Conventional fire alarm system products

1 / 16

Conventional fire alarm control panel


AW-CFP2166

Introduction:
1.

AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4
standard.
2. It is modularized design, the panel can extend from 1 zone to 32 zones easily.
3. It has 2 level control mode by a lock
4. It has 24VDC and 5VDC power supply output.
5. It has FIRE and FAULT signal output.
6. It has 2 general sounders output.
7. Each zone has 1 circuit detectors input .
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. It has SILENCE button to stop BUZZER and SOUNDERS.
11. It has EVACUATE button to start a manual fire alarm immediately.
12. It has battery low protection function, when battery voltage l ower than 21VDC, battery will
Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,
DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

2 / 16

be cut off automatically until the mains power is on.


13. It has an optional GSM module for fire alarm by SMS .
14. It is economic, user-friendly and easy maintenance.
Parameters:
ITEM

1Zone panel

2Zone panel

4-16 Zone panel

4-32 Zone panel

AW-CFP2166-01

AW-CFP2166-02

AW-CFP2166-04
-16

AW-CFP2166-0432

Photo

Model No.
Power specification
Mains supply voltage

110VAC or 240VAC

Internal power supply

27.2VDC

Total output current limited

500mA @
240VAC

500mA @
240VAC

3A @ 240VAC

Main supply monitor for fault

Yes

Battery protection for low voltage

Yes

Batteries (default configuration)

12V2AH*2

3A @ 240VAC

Detector circuit specification


Number of circuit

4-16

4-32

Line fault monitor for open circuit

Yes

Line fault monitor for short circuit

Yes

Line fault monitor for detector


removal

Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor

End of Line device

6.8k ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)

Detector continuity diodes

Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted
to give Detector Removal Fault)

Call point resistor value

470 to 680 , 0.225 or 0.5 watt

Maximum number of smoke/heat


detectors per zone

20 (based on a total detector current of 2mA, each detector consuming 100 A).
Note: if End of Line Monitor Unit is fitted, for correct operation maximum voltage
drop must not exceed 12 volts.

Maximum number of manual call


points per zone

No limit

Sounder circuit specification


Number of general circuits

End of line resistor value


Line fault monitor for open circuit

6.8k ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)


Yes

Line fault monitor for short circuit

Yes

Outputs fused AT
Maximum number of bells @ 20mA
of each sounder output

400mA
20

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

3 / 16

Fuses
Battery fuse

1.5A F 20mm

Sounder outputs

500mA F 20mm

Fire and fault output


Output type

NC and NO relay

Maximum current

100mA

Connection block
Largest acceptable conductor size

2.5mm2

Smallest acceptable conductor size

0.75mm2

Size and weight


Dimensions(mm)
Weight (without batteries)

272*200*70mm
4kg

320*231*90mm
5kg

395X502X124
7kg

Weight (with batteries)

5.8kg

6.8kg

9.6kg

362X565X124
8kg
12.5kg

Conventional photoelectric smoke detector

Model No.:AW-CSD311
Item
Operating Voltage Range:
Standby Current:
Maximum Alarm Current (LED on: )
Operating Humidity Range:
Operating Temperature Range:
Adjustable Sensitivity:
Height:
Diameter:

Parameters
9 to 32 VDC Volts Non-polarized
100A @ 24 VDC
55mA @ 24 VDC
10% to 93% Relative Humidity, Non-condensing
14F to 120F (-10C to 49C)
1-2.5%/FT
2.2 (55 mm) installed in Base
4.0 (103 mm)

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

Weight:

4 / 16

5.5 oz. (155 g)

Conventional fix temperature heat detector

Model No.: AW-CTD805


Item
Height:
Diameter:
Weight:
Installation Temperatures:
Operating Humidity Range:
Operating Voltage Range:
Standby Current:
Maximum Alarm Current (LED on: )
Fixed Temperature Rating:

Parameters
2.2 (55 mm) installed in Base
4.0 (103 mm)
5.5 oz. (155 g)
14F to 122F (-10C to50C)
10% to 93% Relative Humidity Non-condensing
9 to 28VDC Volts Non-polarized
40A @ 24 VDC
30mA @ 24 VDC
135F (57C)

Conventional smoke and heat combined detector

Model No.: AW-CSH202


Item
Operating Voltage Range:
Standby Current:

Parameters
9 to 28VDC Volts Non-polarized
60A @ 24 VDC
Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,
DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

Maximum Alarm Current (LED on: )


Operating Humidity Range:
Operating Temperature Range:
Smoke Sensitivity:
Fixed Temperature Rating:
Rate of Rise Detection:
Height:
Diameter:
Weight:

5 / 16

30mA @ 24 VDC
10% to 93% Relative Humidity, Non-condensing
14F to 120F (-10C to 49C)
1.06.26%FT.
135F (57C)
Responds to greater than 15F/min
2.2 (55 mm) installed in Base
4.0 (103 mm)
5.5 oz. (155 g)

Entrance LED

Model No.:AW-EL2166

Manual Call Point


Model No.
AW-CMC2166-1
(Break glass)

Photo

Parameters
Working voltage:
220VAC/50Hz or 24VDC

Maximum current:

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

6 / 16

AW-CMC2166-2

5A (220VAC/50Hz) or

(Manual reset)

8A(24VDC)

Contactor resistance: 0.1


Working temperature:

AW-CMC2166-3
(Buzzer inside)

-10~+50
Relative humidity: max 932%

Bell AW-CBL2166-A (with iron base)

Bell

Model No.

Diameter

Base

Work voltage

Work current
@

Volume(dB)

24VDC
AW-CBL2166-A-4

4 (100mm)

AW-CBL2166-A-6

6(150mm)

AW-CBL2166-A-8

8(200mm)

AW-CBL2166-A-10

10(250mm)

DC6V
DC12V
DC24V
AC110V
AC230V

85
95
25 mA

97
100

Note: default is including the base.


Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,
DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

7 / 16

Bell AW-CBL2166-B (with plastic base)

Model No.

Diameter

AW-CBL2166-B-2
AW-CBL2166-B-3

2 (55mm)
3 (75mm)

AW-CBL2166-B-4

4 (100mm)

AW-CBL2166-B-6

6 (150mm)

AW-CBL2166-B-8

8 (200mm)

AW-CBL2166-B-10
AW-CBL2166-B-12

Work voltage

Current @ 220VAC

Power (VA)

50 mA
80 mA

8
10

97 mA

22

100 mA

25

105 mA

25

10 (250mm)

125 mA

30

12 (300mm)

150 mA

35

110VAC
230VAC

Strobe Horn/Hooter

AW-CSS2166-2
Parameters:

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

8 / 16

AW-CSS2166-2
Work Voltage

DC20V-DC30V

Work Current (average)

95mA

Flash intensity

1.2WS

Flash cycle

<2.0s

Flasher life
Max alarm volume

30000times
100dB

Alarm voice

A: pokice car
B: Fire Truck ( default)
C: Ambulance
134*115*48mm

Size
Flash light

Model No.: AW-CBL2166


Item
Color

Parameters
red (default),green, yellow,blue

Work voltage

12VDC, 24VDC(default)

Light head diameter

65mm

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

9 / 16

Automatic fire extinguisher control panel

Model No.: AW -GEC2158

Parameters:
ITEM

ELECTRICAL RATING

Mains supply

90 to 270VAC, 50Hz/60Hz(100
Watts maximum)

Mains supply fuse

3 Amp ( F3A L250V)

Power supply rating

3 Amps total including battery


charge 28V +/- 2V

Maximum ripple current

200 millivolts

Battery type

Two 12 Volt sealed lead acid in


series.

Battery charge voltage

27.6VDC nominal

Battery charge current

0.7A maximum

Battery fuse

20mm, 3.15 glass

Current draw in mains fail


condition

0.095 Amps

COMMENT

Replace only with similar


type

7Ah maximum

With buzzer sounding

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

Current draw in second


stage alarm
Current

draw

in

post

discharge condition
Maximum current
from batteries

draw

10 / 16

0.235A

Two zones in fire(470


ohm in circuit)

0.310A

solenoid outputs active

3Amps

With
main
disconnected

power

R0V output

Fused at 500Ma with electronic fuse

Sounder outputs

21 to 28V DC Fused at 500mA with


electronic fuse

1.6Amp total load over all


circuits

Fault relay contact rating

5 to 30VDC 1A Amp maximum for


each

Volt free
contact

changeover

Fire relay contact rating

5 to 30VDC 1A Amp maximum for


each

Volt free
contact

changeover

Local fire relay


rating

5 to 30VDC 1A Amp maximum for


each

Volt free
contact

changeover

5 to 30VDC 1A Amp maximum for


each

Volt free
contact

changeover

5 to 30VDC 1A Amp maximum for

Volt

free

changeover

each

contact

Extract contact rating

5 to 30VDC 1A Amp maximum for


each

Volt free
contact

changeover

Zone quiescent current

0mA minimum, 2mA maximum

Terminal capacity

0.5mm2 to 2.5mm2 solid or stranded


wire

Number of detectors per


zone

Dependent on type

Number of sounders per


circuit

Dependent on type and current


consumption

Detection circuit end of line

6K85% 1/2 Watt resistor

Monitored input end of line

6K85% 1/2 Watt resistor

Sounder circuit end of line

10K5% 1/2 Watt resistor

Extinguishant output end of


line

1N4004 Diode

No. of detection circuits

Four 21 to 28V DC

No. of sounder circuits

Three 21 to 28V DC

contact

First stage contact rating


Second stage contact rating

2X first stage, 1 X second


stage

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

Extinguishant release output

21V to 28V DC. Maximum load 1


Amp

Extinguishant release delay

Adjustable 0 to 75 seconds

SIL, AL, FLT, RST inputs

Switched ve, min resistance 0


ohms, max 470 ohms

Zone normal threshold


(Allowable EOL)

10K ohms to 2K ohms

Detector alarm threshold

1K ohms to 390 ohms

Call point alarm threshold

370 ohms to 150 ohms

Short circuit threshold

130 ohms to 0 ohms

Head removal condition

15.5 to 17.5 volts+/- 5%

Cabling

FP200 or equivalent

Monitored inputs
threshold
(Allowable EOL)
Monitored
threshold

11 / 16

5 second steps

Use 6K8 end of line


resistor

Metal cable glands must


be used.

normal
10K ohms to 2K ohms

inputs

alarm

Monitored inputs
circuit threshold

Short

2K ohms to 150 ohms+/-5%


140 ohms to 0 ohms+/-5%

Status unit/Ancillary board


connection

Two wire RS485 connection with


electronic fuse.

Max. of 16 units-RS485
data cable

Status unit power output

21 to 28V DC, Fused at 500mA


with electronic fuse.

300 milliamp maximum


load

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

12 / 16

Beam smoke detector

AW-BK801
Brief introduction
AW-BK801 Line Beam Smoke Fire Detector (hereinafter referred to as detector) is a
long-interval reflection line infrared beam smoke detector which must be used together with a
reflector. In case of smoke on the light path of the detector, the signal arriving at the receiver
is reduced; when the light reduction rate reaches the preset threshold, the detector will produce the
alarm signal; when the light beam is completely blocked, the detector will produce the fault signal
to prevent the false alarm caused by non-fire blockage. Thanks to the built -in uniprocessor with
excellent performance, the detector has a powerful analysis and judgment capability and can
automatically complete the systematic debug, the compensation for external environmental
parameter variation, and the judgment of fire alarm and fault, and also can give status indication
through the indicator lamp and the signal output terminal. The detector adopting a brand-new and
reasonable structural design is sensitive in adjustment, correct in positioning, easy in
installation, and simple and convenient in debuggi ng method. The detector contains a group of
alarm passive normally open contacts and a group of fault alarm normally closed contacts as well
as 420mA standard signal output to be conveniently connected with the fire alarm system and
DCS system of plants of fire fighting equipment.
Characters:
Wide operating voltage range and wide protective area
Self-diagnosis capability, monitoring of faults in the detector
Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,
DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

13 / 16

Field setup of two levels of sensitivity


Built-in microprocessor, intelligentized fire alarm and fault judgment
Fire alarm and fault passive output contacts and standard 4 -20mA standard power supply
output
Smart design of the detection light path, high antijamming performance, seal protocol,
corrosion protection and waterproof performance
Integration of the transmitting part and the receiving part, simple and convenient
installation, good light path collimation
Automatic compensation function, and automatic compensation for factors of received signal
reduction such as dust pollution, position deflection, ageing of the transmitting tube, etc. to
some extent
Automatic calibration function to enable a single person to complete debug within a short
time, simple operation, easy integration of the transmitting part and the receiving part, simple
and convenient installation, good light path collimation
Technical Parameters
Operating Voltage DC16V~DC32V
Adjusting Angle-6 DEG ~+6 DEG
External Dimensions 206mm95mm95 mm lengthwidththickness
Material and Color of the CasingABS, white
Weight450g
Light path Length8m~100m
Operating Currentmonitoring current 12 mAalarm current 22mAdebugging current
20mA
Sensitivity LevelFire level of sensitivityhigh sensitivity???second level of
sensitivitycommon sensitivity
Fire alarm, fault contact output: fire alarm relayrating of contacts 24V/1A, normally
open during normality and normally closed in case of fire alarm
Fault relayrating of contacts 24V/1A, normally closed during normality and normally open
in case of fault
Indication of status of the detector: 1) Debugging Status: the green, red and yellow indicator
lamps light up or flash in a specific mode, see Debug in the download data for detailed
information.
2) Normal monitoring status: the green indicator lamp flashes
periodically.
3) Fire Alarm: the red indicator lamp keeps lightingthe yellow
indicator lamp blacks out. The fire alarm should be cancelled through being powered again.
4) Fault: the yellow indicator lamp keeps lighting; in case of
fault recovery, the fault signal of the detector is automatically cancelled by the detector.
5) If the light path is completely blocked, the detector reports
a fault and the yellow indicator lamp lights up.
Operating EnvironmentTemperature 10~+50 relative humidity 95 without
condensation
Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,
DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

14 / 16

Protective Areathe maximal protective area of the detector 141001400


Pitch of mounting holes Burying installation size--158mm pitch of the fixed holes for
open installation--79 mm96 mm
Application Places
Warehouses, large-scale storage areas, shopping plazas, body-building centers, gymnasiums,
exhibition halls, hotel halls, printing works, costume plants, museums, prisons, etc, as well as space
with light smoke dust.

UV flame detector

AW-FD602-UV
SPECIFICATIONS
Operating Voltage Range:
Standby Current:
Alarm Current
Spectrum:
Detection Angle:
Detection Sensitivity:
with 2Kg ethanol )
Relay Contact Load:
Normal Status:
Alarm Status:
Protection rating:
Operating Humidity Range:
Operating Temperature Range:

12 to 30 VDC Volts
10 mA @ 24 VDC
30 mA @ 24 VDC
180~290nm
110 degree
Grade I, 25m@flame (Container 33cmX33cm,Height 5cm
1A@DC24V
LED blinking in 5 seconds interval
LED lit steady
IP 32
10% to 93% Relative Humidity, Non-condensing
-10C to 50C (14F to 122F)

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com

Conventional fire alarm system products

15 / 16

Height:
Diameter:
Weight:

1.8 (45 mm) installed in Base


4.0 (103 mm)
5.4 oz. (153g)
0

30

100%

80

VERTICAL VIEWING

30

60

60

UV EMISSION
POINT

HORIZONTAL
VIEWING

60

40
20

90

90
ANODE
CATHODE

FIGURE1

VERTICAL VIEWING

Vertical Detection Angular Sensitivity(Directivity)

0
100%

30

80
60

60

40

VERTICAL VIEWING

30

UV EMISSION
POINT

HORIZONTAL
VIEWING

60

20
90

90
ANODE
CATHODE

FIGURE2

HORIZONTAL VIEWING

Horizontal Detection Angular Sensitivity(Directivity)

Address: 18A LANCHESTER WAY, ROYAL OAK INDUSTRIAL ESTATE,


DAVENTRY, NORTHAMPTONSHIRE ENGLAND Zip Code: NN11 8PH
Tel: 447624095053, Fax: 447624095053-803, Mobile: 447624094280
www.asenware.com