ELECTRIC WIRING
MCY-MAP###HT series
MCY-MAP###HT2D series
Power
supply
(Connection example)
Earth
L
Outdoor unit
capacity type
Wire size*
Maxim running
current
Installation
fuse
0401 type
6 mm, Max. 28 m
25A
32A
0501 type
6 mm, Max. 25 m
28A
32A
0601 type
6 mm, Max. 22 m
31A
40A
Outdoor unit
10
10
L
50
Power cable
(Cord clamp)
90
Earth line
Power cable
21
For Indoor unit power supply (The outdoor unit has a separate power supply.)
Power supply wiring
Item
Model
Wire size
2.0 mm
Max. 20m
3.5 mm
Max. 50m
Note)
Power supply cord specification : Cable 3-core 2.5 mm, inconformity with Design 60245 IEC57.
The connecting length indicated in the table represents the length from the pull box to the outdoor unit when the
indoor units are connected in parallel for power, as shown in the illustration below. A voltage drop of no more than
2% is also assumed. If the connecting length will exceed the length indicated in the table, select the wire
thickness in accordance with indoor wiring standards.
Determine the wire size for indoor unit according to the number of connected indoor units downstream.
[Indoor unit]
Earth
Earth
L N
Earth
L N
Earth
L N
L N
Indoor unit
PMV Kit
Connection cable
PMV
CN82 connector
22