11KV/415VOverheadLineSpecification(REC)
JUNE8,2011 101COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/06/08/11KV415VOVERHEAD
LINESPECIFICATIONREC/#COMMENTS)

11KV/415VoverHeadLinesSpecificationandInstallation(REC):

11KVLIGHTNINGARRESTER(IS:3070(PtII)).
VoltageRatingforLA:
Theratedvoltageoflightningarrestersshallbe9KV(rms).
Thiswillbeapplicabletotheeffectivelyearthed11KVsystemscoefficientofearthnotexceeding80percentasperIS:4004with
allthetransformerneutralsdirectlyearthed.

NormalDischargeCurrentRatingforLA:
Thenominaldischargecurrentratingofthelightningarrestersshallbe5KA.

TestsforLA:
ThefollowingroutineandtypetestsaslaiddowninIS:3070(PartI)shallbecarriedout.
RoutineTest:DryPowerfrequencysparkovertest.
TypeTests(Confirmation):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Voltagewithstandtestsofarresterinsulation.
Powerfrequencysparkovertest
Hundredpercent1.2/550microsecondimpulsesparkovertest
Frontofwaveimpulsesparkovertest.
Residualvoltagetest.
Impulsecurrentwithstandtest.
Operatingdutytest.
Temperaturecycletestonporcelainhousing.
Porositytestonporcelaincomponents.
Galvanizingtestonmetalparts.

11KVDROPOUTFUSECUTOUTS:(IS:9385(partItoIII).)
Thedistributionfusecutoutsshallbeoutdoor,open,dropoutexpulsiontypefusecutoutssuitableforinstallationin50Hz,11
KVdistributionsystem.
Theratedvoltageshallbe12KV.
Theratedcurrentshallbe100A.

RatedLightingImpulsewithstandsVoltageforFuse:
Toearthandbetweenpoles75KV(Peak)
Acrosstheisolatingdistanceoffusebase86KV(Peak)

RatedOneMinutePowerFrequencyWithstandVoltage(Wet&Dry)forFuse:
Toearthandbetweenpoles28KV(rms)
Acrosstheisolatingdistance32KV(rms)

TemperatureRiseLimitforFuse:
Coppercontactssilverfaced650C
Terminals500C
MetalpartsactingasspringThetemperatureshallnotreachsuchavaluethatElasticityofthemetalischanged

RatedBreakingCapacityforFuse:
Theratedbreakingcapacityshallbe8KA(Asymmetrical).

ConstructionDetailsforFuse:
Thecutoutsshallbeofsingleventtype(downward)havingafrontconnectedfusecarriersuitableforanglemounting.
AllferrouspartsshallbehotdipgalvanizedinaccordancewiththelatestversionofIS:2632.NutsandboltsshallconformtoIS:
1364.Springwashersshallbeelectrogalvanized.

FuseBaseTopAssembly:
Thetopcurrentcarryingpartsshallbemadeofahighlyconductivecopperalloyandthecontactportionshallbesilverplatedfor
corrosionresistanceandefficientcurrentflow.
Thecontactshallhaveasocketcavityforlatchingandholdingfirmlythefusecarrieruntilthefaultinterruptioniscompleted
withinthefuse.
Thetopassemblyshallhaveanaluminumalloyterminalconnector.Thetopassemblyshallberobustenoughtoabsorbbulkof
theforcesduringthefusecarrierclosingandopeningoperationsandshallnotoverstressthespringcontact.Itshallalsoprohibit
accidentalopeningofthefusecarrierduetovibrationsorimpact.

FuseBaseBottomAssembly:
Theconductingpartsshallbemadeofhighstrengthhighlyconductivecopperalloyandthecontactportionshallbesilverplated
forcorrosionresistanceandshallprovidealowresistancecurrentpathfromthebottomfusecarriercontactstothebottom
terminalconnector.

FuseCarrierTopAssembly:
Thefusecarriertopcontactshallhaveasolidreplaceablecapmadefromhighlyconductive,anticorrosivecopperalloyandthe
contactportionshallbesilverplatedtoprovidealowresistancecurrentpathfromtheFuseBaseTopContacttotheFuseLink.
Itshallmakeafirmcontactwiththebuttonheadofthefuselinkandshallprovideaprotectiveenclosuretothefuselinktocheck
spreadingofarcduringfaultinterruptions.
Thefusecarriershallbeprovidedwithacastbronzeopeningeye(pullring)suitableforoperationwithahookstickfromthe
groundleveltopulloutorcloseinthefusecarrierbymanualoperation.

FuseCarrierBottomAssembly:
Thefusecarrierbottomassemblyshallbemadeofbronzecastingswithsilverplatingatthecontactpointstoefficientlytransfer
currenttofusebase.
Itshallmakesmoothcontactwiththefusebasebottomassemblyduringclosingoperation.Thebottomassemblyshallhavea
liftingeyeforthehookstickforremovingorreplacingthefusecarrier.

FuseBase(Porcelain):
Thefusebaseshallbeabirdproof,singleunitporcelaininsulatorwithacreepagedistance(toearth)notlessthan320mm.The
topandbottomassembliesasalsothemiddleclampinghardwareshallbeeitherembeddedintheporcelaininsulatorwith
sulphurcementorsuitablyclampedinposition.
Forembeddedcomponents,thepulloutstrengthshouldbesuchastoresultinbreakingoftheporcelainbeforepulloutoccursin
atest.Forporcelaininsulators,thebeamstrengthshallnotbelessthan1000kg.

FuseTube:
Thefusetubeshallbemadeoffiberglasscoatedwithultravioletinhibitorontheoutersurfaceandhavingarcquenchingbone
firelinerinside.
Thetubeshallhavehighburstingstrengthtosustainhighpressureofthegasesduringfaultinterruption.
Theinsidediameterofthefusetubeshallbe17.5mm.Thesolidcapofthefusecarriershallclampthebuttonheadofthefuse
link,closingthetopendofthefuseandallowingonlythedownwardventingduringfaultinterruption.

TypeTests(IS:9385PartI&II)forFuse:
Dielectrictests
Temperaturerisetest

MountingArrangementforFuse:

Thecutoutsshallbeprovidedwithasuitablearrangementformountingtheseon74X40mmor100X50mmchannelcrossarm
insuchawaythatthecenterlineofthebaseisatanangleof15to20degfromtheverticalandshallprovidethenecessary
clearancesfromthesupport.
Mountingarrangementshallbemadeofhighstrengthgalvanizedsteelflatandshallberobustenoughtosustainthevarious
stressesencounteredduringalloperatingconditionsofthecutout.

11KVPORCELAININSULATORS:(IS:731andIS:3188):
Theporcelainshallbesound,freeformdefects,throughverifiedandsmoothlyglazed.Unlessotherwisespecified,theglazeshall
bebrowncolor.
Theglazeshallcoveralltheporcelainpartsofinsulatorsexceptthoseareaswhichserveassupportduringfiringareleft
unglazedforthepurposeofassembly.
Thedesignofinsulatorsshallbesuchthatstressesduetoexpansionandcontractioninanypartoftheinsulatorshallnotleadto
deterioration.
Theporcelainshallnotengagedirectlywithhardmetal.Cementusedinconstructionofinsulatorsshallnotcausefractureby
expansionorlooseningbycontractionandpropercareshallbetakentolocatetheindividualpartscorrectlyduringcementing.
Thecementshallnotgiverisetochemicalreactionwithmetalfittingsanditsthicknessshallbeasuniformaspossible.
Theinsulatorsshouldpreferablybemanufacturedinautomatictemperaturecontrolledkilnstoobtainuniformbakingforbetter
electricalandmechanicalproperties.
BothpinandstraininsulatorsshallconformtoTypeBofIS:731.ThestraininsulatorsshallbeofTongueandClevistype.

TestVoltageforInsulator:
HighestSystemVoltage:12KV(rms)
VisibleDischargeTest:9KV(rms)
WetPowerFrequencyWithstandTest35KV(rms)
PowerFrequencyPunctureWithstandTest(PinInsulator):105KV(rms)
PowerFrequencyPunctureWithstandTest(StrainInsulator):1.3timestheactualdryflashovervoltageoftheinsulator.
ImpulseVoltageWithstandTest:75KV(rms)

FailingLoadforInsulator:
MechanicalFailingLoad(ForPinInsulatorsonly):Theinsulatorsshallbesuitableforaminimumfailingloadof10KNapplied
intransversedirector.
ElectroMechanicalFailingLoad(ForStrainInsulators):Theinsulatorsshallbesuitableforaminimumfailingloadof70KN
appliedaxially.

CreepageDistanceforInsulator:
HighestSystemVoltage:12KV
HeavilyPollutedAtmospherePinInsulator:320mm
HeavilyPollutedAtmosphereStrainInsulator:400mm

Tests:(AsperIS:731)forInsulator.
1. Visualexamination
2. Verificationofdimensions

3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

Visibledischargetest
ImpulseVoltagewithstandTest
WetPowerFrequencyVoltagewithstandTest
TemperatureCycleTest
MechanicalFailingLoadTest
24hourMechanicalStrengthTestforStrainInsulators
PunctureTest
PorosityTest
GalvanizingTest
ElectroMechanicalFailingLoadTest

RoutineTestsforInsulator
1. Virtualexamination
2. Mechanicalroutinetest
3. Electricalroutinetest

AcceptanceTestforInsulator
1.
2.
3.
4.
5.
6.

VerificationofDimensions
TemperatureCycleTest
ElectroMechanicalFailingLoadTest
PunctureTest
PorosityTest
GalvanizingTest

MarkingforInsulator:
Nameortrademarkofmanufacturer
Monthandyearofmanufacture
MinimumfailingloadinKN
ISIcertificatemark,ifany
Markingsonporcelainshallbeprintedandshallbesuppliedbeforefiring.

PinInsulators:
Thepinsshallofsinglepieceobtainedpreferablybytheprocessofforging.
Theyshallnotbemadebyjoining,welding,shrinkfittingoranyotherprocessusingmorethanonepiecematerial.Thepinsshall
beofgoodfinish,freefromflawsandotherdefects.
Thefinishofthecollarshallbesuchthatsharpanglebetweenthecollarandtheshankisavoided.Aluminumferrouspins,nuts
andwashers,exceptthosemadeofstainlesssteel,shallbegalvanized.Thethreadsofnutsandtapedholewhencutafter
galvanizingshallbewelloiledorgreased.

DimensionsforPinInsulators:
PinsshallbeofsmallsteelheadtypeS165PasperIS:2486(PartII)havingstalklengthof165mmandshanklengthof150mm
withminimumfailingloadof10KN.

Tests:(IS:2486(PartI))forPinInsulators
Checkingofthreadsonheads
Galvanizingtest
Visualexaminationtest
Mechanicaltest
Galvanizingtest
Mechanicaltest
Visualexaminationtest

HelicallyFormedPinInsulatorTies:
Helicallyformedtiesusedforholdingtheconductoronthepininsulatorshallbemadeofaluminumalloyoraluminizedsteelor
aluminumcladsteelwiresandshallconformtotherequirementsofIS:12048.Thetiesshallbesuitableforpininsulator
dimensionsofPt.Iandconductorsizesspecified.
Elastomerpadforinsulatorshallbeusedwiththetiestoavoidabrasionoftheconductorcomingintodirectcontactwiththe
insulator.

CrossarmstrapconformingtoIS:2486(Pt.II).
Aluminumalloydiecastthimbleclevisforattachingtothetongueofstrain,insulatorononeendandforaccommodatingthe
loopofthehelicallyformeddeadendfittingattheotherendinitssmoothinternalcontour.
ThethimbleshallbesuitableforallsizesofACSRconductorsasspecified.Thethimbleclevisshallbeattachedtotheinsulator
byasteelcuttingpinusedwithanonferroussplitpinofbrassorstainlesssteel.
ThethimbleshallhaveclevisdimensionsasperIS:2486(PtII).
Helicallyformeddeadendgriphavingaprefabricatedlooptofitintothegroovedcontourofthethimbleononeendandfor
applicationovertheconductorattheotherend.
TheformedfittingshallconformtotherequirementofIS:12048.

FittingsforstrainInsulatorsofBall&SocketType:
CrossarmstrapconformingtoIS:2486(PtII).
Forgedsteelballeyeforattachingthesocketendofthestraininsulatortothecrossarmstrap.
ForgingsshallbemadeofsteelasperIS:2004.Aluminumalloythimblesocketmadeoutofpermanentmouldcast,highstrength
aluminumalloyforattachingtothestraininsulatorononeendandforaccommodatingtheloopofthehelicallyformeddeadend
fittingsattheotherendinitssmoothinternalcontour.
ThethimblesocketshallbeattachedtothestraininsulatorwiththehelpoflockingpinasperthedimensionsgiveninIS:2486
(PtII).

Tests
ThehelicallyformedfittingsforstraininsulatorsshallbesubjectedtotestsasperIS:12048.
TheotherhardwarefittingsshallbetestedasperIS:2486(PartI).

FittingsforstrainInsulatorswithHelicallyFormedConductorsDead
EndGrips:

FittingsforStrainInsulatorsofTongue&ClevisType
Thefittingsshallconsistofthefollowingcomponents:
1. CrossarmstrapconformingtoIS:2486(Pt.II)1989.
2. Aluminumalloydiecastthimbleclevisforattachingtothetongueofstraininsulatorononeendandforaccommodatingthe
loopofthehelicallyformeddeadendfittingattheotherendinitssmoothinternalcontour.Thethimbleshallbesuitableforall
sizesofconductorsrangingfrom7/2.11mmto7/3.35mmACSR.Thethimbleclevisshallbeattachedtotheinsulatorbyasteel
cutterpinusedwithanonferroussplitpinofbrassorstainlesssteel.ThethimbleshallhaveclevisdimensionsasperIS:2486
(Pt.II)1989.
3. Helicallyformeddeadendgriphavingaprefabricatedlooptofitintothegroovedcontourofthethimbleononeendandfor
applicationovertheconductorattheotherend.TheformedfittingshallconformtotherequirementofIS:120481987.
Note:Asthehelicallyformedfittingsaremadetosuitspecificsizesofconductors,thepurchaseshouldclearlyspecifythe
numberoffittingsrequiredforeachsizeofconductor

FittingsforstrainInsulatorswithConventionalDeadendClampsAlternativeto
FittingCovered:
Fittingsforstraininsulatorswithconventionaldeadendclampsforusewithtongue&clevisorball&sockettypeinsulators
shallconsistofthefollowingcomponents:
1. CrossarmsstrapconformingtoIS:2486(Pt.II)1989
2. DeadendclampmadeofaluminumalloytosuitACSRconductorsfrom7/2.11mmto7/3.35mm.Theultimatestrengthofthe
clampshallnotbelessthan3000Kg.TheshapeandmajordimensionsofclampssuitableforB&SandT&Cinsulatorsareshown
infigures7&8respectively.

GUYSTRAININSULATORS:(IS:5300)
Theporcelaininsulatorshallbesound,freefromdefects,thoroughlyverifiedandsmoothlyglazed.
Thedesignoftheinsulatorshallbesuchthatthestressestoexpansionandcontractioninanypartoftheinsulatorshallnotlead
toitsdeterioration.
Theglaze,unlessotherwisespecified,shallbebrownincolor.
Theglazeshallcovertheentireporcelainsurfacepartsexceptthoseareasthatserveassupportsduringfiring.

TypeforGuyInsulators:
ThestandardguystraininsulatorsshallbedesignationsAandCasperIS:5300.
Therecommendedtypeofguystraininsulatorsforuseonguywiresofoverheadlinesofdifferentvoltagelevelsareasfollows:
PowerLineVoltage:11KV
DesignationofInsulators:C
DryoneminutePowerFrequencywithstandVoltage:27KV(rms)
WetoneminutePowerFrequencywithstandVoltage:13KV(rms)
MinimumFailingLoad:88(KN)

Tests:(IS:5300)forGuyInsulators.
1. Visualexamination
2. Verificationofdimensions

3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

Temperaturecycletest
Dryoneminutepowerfrequencyvoltagewithstandtest
Wetoneminutepowerfrequencyvoltagewithstandtest
Mechanicalstrengthtest
Porositytest
AcceptanceTests:(tobeconductedinthefollowingorder)
Verificationofdimensions
Temperaturecycletest
Mechanicalstrengthtest
Porositytest

MarkingforGuyInsulators:
Nameortrademarkofthemanufacturer.
Yearofmanufacture.
ISIcertificatemark,ifany
Markingonporcelainshallbeappliedbeforefiring.

TypeofInsulatorsforGuyInsulators:
ThestandardguystraininsulatorsshallbeofdesignationsAandCasperIS:5300.
Therecommendedtypeofguystraininsulatorsforuseonguywiresofoverheadlinesofdifferentvoltagelevelsareasfollows:
LineVoltage

DesignationofInsulator

415/240Volt

AType

11KV

CType

33KV

CType(2NosofStringsin
Series).

BasicInsulatorLevelforGuyInsulators:
Designationof
Insulator

Dryoneminpower
frequencywithstand

Wetoneminpower
frequency
withstand

AType

18KV(rms)

8KV(rms)

CType

27KV(rms)

13KV(rms)

MechanicalStrengthforGuyInsulators:
Theinsulatorsshallbesuitablefortheminimumfailingloadsspecifiedasunder:
DesignationofInsulator

MinimumFailingLoad

AType

44KN

CType

88KN

RoutineTestasperTests(IS:5300)forGuyInsulators:

1.
2.
3.
4.
5.
6.
7.

Visualexamination
Verificationofdimensions
Temperaturecycletest
Dryoneminutepowerfrequencyvoltagewithstandtest
Wetoneminutepowerfrequencyvoltagewithstandtest
Mechanicalstrengthtest
Porositytest

AcceptanceTests(tobeconductedinthefollowingorder):
1.
2.
3.
4.

Verificationofdimensions
Temperaturecycletest
Mechanicalstrengthtest
Porositytest

DANGERNOTICEPLATES:
AsperprovisionsofIERules1956,DangerNoticePlatesinHindiorEnglishand,inaddition,inthelocallanguagewiththesign
ofskullandbonesarerequiredtobeprovidedonpowerlinesupportsandotherinstallations.
ItisfurtherstipulatedintheI.E.RulesthatsuchNoticePlatesarenotrequiredtobeprovidedonsupportslikePCC,tubular,
wood,steelrails,etc.whichcannotbeclimbedeasilywithouttheaidofladderorspecialappliances.
Toadoptauniformpatternandforhelpingeasyprocurement,aspecificationonDangerNoticePlateshasbeendrawnup.

StandardsofDangerPlate
TheDangerNoticePlatesshallcomplywithIS:25511982.

DimensionsofDangerPlate
TwosizesofDangerNoticePlatesasfollowsarerecommended:
1. Fordisplayat415Vinstallations200x150mm
2. Fordisplayat11KV(orhighervoltages)installations250x200mm
Thecornersoftheplateshallberoundedoff.
ThelocationoffixingholesasshowninFigs.1to4isprovisionalandcanbemodifiedtosuittherequirementsofthepurchaser.

LetteringofDangerPlate
Allletteringsshallbecentrallyspaced.Thedimensionsoftheletters,figuresandtheirrespectivepositionshallbeasshownin
figs.
Thesizeoflettersinthewordsineachlanguageandspacingbetweenthemshallbesochosenthattheseareuniformlywrittenin
thespaceearmarkedforthem.

LanguagesofDangerPlate
UnderRuleNo.35ofIndianElectricityRules,1956,theownerofeverymedium,highandextrahighvoltageinstallationis

requiredtoaffixpermanentlyinaconspicuouspositionadangernoticeinHindiorEnglishand,inaddition,inthelocal
language,withthesignofskullandbones.
ThetypeandsizeofletteringtobedoneinHindiisindicatedinthespecimendangernoticeplatesshowninFig.2and4and
thoseinEnglishareshowninFigs.
Adequatespacehasbeenprovidedinthespecimendangernoticeplatesforhavingtheletteringsinlocallanguageforthe
equivalentofDanger,41511000andVolts.

Material&FinishingofDangerPlate:
Theplateshallbemadefrommildsteelsheetofatleast1.6mmthickandvitreousenameledwhite,withletters,figuresandthe
conventionalskullandcrossbonesinsignalredcolor(referIS:51978)onthefrontside.Therearsideoftheplateshallalsobe
enameled.

TestsofDangerPlate:
Thefollowingtestsshallbecarriedout:
1. VisualexaminationasperIS:25511982
2. DimensionalcheckasperIS:25511982
3. TestforweatherproofnessasperIS:87091977(oritslatestversion)

ACSRandAACoverheadconductors:
AConferenceonStandardizationofSpecificationsandConstructionPracticesinRuralElectrificationwasheldon4thand5th
January,1971inNewDelhi.BesidestheRuralElectrificationCorporation,representativesofvariousStateElectricityBoards,the
IndianStandardsInstitution(BIS),CentralWater&PowerCommission(CEA),CentralBoardofIrrigationandPowerandmany
otherorganizationsparticipatedinthediscussions.
BasedontheconsensusarrivedattheConference,RECSpecificationNo.1/1971covering7/2.21mm(25mm2aluminumarea)
and7/3.10mm(50mm2aluminumarea)AACforuseonLTlinesand7/2.59mm(30mm2aluminumarea)and7/3.35mm(50mm2
aluminumarea)ACSRforuseon11KVandLTlineswasissued.
Subsequently,theSpecificationwasrevisedtoincorporateanadditionalsizeofACSRviz7/2.11mm(20mm2aluminumarea)for
useon11KVandLTlinesandthenagaintoincorporatethreemoresizesofACSRviz.7/3.35mm(50mm2aluminumarea),
7/4.09mm(80mm2aluminumarea)and6/4.72mm+7/1.57mm(100mm2aluminumarea)foruseon33KVlines.
Thesizesofconductorsstandardizedforlinesofdifferentvoltagesareindicatedbelow:

ACSRConductorfor33KVLines:
1. ACSR7/3.35mm(50mm2aluminumarea)
2. ACSR7/4.09mm(80mm2aluminumarea)
3. ACSR6/4.72mm+7/1.57mm(100mm2aluminumarea)

ACSRConductorfor11KVLines
1. ACSR7/2.11mm(20mm2aluminumarea)
2. ACSR7/2.59mm(30mm2aluminumarea)
3. ACSR7/3.35mm(50mm2aluminumarea)

ACSRConductorforLTLines
1.
2.
3.
4.
5.

ACSR7/2.11mm(20mm2aluminumarea)
ACSR7/2.59mm(30mm2aluminumarea)
ACSR7/3.35mm(50mm2aluminumarea)
AAC7/2.21mm(25mm2aluminumarea)
AAC7/3.10mm(50mm2aluminumsarea)

StandardsforACSRConductor:
IS:398(Pt.I)1976andIS:398(Pt.II)1976.

JointinWires&Conductors:
Allaluminumsconductors:Nojointsshallbepermittedinanywire.
AluminumConductorSteelReinforced:

AluminumWiresforACSRConductor:
Notwojointsshalloccurinthealuminumswiresclosertogetherthan15meters.

SteelWiresforACSRConductor:
NojointsshallbepermittedinsteelwiresusedforACSRofSizes20mm2aluminumsarea(7/2.11mm),30mm2aluminumsarea
(7/2.59mm),50mm2aluminumsarea(7/3.35mm)and80mm2aluminumsarea(7/4.09mm).
InthecaseofACSRof100mm2aluminumsarea(6/4.72mm+7/1.57mm)havingsevengalvanizedsteelwires,joints,in
individualwiresshallbepermittedbutnotwosuchjointsshallbelessthan15metersapartinthecompletesteelcore.

TestsforACSRConductor:
Thesamplesofindividualwiresforthetestsshallnormallybetakenbeforestranding.Themanufacturershallcarryoutteston
samplestakenoutatleastfrom10%ofaluminumswirespoolsand10%ofsteelwirecoils.However,whendesiredbythe
purchaser,thetestsamplemaybetakenfromthestrandedwires.
ThewiresusedforallaluminumsconductorsshallcomplywiththefollowingtestsasperIS:398(Pt.I)1976.
1. Breakingloadtest
2. Wrappingtest
3. Resistancetest
Thewiresusedforaluminumsconductors,steelreinforcedshallcomplywiththefollowingtestsasperIS:398
1.
2.
3.
4.
5.

Breakingloadtest
Ductilitytest
Wrappingtest
Resistancetest
Galvanizingtest

Packing&Marking:(IS:17781980)
Thegrossmassforvariousconductorsshallnotexceedbymorethan10%ofthevaluesgiveninthefollowing

ConductorSizeGrossMassforACSRConductor

(1)AAC
25mm2Al.area(7/2.21mm)500Kg.
50mm2Al.area(7/3.10mm)500Kg.

(2)ACSR
20mm2Al.area(7/2.11mm)1000Kg.
30mm2Al.area(7/2.59mm)1000Kg.
50mm2Al.area(7/3.35mm)1500Kg.
80mm2Al.area(7/4.09mm)1500Kg.
100mm2Al.area(6/4.72mm+7/1.57mm)2000Kg.

ConductorSizeNormalconductorlengthforACSRConductor

1.

AAC
25mm2Al.area(7/2.21mm)1.0Km.
50mm2Al.area(7/3.10mm)1.0Km.

1.

ACSR
20mm2Al.area(7/2.11mm)2.0Km.
30mm2Al.area(7/2.59mm)2.0Km.
50mm2Al.area(7/3.35mm)2.0Km.
80mm2Al.area(7/4.09mm)1.5Km.
100mm2Al.area(6/4.72mm+7/1.57mm)2.0Km.
Longerlengthsshallbeacceptable.
Shortlengths,notlessthan50%ofthestandardlengths,shallbeacceptabletothemaximumextentof10%ofthequantity
ordered.

MarkingforACSRConductor:

Thefollowinginformationshallbemarkedoneachpackage:
1.
2.
3.
4.
5.
6.
7.
8.

Manufacturersname
Trademark,ifany
Drumoridentificationnumber
Sizeofconductor
Numberandlengthsofconductor
Grossmassofthepackage
Netmassofconductor
I.S.Icertificationmark,ifany

PrestressedCementConcretePoles(FOS2.5)For11KV&LTLines:
Aresearchprojectforevolvingeconomicaldesignsofcementconcretepolesforuseon11KVandLTLineswasentrustedtothe
CementResearchInstitute(CRI)ofIndia.
ThebasicdesignparametersforthesepolesasgiveninClause6ofthisSpecificationwereapprovedbytheFifthConferenceon
standardizationofSpecificationsandConstructionPracticesinRuralElectrificationheldinMay,1974.
Someofthesedesignparameterswhichwerebasedoncertainforeigncodes/practicesandcertainotherprovisionsofthis
Specification,althoughatvariancewiththestipulationsofIS:16781960,hadbeenadoptedtoachieveeconomyinthedesigns.
However,thesemodificationshavesincebeenincorporatedintherevisedIS:16781978.
ThisSpecificationcoversPCCpoleswithanoveralllengthof7.5M,8.0Mand9.0Msuitableforuseinoverhead11KVandL.T.
powerlinesanddoublepolestructuresfor11/0.4KVsubstations.

ApplicationStandardforPCCPole:
IS:16781978,Specificationforprestressedconcretepolesforoverheadpower,tractionandtelecommunicationlines.
IS:29051966.Methodsoftestforconcretepolesforoverheadpowerandtelecommunicationlines.
IS:73211974.Codeofpracticeforselection,handlinganderectionofconcretepolesforoverheadpowerandtelecommunication
lines.

AveragePermanentLoadforPCCPole:
Thatfractionoftheworkingloadwhichmaybeconsideredoflongdurationoveraperiodofoneyear.

LoadFactorforPCCPole:
Theratioofultimatetransverseloadtothetransverseloadatfirstcrack.

TransverseforPCCPole:
Thedirectionofthelinebisectingtheanglecontainedbytheconductoratthepole.Inthecaseofastraightrun,thiswillbe
normaltotherunoftheline.

TransverseLoadatFirstCrackforPCCPole:

Fordesign,thetransverseloadatfirstcrackshallbetakenasnotlessthanthevalueoftheworkingload.

WorkingloadforPCCPole:
Themaximumloadinthetransversedirection,thatiseverlikelytooccur,includingthewindpressureonthepole.
Thisloadisassumedtoactatapoint600mmbelowthetopwiththebuttendofthepoleplantedtotherequireddepthas
intendedinthedesign.

UltimateFailureforPCCPole:
Theconditionsexistingwhenthepoleceasestosustainaloadincrementowingtoeithercrushingofconcrete,orsnappingofthe
prestressingtendonorpermanentstretchingofthesteelinanypartofthepole.

UltimateTransverseLoadforPCCPole:
Theloadatwhichfailureoccurs,whenitisappliedatapoint600mmbelowthetopandperpendiculartotheaxisofthepole
alongthetransversedirectionwiththebuttendofthepoleplantedtotherequireddepthasintendedinthedesign.

ApplicationforPCCPole:
7.5Mand8.0MPoles
Thesepolesshallbeusedattangentlocationsfor11KVandL.T.linesinwindpressurezonesof50kg/M2,75Kg/M2and100
Kg/M2inaccordancewithRECConstructionStandardsreferredtointhefollowing:

Polelength:7.5M
11KVlineswithoutearthwireL.T.lines,horizontalformation.
ReferencetoRECConstructionStandards:A4,B5

Polelength:8M
11KVlineswithearthwireL.T.lines,verticalformation.
ReferencetoRECConstructionStandards:A5,B6

9.0MPoles
ThesepolesshallbeusedfordoublepolestructuresofdistributiontransformercentersasperRECConstructionStandardsF1to
F4andforspeciallocationsin11KVandL.T.Lines,suchasroadcrossingsetc.

MaterialsforPCCPole::
(1)Cement
Thecementusedinthemanufactureofprestressedconcretepolesshallbeordinaryorrapidhardeningportlandcement
conformingtoIS:2691976(Specificationforordinaryandlowheatportlandcement)orIS:8041E1978(Specificationforrapid
hardeningportlandcement).
(2)Aggregates
AggregatesusedforthemanufactureofprestressedconcretepolesshallconformtoIS:3831970(Specificationforcoarseand
fineaggregatesfromnaturalsourcesforconcrete).Thenominalmaximumsizeofaggregatesshallinnocaseexceed12mm.
(3)Water
Watershouldbefreefromchlorides,sulphates,othersaltsandorganicmatter.Potablewaterwillbegenerallysuitable.
(4)Admixtures
AdmixturesshouldnotcontainCalciumChlorideorotherchloridesandsaltswhicharelikelytopromotecorrosionofpre
stressingsteel.
(5)PrestressingSteel
Theprestressingsteelwires,includingthoseusedasuntensionedwiresshouldconformtoIS:1785(PartI)1966
(Specificationforplainharddrawnsteelwireforprestressedconcrete.PartIcolddrawnstressrelievedwire),IS:1785(PartII)
1967(Specificationforplainharddrawnsteelwire).,orIS:60031970(Specificationforindentedwireforprestressed
concrete).
ThetypedesignsgiveninAnnexureIareforplainwiresof4mmdiameterwithaguaranteedultimatestrengthof175Kg/mm2.
(6)Theconcretemix:
Itshallbedesignedtotherequirementslaiddownforcontrolledconcrete(alsocalleddesignmixconcrete)inIS:13431980
(Codeofpracticeforprestressedconcrete)andIS:4561978(Codeofpracticeforplainandreinforcedconcrete),subjecttothe
followingspecialconditions;
1.
2.
3.
4.

Minimumworkscubestrengthat28daysshouldbeatleast420Kg/cm2.
Theconcretestrengthattransfershouldbeatleast210Kg/cm2.
Themixshouldcontainatleast380Kg.ofcementpercubicmeterofconcrete.
Themixshouldcontainaslowawatercontentasisconsistentwithadequateworkability.Ifitbecomesnecessarytoaddwaterto
increasetheworkability,thecementcontentalsoshouldberaisedinsuchawaythattheoriginalvalueofwatercementratiois
maintained.

DesignRequirementsforPCCPole::
Thepolesshallbeplanteddirectlyinthegroundwithaplantingdepthof1.5meters.
Theworkingloadonthepolesshouldcorrespondtothosethatarelikelytocomeonthepoleduringtheirservicelife.Designs
giveninAnnexureIarefor140Kg.and200Kg.Appliedat0.6Mfromtop.
Thefactorofsafetyforallthesepolesshallnotbelessthan2.5.
Theaveragepermanentloadshouldbe40%oftheworkingload.
TheF.O.S.againstfirstcrackloadshallbe1.0.
Ataveragepermanentload,permissibletensilestressinconcreteshallbe30Kg/cm2.
Atthedesignvalueoffirstcrackload,themodulusofruptureshallnotexceed55.2kg/cm2forM420concrete.
Theultimatemomentcapacityinthelongitudinaldirectionshouldbeatleastonefourthofthatinthetransversedirection.
Themaximumcompressivestressinconcreteatthetimeoftransferofprestressshouldnotexceed0.8timesthecubestrength.
Theconcretestrengthattransfershallnotbelessthanhalfthe28daysstrengthensuredinthedesign,i.e.420x0.5=210Kg/cm2.
Formodelcheckcalculationsonthedesignofpoles,referredtoinAnnexureI,areferencemaybemadetotheRECManualon
ManufacturingofsolidPCC

DimensionsandReinforcementsforPCCPole:
ThecrosssectionaldimensionsandthedetailsofprestressingwireshouldconformtotheparticularsgiveninAnnexureI.
TheprovisionsofholesforfixingcrossarmsandotherfixturesshouldconformtotheRECstandardsreferredtoinclause4of
thisspecificationandinaccordancewiththeconstructionpracticesadoptedbytheStateElectricityBoards.

ManufactureforPCCPole::
Allprestressingwiresandreinforcementsshallbeaccuratelyfixedasshowninthedrawingsandmaintainedinpositionduring
manufacture.Theuntensionedreinforcement,asindicatedinthedrawings,shouldbeheldinpositionbytheuseofstirrups
whichshouldgoroundallthewires.
Allwiresshallbeaccuratelystretchedwithuniformprestressineachwire.
Eachwireorgroupofwiresshallbeanchoredpositivelyduringcasting.Careshallbetakentoseethattheanchoragesdonot
yieldbeforetheconcreteattainsthenecessarystrength.

CoverforPCCPole:
Thecoverofconcretemeasuredfromtheoutsideoftheprestressingtendonshallbenormally20mm.

Welding&LappingofSteelforPCCPole:
Thehightensilesteelwireshallbecontinuousovertheentirelengthofthetendon.
Weldingshallnotbeallowedinanycase.However,jointingorcouplingmaybepermittedprovidedthestrengthofthejointor
couplingisnotlessthanthestrengthofeachindividualwire.

CompactingforPCCPole:
Concreteshallbecompactedbyspinning,vibrating,shockingorothersuitablemechanicalmeans.Handcompactionshallnotbe
permitted.

CuringforPCCPole:
Theconcreteshallbecoveredwithalayerofsacking,canvas,hessianorsimilarabsorbentmaterialandkeptconstantlywetupto
thetimewhenthestrengthofconcreteisatleastequaltotheminimumstrengthofconcreteattransferofprestress.Thereafter,
thepolemayberemovedfromthemouldandwateredatintervalstopreventsurfacecrackingoftheunit,theintervalshould
dependontheatmospherichumidityandtemperature.

TheprestressingwiresforPCCPole:
Itshallbedetensionedonlyaftertheconcretehasattainedthespecifiedstrengthattransfer(i.e.210Kg/cm2).Thecubescastfor
thepurposeofdeterminingthestrengthattransfershouldbecured,asfaraspossible,underconditionssimilartothoseunder
whichthepolesarecured.
Thetransferstageshallbedeterminedbasedonthedailytestscarriedoutonconcretecubestillthespecifiedstrengthindicated
aboveisreached.ThereafterthetestonconcreteshallbecarriedoutasdetailedinIS:13431960(Codeofpracticeforpre

stressedconcrete).
Themanufacturershallsupplywhenrequiredbythepurchaserorhisrepresentative,resultofcompressivetestconductedin
accordancewithIS:4561964(Codeofpracticeforplainandreinforcedconcrete)onconcretecubesmadefromtheconcrete
usedforthepoles.
Ifthepurchasersodesires,themanufacturershallsupplycubesfortestpurposesandsuchcubesshallbetestedinaccordance
withIS:4561964(Codeofpracticeforplainandreinforcedconcrete).
Thedetensioningshallbedonebyslowlyreleasingthewires,withoutimpartingshockorsuddenloadtothepoles.Therateof
detensioningmaybecontrolledbyanysuitablemeanseithermechanical(screwtype)orhydraulic.
Thepolesshallnotbedetensionedorreleasedbycuttingtheprestressingwiresusingflamesorbarcropperswhilethewiresare
stillundertension.

SeparateeyehooksorholesforPCCPole:
Itshallbeprovidedforhandlingandtransport,oneeachatadistanceof0.15timestheoveralllength,fromeitherendofthepole.
Eyehooks,ifprovided,shouldbeproperlyanchoredandshouldbeonthefacethathastheshorterdimensionofthecross
section.Holes,ifprovidedforliftingpurposes,shouldbeperpendiculartothebroadfaceofthepole.
Stackingshouldbedoneinsuchamannerthatthebroadsideofthepoleisvertical.Eachtierinthestackshouldbesupportedon
timbersleeperslocatedat0.15timestheoveralllength,measuredfromtheend.Thetimbersupportsinthestackshouldbe
alignedinaverticalline.
Polesshouldbetransportedwiththeirbroadfacesplacedverticallyandinsuchamannerthatshocksareavoided.Supports
shouldbesoarrangedthattheyarelocatedapprox.atadistanceequalto0.15timestheoveralllengthfromtheends.
Theerectionofthepoleshouldbecarriedoutinsuchawaythattheerectionloadsareappliedsoastocausemomentwith
respecttothemajoraxis.i.e.theropeusedforhoistingthepoleshouldbeparalleltothebroaderfaceofthepole.

TestingofPCCPole:
TransverseStrengthTest
PolesmadefromordinaryPortlandcementshallbetestedonlyonthecompletionof28daysandpolesmadefromrapid
hardeningcementonlyonthecompletionof14days,afterthedayofmanufacture.
Thepolemaybetestedineitherhorizontalorverticalposition.Iftestedinhorizontalposition,provisionsshallbemadeto
compensatefortheoverhangingweightofthepole,forthispurposetheoverhangingportionofthepolemaybesupportedona
movabletrolleyorsimilardevice.
Thepoleshallberigidlysupportedatthebuttendforadistanceequaltotheagreeddepthofplantingi.e.1.5M.
Loadshallbeappliedatapoint600mmfromthetopofthepoleandshallbesteadilyandgraduallyincreasedtodesignvalueof
thetransverseloadatfirstcrack.Thedeflectionatthisloadshallbemeasured.
Aprestressedconcretepoleshallbedeemednottohavepassedthetestifvisiblecracksappearatastagepriortotheapplication
ofthedesigntransverseloadforthefirstcrack.
Theloadshallthenbereducedtozeroandincreasedgraduallytoaloadequaltothefirstcrackloadplus10%oftheminimum
ultimatetransverseload,andheldupfor2minutes.
Thisprocedureshallberepeateduntiltheloadreachesthevalueof80percentoftheminimumultimatetransverseloadand
thereafterincreasedby5percentoftheminimumultimatetransverseloaduntilfailureoccurs.Eachtimetheloadisapplied,it
shallbeheldfor2minutes.
TheloadappliedtoprestressedconcretepoleatthepointoffailureshallbemeasuredtothenearestfiveKilograms.
Thepoleshallbedeemednottohavepassedthetestiftheobservedultimatetransverseloadislessthanthedesignultimate
transverseload.

MeasurementofPoleCoverforPCCPole:
Aftercompletionofthetransversestrengthtest,thesamplepoleshallbetakenandcheckedforcover.
Thecoverofthepoleshallbemeasuredat3points,onewithin1.8metersfromthebuttendofthepole,thesecondwithin0.6
meterfromthetopandthethirdatanintermediatepointandthemeanvaluecomparedwiththespecifiedvalue.

Themeanvalueofthemeasuredcovershouldnotdifferbymorethan()1mmfromthespecifiedcover.Theindividualvalues
shouldnotdifferbymorethan()3mmfromspecifiedvalue.
Iftheserequirementsarenotmet,theworkmanshipwithreferencetoaligningoftheendplatesandprestressingwiresand
assemblyofmouldsshouldbeimprovedandinspectionatpreproductionstagetightenedsuitably.

MarkingforPCCPole:
Thepoleshallbeclearlyandindeliblymarkedwiththefollowingparticularseitherduringoraftermanufacturebutbefore
testingatapositionsoastobeeasilyreadaftererectioninposition.
1. Monthandyearofmanufacture
2. TransversestrengthofpoleinKg.
3. MakersserialNo.andmark

MainPointsshouldbelookafterforOverheadLineInstallation:
Overheadlines:
ThegeneralprecautionsduringstorageandhandlingofshallbetakeninaccordancewithrelevantIScode.
Whilelayingtheconductorshallbetakenfromtopofthedrumandtherepeatedinthedirectionofarrowonit..Careshallbe
takentoavoidcontactwithsteelworks,fence,etcbygivingsoftwoodprotection,usingwoodenrollers.
Propertoolsshallbeusedduringstringingwork.Duringstringingoperationstandardsagtableorchartshallbefollowedand
careshallbetakentoensurethattherearenokinksintheconductor.Jointsinconductorsshallbestaggered.Midspanjointsin
conductorsshallbeavoided.
Afterstringingtheconductor,itshallbeclampedpermanentlywithshackleorstrainclamps.Anangleorsectionshallbe
selectedwhilepullingupconductors.

Jumpers:
Whilestringing,sufficientlengthshallofconductorsbekeptatshackleterminationsformakingjumpers.Jumpersshallbeneat
andasfaraspossiblesymmetricaltorunofconductors.Theseshallbemadetopreventoccurrenceoffaultsduetowindorbirds.
PGclampsmaybepreferredtobindingofconductorsatjumperlocationorservicetaps.

CrossArms:
ThecrossarmsshallbemadeofMSStructuralsteel.Thelengthofcrossarmsshallbesuitableforaccommodatingthenumberof
insulatorsonthemwithspacingofconductor.Agapofminimum50mmshallbeleftfromthecenterofpinholetoendofcross
armoneitherside.ThecrossarmshallbecompletewithpoleclampmadeofMSflatofsizenotlessthan50x6mmwith
necessarynuts,bolts,washers,etc.Thelengthofcrossarmforcarryingguardwiresshallalwaysrunnotlessthan300mm
beyondoutermostbareconductorofconfiguration.
Crossarmsshallbeproperlyclampedtothesupporttakingintoconsiderationtheorientationoflines.

Porcelaininsulatorsandfittings:
TheporcelaininsulatorsshallbeconfirmingtoIS7311971foroverheadlines.Thisshallbeglazed,crack/burrfree.
Theinsulatorshallhaveadequatemechanicalstrength,highdegreeofresistancetoelectricalpunctureandresistancetoclimatic
andatmosphericattack.

Allironpartsshallbehotdipgalvanized&alljointsshallbeairtight.Pininsulators/shackleinsulators/discinsulatorsshallbe
erectedoncrossarmsandDironclampshallbeusedorasspecifiedbyEngineerincharge.Shackleinsulatorsshallbeusedin
conjunctionwithDironclampswhenconfigurationofconductorisvertical.
Theseshallalsobeerectedoncrossarmatintermediatesupportincaseoflonglines,deviationfromstraightlines.Careshallbe
takenthatinsulatorsarenotdamagedduringerection.

Bindingmaterial:
Bindingofconductorwiththeinsulatorshallbedonewithsoftaluminumwire/conductor.Thebindingofconductorto
insulatorshallbesufficientlyfirmandtighttoensurethatnointermittentcontactdevelops.Theendofbindingwireshallbe
tightlytwistedinclosespacedspiralaroundtheconductortoensuregoodelectricalcontactandstrengthentheconductor.

Supportsandspacingofpoles:
Supportofoverheadlineshallbeofadequatestrengthconfirminginallrespectstorules76ofIndianelectricityrules.
Polespacingandclearancebetweenlowestconductorabovethegroundlevelacross/alongthestreetshallbeinaccordancewith
rule85ofIndianelectricityrules.Suitablefoundationshallbeprovidedforerectionofpoles.
Thefoundationshallincludeexcavationinalltypesofsoilandrocksandbackfilling,RCC,reinforcement,formwork.
Excavationforfoundationsforpoles/stay/strut:Afterthelocationofsupports/stayarepeggedaccurately,theexcavation
workshallbetakenupandcareshouldbetakenwhileexcavatingthatpitsarenotoversized.
Thepitshouldbeexcavatedinthedirectionoftheline.Thedepthandsizeofpitshallbesuchthatnormally1/6thofthelengthof
poleisburiedinthegroundandsuitableforfoundationofsupport.
Forstaythepositionofpitshallnormallybesuchstaymakesaslargeanangleaspossiblewiththesupportanditshallbeinthe
rangeof40to60degrees.
Thelengthofstayrodshallproject450mmabovethegroundlevel.Thepitforstrutshallbelocatedatadistancenotlessthan
1.8Mfromthepole.
Thedepthofpitshallbesuchthatatleast1.2Mofthestrutisburiedintheground.

Stay/strut:
Staysetshallconsistofstayrod,anchorplate,bowtightened/turnbuckle,thimbles,staywireandstaininsulators.
Thestayrodshallbewithstaygripincaseofturnbuckleisusedinsteadofbowtightened.Theentirestaysetassemblyshallbe
galvanized.Thestaywireshallbeeither7/4.0mmdiameteror7/3.15mmdiameterGIhavingtensilestrengthofnotlessthan70
kgf/sqmmandconfirmingtoIS2141.T
TheanchorplateshallbeofMSgalvanizedandnotlessthan300mmx300mmx6.4mmthick.Thestayrod/bucklerodsshall
beminimum16/19mmdiametergalvanizedsteelrodhavingtensilestrengthnotlessthan42kgf/sqmm.Minimumlengthof
stayrodandbuckleshallbe1800mmand450mmrespectively.

Erectionstaysets:
TheanchorplateshallbegalvanizedMSplate.Thestayrodwithanchorplateshallbeembeddedincementconcrete1:3:6.Astay
shallbeprovidedatallangleandterminalpoles.Doublestayshallbeprovidedatalldeadendsandinsuchcase,theseshallbe
asfaraspossibletobesetparalleltoeachother.

Cageguard:
Allmetalsupportsofoverheadlinesandmetallicfittingattachedshallbepermanentlyandeffectivelyearthed.Cageguard/
cradleguardshallbemadeof6SWGGIwireconfirmingtoIS2633includingnetting,stretchingandjointingofcageandlacing
by10/12SWGGIwire,bindingby14/16SWGGIwire.

Dangerboards:
AllsupportscarryingHVlinesshallbefittedwithdangerplatesconfirmingtoIS2551atheightof3Mfromgroundindicating
thevoltageofline.ThescriptshallbebothinEnglish/Hindi.

Anticlimbingdevices:
NecessaryarrangementforpreventingunauthorizedpersonsfromascendinganyofthesupportsandstructurecarryingHV
lineswithouttheaidofladderorspecialapplianceshallbemade.
UnlessotherwisespecifiedbarbedwireconfirmingtoIS278havingfourpointsbarbedspaced75+/12mmapartshallbe
wrappedhelicallywithapitchof75mmaroundthelimbofsupportandfirmlycommencingfromtheheightof3.5Mandupto
5or6Masdirectedbytheengineer.

Lightningarrestor:
LightningarrestorsuitableforHTlinesshallbeinstalledoneunitperphaseatterminations,transformerstations,etc.
Thedevicesshallbeconnectedaheadoffuseprovidedifany.IndependentearthelectrodeshallbeprovidedforLA.
TheearthleadfromearthelectrodetoLAshallbecontinuous.TheLAshallconfirmtoIS3070andshallbenonlinear
distributionclass.
TheLAshallbenonlineartype,distributionclass,outdoortypesuitableforeffectivelyearthedsystem.TheLAshallconsistof
lineterminalstud,earthterminalstud,numberofsparkgapsinserieswithnonlinearresistor,thewholeassemblyhousedinside
ahermeticallysealedporcelainbushing.
Neoprenerubbergasketshallbeprovidedbetweenmetalcapsandporcelainbushing.Nonlinearresistorshallbesiliconcarbide
blocksmetalizedatbothendstoensuregoodelectricalcontactbetweenterminals,nonlinearresistor&sparkgaps.
MountingbracketshallbehotdipgalvanizedsuitableformountingLAonstructure.

CableLayingDirectinGround:
Themethodshallbeadoptedwherethecablerouteisthroughopencountry,alongroad/lanes,etcandwherenofrequent
excavationsareencounteredandreexcavationispossiblewithoutaffectingotherwork.

Widthoftrenches:
Thewidthoftrenchforlayingsinglecableshallbe35cmWheremorethanonecablearetobelaidinthesametrenchin
horizontalformation,widthoftrenchshallbeincreasedsuchthattheinteraxialspacingbetweenthecablesfor415voltsshallbe
20cmandfor11shallbe35cm.

Depthoftrenches:
Wherecablesarelaidinsingleformation,thetotaldepthoftrenchshallnotbelessthan75cmforcableupto1.1KVgradeand
shallnotbelessthan120cmforcableabove1.1KVgrade.Wherevermorethanonetierformationisunavoidableandvertical
formationisadopted,thedepthoftrenchshallbeincreasedby30cmforeachadditionaltiertobeformed.

Protectivecovering:
Cablelaidintrenchesshallhavecoveringofcleandrysandnotlessthan170mmabovethebasecushionofsandbeforethe
protectivecoverislaid.
ThecablesshallbeprotectedbyBclass/secondclassbrickofnotlessthan20cmx10cmx10cmorprotectivecoverplacedon
topofthesandandbothsidesofcableforfulllengthofthecabletothesatisfactionofEngineerincharge.

Backfilling:
Thetrenchesshallbebackfilledwitexcavatedearthfreefromstonesorotherscrapedgeddebrisandshallberammedand
watered,ifnecessary,insuccessivelayersnotexceeding300mmunlessotherwisespecified.

Routemarker:
RoutemarkershallbeprovidedalongstraightrunsofcablesandatpointsofchangeindirectionasapprovedbyEngineerin
chargeandingeneralatintervalsnotexceeding100metersinstraightrun.Routemarkershallbemadeoutof100mmx100mm
x5mmGI/Alplateboltedorweldedon35mmx35mmx6mmMSangleironof600mmlong.
Suchroutemarkersshallbemountedandgroutedparalleltoand0.5meterawayfromthesideoftrench.Theworkcablewith
voltagegradingandsizeofcableshallbeinscribedonthemarker.

(https://electricalnotes.files.wordpress.com/2011/06/crossarm.png)

(https://electricalnotes.files.wordpress.com/2011/06/1.png)

(https://electricalnotes.files.wordpress.com/2011/06/2.png)

(https://electricalnotes.files.wordpress.com/2011/06/3.png)

(https://electricalnotes.files.wordpress.com/2011/06/guystrain.png)

(https://electricalnotes.files.wordpress.com/2011/06/guyset.png)

(https://electricalnotes.files.wordpress.com/2011/06/crimpedtension.png)

(https://electricalnotes.files.wordpress.com/2011/06/straininsulator.png)

(https://electricalnotes.files.wordpress.com/2011/06/pipeearthing.png)

(https://electricalnotes.files.wordpress.com/2011/06/pinins.png)

(https://electricalnotes.files.wordpress.com/2011/06/insulatorpin.png)

(https://electricalnotes.files.wordpress.com/2011/06/dangerboard.png)

(https://electricalnotes.files.wordpress.com/2011/06/dangerboard11kv.png)
About these ads (https://wordpress.com/about-these-ads/)

FILEDUNDERUNCATEGORIZED
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

101Responsesto11KV/415VOverheadLineSpecification(REC)

ShonaBalajisays:
June14,2011at6:17am
excellent
Reply
Eng.Asadsays:
March25,2013at8:36am
Distancebetweentowpolesof20KVoverheadline.
Reply
karthiksays:
September2,2011at11:52am
awesomesir.itshighlyusefulforeveryelectricalengineer
Reply
kennyjamessiamesays:
September19,2011at9:41pm
Hi,pleasesendmetheqoutefortheDROPOUTFUSELINKASSEMBLYCOMPLETE,11KV.
GivemepricesbothFOBandCIFZambiafor300pieces.
Iwaittohearfromyou.
ithankyouinanticipation.
Regards
Kenny.
JSKCoLTD
Reply
VinayGhadesays:
August6,2014at8:08pm
DearSir,
imVinayGhadeBEelectricalengineerhavingaround7yearsexperienceindesigningfield.iwanttogomuchdeeperinthis
field.Anydesigncourseyouofferoranybooksthatistoberefer.
Reply
dillipkumargarnayaksays:
September14,2014at6:49pm
good
Reply
vikassays:
October3,2011at4:09pm
WhatshouldbetheminimumspacingbetweenLToverheadconductors?IsthereanyISorIEruleforthis.
Reply
Jignesh.Parmarsays:
October6,2011at10:39am
YesInbothHorizontalcongu.andforVerticalconfug.200mmforverticalconfu.and300mmforhorizontalconfuforPP
thisisindicateinCPWDnoms.PleasereadmyAbstractnotes.Youwillfindit.
Reply
vikassays:
October4,2011at2:31pm
IsthereanyISorIErulespecifyingthespacingbetweentwoconductorsof415Voverheadline.
Reply
Jignesh.Parmarsays:
October6,2011at10:38am
YesInbothHorizontalcongu.andforVerticalconfug.200mmforverticalconfu.and300mmforhorizontalconfuforPP
thisisindicateinCPWDnoms.PleasereadmyAbstractnotes.Youwillfindit.
Reply
AnujBhatnagarsays:
October20,2011at8:45am
HiJignesh,

CanyoupleasesendmethedrawingandspecificationofDeadEndClampandSuspensionClamp.
Thanks,
Anuj
email:
Reply
M.VENKATARAOsays:
November20,2011at9:52am
Dearsir
whatistheminiumdistancefrompoletopolein11kvoverheadtransmissionline?
Reply
Jignesh.Parmarsays:
November27,2011at3:53pm
MinimumDistance???StartfromZeroNormally25Meterto60Meteraccordingtogeographiccondition,Typeof
Conductor,TypeofPole..
Reply
VASIMSHAIKHsays:
November22,2011at5:09am
canuplzgivemecompletedetailsoferection.Rightfrompolepitdimensiontostringing.Lookingforapositivereply.thanks
Reply
satheeshsays:
December1,2011at6:02am
HelloSir
howtocalculatetheDropoutFuseratingfor100KVAtransformer.andformulas..plstellme
Reply
paulsonsays:
December6,2011at10:51am
howcanweterminatea630KVAtransformerysecondarysidetoLToverheadline.4x400sq.mmcableisrequired.isthereDP
structurerequiredoranyothersolution?
Reply
deepeshsahusays:
January12,2012at5:43pm
itiscompulsorytousetrinangularconfigurationin11kvpole?
canweuserectangularconfiguration?
sirplesereply
Reply
M.SATYANARAYANAREDDYsays:
January14,2012at2:19am
itiscompulsarytomaintainthe90deg(Straight)anglewhen33kvlinecrossingtheroad,anyalternativestoroadcrossingwith
above90deg(cross)
Reply
vijaysays:
February1,2012at11:18pm
mystationswitchyardthatis11/415vlightingarrestorwhichisaheadofhgfusesetisalwaysbusting.andmyswitchyardis
under33KVline.pleasehelpmeoutwhythiswashappening
Reply
Pradipsays:
February4,2012at9:39am
iwanttocalculationofillumenationofstreetlightscheme3kilometerroadlength,wide15mtr.poletopoledistance30mtr.
totalno.ofpoles.100nospolerequire.divder(soassumedoublefittimg.,poleheight9mtr.)&howtocalulatevoltagedrop
,cableselections.
Reply
A.ALMOHAMADEDsays:

February12,2012at5:41pm
caniknowthemax.loadof11kvfeeder.andthelong
Reply
Jignesh.Parmarsays:
February13,2012at2:24pm
Dependson:
(1)ConductorSize(Amp)
(2)Lengthofline
(3)PermissibleVoltageDrop
(4)TypeofLoad
Reply
k.karthicksays:
February28,2012at11:42am
wonderfulsir,
Reply
Paragsays:
April6,2012at8:06am
Pleaseprovideustotaldetails&drawingsforvcrossarms,straightcrossarms&others.
Thanks,
Reply
MuhammadFarooqKhansays:
June7,2012at4:50pm
Hi,
Iwanttocalculatetheconductorsizeof38km11kvOHL.mytotalloadisgiveninA(KVA)whichis21000KVA.
Pleasehelpmeout.suggestmeaformulaandsizeofconductor.
Reply
Jignesh.Parmarsays:
June8,2012at5:03pm
Calculate%RegulationfromexcelsheetgiveninExceltools
Reply
MuhammadFarooqKhansays:
June9,2012at5:15am
thereisnosuchtooltocalculatetheConductorsizeforOVERHEADLINECONDUCTOR.
didACSR7/3.40mmcanbeartheabovegivenload?forcaseof11kv
Reply
RollyMondelosays:
June18,2012at12:17pm
Dearsir
whatistheminimumhorizontalandverticaldistancefromstreetlightpoleina32KVoverheadtransmissionline?
Reply
RollyMondelosays:
June18,2012at1:08pm
sir,alsosendmethestandardhorizontalandverticalclearanceinanyhighvoltagetransmissionline.thankyouandmore
power!
Reply
M.Viswanathansays:
June22,2012at12:03pm
DearSir,
Irequiredthestructuralfoundationdetailsforthefollowing;
1)DPstructurefor11kVlinewith250kVAtransformermountedsingleincomercumoutgoing.
2)and11kVEBpost(RCC)
Reply
sanusays:

August21,2012at8:22am
respectedsir,
canupleasetellmefromwhereicangetrecconstructionmanual.andwhichpublisherispublishingthatbook.igraetlyneedthat
book.thanks
Reply
EhsanUllahsays:
September1,2012at4:30am
Dearsir,
pleasetellmethedepthof11kvapole.
Reply
Jignesh.Parmarsays:
September2,2012at3:31am
11KVA!!
Reply
SharadTaidesays:
September21,2012at4:18pm
Canupleasetellmethesafesthorizontalandverticaldistancefromthesteelshed.heightofsteelshedis6m&8M
Reply
faucetsays:
November1,2012at7:38pm
Itsinrealityagreatandusefulpieceofinfo.Iamsatisfiedthatyousharedthishelpfulinformationwithus.Pleasekeepus
informedlikethis.Thanksforsharing.
Reply
M.VENKATARAOsays:
November2,2012at7:07am
SirifphasesequencechangesinHTsideoftransformerthenL.Tsidephasesequencechangesornot?
Reply
danielsays:
November7,2012at11:38pm
canihvthediagramorpictureofcradleguard?
Reply
wamidhtahasays:
November10,2012at11:37am
DearSirineedplease(Electricalpole,span,sag,calculationinexcelsheet)
ifyoucansendittomymail
thankyouforeward
Reply
srinivassays:
January9,2013at1:01pm
Dearsir,
pleaseinformationElectricalpole,span,sag,calculationinexcelsheet)electricalinstallationestimating&costing.
Thankyou,
Regards,
srinivasulu.R
Reply
wamidhtahasays:
January12,2013at10:47am
DearSirs;
areyoucanthisexelsheetfor(Electricalpole,span,sag,calculation)
inecessaryneedit
iwaityourreplayinmymail
thankyouforwardforyourattention
eng.wamidh/iraq
Reply
Jignesh.Parmarsays:

January12,2013at2:24pm
Dearwamidhtaha,
IhavenotsuchtypeofExcelSheet..
MarathiLekh!arathiKavita,!arathivinodsays:
January31,2013at1:06pm
Magnificentitemsfromyou,man.Ivebeawareyourstuffpriortoandyouaresimplyextremelyfantastic.Iactuallylikewhat
youhaveboughthere,certainlylikewhatyouarestatingandthewaybywhichyouassertit.Youremakingitenjoyableandyou
continuetocarefortostayitsmart.Icantwaittolearnmuchmorefromyou.Thatisactuallyawonderfulwebsite.
Reply
ChetanBhavsarsays:
March23,2013at7:43am
reallygreatgreatinfohelpedinmyprojectthanksalot..!!!!!!!!!!!
Reply
Yogeshsays:
April8,2013at10:12am
DearAll,
Inourproject,sendingendvoltageisaround400Voltsandreceivingendvoltageis360Vfor150MetersOHline.Hereweare
getting40Vdropforaverysmalldistance.Letmeknowthereasonforthisvoltagedrop.
Reply
Jignesh.Parmarsays:
April9,2013at6:07am
Yourquestionhasinsufficientinformation.
1.whatisload.(1w..100w.)
2.whichsizeofoverheadconductorhaveyouused.
Reply
maheshsays:
April24,2013at11:58am
hi,
disismahesh
myquestion:ifiwanttoundergroundacablewhichisalreadyoverheadedfromthestreetpoletothetransformerofrating
250kva,whichsqmmcableihavetouse?
Reply
Jignesh.Parmarsays:
April25,2013at4:16pm
NotgettingyourPoint???
Reply
ErGSinghsays:
May5,2013at3:26am
HelloJignesh,
Reallyusefulstuff,canwestartathreaaboutearthingofUGcables?
Reply
Jignesh.Parmarsays:
May5,2013at4:25am
AlreadygiveintheBlogsearchinoldposts
Reply
AFsays:
May19,2013at9:15am
Indeedveryinformative.
Aquestion:
Ihaveseenthatthethehorizontaldistancebetweenthe3phases(conductors)of11kVOHlineisnotsame;2phasesare
relativelycloser,ascomparedtothe3rdone.Doesanybodyknowthereason?
Reply
Jignesh.Parmarsays:
May19,2013at10:37am

Where??Horizontaldistanceshouldbesameinthreephasedistribution..
Reply
NIKUNJCHAUHANsays:
May25,2013at4:42am
RESPECTEDSIR,
IFYOUHAVENOTESOREXCELTOOLABOUTCALCULATIONOFLOADFLOWANALYSISTHENPLEASEUPLOADIT.
THANKYOU.
Reply
HRArunsays:
June11,2013at9:45am
PleaseprovidethesctionaldrawingsofRCC8.0Mtrpole,RCC9.0Mtrpole,PSC9.0Mtrpole
Reply
Rafiqsays:
June22,2013at11:35am
HI,
Howmanytransformerscanbeinstalledin11/0.4KVpackageSUBSTATION/?
ThankYou
Reply
dillipkumargarnayaksays:
September14,2014at7:02pm
HI,
Howmanytransformerscanbeinstalledin11/0.4KVpackageSUBSTATIONandalltransformercalculation
Reply
Rameshsays:
June27,2013at6:40am
sir,pleasesendmemaintenancescheduledoublepoleisolationunit
Reply
Rajasays:
July20,2013at7:25pm
Really,greatusetome
Reply
PrabakaranBalaramansays:
July25,2013at5:59pm
sir,plzsayabouttheclearancedistancebetweenthepoletopoleandalsodistancebetweengroundsurfacetoconductor
Reply
BHAGWANSURYAWANSHIsays:
August8,2013at10:03pm
TanksforgivingthatmuchinformationIamveryhappytoreadthiscanigetmuchmoreinformationfromyou
Reply
SarojaRanjanPattanayaksays:
August14,2013at10:13pm
DearSir,
A11KVsubstationisinstalledontheroadatadistanceof5ftfrommyresidentialhouseand3feetfrommyboundarywall.
RequestyoutomentiontheminimumdistancethatistobemaintainedduringHVsubstationinstallations
Reply
jollybhatiasays:
August16,2013at7:06am
Hi
Canutellmewhatshouldbethemaximumcurrentwhichwecangetonltsideon11kvlineandwhatshouldbetherattingof
thetransformer..
Reply
s.alisays:
September21,2013at6:58am

timetotimeicollectinformationrelatedtomyjobwhichstandsveryhelpfulforme,thanks,thistimeiwantinformation
regardingcalculationofsagin11kvtransmissionlineiamdiplomaengineerinelectricalengineeringbyqualificationwith
experience.
Reply
vinodsays:
October22,2013at8:56am
WhethericangetcompleteBillofMaterialfor11KVswitchyardand11KVoverheadtransmissionline
Reply
M.Y.DESAIsays:
October29,2013at9:33am
Hi,
Sir.
wheather415vmultistrandedwithinsulationaluminumconductorsforoverheadlindavailableinmarket,ifyespl.senddetails.
Thanks.
Reply
utkalmishrasays:
November23,2013at7:25pm
respectedsir
sirpleasetellmewhattypeofproblemwilloccurifwellbindingaconductorwithinsulatorbyAACinltline?
regards
er.UTKALMISHRA
Reply
BadshahMohideensays:
December5,2013at5:08am
HiMr.Jignesh,
Congratulateforthewebsiteandyourexcellenteffort.Ihaveadoubt,WhetherthejumperscanbeusedasaIsolationpoint
duringoutagesof11KV&33KVOHLlinesi.e.toisolatesectionofOHL,thejumperscanremovedandusedasisolationpoints.
Reply
ankushsays:
December28,2013at6:08pm
thanks
Reply
AshokKr.Thakursays:
December30,2013at3:01pm
HelloMr.Jignesh,Cudukindlyletmeknowtheweightof6swgGIwirethatisrqdforcageguardof11kvOHL?
Reply
STEWARTMAWANAsays:
March27,2014at10:19am
HyMrJignesh,cldyouplizkindlyassistonhwcanIcalculatecablesizewhenwiringa600VA
TXwhichdraws75Aatasupplyof0240230180and100anditsoutputis24Vac
Reply
REHAANHASSANsays:
April12,2014at7:30pm
Inruralareaandpopulationdensityishighandlocalityfullwithbamboosandlargetreesinmagrahatofsouth24parganasof
westbengal.Atthesetypeofplaceswhatisthedistancebetweentwopolesforwringof440saidlinesandalsofor220saidlines
assuggestedanddirectedbygovernment.Andwhatmeasuresshouldbetaken.
Reply
angelitocortezsays:
June20,2014at8:39pm
Gooddaysir,pleasecansendmethedistanceoftransmissiontower33kVwithwiresize366.2mmsquareandwhatisthe
requiredheightoftoweruseinopenareainwellsite(oilandgascompany)
Reply
MarioEnriquezsays:
June23,2014at4:00pm

Mr.Jignesh,
Currently,12KValuminumwiresrunoverawaterway290feet,poletopole.Howmuchwiresagistherebetweenthepoles,
assumingwireshavebeeninstalledtostandardspecificationsfor12KVdistribution?Whatreductioninwiresagcanbeexpected
ifthespanisreducedto220feet?(Thanksforyourimpressivesite.)
Reply
sunilmanesays:
August24,2014at5:15pm
Iwanttoknow
11kvconductorstypesandtheircurrentcapacity.pl.
Reply
dillipkumargarnayaksays:
September14,2014at6:51pm
11kvacabulemeserment
Reply
Venusays:
August25,2014at6:11am
HiJIGNESHineedallcomponentlist(smallcomponentsalsolikefuse)ofdistributionsystemfrom11kvto240vpleasegivemea
list
Reply
angelitocortezsays:
August29,2014at8:40am
Imsogladtothankyouitsagreatgreatinformationcanigetmoreinformationfromyou.Godblessyoualways.mayiknow
thedropvoltageofdifferentsizeofcableineverymeter.andwhatistherequiredsizeofcableiuseforeveryKva
Reply
shrikrishnadubeysays:
August31,2014at9:23am
sirwhyweareusing9kvLAin11kvsystem?
Reply
Hidayatsays:
September4,2014at7:03pm
whatisC&DFtest.whatisdissipationfactor
Reply
DBDandapatsays:
September9,2014at11:44am
(i)Ihave11KVO/Hdistributionlineabout1.7KM(only)andeachindividualpolesareearthedwithEarthspikes(Earth
resistanceofeachloactionislessthan5Ohm).ButInspectorisinsistingustoprovidecontiniousearthingforthesaidO/Hlineas
perIErules.IcouldnottracedthesamefromIErulebook.Expectingyourreplyandpossiblehelp.
(ii)Wheredumpersarebeingoperated,whatwillbethegroundclearance(min)for11KVO/Hline
Reply
imprasad79says:
September12,2014at6:32am
(1)Continuousearthwireofpropersizewhichissolidlyearthedatsubstationistorunallalongtherouteofoverheadline.For
reasonofsafetyaftereveryfifthspan,thepoleistobeprovidedwiththeearthfromtheground.Thiswireissolidlyconnectedto
theearthprovidedatthesubstationandlateroneverysixthpoleisearthed.Galvanizedironwireof8SWGorbiggersizeisused
asearthingconductor.Themaximumcontinuityresistanceofearthshouldnotbemorethan5Ohms.
(11)Minimumclearanceofconductorabovegroundwhilecrossingtheroadorapublicthroughfarefor11KVis6.1Meterand
VerticalClearanceabovebuildingif11KVlineispassingoveritis3.66Meter.ConsideringadumperofCat777OBDumpTruck
(Empty)100tTRK9780x6105x5147,itsheightwillbeapprox5.2Meter.
Usingalltheabovementioneddata,Poleof9Meterwillgiveenoughclearancewhichsufficeyourpurpose.
Reply
samansays:
October14,2014at7:57am
whyweareusing3insulatorbracetfor11kVA

Reply
KaiserAhmadsays:
November20,2014at6:20pm
DearSir
WhatshouldbetheworkingloadforaPCCPole,9.0MtrlongwithFOS:2.5.
Thepolehastobeusedfor11kVlineinawindpressurezoneof75kg/sqmm.
Reply
ntejeswarsays:
November24,2014at2:38am
dearsir
thisisveryusefulformeandiwant11kv/0.440kvsinglelinediagramofoutdoorsubstation
Reply
vinodnaiksays:
November24,2014at1:21pm
siriwantRCCpolestandarddrawingforall7.5m,9m,11m..
Reply
DileepKumarSahusays:
December9,2014at11:39am
Whatisthemeaningofconductornames(ACSRDog,Rabbit&Weasel)?Dotheybelongtospecificvoltagelinerating?
Reply
prabirduasays:
December15,2014at9:56am
IPolitelyrequestyouCanyousendtomealltypeofelectricaliscoadlist.
Reply
VinodRanasays:
January8,2015at11:12am
MrParmar
ThisisRanafromDelhi
Howmuchvoltagedifferenceisallowedineachphasevoltageof11KVline.
MyincomingvoltageisshowingRPhase11000VoltsYPhase110100andBphaseis11500volts.Isitpermissible.thesame
correspondingdifferenceiamgettinginLTalso415,410.400ineachphase.
Howtoresolveit.
Rgs
Reply
VinodRanasays:
January8,2015at11:14am
PLread110100as11100volts
Reply
AMANsays:
January13,2015at2:26am
THANKYOU.ITISVERYHELPFUL.
Reply
sakthivelsays:
January21,2015at3:30am
pleasetelmetheinsulatornamewhichusedindpyard
Reply
tkmishrasays:
January29,2015at11:13am
R/sweareengagedindistributionsystemdealingwith33kv11kvand440v,workinginmpeb(nowmppkvvclwerequiredto
purchaseitemslocallybutwedonthavesuitablespecificationbook.Canusuggestmesomesuchbooks
Reply
SamsonPaulsays:

March13,2015at10:08am
Hello,
IreallylikethisarticlesinethisarticleissoinformativeformeasIamcurrentlydoingmyfinalyearprojectondesigninga11kV
distributiongridextesionwiththeutilitycompanyinmycountry.
AmafinalyearelectricalengineeringstudentatthePapuaNewGuineaUniversityofTechnology.
Amaskingifyoucouldhelpmewithmyprojectwithnecessaryinformation.
Thankyouverymuch.
Reply
raselsays:
March20,2015at4:04pm
Wouldyoupleaseinformmewhatshouldbethestandardheightofa11/.44kvsubstationbuildingasperelectricalrules.
Thanks
Reply
AnandKumarK.S.,Sr.Technicalofficer,ElectricalDivision,CSIRNationalAerospaceLaboratories,Bangaloresays:
March27,2015at1:41pm
Dearsirinformationisveryusefultoprofessionalengineers
Reply
N.NYNARKUMARsays:
March31,2015at7:36am
Dearsir
Iwouldliketothankfultosaytothat,Iamnynarkumariamworkingonrggvyprojectandihavecompleteinoneyear,todayi
amstudiedinyourRecspecifications.itisveryvaluableinformationforallsiteengineers.butihaveasmalldoughfor
transformerearthingAndLAinstallation.pleasegivemethevaluableanswer.
Reply
D.B.V.R.K.S.Sarmasays:
May26,2015at12:11am
Respectedsir
Goodmorningtheinformationyouhaveprovidedisusefulforeverypersonalwhoisattachedwithelectricaldistribution
system,thanksforprovidingtheinformation,nowcomingtomydoubti.eIwanttoknowthereasonbehindmaintaininga
distanceof1200mminbetweenlinesupportandearthingelectrodeindistributionsystem.
Reply
jhulansays:
June3,2015at8:14am
Howmany9mstpPolerequere1km11kvline
Reply
KashmiraLalsays:
July3,2015at7:01am
DearJignesh,
Pl.adviseforanymachineorattachmentusedtoerectelectricpoles.
Thanks,
Kashmira
Reply
Dharmendrasays:
July5,2015at4:11am
Good
Reply
MUKESHKUMARsays:
July7,2015at1:56pm

DearJignesh,

DearJignesh,
Isawapairofshieldorgroundwirestrung/runningbelowphaseconductorsin11KVoverheadpowerline.Isthisrequiredina
3phase11KV/415voltsoverheaddistributionlines/streetlightingutilitypolesalso;speciallyonstreetcrossing?Idontseeone
inmylocality.Pleaseclarify.
Reply
AmitGuptasays:
July10,2015at7:11am
Howtolocateafaultin11KVOHlineeasily.TheLineisrunningthroughfarmerslandandsomeoftreetouchestheOHline
causeearthfaultor/andovercurrentfaultresultintripingthesystem.
Reply