Académique Documents
Professionnel Documents
Culture Documents
Introduction
Table of Contents
Page
Safety ............................................................ 2
Getting Started ............................................... 3
First Steps ..................................................... 3
International Safety
Standards for Test Tools
Overvoltage
Category
Summary Description
CAT IV*
CAT III
CAT II
CAT I
Electronic
Getting Started
Lighting Panel
Lighting
Load
Utility
XFMR
MV/480Y
Switch Gear
Motor
M.C.C.
PF
Correction
Capacitor
ASD
Induction
Motor
Recept.
XFMR
480/208Y
Recept.
L.C.
Receptacle
Load
First steps
1. Make a map: Obtain or
create a current one-line
Its tough to diagnose PQ problems without having a working
knowledge of the site being
investigated. You can start by
locating or reconstructing a
one-line diagram of the site.
The one-line will identify the
ac power sources and the loads
they serve. The as built oneline, the one with red-lines, is
the one you want.
If you work on-site, the map
might already exist in your
head, but it will be a big help to
everyone, including yourself, if
its on paper. If youre coming to
a work site for the first time,
getting an up-to-date one-line
means identifying new loads or
other recent changes in the system. Why go to this effort? Systems are dynamic; they change
over time, often in unplanned
and haphazard ways. Furthermore, while some problems are
local in origin and effect, there
are many problems that result
from interactions between one
part of the system and another.
2. Do a walk around
of the site
Sometimes a visual inspection
will offer immediate clues:
A transformer thats much
too hot
Wiring or connections discolored from heat
Receptacles with extension
strips daisy-chained to extension strips
Signal wiring running in the
same trays as power cables
Extra neutral-ground bonds
in sub-panels.
Grounding conductors connected to pipes that end in
mid-air.
At a minimum, you will get a
sense of how the facility is
wired and what the typical
loads are.
3. Interview affected
personnel and keep
an incident log
Interview the people operating
the affected equipment. You will
get a description of the problem
and often turn up unexpected
clues. Its also good practice to
keep a record of when problems
happen and what the symptoms
are. This is most important for
problems that are intermittent.
The goal is to find some pattern
that helps correlate the occurrence of the problem in the
victim load to a simultaneous
event elsewhere. Logically, this
trouble-logging is the responsibility of the operator closest to
the affected equipment.
Section 1
Receptacle Branch Circuit
Many PQ problems show up at
the branch circuit level. Theres
a simple reason for this: thats
where most of the sensitive
loads (and sensitive employees)
are located. Its also the end of
the line of the electrical system, and the place where shortcomings cant be hidden. Lets
assume youve been called in
to solve the problem. Youve
already talked to the people involved, have a rough idea of the
symptoms (equipment lock-ups,
intermittent resets or crashes,
etc.) and as much sense of the
timing and history of the problems as you can get. So its time
to gather hard evidence: its
time to take measurements.
Our primary focus with
troubleshooting at the receptacle level is to determine if the
Line-Neutral (L-N) voltage available is of sufficient stability and
amplitude to supply the needs
of the load(s).
2. Peak voltage
The peak value is critical to
electronic loads because the
electronic power supply charges
its internal capacitors to the
peak value of the line voltage.
If the peak is too low, it affects
the ability of the caps to charge
fully and the ability of the
power supply to ride through
momentary dips in the line voltage. For an RMS voltage of
115V, the peak value would be
1.414 x 115V = 162.6V, if the
waveform were a sine wave.
However, as we just saw from
the flat-topped waveform, what
we have is far from a sine wave
and will have a lower peak
value.
4. Recording (short-term)
The limitation of the above
measurement is that it is static.
Many loads require more current, usually referred to as inrush current, when they are first
turned on. This momentary high
Measurement
current may cause a momentary
low voltage (sag) because of the
1. Waveform
additional IR drop through the
The waveform gives us quick
conductors. Such sags are often
snapshot information. An ideal
caused by loads drawing inrush
waveform would be a sine
currents on the same branch
wave. In this case, (see Fig 1.1)
circuit, or on the same
the voltage waveform is flatpanelboard.
topped, which is typical of a
You can measure a worstbuilding with many non-linear
case sag of 100 ms or more
3.
RMS
voltage
loads such as computers and
(about 6 cycles at 60 Hz) by usNominal line voltage is measured ing the MIN MAX function of the
other office equipment (see
in RMS (root-mean-square)
Flat-topped voltage, page 5).
Fluke 87 while energizing the
load. What if you want to know
if there are recurring sags? The
Table 1.1 Measurements on receptacle branch circuits.
Sags & Swells trending feature
Voltage Measurements
Look for
Instrument
of the Fluke 43 Power Quality
1. Waveform
Snapshot of severity of
43 PQ Analyzer
Analyzer will continuously capvoltage distortion
41B Harmonics Analyzer
ture sags of as little as single
2. Peak voltage
Excessive flat-topping
43 PQA, 41B
cycle duration (17 ms). A four87 DMM (Peak MIN MAX)
minute to a one-hour recording
3. RMS voltage
Low rms (steady-state low
43 PQA (Sags/Swells)
time (i.e., anywhere from a
rms or intermittent/cyclical
41B (MIN MAX)
single cup of coffee to a lunch
sags)
87 DMM (MIN MAX)
break) may be enough to tell
4. Recording (short-term)
Sags, swells, interruptions
43 PQA
you if there are recurring sags
while troubleshooter remains (Sags/Swells or Transients)
and swells.
on-site (4 minutes to 1 hour
typical recording time)
5. Recording (long-term)
VR101S
6. Neutral-ground
43 PQA, 87 DMM
Flat-topped voltage
The flat-topped waveform is
typical of the voltage in a commercial building with computer
loads. What causes flat-topping?
The utility supplies ac power,
but electronic equipment runs
on dc power. The conversion
of ac into dc is done by a power
supply. The PS has a diode
bridge which turns ac into pulsating dc, which then charges a
capacitor. As the load draws the
cap down, the cap recharges.
However, the cap only takes
power from the peak of the
wave to replenish itself, since
thats the only time the supplied
voltage is higher than its own
voltage. The cap ends up drawing current in pulses at each
half-cycle peak of the supplied
voltage. This is happening with
virtually all the electronic loads
on the circuit. Now that we see
what the loads are demanding
from the source, lets take a look
at what the source can supply.
If the source were perfectly
stiff, meaning that it had an
infinite capacity to supply all
the current that was required,
then there would be no such
thing as flat-topping (or sags
or any voltage distortion). Think
of it this way: if you had all the
money in the world, you
wouldnt get distorted either
when the bills came in. But in
the real world there are practical limits to what a source can
Diode-Capacitor
Input Circuit
Switching
Power Supply
5. Recording (long-term)
For longer term recording, the
VR101S Voltage Event Recorders will record sags, swells, outages, transients and frequency
deviations while plugged into
the outlet (see Recording at the
Receptacle Outlet, page 7). The
device can be left on-site, unattended, for days and weeks, all
the time catching intermittent
events (4000 event buffer). Now
you can see why its so important to ask the user to keep a
troubleshooting log: correlation
of equipment malfunction with
voltage events is hard evidence
of a PQ problem.
6. Neutral-to-ground voltage
Lets say that you make a
simple L-N measurement at the
outlet and get a low reading.
You cant tell if the reading is
low because the feeder voltage
is low (at the subpanel), or if the
branch circuit is overloaded. You
could try to measure the voltage
at the panel, but its not always
easy to tell which panel feeds
the outlet youre measuring and
its also sometimes inconvenient
to access a panel.
N-G voltage is often an easier
way of measuring the loading
on a circuit. As the current travels through the circuit, there is a
certain amount of voltage drop
in the hot conductor and in the
neutral conductor. The drop on
the hot and neutral conductors
will be the same if they are the
same gauge and length. The total voltage drop on both conductors is subtracted from the
source voltage and is that much
less voltage available to the
load. The greater the load, the
greater the current, the greater
the N-G voltage.
Think of N-G voltage as the
mirror of L-N voltage: if L-N
voltage is low, that will show
up as a higher N-G voltage
(see Fig. 1.4).
1
2
3
To panel
ground buss
3
To transformer
X0
N-G voltage
200 ft
60m
50 ft
15m
Laser
Printer
Copier
Shared neutrals
Some buildings are wired so
that two or three phases share a
single neutral. The original idea
was to duplicate on the branch
circuit level the four wire (three
phases and a neutral) wiring of
panelboards. Theoretically, only
the unbalanced current will return on the neutral. This allows
one neutral to do the work for
three phases. This wiring shortcut quickly became a dead-end
with the growth of single-phase
non-linear loads. The problem
is that zero sequence current
Solutions
Performance Wiring vs.
Code Minimum
Any experienced PQ troubleshooter will tell you that the
first place to look for most problems is in the building wiring
system (including its grounding
system). Quality power depends
on quality wiring; the term the
industry uses is performance
wiring (See Table 1.2). The basic intent of performance wiring
is to maintain or restore L-N
voltage to the load. There is a
distinction between performance wiring and code minimum wiring. The NEC sets the
absolute minimum requirements
for a wiring job and is primarily
concerned with fire prevention
and personnel safety. The NEC
Power conditioning
There are also situations where
receptacle-installed power conditioning devices are a good solution, either as a complement
to the wiring changes or as an
economically viable alternative
to some wiring changes.
200 ft
60m
Recording at the
receptacle outlet
By monitoring voltage events at
the receptacle, you can see exactly the same voltage that the
sensitive load sees.
The VR101 is plugged into
an outlet, and can record up
to 4000 events, including:
Voltage sags and swells (rms)
Outages
Transients (L-N and N-G)
with peak values
Frequency deviation
Events are identified by type,
real-time stamp, and duration.
VR101S operation
Set up
Use EventView software to
configure the device. The unit
comes with default thresholds,
but users can enter new thresholds. An optical wand, supplied
with the software, transfers
new configurations to the VR101.
Plug in
The VR101 is left on-site for as
long as needed. No computer
connection is necessary. It
draws power from the line and
in the event of outages, a builtin battery saves data.
50 ft
15m
Laser
Printer
Download
The VR101 is taken to the
computer. The optical wand
retrieves its data.
Copier
Reason
Analyze
Events are displayed in spreadsheet format in EventView
software. Charts, graphs and
waveform graphics are also
provided for report generation.
Section 2
Service Panels
Check-out the service panel
as follows:
Visual inspection
Feeder conductor current test
Neutral conductor current test
(feeder and branch)
Phase-to-neutral voltage test
(feeder and branch)
Neutral-to-ground voltage
test (feeder)
Circuit breaker voltage drop
and current on branch phase
conductors
The service panel is where the
effects of single-phase harmonic
loads are easy to measure. A
true-rms meter ensures accurate
readings of non-linear voltages
and currents (see Why Truerms, page 27).
Visual inspection
Measurement
Look for
Instrument
Same
Low voltage.
Same
Shared neutrals.
Same
43, 87
Line
Neutral
N-G
Bond
Ground
Panel
Sub-Panel
Figure 2.1 Sub-panel N-G bonds cause load return currents to flow on ground conductors.
This causes corrosion of pipes in grounding system as well as noisy grounds.
Measurements
1. Feeder phase current
Check each phase to make sure
it is not overloaded. Also check
for excessive unbalance.
2. Feeder neutral current
Measure the feeder neutral
conductor for cumulative neutral current. Third harmonic
currents from all three phases
will add arithmetically in the
neutral.
3. Feeder neutral-to-ground
voltage test
As at the receptacle, excessive
N-G voltage indicates overloading. A N-G voltage at or very
near zero indicates the existence of an illegal N-G bond in a
subpanel.
Circuit breaker
voltage drop
Feeder
phase
current(s)
Feeder
neutral
current
4. Phase-to-neutral
voltage test
Phase-to-neutral voltages are
measured and recorded. They
can be compared with receptacle L-N voltages to measure
voltage drop.
5. Branch neutral current
Measure each branch neutral
for overloading. The neutrals
are measured instead of the
phase conductors because they
might share the return current
of several phase conductors,
yet they are not protected
by breakers.
6. Circuit breaker
voltage drop
The voltage drop across a set
of breaker contacts will give
you a quick measure of the
wear of those contacts. Ideally,
the voltage drop should be
zero. In practice, there will be
some voltage drop in the mV
range, with the exact value being dependent on the load current. As a general rule, the
voltage drop should not exceed
20-100 mV, depending on load.
Replace worn breakers.
Branch
L-N
voltage
Solutions
Table 2.2 Service panel recommendations.
Recommendation
Reason
Section 3
Transformers
Transformers are subject to
overheating from harmonic currents. Transformers supplying
non-linear loads should be
checked periodically to verify
operation within acceptable
limits. Transformers are also
critical to the integrity of the
grounding system.
Measurements
1. Transformer loading (kVA)
If the transformer has a fourwire wye secondary, which is
the standard configuration for
commercial single-phase loads,
actual kVA can be easily
determined. (See Figure 3.2)
Connect voltage probes on
Phase 1 and Neutral and
clamp current probe on same
phase. Repeat for Phase 2
and 3.
Read kVA of each phase and
sum all three for total transformer kVA.
Red
Black
1
Red
kVA1
2
Red
Black
kVA2
Black
N
Black
3
Red
kVA3
Unbalanced load:
kVATOTAL = kVA1 + kVA2 + kVA3
2. Harmonic spectrum
The harmonic spectrum of the
secondary (load) current will
give us an idea of the harmonic
orders and amplitudes present:
In a transformer feeding
single-phase loads, the principal harmonic of concern is
the 3rd. The 3rd will add
arithmetically in the neutral
and circulate in the delta primary of a delta-wye transformer. The good news is
that the delta-wye tends to
isolate the rest of the system
from the 3rd (though not the
5th, 7th or other non-triplen
harmonics). The bad news is
that the transformer pays the
price with additional heat.
In a transformer feeding
three-phase loads which include drives or UPS systems
with 6-pulse converters, the
5th and 7th harmonic will
tend to predominate. Excessive 5th is of particular concern because it is negative
sequence. It will tend to
produce counter-torque and
overheating in polyphase
motors.
0
+
0
+
0
Measurement
Look for
Instrument
Rotation
Positive
Forward
Negative
Reverse
Zero
None
Table 3.2 IEEE 519 limits for harmonic currents at the point of common coupling.
(All percentages are % of I L, maximum demand load current.)
Odd Harmonics
SCR=Isc/IL
<11
11-17
17-23
23-35
>35
<20
4.0%
2.0%
1.5%
0.6%
0.3%
TDD
5.0%
20-50
7.0%
3.5%
2.5%
1.0%
0.5%
8.0%
50-100
10.0%
4.5%
4.0%
1.5%
0.7%
12.0%
100-1000
12.0%
5.5%
5.0%
2.0%
1.0%
15.0%
>1000
15.0%
7.0%
6.0%
2.5%
1.4%
20.0%
5. Ground currents
Two prime suspects for excessive ground current are illegal
N-G bonds (in subpanels, receptacles or even in equipment) and so-called isolated
ground rods:
4. K-factor
Subpanel N-G bonds create
K-factor is a specific measure of
a parallel path for normal rethe heating effect of harmonics
turn current to return via the
in general and on transformers
grounding conductor. If the
in particular. It differs from the
neutral ever becomes open,
THD calculation in that it emthe equipment safety ground
phasizes the frequency as well
becomes the only return
as the amplitude of the harpath; if this return path is
monic order. This is because
high impedance, dangerous
heating effects increase as the
voltages could develop.
square of the frequency.
(Figure 2.1, page 8.)
A K-4 reading would mean
Separate isolated ground
that the stray loss heating
rods almost always create
effects are four times normal. A
two ground references at
standard transformer is, in efdifferent potentials, which in
fect, a K-1 transformer. As with
turn causes a ground loop
THD, it is misleading to make a
current to circulate in an atK-factor reading at the load or
tempt to equalize those poreceptacle because there will be
tentials. A safety and
a certain amount of upstream
equipment hazard is also
cancellation; transformer K-faccreated: in the case of lighttor is what counts. Once the
ning strikes, surge currents
K-factor is determined, choose
travelling to ground at differthe next higher trade size. Kent earth potentials will
factor rated transformers are
create hazardous potential
available in standard trade sizes
differences. (See page 31.)
of K-4, K-13, K-20, K-30, etc.
K-13 is a common rating for a
480V
Transformer grounding
The proper grounding of the
transformer is critical. (Table
3.3.) NEC Article 250 in general
and 250-26 in particular
address the grounding requirements of the SDS.
A ground reference is established by a grounding connection, typically to building
steel (which, in turn, is required to be bonded to all
cold water pipe, as well as
any and all earth grounding
electrodes). Bonding should
be by exothermic weld, not
clamps that can loosen over
time. The grounding electrode conductor itself should
have as low a high-frequency
impedance as possible (not
least because fault current
has high frequency components). Wide, flat conductors
are preferred to round ones
because they have less inductive reactance at higher
frequencies. For the same
reason, the distance between
the grounding electrode conductor connection to the system (i.e., N-G bond at the
transformer) and the grounding electrode (building steel)
should be as short as possible: in the words of the
Code, as near as practicable
to and preferably in the
same area...
The neutral and ground
should be connected at a
point on the transformer neutral bus. Although permitted,
it is not advisable to make
the N-G bond at the main
panel, in order to maintain
the segregation of normal return currents and any ground
currents. This point at the
transformer is the only point
on the system where N-G
should be bonded.
208Y/120V
Neutral
Solutions
There are a number of solutions
for transformer-related PQ
problems:
Install additional distribution
transformers (Separately
Derived Systems)
Derate transformers
Install K-rated transformers
Used forced air cooling
1. Separately Derived
System (SDS)
The distribution transformer is
the supply for a Separately
Derived System (SDS), a term
which is defined in the NEC
(Article 100). The key idea is
that the secondary of this transformer is the new source of
power for all its downstream
loads: this is a powerful concept
in developing a PQ distribution
system. The SDS accomplishes
several important objectives, all
beneficial for PQ:
It establishes a new voltage
reference. Transformers have
taps which allow the secondary voltage to be stepped up
or down to compensate for
any voltage drop on the
feeders.
It lowers source impedance
by decreasing, sometimes
drastically, the distance
between the load and the
source. The potential for voltage disturbances, notably
sags, is minimized.
It achieves isolation. Since
there is no electrical connection, only magnetic coupling,
between the primary and
secondary, the SDS isolates
its loads from the rest of the
electrical system. To extend
this isolation to high frequency disturbances, specially constructed isolation
transformers provide a
shield between the primary
and secondary to shunt RF
(radio frequency) noise to
ground. Otherwise, the capacitive coupling between
primary and secondary
would tend to pass these
high-frequency signals right
through.
2. K-rated transformers
3. Derating standard
transformers
Some facilities managers use
a 50% derating as a rule-ofthumb for their transformers
serving single-phase, predominantly nonlinear loads. This
means that a 150 kVA transformer would only supply 75
kVA of load. The derating curve,
taken from IEEE 1100-1992
(Emerald Book), shows that a
transformer with 60% of its
loads consisting of SMPS
(switched-mode power supplies), which is certainly possible in a commercial office
building, should in fact be
derated by 50%.
The following is an accepted
method for calculating transformer derating for single-phase
loads only. It is based on the
very reasonable assumption
that in single-phase circuits, the
third harmonic will predominate
and cause the distorted current
waveform to look predictably
peaked.
Use a true-rms meter to make
these current measurements:
1. Measure rms and peak current of each secondary
phase. (Peak refers to the instantaneous peak, not to the
inrush or peak load rms
current).
2. Find the arithmetic average
of the three rms readings and
the three peak currents and
use this average in step 3
(if the load is essentially
balanced, this step is not
necessary).
3. Calculate Xformer Harmonic
Derating Factor:
xHDF = (1.414 * I RMS) / I PEAK
20
40
60
80
100
Section 4
Noise
20 - 30V
logic signal
Noise
3 - 5V
logic signal
Coupling mechanisms
There are four basic mechanisms of noise coupling. It pays
to understand them and how
they differ one from the other
because a lot of the troubleshooters job will be to identify
which coupling effect is dominant in a particular situation.
1. Capacitive coupling
This is often referred to as
electrostatic noise and is a
voltage-based effect. Lightning
discharge is just an extreme
example. Any conductors separated by an insulating material
(including air) constitute a capacitorin other words, capacitance is an inseparable part of
any circuit. The potential for
capacitive coupling increases as
frequency increases (capacitive
reactance, which can be
thought of as the resistance to
capacitive coupling, decreases
with frequency, as can be seen
in the formula: X C = 1/ 2 fC).
2. Inductive coupling
This is magnetic-coupled noise
and is a current-based effect.
Every conductor with current
flowing through it has an associated magnetic field. A changing current can induce current
in another circuit, even if that
circuit is a single loop; in other
words, the source circuit acts as
a transformer primary with the
victim circuit being the secondary. The inductive coupling
effect increases with the following factors: (1) larger current
flow, (2) faster rate of change of
current, (3) proximity of the two
conductors (primary and secondary) and (4) the more the
adjacent conductor resembles a
coil (round diameter as opposed
to flat, or coiled as opposed to
straight).
Here are some examples of
how inductive coupling can
cause noise in power circuits:
B
-
Noise Coupling
-G
N-G
Ground
3. Conducted noise
While all coupled noise ends up
as conducted noise, this term is
generally used to refer to noise
that is coupled by a direct, galvanic (metallic) connection. Included in this category are
circuits that have shared conductors (such as shared neutrals
or grounds). Conducted noise
could be high frequency, but
may also be 60 Hz.
These are some common
examples of connections that
put objectionable noise currents
directly onto the ground:
Sub-panels with extra N-G
bonds
Signal Grounding
To understand the importance of
clean signal grounds, lets discuss the distinction between
Differential Mode (DM) vs. Common Mode (CM) signals. Imagine a basic two-wire circuit:
supply and return. Any current
that circulates or any voltage
read across a load between
the two wires is called DM
(the terms normal mode, transverse mode and signal mode
are also used). The DM signal is
typically the desired signal (just
like 120V at a receptacle).
Imagine a third conductor, typically a grounding conductor.
Any current that flows now
through the two original conductors and returns on this third
conductor is common to both of
the original conductors. The CM
current is the noise that the
genuine signal has to overcome.
CM is all that extra traffic on the
highway. It could have gotten
there through any of the coupling mechanisms, such as
magnetic field coupling at
power line frequency or RFI at
higher frequencies. The point is
to control or minimize these
ground or CM currents, to make
life easier for the DM currents.
Measurement
CM currents can be measured
with current clamps using the
zero-sequence technique. The
clamp circles the signal pair (or,
in a three-phase circuit, all
three-phase conductors and the
neutral, if any). If signal and return current are equal, their
equal and opposite magnetic
fields cancel. Any current read
must be common mode; in other
words, any current read is current that is not returning on the
signal wires, but via a ground
path. This technique applies to
signal as well as power conductors. For fundamental currents, a
ClampMeter or DMM + clamp
would suffice, but for higher frequencies, a high bandwidth instrument like the Fluke 43
Power Quality Analyzer or
ScopeMeter should be used
with a clamp accessory.
Transients
Causes
Transients are unavoidable.
They are created by the fast
switching of relatively high currents. For example, an inductive
load like a motor will create a
kickback spike when it is turned
off. In fact, removing a Wiggy (a
solenoid voltage tester) from a
high-energy circuit can create a
spike of thousands of volts! A
capacitor, on the other hand,
creates a momentary short circuit when its turned on. After
this sudden collapse of the applied voltage, the voltage rebounds and an oscillating wave
occurs. Not all transients are the
same, but as a general statement, load switching causes
transients.
In offices, the laser copier/
printer is a well-recognized
bad guy on the office branch
circuit. It requires an internal
heater to kick in whenever it is
used and every 30 seconds or
so when it is not used. This
constant switching has two
effects: the current surge or inrush can cause repetitive voltage sags; the rapid changes in
current also generate transients
that can affect other loads on
the same branch.
Measurement and recording
Transients can be captured by
DSOs (Digital Storage Oscilloscopes). The Fluke 43 PQ
Analyzer, which includes DSO
functions, has the ability to
capture, store and subsequently
display up to 40 transient
waveforms. Events are tagged
with time and date stamps (real
time stamps). The VR101S Voltage Event Recorder will also
capture transients at the receptacle. Peak voltage and real time
stamps are provided.
500
400
300
200
140
120
110
100
90
80
70
110V
Voltage-Tolerance
envelope
90V
40
0
0.001c
0.01c
1s
0.1c
0.5c 1c
1ms
3ms
20ms
10c
100c
0.5s
1000c
10s
Steady
state
Section 5
Lightning Protection
Lightning protection plays a
vital part in the overall power
quality of an installation. Lightning occurrence varies by geography, with Florida being the
lightning capital of the U.S.
Lightning does not have to
score a direct hit to be disruptive. It has so much energy that
it couples surges into conductors, both those exposed to air
and those buried in the ground.
Basic lightning protection has
two main requirements:
1. Effective grounding
A low impedance of the grounding electrode system to earth is
important. But, equally important is that all parts of the
grounding system be bonded
together: all ground electrodes
are bonded (and extraneous
ground rods removed), structural
steel is tied to service entrance
ground, all grounding connections are tight and free of corrosion, etc. This minimizes the
phenomenon called transferred
earth potential, where large
surge currents create large voltage differences between two
ground points with different
impedances to earth. This same
grounding practice is important
for performance reasons, as it
tends to minimize ground loop
currents that circulate in an
attempt to equalize ground
potentials.
Check
Look for
Reason
Surge arrestors
Grounding electrode
connections are not loose
or corroded.
Grounding conductor
should not be coiled or
have unnecessary bends.
Grounding electrode
conductors at service
entrance or at SDS
Separately driven
(isolated) electrode
Same as aboveentire
grounding system should be
an equipotential ground
plane for lightning.
2. Surge arrestors
A surge arrestor is a protective
device for limiting surge voltages by discharging or bypassing surge current... (NEC 280).
Since the surge current is bypassed to ground, surge arrestors are only as effective as the
grounding system.
Surge arrestors are sized for
the location where they are installed. Three categories are defined (ANSI/IEEE C62.41-1991).
Load
Surge
Arrestor
Surge
Arrestor
Sub
Panel
Main
Service
Surge
Arrestor
Section 6
Measurements
1. Voltage unbalance
Voltage unbalance should not
exceed 1-2% (unless the motor
is lightly loaded). Why such a
small number? Voltage unbalance has a very large effect on
current unbalance, in the neighborhood of 8:1. In other words,
a voltage unbalance of 1% can
cause current unbalance of 8%.
Current unbalance will cause
the motor to draw more current
than it otherwise would. This in
turn causes more heat and heat
is the enemy of motor life, since
it deteriorates the winding insulation.
Look for
1. Voltage unbalance
Unbalance <1%
43, 41B, 87
2. Voltage %THD
%THD <5%
43, 41B
3. Current unbalance
Unbalance <10%
43, 41B
87 w/80i-400
Single phasing
(extreme current
unbalance)
4. Loading
5. Inrush current
6. Power factor
1
2
Instrument
Same
43
43, 41B
3. Current unbalance
To find current unbalance, measure amps in all three phases.
Do the same calculation as for
voltage unbalance. In general,
current unbalance should not
exceed 10%. However, unbalance can usually be tolerated if
the high leg reading doesnt exceed the nameplate FLA (Full
Load Amps) and SF (Service
Factor). The FLA and Service
Factor are available on the motor nameplate. If the voltage unbalance and the voltage THD
are within limits, high current
unbalance can be an indication
of motor problems, such as
damaged winding insulation or
uneven air gaps.
Current measurement will
also find single-phasing. If a
three-phase motor loses a
phase (perhaps caused by a
blown fuse or loose connection),
it may still try to run single
phase off the remaining two
phases. Since the motor acts
like a constant power device, it
will simply draw additional current in an attempt to provide
sufficient torque. A voltage measurement alone will not necessarily find this condition, since
voltage is induced by the two
powered windings into the
non-powered winding.
Flattopping
T3
M
Single-phasing
Load
red
black
red
kW1
kVA
Load
red
black
kW2
black
Section 7
Voltage distortion
If high-voltage distortion shows
up as excessive flat-topping, it
will prevent dc link capacitors
from charging fully and will
diminish the ride-through
capability of the drive. Thus a
voltage sag which would not
ASDs as Victim Loads
normally affect a drive will
cause the drive to trip on
Although ASDs are usually
undervoltage.
depicted as the culprit in the
PQ scenario, there are ways
Improper grounding will affect
in which they can be a victim
the internal control circuits of
load as well.
the drive, with unpredictable
Capacitor switching transients results.
High-energy (relatively lowfrequency) transients that are
ASDs as Culprit Loads
characteristic of utility capacitor A drive can definitely be a culswitching can pass through the prit load and have a major imservice transformer, feeders,
pact on system PQ. But before
and converter front-end of the
we talk of problems, lets put in
drive directly to the dc link bus, a good word for the positive efwhere it will often cause a dc
fects of drives on PQ. First of all,
link overvoltage trip. Input dithey offer built-in soft-start caodes could also be blown out
pabilities. This means there will
by these transients.
Table 7.1 Line-side measurements on ASDs.
Measurement
Look for
Instrument
Voltage waveform
43
Harmonic spectrum
43, 41B
Displacement PF
43, 41B
Voltage unbalance
43, 41B
Induction
Motor
M
Line
Reactors
Harmonics solutions
12-pulse converter
If the delta-wye/delta-delta are
packaged together (delta primary, delta and wye secondary)
and each secondary feeds one
of two paralleled six-pulse converters, a 12-pulse front-end is
created with all the benefits
mentioned above. 18-pulse
designs are also available. Because of the extra cost, this type
of solution tends to only get
used on high HP loads.
Active filters
This relatively new technology
is based on an elegant concept
using power electronics to solve
the problems created by power
electronics. It senses the instantaneous ac sine wave; it then
actively cancels the harmonics
it detects by generating equal
and opposite polarity harmonics, thus recreating the sine
wave. Commercial packages
might provide voltage regulation as well.
Active PF Correction
Another recent solution is for
manufacturers to offer converter
front ends using fast switching
technology that generates a
minimum amount of harmonics
and has near unity power factor
(both Total PF and DPF).
Line
Load
Why True-rms
True-rms test tools are necessary for accurate
measurements of distorted waveforms. For more
information, see the Fluke application note Why
True-rms, document number B0294A.
A comparison of average-responding and true-rms multimeters
Multimeter Reading
Waveform
Description
Average-sensing
DMM
True-rms
DMM
Sine wave
Correct
Correct
Square wave
(flat-top voltage)
10% high
Correct
Current to single
phase diode rectifier
40% low
Correct
Current to 3 phase
diode rectifier
5-30% low
Correct
Displacement Power
Factor
Lower DPF is caused by motor
loads which introduce the need
for Reactive Power (Volt-Amp
Reactive or VARs). The system
has to have the capacity, measured in Volt-Amps (VA) to supply both VARs and Watts. The
more VARs needed, the larger
the VA requirement and the
smaller the DPF. The cost of
VARs is accounted for in a
power factor penalty charge.
Utilities often levy additional
charges for DPF below a certain
level; the actual number varies
widely, but typical numbers are
0.90 to 0.95.
To reduce VARs caused by
motor loads, power factor correction capacitors are installed.
Upstream system capacity, both
in the plant and at the utility
level, is released and available
for other uses. (Fig. 7.6)
Historically, this has been the
gist of the PF story: a relatively
well-known problem with a
relatively straightforward
solution.
Before: PF = 42%
3.3A
Active
165 Watts
Reactive
360 VAR
Active
165 Watts
Reactive
360 VAR
Capacitor
60 F
1/6 HP Motor
Figure 7.6 Capacitor corrects Displacement Power Factor (DPF).
1/6 HP Motor
A. System Diagram
B. Equivalent Circuit
XS
XT
XT
XC
XC
XS
Harmonic
source
kvar
(nonwork producing)
VA
Harmonics
(nonwork
producing)
kW
(work producing)
Section 8
1. Power consumption
Excessive phase unbalance can
cause voltage unbalance, which
in turn can affect three-phase
motor loads.
4. Voltage stability
The sags and swells mode of
the Fluke 43 is especially useful
for recording repetitive voltage
sags which can show up as
flickering lights. Both current
2. Power Factor
and voltage are monitored siBallast with low PF might have multaneously. This helps us to
lower cost-of-purchase but
tell if sags are downstream of
higher cost-of-operation.
the measuring point (loadrelated) or upstream (source3. Total Harmonic Distortion related). For example, if voltage
sags while current swells, a
Current THD should be considered when selecting ballast, es- downstream current inrush
likely caused the sag. If both
pecially if there is a possibility
voltage and current sag, some
of transformer overloading.
event upstream caused
the sags.
Table 8.1 Measurements on commercial lighting loads.
It could be an upstream
load like a motor on a parallel
Measurement
Look for
Instrument
branch circuit which drew
1. Power
Balance among three phases.
43, 41B
down the feeder voltage. Or
consumption (kW)
it could be source voltage2. Power Factor
Magnetic ballast will have low DPF. Electronic
43, 41B
related, for example, a lightning
(DPF and PF)
ballast may have low total PF, although new
generations of ballast often have harmonic
strike or breaker trip/reclosure
mitigation built-in.
on the utility distribution
3. Total Harmonic
Current %THD <20% is desirable.
43, 41B
system.
Distortion (%THD)
4. Voltage Stability
43
480V Phase-to-Phase
2
3
277V Phase-to-Neutral
N
Lighting Panel
Figure 8.1
Load Current
Neutral Return
Current Error
Separately
Derived
System
Line
N-G
Bond
Line
Neutral
Ground
Neutral
Ground
Panel
Earth Ground
Isolated Ground,
Ground Rod, Cold Water Pipe, Etc.
Isolated ground rod can cause ground loops. Common problem with CNC machine tool installations.
The following Fluke test tools are referred to in this application note.
Model
Test Tools
Power
Recording
Real-Time Clock
Fluke 43
Fluke 41B
Fluke VR101S
Fluke 36
Power Quality
Analyzer
Harmonic
Analyzer
Voltage Event
Recorder
Digital
Multimeter
ClampMeter
TrendPlot, PC logging
PC logging
To 51st harmonic
Voltage Transients
20 nanoseconds
with waveform
1 microsecond
event recording
250 microsecond
Peak MIN/MAX
Single cycle
event recording
100 millisecond
MIN/MAX
Outages
Documentation,
RS232 Computer
FlukeView
Power Quality Software
FlukeView 41
Software
Noise
Peak
True-rms
To 31st harmonic
20 MHz scope
Fundamental
References and
acknowledgments
Harmonics
Waveform
EC&M Practical Guide to Quality Power for Sensitive Electronic Equipment, 2nd Edition.
Dranetz Field Handbook for
Power Quality Analysis.
Ontario Hydro Power Quality
Reference Guide.
Association of Energy
Engineers: Fundamentals
of Power Quality.
IEEE Std 1100-1992: Recommended Practice for Powering
and Grounding Sensitive Electronic Equipment.
EPRI, Electrotek Concepts, Inc.:
Power Quality for Utility and
Industrial Applications
Power Quality Assurance
Magazine
100 millisecond
MIN/MAX
EventView
Software
MIN/MAX
MAX Hold
Understanding and
Managing Harmonics
Part Number: 609096
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
U.S.A. (800) 443-5853 or
Fax (425) 356-5116
Europe/M-East (31 40) 2 678 200 or
Fax (31 40) 2 678 222
Canada (905) 890-7600 or
Fax (905) 890-6866
Other countries (425) 356-5500 or
Fax (425) 356-5116
Web access: http://www.fluke.com
1998 Fluke Corporation. All rights reserved.
Printed in U.S.A. 9/98 B0333UEN Rev A
Printed on recycled paper.