Instruction Manual of Capacitor Voltage Transformers

0GR.463.354-2010
1

Technical characteristics
Capacitor voltage tranformers (hereinafter referred to as CVTs) have the
following characteristics
aIron core C technology makes CVTs more stable and reliable.
bRapid-saturable damp technique can effectively suppress ferro-resonance and keep
three-phase open-delta residual voltage below 1V.
cResidual voltage of transient response can be below 5%. This is able to meet the
requirements of quick relay protection device.
dThe quality is reliable due to good dielectric and insulation material, advanced
design and vacuum impregnation, and excellent partial discharge.
eCVTs do not need to be made maintenance, oil filter and oil change, oil sample
inspection during normal service.

Purpose and applicable range

2.1

Purpose
CVTs series is used for high-voltage, extra-high voltage, ultra-high voltage power

system at rated frequency 50Hz. They are intended to provide voltage signal for electrical
measurement instrument, protection and control device, and as a coupling capacitor for
carrier coupling device for power line.
2.2 Applicable range
CVTs are installed outdoor. Ambient air temperature for installation and operation
area is -40 to +55. Altitude does not exceed 2000m.if altitude exceeds 2000m, CVTs
can be specially manufactured in accordance with the purchaser after agreed between the
purchaser and manufacturer. Wind velocity is not more than 150km/h. Earthquake
intensity does not exceed 8 without serious pollution, vibration and bump.

3
3.1

Type and main technical data


Description of type
When the subscript (serial number of design) is double-digit, it represents euipped with
1

intermediate earthing switch.


When the last letter is TH or G, it respectively represents damp tropics and plateau.
T

YD

66/ 3

0.02

F
non-effectively earthed neutral
antipollution
rated capacitance F
rated phase voltage kV
serial number of design
capacitor voltage transformer
equipment

Note: Serial number of design represents that number of secondary winding. In case of 3, represents
that number of secondary winding of the product is 3. In case of 13, represents that the product is
equipped with intermediate earthing switch and number of secondary winding is 3.

3.2
3.2.1

Main technical data


CVTs can continuoulsy operate at 1.2 times rated primary voltage. CVTs for

effectively earthed neutal system can operate for 30s at 1.5 times rated primary voltage.
CVTs for auto tripping non-earthed neutral system without earth fault can operate for 8h at
1.9 times rated primary voltage.
3.2.2

Connection group of intermediate transformer winding is 1/1/1-12-12 or

1/1/1/1-12-12-12 or 1/1/1/1/1-12-12-12-12
3.2.3

Creepage distance of the product having a H in the type is not less than 25mm/kV

calculated on system highest voltage. Special creepage distance is given in annotations of


certificate of product.
3.2.4

Insulation level of CVTs are given in Table 1.

3.2.5 Accuracy class and corresponding voltage error, phase angle error, and operating
conditions of CVTs are given in Table 2.

Table 1

Insulation Level of CVTs

kV

35/ 3 66/ 3 110/ 3 115/ 3 132/ 3 150/ 3 220/ 3 230/ 3 275/ 3 330/ 3 400/ 3 500/ 3 765/ 3 1000/ 3

Rated primary voltage


System rated voltage

35

110

115

132

150

220

230

275

330

400

500

750

1000

System highest voltage

40.5 72.5 126

123

145

170

252

245

300

363

420

550

800

1100

66

Rated short duration


power-frequency withstand
voltage

1300

95

160

200

230

275

325

395

460

460

510

520

740

975

200

350

480

550

650

750

950

1050

1050

1175

1425

1675

2100

2400

850

950

1050

1175

1550

1800

5 min

r.m.s1min
Rated lightning impulse
withstand voltage
peak1.2/50s
Rated switching impusle
withstand voltage
peak250/2500s

Table 2

Operating Conditions and Error Limit Value of CVTs

Item
Error limit
value

Operating
conditions

Measuring accuracy class

Protection accuracy

0.2

0.5

1.0

3.0

3P

6P

Voltage error

0.2

0.5

1.0

3.0

3.0

6.0

Phase displacement
error

10

20

40

Not
specified

120

240

Voltage

80120

5150 or 5190

Permissible frequency
range

99101

96102

Permissible temperature
range

Lower to upper limit temperature of temperature category

Burden
Burden power factor

25100
0.8lagging

NoteThe value in brackets is applied to CVTs for neutral non-effectively earthed system.

3.2.6

Carrier capacitance of capacitor divider C, and tolerance of high-voltage capacitance

C1 and intermediate capacitance C2 shall be -5 to +10 of ratings. The error between


tolerance of C1 and C2 does not exceed 5.
3.2.7

Tangent of loss angle of capacitor divider ( tan) is not more than 0.0012.

3.2.8

CVTs shall conform to GB/T 4703Capacitor Voltage Transformers.

3.2.9

Main technical data of CVTs are given in Table 3.

Operating theory and main structure

4.1 Operating theory


CVT is divided voltage by capacitor divider. Intermediate transformer changes intermediate
3

voltage to secondary voltage. The sum of reactance of compensation reactor and leakage
reactance of CVT, and equivalent capacitive reactance [

1
] in serial resonance can
(C 1 + C 2 )

eliminate voltage variation due to capacitive reactance voltage drop with the change of
secondary burden. This can make voltage stable. The electrical principle diagram is given in
Figure 1.
4.2

Main structure

CVTs have two kinds of structure of combination single stack and separation. Both of them
consist of capacitor divider and electromagnetic unit. The capacitor divider consists of one or
more section capacitors in series. Line terminals are on the top of capacitor divider.

Figure 1 Electrical principle diagram


Where,
C Carrier capacitance
1a1nSecondary 1a1n winding terminal
C1 High-voltage capacitance
2a2n Secondary 2a2n winding terminal
C2 Intermediate capacitance
dadn Residual voltage winding terminal
Up Primary voltage
XL Low-voltage terminal of compensation reactor
A Intermediate terminal
Earthing terminal
T Intermediate transformer
N Carrier communication terminallow-voltage terminalnot exposed weather
L Compenstiaon reactor
D Damp device
P Protection device
J Carrier combination device with arrestersprovided by purchaser
S Intermediate earthing switch (distribute when the purchaser requires)
4

The electromagnetic unit consists of intermediate transformer, compensation reactor


and damp device(ferro-resonance suppression) mounted in the tank. Secondary winding
terminals and carrier communication terminals are leaded by outgoing terminal box on the
face of the tank.
CVTs equipped with intermediate earthing switch belong to special products. Please
specify them when ordering. Intermediate earthing switch is mounted on the wall of the tank.

5 Lifting and storage


5.1 Lifting single section capacitor is necessary during packing, devanning, testing and

erection, etc. For CVTs having a 220kV and up to 220kV, it is not permissible that more
section capacitors are stacked to lift.
5.2 During transportation and storage, CVTs have to keep right side up, preventing from

collision and other mechanical hurt. CVTs shall be stored a place where ambient air
temperature is -40 to +55, without flammability, explosion, corrosion and vibration.

6
6.1

Installation and commissioning


CVTs shall be mounted on solid horizontal base in accordance with clause 2.2.

Connection between CVTs and the base is fixed by screws, nuts and washers. Connection
between capacitors is also fixed by screws, nuts and washers.
6.2 Line terminals on primary side of CVTs is connection board on the top cover of
capacitor divider. Terminal N, in secondary outgoing box, is connected with carrier coupling
device or directly

. (During operation, this terminal has to directly connected with

by connection sheets provided by manufacturer. As carrier communication, this terminal is


connected in series to the carrier coupling device, then disconnect connection sheets). The
tank must be solidly directly connected to the ground. Secondary circuit is made an electrical
joint by secondary outgoing terminals in outgoing box.
6.3 Capcitor divider and electromagnetic unit of each ex-factory CVT have been adjusted
the error, so the CVT shall not be exchangeable each other.
6.4

Intermediate earthing switch is short-circuited connected with intermediate transformer

for the CVT testings at site. The handle of intermediate earthing switch during CVT service
5

has to fix at normal operation, otherwise intermediate transformer is short-circuited


connected. It is prohibited from using intermediate earthing switch at energization.
Schematic diagram of the handle is given in Figure 8.
6.5 CVTs are energized as long as mechanical and electrical joints are correct and reliable.
6.6

Internal terminal in secondary outgoing terminal box has connected with the tank.

7 Service and safety


7.1 Service conditions of CVTs shall be in accordance with clause 2.2, 3.2.4, 3.2.5.
7.2 When communication terminal N is regarded as carrier communication, it is
earthed through carrier combination device. Otherwise, it is directly connected to the
ground not to open circuit. When low-voltage terminal XL of compensation reactor is
operating, it must directly be connected to the ground to prohibit open circuit except
energization inspection.

7.3 After CVTs are cut off power supply to remove service, touch them after the electrical
conductive part is discharged many times by earth rod.

Maintenance

8.1 It is suggested that capacitance and tan value are checked once each year. During

inspection, ambient air temperature is 2510. The device of capacitance and dielectric
loss measurement is higher than class 3. When the tolerance between capacitance and
measured value in certificate of product exceeds 5% or tan exceeds 0.3%, CVTs shall
be stopped service.
8.2 CVTs are hermetically internally filled in insulating oil. Sealing state of CVTs is usually
checked during service. Inspection location is joint position among upper and lower cover
plate of the capacitor and porcelain bushings, and joint position between outgoing plate
inner secondary outgoing box and the tank. In case of leakage, CVTs shall be stopped
service.
8.3 Oil level in a visual window shall be usually checked during service. When CVTs are
operating at maximum ambient air temperature +55, it is natural that oil level does not
exceed maximum position of the window. When CVTs are operating at minimum ambient
6

air temperature -40, it is natural that oil level does not exceed minimum position of the
window. Once oil level exceeds maximum or mimimum position of the window, detect
whether capacitance and temperature rise of CVTs are abnormal. If the tolerance between
two measured capacitance of single section capacitor is 1%, CVTs shall be removed service
to make an inspection. Temperature rise of the same capacitor and electromagnetic unit of
the same product is compared, using infrared temperature measurement device. In case of
abnormal, CVTs shall be removed service to make an inspection.
During service, do not need to make oil filter, oil change and oil sample inspection.

8.4 Testing principle diagram of capacitance and tan measurement are given in Figure 9
to11. Capacitance and tan inspection are carried out by other correct methods.
Electrical principle diagram of capacitance and tan measurement on CVTs equipped
with intermediate earthing switch are made according to Figure 9 and 10. Electrical
principle diagram of capacitance and tan measurement on CVTs without intermediate
earth switch is given in Figue11. The measurement is carried out by other correct
methods.
At measurement, strictly conform to testing principle diagram and explanation.
8.5 CVTs are enclosed products, capacitor divider can not be separated from electromagnetic
unit unless the manufacturer agrees. During acceptance and service, do not make a withstand
voltage test on forming the whole of connecting lower section capacitor and electromagnetic
unit.
8.6 Burden of secondary windings shall be in the range of 25% to 100% of corresponding
rated burden. Residual voltage windings shall be equipped without burdens during normal
operation, otherwise error limit value of secondary output voltage do not guarantee a
specified range in Table 2.
8.7 During service, usually check whether mechanical and electrical joints of CVTs are
normal and reliable.
8.8 After CVTs are cut off power supply to remove service, touch them after the electrical
conductive part is discharged many times by earth rod.

9 Common faults and solution


9.1 The tank oil leakage of electromagnetic unit of CVTs. The tank oil leakage is usually
appeared on the edge around insulation board inner secondary outgoing box. The
solution is that tighten surrounding sealing screws.
9.2 Terminal N on the insulation board has discharged to the earthing tank. Burning
insulation board is not directly connected to because terminal N is not regarded as
carrier communication.

10 List of supply of CVTs is given in Table 4.


11 Type selection of CVTs
If only rated primary voltage, rated capacitance, number of secondary winding, voltage
and accuracy class/burden of each secondary winding are determined, type of CVTs is
selected.
For example, known rated primary voltage of 110/ 3 kV,

rated capacitance of

0.01F, 3 secondary windings, respective voltage of 0.1/ 3 kV, 0.1/ 3 kV, 0.1 kV
corresponding accuracy class/burden: 0.2/50VA, 0.5/50VA, 3P/50Vthen item 11 CVT
TYD3110/3-0.01H in Table 3 can satisfy the requirments. In case of equipped with
intermediate earthing switch, please select TYD13110/ 3 -0.01H.
Special design is able to be carried out in accordance with the purchaser.

Table 3 Main Technical Data of CVTs

SN

Type

Rated
voltage
kV

1*

TYD235/ 3 -0.01HF

2*

TYD335/ 3 -0.01HF

TYD235/ 3 -0.02HF

TYD335/ 3 -0.02HF
4

TYD366/ 3 -0.01HF
5*

TYD366/ 3 -0.015HF
6*

TYD366/ 3 -0.02HF
7
TYD2110/ 3 -0.007H
*

TYD12110/ 3 -0.007H
TYD3110/ 3 -0.007H
*

TYD13110/ 3 -0.007H
TYD2110/ 3 -0.01H
10
TYD12110/ 3 -0.01H
TYD3110/ 3 -0.01H
11
TYD13110/ 3 -0.01H

12

TYD4110/ 3 -0.01H
TYD14110/ 3 -0.01H

TYD3110/ 3 -0.015H
13*
TYD13110/ 3 -0.015H

35/ 3
0.1/ 3
0.1/3
35/ 3
0.1/ 3
0.1/ 3
0.1/3
35/ 3
0.1/ 3
0.1/3
35/ 3
0.1/ 3
0.1/ 3
0.1/3
66/ 3
0.1/ 3
0.1/ 3
0.1/3
66/ 3
0.1/ 3
0.1/ 3
0.1/3
66/ 3
0.1/ 3
0.1/ 3
0.1/3
110/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1

Rated
capacitance

Accuracy
class/
secondary
burden VA

0.01

1a1n0.2/20
dadn3P/100

0.01

1a1n0.2/10
2a2n0.5/20
dadn3P/100

0.02

1a1n0.2/30
dadn3P/100

0.02

1a1n0.2/20
2a2n0.5/20
dadn3P/100

0.01

1a1n0.2/10
2a2n0.5/20
dadn3P/100

0.015

1a1n0.2/20
2a2n0.5/20
dadn3P/100

0.02

1a1n0.2/20
2a2n0.5/20
dadn3P/100

0.007

an0.2/50
dadn3P/100

0.007

1a1n0.2/50
2a2n0.5/75
dadn3P/100

0.01

an0.2/50
dadn3P/100

0.01

1a1n0.2/50
2a2n0.5/75
dadn3P/100

0.01

1a1n0.2/50
2a2n0.5/50
3a3n0.5/50
dadn3P/100

0.015

1a1n0.2/75
2a2n0.5/100
dadn3P/100

Outline
and
installation
hole
Outline
dimensionmm drawing
LW1H
AL1W2

7606851490
425
Pitch of holes
500500

CG
Weight H Height
kg
h
mm

480

610

642

800

Figure 2
7606852100
425
Pitch of holes
500500

6705902040
425
Pitch of holes
480480
7606852100
425
Pitch of holes
550550
6705902040
425
Pitch of holes
480480

7606852100
425
Pitch of holes
550550

480

800

490

800

480

800

490

800

510

800

500

800

Table 3continued

SN

Type

Rated
voltage
kV

Rated
capacitance

Accuracy class/
secondary burden
VA

110/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
110/ 3
0.1/ 3
0.1/ 3
0.1

TYD2115/ 3 -0.01H

115/ 3
0.1/ 3
0.1

0.01

20*

TYD3132/ 3 -0.015H

132/ 3
0.1/ 3
0.1/ 3
0.1

0.015

21*

TYD2220/ 3 -0.0035H 220/ 3


0.1/ 3
TYD12220/ 3 -0.0035H
0.1

0.0035

an0.2/50
dadn3P/100

220/ 3
0.1/ 3
0.1/ 3
0.1

0.0035

1a1n0.2/50
2a2n
0.5/100
dadn3P/100

220/ 3
0.1/ 3
0.1

0.005

TYD3110/

3 -0.02H

14
TYD13110/ 3 -0.02H

15

16

17*

TYD4110/ 3 -0.02H
TYD14110/ 3 -0.02H

TYD3110/ 3 -0.025H
TYD13110/ 3 -0.025H

TYD4110/ 3 -0.025H
TYD14110/ 3 -0.025H

TYD3110/ 3 -0.04H
*

18

TYD13110/ 3 -0.04H

19*

TYD3220/ 3 -0.0035H
*

22

TYD13220/ 3 -0.0035H
TYD2220/ 3 -0.005H
23
TYD12220/ 3 -0.005H
TYD3220/ 3 -0.005H
24
TYD13220/ 3 -0.005H
TYD4220/ 3 -0.005H
25
TYD14220/ 3 -0.005H

220/ 3
0.1/ 3
0.1/ 3
0.1
220/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1

Outline
and
installation
holes
Outline
dimensionmm drawing
LW1H
AL1W2
7606852100
425
Pitch of holes
550550

0.02

1a1n0.2/100
2a2n0.5/100
dadn3P/100

0.02

1a1n0.2/50
2a2n0.5/50
3a3n0.5/50
dadn3P/100

7606852120
425
Pitch of holes
550550

0.025

1a1n0.2/100
2a2n0.5/100
dadn3P/100

7606852100
425
Pitch of holes
550550

0.025

1a1n0.2/75
2a2n0.5/75
3a3n3P/75
dadn3P/100

7606852080
425
Pitch of holes
550550

0.04

1a1n0.2/100
2a2n0.5/100
dadn3P/100
an0.2/50
dadn3P/100
1a1n0.2/75
2a2n0.5/100
dadn3P/100

an0.2/50
dadn3P/100

0.005

1a1n0.2/50
2a2n0.5/75
dadn3P/100

0.005

1a1n0.2/50
2a2n0.5/50
3a3n0.5/50
dadn3P/100

7606852130
425
Pitch of holes
550550
6705902000
425
Pitch of holes
480480
7606852335
430
Pitch of holes
550550
6705903354
425
Pitch of holes
480480
7606853390
425
Pitch of holes
550550
6605903354
425
Pitch of holes
480480
7606853390
425
Pitch of holes
550550
7606853390
425
Pitch of holes
550550

Weight
kg

CG
Height
h
mm

610

800

715

800

610

800

715

800

740

1000

460

800

740

1100

668

1340

780

1375

668

1340

780

1375

780

1375

Figure 2

Figure 3

10

Table 3continued

SN

Type

Rated
voltage
kV

26

27

28

29

30

31*

32*

33*

34

35

36*

37*

220/ 3
0.1/ 3
0.1/ 3
TYD13220/ 3 -0.0075H
0.1
220/ 3
TYD3220/ 3 -0.01H
0.1/ 3
0.1/ 3
TYD13220/ 3 -0.01H
0.1
220/ 3
TYD4220/ 3 -0.01H
0.1/ 3
0.1/ 3
TYD14220/ 3 -0.01H
0.1/ 3
0.1
220/ 3
TYD3220/ 3 -0.0125H
0.1/ 3
0.1/ 3
TYD13220/ 3 -0.0125H
0.1
220/ 3
TYD4220/ 3 -0.0125H 0.1/ 3
0.1/ 3
TYD14220/ 3 -0.0125H 0.1/ 3
0.1
220/ 3
0.1/ 3
TYD3220/ 3 -0.02H
0.1/ 3
0.1
TYD3220/ 3 -0.0075H

TYD2230/ 3 -0.005H

230/ 3
0.1/ 3
0.1

275/ 3
TYD3275/ 3 -0.0075H 0.1/ 3
0.1/ 3
0.1
330/ 3
TYD3330/ 3 -0.005H 0.1/ 3
0.1/ 3
TYD13330/ 3 -0.005H
0.1
330/ 3
TYD4330/ 3 -0.005H 0.1/ 3
TYD14330/ 3 -0.005H 0.1/ 3
0.1/ 3
0.1
330/ 3
TYD3330/ 3 -0.0075H 0.1/ 3
0.1/ 3
TYD13330/ 3 -0.0075H
0.1
330/ 3
TYD3330/ 3 -0.01H
0.1/ 3
0.1/ 3
TYD13330/ 3 -0.01H
0.1

Rated
capacitance
F

Accuracy
class/
secondary
burden VA

0.0075

1a1n0.2/100
2a2n0.5/100
dadn3P/100

0.01

1a1n0.2/100
2a2n0.5/100
dadn3P/100

0.01

1a1n0.2/50
2a2n0.5/50
3a3n0.5/50
dadn3P/100

0.0125

1a1n0.2/100
2a2n0.5/100
dadn3P/100

0.0125

1a1n0.2/100
2a2n3P/100
3a3n3P/100
dadn3P/100

0.02

1a10.2/100
2a20.5/100
dadn3P/100

0.005

an0.2/50
dadn3P/100

0.0075

1a1n0.2/75
2a2n0.5/75
dadn3P/100

0.005

1a1n0.2/75
2a2n0.5/100
dadn3P/100

0.005

1a1n0.2/50
2a2n0.5/50
3a3n3P/50
dadn3P/100

0.0075

1a1n0.2/100
2a2n0.5/100
dadn3P/100

0.01

1a1n0.2/100
2a2n0.5/100
dadn3P/100

Outline and
installation
holes
dimensionmm
LW1H
AL1W2

Outline
drawing

7606853440
425
Pitch of holes
550550

7606853410
425
Pitch of holes
550550

CG
Height
h
mm

Weight
kg

785

1375

860

1375

1025

1375

860

1375

1025

1375

1100

1580

668

1340

1441

2230

Figure 3

7606853440
425
Pitch of holes
550550
7606853410
425
Pitch of holes
550550
7606853530
425
Pitch of holes
550550
6605903340
425
Pitch of holes
480480

7606854770
430
Pitch of holes
550550
Figure 4

11

Table 3continued

SN

Type

Rated
voltage
kV

TYD3400/ 3 -0.005H
38

39

TYD3500/ 3 -0.005H
TYD13500/ 3 -0.005H

TYD4500/ 3 -0.005H
40
TYD14500/ 3 -0.005H

41

TYD3525/ 3 -0.005H
TYD13525/ 3 -0.005H
TYD4525/ 3 -0.005H

42
TYD14525/ 3 -0.005H

43

TYD3550/ 3 -0.005H
TYD13550/ 3 -0.005H
TYD4550/ 3 -0.005H

44

45

TYD14550/ 3 -0.005H

TYD13765/ 3 -0.005H

TYD14765/ 3 -0.005H
46

400/ 3
0.1/ 3
0.1/ 3
0.1
500/ 3
0.1/ 3
0.1/ 3
0.1
500/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
525/ 3
0.1/ 3
0.1/ 3
0.1
525/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
550/ 3
0.1/ 3
0.1/ 3
0.1
550/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1
765/ 3
0.1/ 3
0.1/ 3
0.1
765/ 3
0.1/ 3
0.1/ 3
0.1/ 3
0.1

Rated
capacitance
F

Accuracy class/
secondary burden
VA

1a1n0.2/75

Outline and
installation
holes
dimensionmm
LW1H
AL1W2

dadn3P/75

CG
Weight Height
h
kg
mm

7606855490

2a2n0.5/75
0.005

Outline
drawing

430
Pitch

of

holes

1825

2400

2020

2800

2020

2800

2360

2800

2020

2800

2020

2800

2020

2800

3220

3900

550550
1a1n0.2/75
0.005

2a2n0.5/75
dadn3P/75
1a1n0.2/75
2a2n0.5/75

0.005

3a3n3P/75

Figure 5

dadn3P/100
1a1n0.2/75
0.005

2a2n0.5/75
dadn3P/75

0.005

7606856185
430

1a1n0.2/75

Pitch of holes

2a2n0.5/75

550550

3a3n3P/75
dadn3P/100
1a1n0.2/75

0.005

2a2n0.5/75
dadn3P/75
1a1n0.2/75

0.005

2a2n0.5/75
3a3n3P/75
dadn3P/100
1a1n0.2/50

0.005

2a2n0.5/50
dadn3P/50

0.005

10077108265

1a1n0.2/30

6 34

evenly

2a2n0.5/50

distributed on

3a3n0.5/50

the circle 805

Figure 6

dadn3P/50

12

Table 3 (end)

SN

Type

Rated
voltage

Rated
capacitance

kV

Accuracy class/
secondary burden
VA

Outline and
installation
holes
dimensionmm
LW1H
AL1W2

Outline
drawing

CG
Weight Height
h
kg
mm

Capacitor divider
103571012600
6 34

47

1000/
0.1/
TYD 1000/ 3 -0.005H
0.1/
0.1/
separation
0.1

3
3
3

0.005

evenly

1a1n0.2/15

distributed on

2a2n0.5/15

the circle805

3a3n0.5/15

electromagnetic unit

dadn3P/15

1215810645

Figure 7

5880

425
Pitch

of

holes

550550
Note CG: centre of gravity.
Type with *in SN is irregular product, which is not recommended.
Accuracy class/secondary burden is made a commissioning in accordance with the purchaser.

13

5520

Table 4 List of Supply of CVTs


Parts of each CVT
capacitor

Electromagnetic unit
SN

Type

Single stack
Whole

Separation
Electromagnetic
unit

connector

divider
Lower section
capacitor

Middle

Upper

Line

corona

stud

section section

nut

Spring

Flat

washer

washer

terminal

Package

Instruction

case

manual

divider

TYD35

TYD66

TYD110

TYD115

TYD132

TYD220

TYD230

TYD275

1
1

16

16

16

16

16

16

16

32

32

32

TYD330

16

32

32

32

10

TYD400

20

40

40

40

11

TYD500

20

40

40

40

12

TYD500

30

60

60

60

13

TYD765

30

60

60

60

14

TYD1000

40

80

80

80

1
1

15
Note Each section capacitor is assembled on the basis of capacitor number and sequence on nameplate.
Stud of product 220kV is GB/T 901lineM12120,busbarM14130. Stud of product 330kV is GB/T 901M14130. Stud of 500kV product is GB/T 901M14
140. Stud of product 765kV is GB/T 901M16140.Stud of 1000kV product is GB/T 901M20160. Nuts and washers match to corresponding studs
Ex-factory line terminals has been mounted on the cover on upper section capacitor divider or put in the package case of corona.
Serial number of design is filled in . Please see clause 3.1 for details.

14

Figure 2
1 High-voltage capacitance C1

2 Intermediate voltage capacitance C2

3 Intermediate-voltage bushing

4 Secondary outgoing box

5 Connection board

6 Electromagnetic unit

7 Low-voltage bushing

8 Line terminal

9 Connection sheet

D Damp device

N Carrier communication terminal

L Compensation reactor

P Protection device

T Intermediate transformer

XL Low-voltage terminal of compensation reactor


1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
15

Figure 3
1 High-voltage capacitance C1

2 Intermediate voltage capacitance C2

3 Intermediate-voltage bushing

4 Secondary outgoing box

5 Connection board

6 Electromagnetic unit

7 Low-voltage bushing

8 Line terminal

9 Connection sheet

D Damp device

N Carrier communication terminal

L Compensation reactor

P Protection device

T Intermediate transformer

XL Low-voltage terminal of compensation reactor


1a1n Secondary 1a1n winding terminal
2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
16

Figure 4
1 Corona

2 High-voltage capacitance C1

4 Intermediate-voltage bushing

Intermediate capacitance C2

5 Secondary outgoing box

6 Connection board

7 Electromagnetic unit

8 Low-voltage bushing

9 Line terminal

10 Connection sheet

D Damp device

N Carrier communication terminal

L Compensation reactor

P Protection device

T Intermediate transformer

XL Low-voltage terminal of compensation reactor

1a1n Secondary 1a1n winding terminal


2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
17

Figure 5
1 Corona

2 High-voltage capacitance C1

4 Intermediate-voltage bushing

Intermediate capacitance C2

5 Secondary outgoing box

6 Connection board

7 Electromagnetic unit

8 Low-voltage bushing

9 Line terminal

10 Connection sheet

D Damp device

N Carrier communication terminal

L Compensation reactor

P Protection device

T Intermediate transformer

XL Low-voltage terminal of compensation reactor

1a1n Secondary 1a1n winding terminal


2a2n Secondary 2a2n winding terminal
dadn Residual voltage winding terminal
18

Figure 6
1 Corona

2 High-voltage capacitance C1

4 Intermediate-voltage bushing

Intermediate capacitance C2

5 Secondary outgoing box

6 Connection board

7 Electromagnetic unit

8 Low-voltage bushing

9 Line terminal

10 Connection sheet

D Damp device

N Carrier communication terminal

L Compensation reactor

P Protection device

T Intermediate transformer

XL Low-voltage terminal of compensation reactor

1a1n Secondary 1a1n winding terminal

2a2n Secondary 2a2n winding terminal

3a3n Secondary 3a3n winding terminal

dadn Residual voltage winding terminal


19

Figure 7
1 Corona
2 Line terminal
3 High-voltage capacitance C1
4 Intermediate capacitance C2
5 Low-voltage bushing
6 Pedestal
7 Intermediate-voltage bushing
8
Electromagnetic unit
9 Secondary outgoing box
10 Earthing board
11 Connection wire
P Protection device
L Compensation reactor
T Intermediate transformer
D Damp device
N Carrier communication terminal
A2 Primary voltage terminal of electromagnetic unit
XL Low-voltage terminal of compensation reactor
A1 Intermediate terminal of capacitor divider
1a1n Secondary 1a1n winding terminal 2a2n Secondary 2a2n winding terminal
3a3n Secondary 3a3n winding terminal dadn Residual voltage winding terminal
20

Figure 8 Schematic diagram of earthing switch handle position

Figure 9-1

Principle diagram

of C1 and tan measurement

Figure 9

Figure 9-2

Principle diagram

of C2 and tan measurement

Principle diagram of capacitance and tan anti-connection measurement of


auto anti-interference dielectric loss instrument

Figure 10-1 Principle diagram


of C1 and tan measurement

Figure 10-2

Principle diagram

of C2 and tan measurement

Figure 10 Principle diagram of capacitance and tan self-excitation measurement of


auto anti-interference dielectric loss instrument

21

Figure 11-1

Principle diagram of capacitance C1 and tan self-excitation measurment of auto


anti-interference dielectric loss instrument

Figure 11-2 Principle diagram of capacitance C2 and tan self-excitation measurement of


auto anti-interference dielectric loss instrument

Figure 11 Principle diagram of capacitance and tan self-excitation measurement of


auto anti-interference dielectric loss instrument