Vous êtes sur la page 1sur 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5


MLFB: 7SD52215NB997HJ4
Parameter set version: V04.61.04
Device path: C:\Siemens\Digsi4\D4PROJ\Dewa\P7DI\GV\SD\00000037
Author:
Creation date: 30.03.11 08:56:26
Last modified: 02.04.11 18:49:12
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 General Device Settings
1.1 Group Device
2 Power System Data 1
2.1 Group Power System Data 1; Group Transformers
2.2 Group Power System Data 1; Group Power System
2.3 Group Power System Data 1; Group Breaker
2.4 Group Power System Data 1; Group CT Data
3 Settings groups
3.1 Group Power System Data 2; Group Local Line End
3.2 Group Power System Data 2; Group Line Status
3.3 Group Differential Protection; Group General
3.4 Group Differential Protection; Group Diff Protection
3.5 Group Differential Protection; Group Inrush
3.6 Group Intertrip
3.7 Group DTT Direct Transfer Trip
3.8 Group Backup overcurrent; Group General
3.9 Group Backup overcurrent; Group I>>
3.10 Group Backup overcurrent; Group I>
3.11 Group Backup overcurrent; Group Inverse
3.12 Group Backup overcurrent; Group I - STUB
3.13 Group Measurement Supervision; Group Symmetry
3.14 Group Measurement Supervision; Group Fuse Fail. Mon.
3.15 Group Measurement Supervision; Group I/U-Monitoring
3.16 Group Measurement Supervision; Group VT mcb
3.17 Group Measurement Supervision; Group Load Angle
3.18 Group Earth fault overcurrent; Group General
3.19 Group Earth fault overcurrent; Group 3I0>>>
3.20 Group Earth fault overcurrent; Group 3I0>>
3.21 Group Earth fault overcurrent; Group 3I0>
3.22 Group Earth fault overcurrent; Group 3I0 InverseTime
3.23 Group Earth fault overcurrent; Group Direction
3.24 Group Fault Locator; Group Fault Locator
3.25 Group Breaker Failure; Group Breaker Failure

3
3
4
4
4
4
4
5
5
5
5
5
5
6
6
6
6
6
6
7
7
7
7
7
8
8
8
8
8
9
9
9
9
Page 1 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

3.26 Group Breaker Failure; Group End fault stage


3.27 Group Breaker Failure; Group PoleDiscrepancy
3.28 Group Protection Interface (Port D+E); Group General
3.29 Group Protection Interface (Port D+E); Group Interface 1
3.30 Group Differential Topology

02.04.11 19:09:41

9
10
10
10
10

Page 2 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

1 General Device Settings


1.1 Group Device
No.
0610

Settings
Fault Display on LED / LCD

Value

Group

Display Targets on every Pickup All

0625A Minimum hold time of lachted LEDs

0 min

All

0640

image 1

All

Start image Default Display

Page 3 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

2 Power System Data 1


2.1 Group Power System Data 1; Group Transformers
No.

Settings

Value

Group

0201 CT Starpoint

towards Line

All

0203 Rated Primary Voltage

400.0 kV

All

0204 Rated Secondary Voltage (Ph-Ph)

110 V

All

0205 CT Rated Primary Current

2000 A

All

0206 CT Rated Secondary Current

1A

All

0210 U4 voltage transformer is

not connected All

0211 Matching ratio Phase-VT To Open-Delta-VT

1.00

0220 I4 current transformer is

not connected All

0221 Matching ratio I4/Iph for CT's

1.000

All
All

2.2 Group Power System Data 1; Group Power System


No.
0207

Settings

Value

System Starpoint is

Group

Solid Earthed

All

0208A 1-1/2 Circuit breaker arrangement

NO

All

0230

Rated Frequency

50 Hz

All

0236

Distance measurement unit

km

All

0237

Setting format for zero seq.comp. format

Zero seq. comp. factor K0 and angle(K0)

All

2.3 Group Power System Data 1; Group Breaker


No.

Settings

Value

Group

0240A Minimum TRIP Command Duration

0.20 sec All

0241A Maximum Close Command Duration

1.00 sec All

0242

0.10 sec All

Dead Time for CB test-autoreclosure

2.4 Group Power System Data 1; Group CT Data


No.

Settings

Value Group

0251 k_alf/k_alf nominal

1.50

All

0253 CT Error in % at k_alf/k_alf nominal

3.0 %

All

0254 CT Error in % at k_alf nominal

10.0 % All

Page 4 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3 Settings groups
3.1 Group Power System Data 2; Group Local Line End
No.

Settings

Value

Group

1103 Measurement: Full Scale Voltage (100%)

400.0 kV

1104 Measurement: Full Scale Current (100%)

2000 A

1105 Line Angle

86

1107 P,Q operational measured values sign

not reversed

1111 x' - Line Reactance per length unit

0.1411 Ohm / km

1112 c' - capacit. per unit line len. F/km

0.010 F/km

1113 Line Length

11.9 km

1120 Zero seq. comp. factor K0 for zone Z1

0.540

1121 Zero seq. comp. angle for zone Z1

-6.20

1122 Zero seq.comp.factor K0,higher zones >Z1

1.000

1123 Zero seq. comp. angle, higher zones >Z1

0.00

1124 center phase of feeder

unknown or symmetrical A

3.2 Group Power System Data 2; Group Line Status


No.

Settings

Value

Group

1130A Pole Open Current Threshold

0.05 A

1131A Pole Open Voltage Threshold

30 V

1132A Seal-in Time after ALL closures

0.30 sec

1133A minimal time for line open before SOTF

1.00 sec

1134

Recognition of Line Closures with

Manual Close BI only A

1135

RESET of Trip Command

Pickup Reset

1136

open pole detector

OFF

1150A Seal-in Time after MANUAL closures

0.30 sec

1151

Manual CLOSE COMMAND generation

NO

1152

MANUAL Closure Impulse after CONTROL

<none>

All

3.3 Group Differential Protection; Group General


No.

Settings

Value Group

1201 State of differential protection ON

3.4 Group Differential Protection; Group Diff Protection


No.

Settings

Value

Group

1210

I-DIFF>: Pickup value

0.30 A

1213

I-DIFF>: Value under switch on condition

0.30 A

1217A I-DIFF>: Trip time delay

0.00 sec A

1219A Min. local current to release DIFF-Trip

0.00 A

1233

I-DIFF>>: Pickup value

1.3 A

1235

I-DIFF>>: Value under switch on cond.

1.3 A

Page 5 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3.5 Group Differential Protection; Group Inrush


No.

Settings

Value

Group

2301 Inrush Restraint

OFF

2302 2nd. harmonic in % of fundamental

15 %

2303 Cross Block

NO

2305 Maximum inrush-peak value

15.0 A

2310 Time for Crossblock with 2nd harmonic

0.00 sec A

3.6 Group Intertrip


No.

Settings

Value

Group

1301 State of transmit. the intertrip command

YES

1302 Reaction if intertrip command is receiv.

Trip

1303 Delay for intertrip via binary input

0.02 sec A

1304 Prolongation for intertrip via bin.input

0.00 sec A

3.7 Group DTT Direct Transfer Trip


No.

Settings

Value

2201 Direct Transfer Trip (DTT) ON


2202 Trip Time Delay

Group
A

0.00 sec A

3.8 Group Backup overcurrent; Group General


No.

Settings

2601 Operating mode

Value
ON

Group
A

2602 Trip time delay after SOTF 0.00 sec A

3.9 Group Backup overcurrent; Group I>>


No.

Settings

Value Group

2610 Iph>> Pickup

1.25 A A

2611 T Iph>> Time delay

oo sec A

2612 3I0>> Pickup

oo A

2613 T 3I0>> Time delay

oo sec A

2614 Instantaneous trip via Teleprot./BI

NO

2615 Instantaneous trip after SwitchOnToFault

NO

3.10 Group Backup overcurrent; Group I>


No.

Settings

Value Group

2620 Iph> Pickup

oo A

2621 T Iph> Time delay

oo sec A

2622 3I0> Pickup

oo A

2623 T 3I0> Time delay

oo sec A

2624 Instantaneous trip via Teleprot./BI

NO

2625 Instantaneous trip after SwitchOnToFault

NO

Page 6 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3.11 Group Backup overcurrent; Group Inverse


No.

Settings

Value

Group

2640 Ip> Pickup

oo A

2642 T Ip Time Dial

oo sec

2646 T Ip Additional Time Delay

0.00 sec

2650 3I0p Pickup

oo A

2652 T 3I0p Time Dial

oo sec

2656 T 3I0p Additional Time Delay

0.00 sec

2660 IEC Curve

Normal Inverse A

2670 Instantaneous trip via Teleprot./BI

NO

2671 Instantaneous trip after SwitchOnToFault

NO

3.12 Group Backup overcurrent; Group I - STUB


No.

Settings

Value Group

2630 Iph> STUB Pickup

oo A

2631 T Iph STUB Time delay

oo sec A

2632 3I0> STUB Pickup

oo A

2633 T 3I0 STUB Time delay

oo sec A

2634 Instantaneous trip via Teleprot./BI

NO

2635 Instantaneous trip after SwitchOnToFault

NO

A
A

3.13 Group Measurement Supervision; Group Symmetry


No.
2901

Settings

Value Group
OFF

2902A Voltage Threshold for Balance Monitoring

Measurement Supervision

50 V

2903A Balance Factor for Voltage Monitor

0.75

2904A Current Balance Monitor

0.10 A A

2905A Balance Factor for Current Monitor

0.50

2908A T Balance Factor for Voltage Monitor

5 sec

2909A T Current Balance Monitor

5 sec

3.14 Group Measurement Supervision; Group Fuse Fail. Mon.


No.
2910

Settings

Value

Fuse Failure Monitor

Group

ON

2911A Minimum Voltage Threshold U>

30 V

2912A Maximum Current Threshold I<

0.10 A

2913A Maximum Voltage Threshold U< (3phase)

30 V

2914A Delta Current Threshold (3phase)

0.10 A

2915

with current supervision A

Voltage Failure Supervision

2916A Delay Voltage Failure Supervision

3.00 sec

3.15 Group Measurement Supervision; Group I/U-Monitoring


No.

Settings

Value

Group

2931 Fast broken current-wire supervision Alarm only A

Page 7 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3.16 Group Measurement Supervision; Group VT mcb


No.

Settings

Value Group

2921 VT mcb operating time 0 ms

3.17 Group Measurement Supervision; Group Load Angle


No.

Settings

Value Group

2941 Limit setting PhiA

200

2942 Limit setting PhiB

340

2943 Minimum value I1>

0.05 A A

2944 Minimum value U1> 20 V

3.18 Group Earth fault overcurrent; Group General


No.

Settings

Value

Group

3101

Earth Fault overcurrent function

ON

3102

Block E/F for Distance protection

NO

3174

Block E/F for Distance Protection Pickup

in each zone

3175

Block E/F for Differential Prot. Pickup

NO

3104A Stabilisation Slope with Iphase

10 %

3170

2nd harmonic ratio for inrush restraint

15 %

3171

Max.Current, overriding inrush restraint

7.50 A

3172

Instantaneous mode after SwitchOnToFault

with Pickup and direction A

3173

Trip time delay after SOTF

0.00 sec

3.19 Group Earth fault overcurrent; Group 3I0>>>


No.

Settings

Value

Group

3110 Operating mode

Inactive

3111 3I0>>> Pickup

4.00 A

3112 T 3I0>>> Time delay

0.30 sec A

3113 Instantaneous trip via Teleprot./BI

NO

3114 Instantaneous trip after SwitchOnToFault

NO

3115 Inrush Blocking

NO

3.20 Group Earth fault overcurrent; Group 3I0>>


No.

Settings

Value

Group

3120 Operating mode

Non-Directional A

3121 3I0>> Pickup

0.08 A

3122 T 3I0>> Time Delay

oo sec

3123 Instantaneous trip via Teleprot./BI

NO

3124 Instantaneous trip after SwitchOnToFault

NO

3125 Inrush Blocking

NO

Page 8 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3.21 Group Earth fault overcurrent; Group 3I0>


No.

Settings

Value

Group

3130 Operating mode

Inactive A

3131 3I0> Pickup

0.05 A

3132 T 3I0> Time Delay

oo sec

3133 Instantaneous trip via Teleprot./BI

NO

3134 Instantaneous trip after SwitchOnToFault

NO

3135 Inrush Blocking

NO

3.22 Group Earth fault overcurrent; Group 3I0 InverseTime


No.

Settings

Value

Group

3140 Operating mode

Inactive

3141 3I0p Pickup

0.10 A

3143 3I0p Time Dial

0.50 sec

3147 Additional Time Delay

0.00 sec

3148 Instantaneous trip via Teleprot./BI

NO

3149 Instantaneous trip after SwitchOnToFault

NO

3150 Inrush Blocking

NO

3151 IEC Curve

Normal Inverse A

3.23 Group Earth fault overcurrent; Group Direction


No.
3160

Settings

Value

Polarization

Group

with U0 + IY or U2 A

3162A ALPHA, lower angle for forward direction

338

3163A BETA, upper angle for forward direction

130

3164

Min. zero seq.voltage 3U0 for polarizing

1.9 V

3166

Min. neg. seq. polarizing voltage 3U2

1.9 V

3167

Min. neg. seq. polarizing current 3I2

0.12 A

3168

Compensation angle PHI comp. for Sr

255

3169

Forward direction power threshold

0.3 VA

3.24 Group Fault Locator; Group Fault Locator


No.

Settings

Value Group

3802 Start fault locator with TRIP A


3806 Load Compensation

YES

3.25 Group Breaker Failure; Group Breaker Failure


No.

Settings

Value

Group

3901 Breaker Failure Protection

ON

3902 Pick-up threshold I>

0.09 A

3904 T1, Delay after 1pole start (local trip)

0.00 sec A

3905 T1, Delay after 3pole start (local trip)

0.00 sec A

3906 T2, Delay of 2nd stage (busbar trip)

0.15 sec A

3907 T3, Delay for start with defective bkr.

oo sec

3908 Trip output selection with defective bkr

NO

3909 Check Breaker contacts

NO

Page 9 of 10

SIMATIC

DEWA / REVISED V1.2 / BRSH SS_F_DREP_M1FP_7SD5/7SD522

02.04.11 19:09:41

3.26 Group Breaker Failure; Group End fault stage


No.

Settings

3921 End fault protection

Value

Group

OFF

3922 Trip delay of end fault protection 2.00 sec A

3.27 Group Breaker Failure; Group PoleDiscrepancy


No.

Settings

Value

Group

3931 Pole Discrepancy supervision

OFF

3932 Trip delay with pole discrepancy

2.00 sec A

3.28 Group Protection Interface (Port D+E); Group General


No.

Settings

Value

Group

4509 Time delay for data disturbance alarm

0.10 sec A

4510 Time del for transmission failure alarm

6.0 sec

4512 Remote signal RESET DELAY for comm.fail

0.00 sec A

3.29 Group Protection Interface (Port D+E); Group Interface 1


No.

Settings

Value

Group

4501

State of protection interface 1

ON

4502

Connection 1 over

Direct connection with fibre optic cable

4505A Prot 1: Maximal permissible delay time

30.0 ms

4506A Prot 1: Diff. in send and receive time

0.000 ms

4513A Prot 1: Maximal permissible error rate

1.0 %

4515A Prot.1: Block. due to unsym. delay time

YES

3.30 Group Differential Topology


No.

Settings

Value Group

4701 Identification number of relay 1

117

4702 Identification number of relay 2

118

4710 Local relay is

relay 1 A

Page 10 of 10