Académique Documents
Professionnel Documents
Culture Documents
D Paunescu, F Lazar
B Pavlov
J ZakonjSek
Transelectrica, Romanis
THEORETICAL BACKGROUND
z, z,+ + z,
E .E,
.,
6)
= -j
cos( .
t
flow as a function of
,-.,
OSCILLATION
DETECTION
IMPEDANCE MEASUREMENT
BASED
ON
-+
Figure 5: = / A t
SO
60
40
d 20
?i
n
-20
40
Figure 6: Impedance trajectory as seen by pole slip protection in Tantareni SiS after a three-phase fault at Kozloduy S/S
This is sufficient condition for protection to declare
system oscillation. Big generation units behind line ends
do not permit long oscillations with more than one slip.
The pole slip protection is for this reason set to trip the
corresponding circuit breaker even before the complete
slip really appears, in this case when the measured
impedance reaches the leA tripping line at
approximately (-5 + j28) ohm.
The operating characteristic of the pole slip protection
applied provides a possibility to control the tripping
conditions with respect to the phase angle between
EMFs of power generators in both subsystems. This
prevents additional stresses of primary equipment. It
also provides remote hack-up possibilities for swings
with their ECO behind the remote ends of the protected
line (see the area around the Kozloduy SiS in Figure 6).
CONCLUSIONS
Asynchronous operating conditions are a fact in modem
power systems and should he eliminated as fast as
References
1. Y G Painthankar, 2000, Transmission Network
Protection - Theoly and Practice
2. ABB Manual IMRK 506 074,06-2001