where R=radius of brake drum of motor in meter
S1, S2 = spring balance reading in kg
2 N rT
4. Output power Po =
(in watts)
60
5. Input power
Pi = W (in watts)
6. % efficiency % = Output power/ Input power*100
PRECAUTIONS
The motor should be at the no load condition while starting.
PROCEDURE
1. Connections are given as per the circuit diagram.
2. The induction motor is started on no load by using transformer starter.
3. Under no load condition, reading of ammeter, voltmeter and wattmeter are noted
down.
4. Speed is measured by using tachometer.
5. The motor is loaded gradually by increasing tension on the belt over the brake
drum.
6. At each load, the readings of ammeter, voltmeter and wattmeter are noted, speed
is measured and spring balance readings are noted down.
7. The above procedure is repeated till the rated current is reached.
8. The load on motor is gradually reduced to zero and then supply is switched OFF
CIRCUIT DIAGRAM:

www.eeecube.blogspot.com

www.eeecube.blogspot.com

RESULT

www.eeecube.blogspot.com

EX.NO.7 SEPERATION OF LOSSES IN A THREE PHASE INDUCTION


MOTOR
AIM
To separate the no load losses in a given three phase induction motor
APPARATUS REQUIRED
S.NO
APPARATUS

RANGE

TYPE

QUANTITY

FORMULA USED
Magnetic Loss = Wo.-mechanical losses-3Io2Rs
Where Wo = wattmeter reading
Io = current at rated voltage
Rs = stator resistance
Mechanical losses are obtained from the graph
PRECATIONS
1. The motor should be at the no load condition while starting.
2. The 3 auto-transformer (variac) should be kept at initial zero position.
PROCEDURE
SEPERATION OF LOSSES
1. Connections are given as per the circuit diagram.
2. The 3 A.C supply is given by closing the TPST switch.
3. The induction motor is started gradually by applying voltage through the 3 autotransformer.
4. At rated voltage, power input Wo is measured by using wattmeter and no load
current Io and voltage Vo are noted.
5. Voltage is gradually reduced till the motor continues to run.
6. For each voltage, readings of ammeter, voltmeter and wattmeter are noted.
MEASUREMENT OF STATOR RESISTANCE (Rs)
1. Connections are given as per the circuit diagram.
2. The D.C supply is given through a DPST switch.
3. The loading rheostat is varied, the readings of ammeter and voltmeter are noted.
4. Armature resistance in ohms is calculated as Rs/ph = (V*1.5)/2I

www.eeecube.blogspot.com

CIRCUIT DIAGRAM:

www.eeecube.blogspot.com

www.eeecube.blogspot.com

EX.NO. 8 & 9 REGULATION OF ALTERNATOR BY EMF AND MMF


METHOD
AIM :
To predetermine the percentage regulation of the given alternator by EMF
(Synchronous Impedance Method) and MMF (Ampere Turns Method), by conducting
OC and Short circuit test.
APPARATUS REQUIRED:
SI NO

APPARATUS REQUIRED

NAME PLATE DETAILS :

FUSE RATING CALCULATION :


DC shunt motor =>125 % of rated current .
Alternator
=> 125 % of rated current .

TYPE

RANGE

QUANTITY

www.eeecube.blogspot.com

CIRCUIT DIAGRAM :

FORMULA USED:
EMF Method :
Re = 1.6 * Rs
Where,
Rs - DC resistance and
Re - Equivalent AC resistance
E1/I1 Where
E1 = OC voltage
I1 = SC voltage
Zs = E1(open cicuit voltage) / I1(short circuit current)
Xs = (Zs2 Re2)1/2
Eo = [(Vcos + Ire)2 + (Vsin (+ or -) IXs)2]1/2
Where,
+
sign for lagging Power Factor
- sign for leading Power Factor
% Regulation (up) = [(Eo V)/V] * 100
MMF Method :
If = [ If12 + If22 -2 If1 If2 Cos ( 90 (+ or -) ) + for lagging power factor,
- for leading power factor.
Where,
If1 - Field current corresponding to V1.
If2 - Field current corresponding to Isc
V1 = V+I*Re*Cos
% Regulation (up) = [(Eo V)/V] * 100
Eo - Voltage corresponding to If.
PRECAUTION
1.DC shunt motor field rheostat should be in minimum resistance position to get
minimum speed at the time of starting.
2.Alternator field rheostat should be in minimum position.
3.DPST and TPST switches should be in open position.
PROCEDURE

www.eeecube.blogspot.com

OC Test:
1.Connections are made as per the circuit diagram is obtained.
2.The supply is obtained from control panel.
3.Observing the precautions, DPST switch on motor side is closed.
4.Using 3-point starter, the DC motor is started.
5.Varying the field rheostat of DC shunt motor, it is set to run at rated speed as per name
plate detail.
6.DPST switch in alternator field circuit is closed.
7.Keeping the TPST switch of alternator side open, the field current is varied using the
alternator potential divider. For various values of alternator field current (If), the
generated AC line voltage (EOL) is noted down and the readings are tabulated.
(This should be done upto125% of rated voltage).
BLOCKED ROTOR TEST :
Note:
1.TPST switch, on alternator side is closed.
2.By slowly increasing potential divider from minimum potential position, the values of If
and corresponding Isc values are noted till rated current flows through the alternator.
3.The readings are tabulated.
4.Potential divider is adjusted to original position. [minimum potential position] and
field rheostat on motor side is s\adjusted to minimum resistance position.
5.DPST and TPST switches are opened.
6.The supply is switched off.
OBSERVATION TABLE
OPEN CIRCUIT TEST:
If
(A)

V
(volt)

Vph
(volt)

SHORT CIRCUIT TEST :


If
(A)

V
(volt)

TABULATION :

www.eeecube.blogspot.com

SI.NO

Power Factor (Cos )

No-load
Voltage (volt)
E0

Terminal
Voltage (volt)

%Regulation=
[(Eo-V)/V]*100

MODEL CALCULATION
EMF Method :
Re = 1.6 * ______ Ohm
Where,
Rs - DC resistance and
Re - Equivalent AC resistance
Zs = __(open cicuit voltage) / __(short circuit current)
Xs = (__2 __2)1/2
Eo = [(___*_____*____+ ___)2 + (____*____ (+ or -) ____)2]1/2
Where,
+ sign for lagging Power Factor
- sign for leading Power Factor
% Regulation (up) =[ (__ __)/]*100
=-

MMF Method :
If = [ ___2 + ___2 - 2 *___* ___* Cos ( 90 (+ or -) ___ ) + for lagging power factor, - for
leading power factor.
Where,
If1 - Field current corresponding to V1.
If2 - Field current corresponding to Isc
V1 - V+IRecos
% Regulation (up) = [(__ __)/__] *100
Eo - Voltage corresponding to If.

www.eeecube.blogspot.com

RESULT :

www.eeecube.blogspot.com
EX.NO.10. LOAD TEST ON 3-PHASE SLIP RING INDUCTION MOTOR
AIM :
To determine the performance characteristics of 3-phase squirrel cage induction
motor by direct loading.
APPARATUS REQUIRED:
SI NO APPARATUS REQUIRED

TYPE

RANGE QUANTITY

NAME PLATE DETAILS :

FUSE RATING CALCULATION :


125% of rated current.
No-load test - 25% of rated current.
FORMULA :
Torque,
T = (S1 S2) * 9.81 * r (Nm)
Input power
(Pi) = (W1 + W2) (Watt)
Output power
(Po) = 2 NT / 60 (Watt)
Efficiency
= Po X 100
Pi
Cos = W/(31/2 VLIL)
Slip = (Ns N) / Ns *100
PRECAUTION:
1. TPST switch should be at open position.
2. 3-phase autotransformer should be at minimum voltage position.
3. There should be no-load at the time of starting(Loosen the belt on the brake drum)

www.eeecube.blogspot.com

4. Brake drum should be filled with water.


PROCEDURE:
1.
2.
3.
4.
5.
6.
7.

The connections are made as per the circuit diagram.


Power supply is obtained from the control panel.
The TPST switch is closed.
Rated voltage of 3-phase induction motor, is applied by adjusting autotransformer
The initial readings of ammeter, voltmeter and wattmeter are noted.
By increasing the load step by step, the reading of ammeter, voltmeter and wattmeter
Step1 to 6 is repeated till the ammeter shows the rated current of 3-phase induction
motor.
8. Decrease the load, bring auto-transformer to its minimum voltage position.
9. Switch off the supply.

OBSERVATION TABLE :

S.N
O

V (volt)

I (A)

Speed
(rpm)

Spring Balance

S1(Kg)

S2(Kg)

Torque
=((S1 S2) *
9.81 * R)

I/P

O/P
2
(V*IL) NT

N-m

watt

60
(watt)

Efficiency =
Output Power
Input Power
100
%

%
slip

www.eeecube.blogspot.com

RESULT :
Thus the load test on three phase Induction Motor is verified experimentally.

VIVA QUESTIONS :
1.Explain what is meant by a 3-phase induction motor?
2.Write the classification of 3-phase induction motor?
3.State the steps to draw the equivalent circuit of 3-phase induction motor?
4.State the condition for maximum torque of 3-phase induction motor?
5.Give the different methods of speed control of I.M.
6.How do you calculate slip speed?
7.State the condition when induction motor acts as induction generator?
8.Give the other name for induction generator?

Vous aimerez peut-être aussi