GEA DENCO® -OfficeCool with HX-Factor

The future of high-performance air conditioning

engineering for a better world GEA Heat Exchangers


High level, high
temperature return air

26 °C back to the Zone Unit


to complete the cycle

No requirement for large plant rooms

Construction savings

Quiet operation

Energy savings

Installation can be deferred until final build/let

Easy to design
12 –16 °C Conditioned air
under the floor

Quick easy office modifications possible

[2] PR-2013-0008-GB · Subject to modification · K0-11/2013


Individual control of local environment

System redundancy

24 °C Office space quickly and easily adapted for new occupants


Occupants control their
own local environment
depending on their needs

20 °C Quick installation

Mixed air supply


from LECU to room
at low velocity Reduced “slab to slab” height

PR-2013-0008-GB · Subject to modification · K0-11/2013 [3]


GEA Air Handling
Units (AHUs)

GEA Chillers BMS or GEA Standalone Control System

Complete system solutions from GEA


GEA DENCO ® -OfficeCool
components and connections

Zone Unit
The Zone Unit provides the primary air conditioning to its zone, with each zone
measuring up to 300 m 2. Zone Units are drawn through vertical type, either top return
(ZD type) or bottom return (ZU type) supplying conditioned air into a raised floor void.
Zone Units have all necessary components such as filters, cooling coils, control valves,
microprocessor controllers, and inverter driven fan motors to achieve the required
underfloor condition with the maximum efficiencies. Options include heating (electrical,
low-pressure hot water, or direct expansion), and dehumidification and humidification
using water vapour. Zone Unit configuration can be either top return bottom discharge
or bottom return bottom discharge, and are available in three standard sizes (from
10 kW – 30 kW). Other sizes are available on request.

[4] PR-2013-0008-GB · Subject to modification · K0-11/2013


GEA offers complete system solutions

Zone Unit LECUs

Local Environmental Control Unit (LECU)


Each Zone Unit is connected to up to 35 LECUs, which gives the GEA DENCO ® -
OfficeCool Air Conditioning System the exceptional ability to cope with changing office
layout requirements. The LECU is an intelligent fan tile, easily positioned anywhere
in the raised floor and provides the user with control over their “micro-climate”. Each
LECU includes a fan, a modulating damper and intelligent controller and will main-
tain the locally desired set temperature by re-circulating a varying mixture of air from
the room and conditioned air from under the raised floor.

Air Handling Unit (AHU)


The AHU is sized to meet the fresh air requirements of the offices and delivers the
fresh air to the return air side of the Zone Unit.

Chiller
The Chiller is sized to meet the cooling requirements of the entire building.

PR-2013-0008-GB · Subject to modification · K0-11/2013 [5]


5
6 7

4 4

4 4 4

1 Zone Unit 3 Return air grilles 5 AHU 7 Chiller


2 LECU 4 Ceiling grille 6 Heat pump

[6] PR-2013-0008-GB · Subject to modification · K0-11/2013


The GEA DENCO® -OfficeCool concept –
designed to users´ specifications
Configurations for every room size, every requirement and condition

External plant space


The heat rejection equipment, such as Chillers, Heat Pumps and Air Handling Units
can all be installed externally.

Bottom air supply and return (ZU type Zone Unit and LECU)
Where no ceiling is installed or where the integrity of the space above the raised floor
is important, the Zone Unit supplies and returns the air within the access floor space.
This space is simply divided into supply and return air plenums with underfloor
barriers. Cooling and heating can be provided by chilled water and low pressure hot
water or by heat pumps. The space is conditioned by the Zone Unit, and the LECUs
provide the occupants with the ability to control their space.
Benefits at a glance
Almost cost free relocation
Bottom air supply and high level return (ZD type Zone Unit and LECU) capability
The Zone Unit supplies conditioned air into the access floor void and hot air is returned Exceptionally quiet operation
to the Zone Unit at high level. Cooling and heating can be provided by chilled water Local environment control for
and low pressure hot water or by heat pumps. The space is conditioned by the Zone individuals
Unit, and the LECUs provide the occupants with the ability to control their space. Control of temperature and
humidity for a healthier
environment
Bottom air supply and ceiling return (ZD type Zone Unit and LECU) Filtration of both fresh air and
The Zone Unit supplies conditioned air into the access floor void and hot air is returned re-circulated air for a healthier
to the Zone Unit through a suspended ceiling. Cooling and heating can be provided by environment
chilled water and low pressure hot water or by heat pumps. The space is conditioned Economical operation
by the Zone Unit, and the LECUs provide the occupants with the ability to control their Easy maintenance with all
space. services at low level in the
raised floor
Elimination of draughts
Conditioning by external Air Handling Unit (AHU and LECU)
The air conditioning of the space can be done by an externally mounted Air Handling
Unit, which supplies conditioned air through ducts into the access floor. The hot air is
returned to the Air Handling Unit through the ceiling and duct system. The LECUs
provide the occupants with the ability to control their space.

PR-2013-0008-GB · Subject to modification · K0-11/2013 [7]


Components
Zone Unit and LECU

Cooling coils

CW or DX multi-row
constructed
3/8" OD copper tubes
with mechanically
bonded aluminium fins
Coils are tested up to 33 bar

Filter

High-quality EU4 Z-Line filter


F7 filters, EU7 and washable
filters are also available
Differential pressure switch
in the microprocessor
control system indicates
necessary filter change

Heating

Low pressure hot water, with


coils constructed of 3/8” OD
copper tube, and mechanically
bonded aluminium fins
In heat pump installations,
reverse cycle heat pump
provides heating through
the evaporator/condenser coil
Electric Heating (optional),
with stainless steel fins on
heating elements and over
temperature thermostatic
safety cut out

Inverter driven fans

Quantity (1, 2 or 3) depending


on unit size
Double inlet, double width
with forward curved impeller
Directly driven by an integral
motor
Fans will automatically modulate
EC Plug Fans are now available Zone Unit
on some models

[8] PR-2013-0008-GB · Subject to modification · K0-11/2013


Controls LECU and components

Several controller options Grilles


available Rectangular and circular grilles available
Standard controller pC05
All units can be fitted, Fan section
as an option, with a Single forward curved crossflow fan
Trend IQ3Xact control Integrated single IP 44 closed type
Various interfaces for central electric motor
building management EC Centrifugal Fans are available
systems, etc. on request
Monitoring display
Filter (optional)
G2 filter in sheet metal frame

Electric heater
250 or 500 W electric heater

Control system and accessories


Sensors Handheld IR Remote Controller with
IR Receiver PCB or IR Remote Controller
LED display with ability to change air-flow
Water sensor (optional)
or set point
Sensors for measuring
air conditions
Components
PlantWatch Pro touch screen display
PlantVisor for remote system monitoring
Trend IQ View 8 with touch screen display

Steam humidifier (optional)

Proportional control electrode


steam humidifier
Microprocessor control with
alarm and diagnosis unit

LECU
Chilled water control valves

Continously modulated
2- or 3-way valves
Provided with vapour sealed
insulation

PR-2013-0008-GB · Subject to modification · K0-11/2013 [9]


Technical data
Energy savings, carbon footprint and cost-efficiency
Design advice provided by local GEA DENCO ® -OfficeCool specialist office. Specifications and unit schedules provided by local GEA
office for inclusion into design schedules. Life cycle cost analyses (LCCA) can be provided on request. Selection data below, for
standard chilled water units. Full selection carried out by local GEA DENCO ® -OfficeCool specialist office. DX, heat pump and AHU
selections provided on request.

Unit size ZD 12 ZD 28 ZD 42

Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended
Air supply Downflow
Cooling capacity
Total (1) kW 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0
Sensible (1) kW 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5
Fan
Fan type Inverter controlled forward curved centrifugal fan
Fan no. n. 1 1 1 2 2 2 3 3
Air flow (4) m3/h 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600
m3/s 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8
Ext. static pressure Pa 25 25 25 25 25 25 25 25
Fan Power kW 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9
Specific fan power W/l/s 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5
Cooling coil Copper tube / aluminium fin

Water flow (3) l/s 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0
Water temperature °C (3) kPa 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Pressure drop-coil & kPa 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0
valve (1)
Electric heater (optional) Low watt density finned tube
Capacity kW 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0
Current A 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0
Heating steps n. 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0
Humidifier (optional) Fail safe electrode boiler

Capacity kg/h 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
Power kW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Power supply
Power source 400 V / 3 Ph / 50 or 60 Hz
Cooling only power kW 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1
Max. power kW 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9
Piping connection Copper tube
Condensate drain mm 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
Humidifier in. mm 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Chilled water in & out mm 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
Dimension
Length mm 647 647 647 1,247 1,247 1,247 1,847 1,847
Depth mm 654 654 654 654 654 654 654 654
Height mm 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
Weight (2) kg 215 215 215 355 355 355 430 430

(1) Rated at return air 26 °C / 50 % and outdoor air temperature 35 °C; (2) For cooling only unit; (3) 7 / 13 °C; (4) Recommended airflows used to maintain office noise level

[ 10 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


Energy comparison GEA DENCO ® -OfficeCool vs traditional FCU and AHU model Typical building rating achieved in UK

600 A 0-25
B 26-50 47 This is how efficient
the building is.
Costs in €

400
GEA DENCO ®-OfficeCool C 51-75
200
Traditional D76-100
E 101-125
0 F 126-150
ar r ay n g
Ja
n
Fe
b
M A p M Ju Ju
l
Au Se
p c t N ov D e c G Over 150
O

ZU 12 ZU 28 ZU 42

Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap.
Upflow

42.0 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0
32.7 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7

3 1 1 1 2 2 Text 2 3 3 3
8,700 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700
2.4 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4
25 25 25 25 25 25 25 25 25 25
1.8 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8
0.75 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75

1.4 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4
7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
36.0 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0

6.0 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0
9.0 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0
2.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0

1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.0 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0
9.8 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8

22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0

1,847 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847
654 850 850 850 800 800 800 800 800 800
1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
430 230 230 230 370 370 370 445 445 445

PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 11 ]


LECU operation and control
For flexible office concepts

Cooling mode Cooling mode


return air sensor If the room sensor detects that the local tem-
raised modular
independent
floor
perature is too warm, it interrogates the un-
chosen temp

controller
derfloor sensor. If the underfloor tempera-
ture is below that of the room air, the
damper is modulated open to allow cooling
to the space. The damper is modulated suffi-
heater
(optional) ciently to offset the heat gain to the space.
fan fully modulating floor void
damper sensor

Heating mode
Heating mode If the room sensor detects that the local tem-
return air sensor perature is too cold, it interrogates the under-
independent
raised modular
floor sensor. If the underfloor temperature is
floor
chosen temp

controller
above that of the room air, the damper is
modulated open to allow heating to the space.
The damper is modulated sufficiently to off-
set the heat loss to the space.
heater
(optional)
fan fully modulating
damper
floor void
sensor
Recirculation mode
When the room sensor detects that the local
Recirculation mode temperature matches the set point, the damp-
return air sensor er will be closed and the unit will be in recir-
independent
raised modular
culation mode. An adjustable bleed damper
floor
chosen temp

controller
allows sufficient air from the floor void to
provide the fresh air requirements for the
space.

heater
(optional)
Electric heater mode (optional)
fan fully modulating floor void
damper sensor
Under exceptional circumstances, if the
room sensor detects that the local tempera-
Electric heater mode ture is too cold and upon interrogation of the
return air sensor underfloor sensor it is determined that there
independent
raised modular is insufficient heat available, the controller
floor
controller
chosen temp

will modulate the damper fully closed and


initiate the electric heater battery. The heater
will be on until such time that either the un-
der floor temperature increases sufficiently
heater
(optional)
to meet the heating requirement, or the room
fan fully modulating floor void
damper sensor
temperature increases to the set point.

[ 12 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


Local Environment Control Unit (LECU)
The LECU gives the GEA DENCO ® -OfficeCool Air Conditioning System an exceptional
ability to cope with the changing work space layout requirements. It is an intelligent
fan tile, easily positioned anywhere in the floor of any work space. The LECU has 3
selectable fan speeds as standard (although 0-10 volt versions are now available on
some models) and an adjustable set-point to meet users requirements. It maintains the
locally desired set temperature by re-circulating a varying mixture of air from the
room and conditioned underfloor air.

The LECU has its own frame and can be used with stringerless raised floors. It exactly
matches a 600 x 600 raised floor panel and only weighs 18 Kg. Relocation of LECUs can
be accomplished in minutes and enables the GEA DENCO ® -OfficeCool Air Conditioning
System to adapt to your changing work space layout.

Adjustment of the LECU operation is available in different forms. At its simplest,


adjustment of the set point and fan speed can be done directly via an infra red, hand-
held remote control or the optional display mounted on the LECU.

The Building Management System (BMS) allows monitoring or adjustment of the set
point and fan speed as well as monitoring of the entire system using selectable vari-
ables. When the LECU and the Zone Units are networked, the Zone Unit can be con-
trolled by the average of the readings on the room sensors of the LECUs within any
particular zone.

PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 13 ]


Control configuration possibilities
Under what conditions which configuration is used?

Zone Unit 1 Zone Unit 2 Zone Unit 3

On Floor Touch
Screen Group
Controller

RS 485 Serial Card RS 485 Serial Card RS 485 Serial Card


Field Card Field Card Field Card

Data Cable

Building IT
infrastructure

LECU 1 LECU 1 LECU 1

LECU 2 LECU 2 LECU 2 Control System / BMS

5 m network
cable supplied
with each
LECU

Intranet /
Internet

LECU 15 LECU 15 LECU 15 Remote access or


user terminal access

[ 14 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


On Floor Touch
Screen Group A fully linked control system provides communica-
Controller
tion between end users and individual LECUs. With
integration possible between the building´s own BMS
and/or a purpose built control system just for GEA
DENCO ® -OfficeCool.

Linked Zone Unit


Controllers
GEA’s own purpose written software allows for seam-
less communication of all GEA DENCO ® -OfficeCool
components, with data logging, alarm warnings as
standard. User input is possible from many locations
for ease of access, quick and easily adjustable temper-
ature settings for maximum flexibility and comfort
Zone Unit Field Cards
for all.
Building IT
backbone
switch
Other options for layout and operation
There are a number of additional features which
allow the users to get the maximum benefit from the
Standard ethernet cable RJ45
GEA DENCO ® -OfficeCool Air Conditioning System.
An on floor touch screen group controller, or IQView 8,
can be installed in the system. These provide a “mini-
headend” capability for smaller installations that
have no BMS, or where a BMS is installed, it provides
tenants, or users, with the control over the equipment
installed at floor plate level.

Standalone Control System

PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 15 ]


Dimensional drawings and technical data
Zone Unit

ZD version ZU version
Model size ZD 12 ZD 28 ZD 42 ZU 12 ZU 28 ZU 42
Weights and dimensions
Weight kg 215 355 430 230 370 445

Height (H) mm 1,940 1,940 1,940 1,940 1,940 1,940


Width (W) mm 647 1,247 1,847 647 1,247 1,847
Depth (D) mm 654 654 654 850 800 800

ZD 12 ZD 28 ZD 42
1,940

1,940

1,940
H

H
647 654 1,247 654 1,847 654
W D W D W D

Unit Front
600 min

Service
Access

ZU 12 ZU 28 ZU 42
1,940

1,940

1,940
H

647 850 1,247 800 1,847 800


W D W D W D

[ 16 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


LECU

LECU

Weights and dimensions


Weight kg 18
W1: 494 W2: 500

H: 222
Top dimension mm 600 x 600
Height (H) mm 222
Width 1 (W1) mm 494
D1: 637
Width 2 (W2) mm 500 D2: 595
Width 3 (W3) mm 595
Depth 1 (D1) mm 637

W3: 595
Depth 2 (D2) mm 595

Concept Rule of Thumb

Fan FLA 0.5 Approx. Area Approx. no. of


Zone Unit
W 40 capacity covered LECUs required

Electric heater FLA 2.2 ZD 42 30 kW 300 m2 15


W 50 ZD 28 20 kW 200 m 2
10
Unit without heater fitted FLA 0.5 ZD 12 10 kW 100 m 2
5
Unit with heater fitted FLA 2.7 To calculate approximate number of Zone Units:
LECU underfloor pressure 0 (Pa) No. of Zone Units = total load / approx. capacity
Fan Speed Airflow Noise Level
To calculate approximate number of LECUs:
m3/s m3/hr NR
Number of LECUs = supply airflow / 0.11
1 0.08 288 28
2 0.1 360 33 To double check the number of LECUs:
3 0.12 432 40 Number of LECU = floor plate area / 15 m2

* Approximate distance between unit outlet 25 m

PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 17 ]


Solutions with HX-Factor
The HX-Factor is our promise. It stands for our

unique expertise in heat exchange (HX = HEAT

EXCHANGE) and marks out all our products

and services. GEA DENCO ® -OfficeCool is a very

modular solution with systematic sophistication,

which promises the following: made-to-measure

and space-saving climate control with maximum

reliability and energy-efficiency.

Quality
Certificates
Quality Assurance – Always focusing on the customer
EN ISO 9001:2008
CE marking for all EU Quality management with HX-Factor from development to after-sales
relevant products We, the GEA experts for climate and environment solutions, are the European market
Safety of Machinery: leaders for the entire spectrum of air treatment. Quality is one of our key success factors.
EN 60204-1:2006+A1:2009 Looking back on more than 100 years of experience we have continuously improved
Safety of Machinery: and optimized our products and business operations, keeping one central goal in focus:
N ISO 12100-1:2003 Exceeding our customers´ expectations. Our major quality feature is the HX-Factor. It
Safety of Machinery: is our performance commitment and stands for unique expertise in heat exchange (HX
EN ISO 12100-2:2003 = HEAT EXCHANGE). The HX-Factor is the one special personal strength that every
EMC Emissions: single employee invests into the production processes. In order to keep our staff as
EN 61000-6-3:2007 healthy and motivated as possible, we are committed to comply with applicable regu-
EMC Immunity: lations and requirements. Regular training ensures that our employees maintain their
EN 61000-6-2:2005 skills in accordance with the latest developments. The HX-Factor is also the sum of all
Refrigeration Systems: attributes that make our products convincing – in the case of DENCO ® -OfficeCool it is
EN 378-1/2/3/4:2008 cost and energy efficiency as well as flexibility. Finally, the HX-Factor is what we live
ASME 9 in the heat exchange business to be engineering for a better world. Numerous certifi-
cations prove our competence.

[ 18 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


Production facility in Wuhu, China Factory in Wurzen, Germany Looking inside the GEA site at Hereford, UK

Aerial photograph showing the factory Production facility in Pune, India The Turkey location in Istanbul
in Liberec, Czech Republic

Manufacturing Centers
Air treatment competence around the globe

Over the past 100 years the GEA experts for room climate solutions have established Global approach
an international network of manufacturing sites. Centers of excellence for air handling International quality standards
units, close control units, decentral air treatment, and clean rooms are located in several Constant improvement
countries throughout Europe and Asia. All of them deal constantly with the continu- Flexible standardization
ous improvement in production processes and optimization according to the latest Just in time production
international standards. With a clear focus on standardization, all sites can assure a Customer in focus
high level of production flexibility. Furthermore, just in time production with short
delivery times helps fulfil customer requirements. With integrated research and devel-
opment facilities, we are able to handle even the most technically demanding projects.
One of our special skills is advanced knowledge in metal sheet processing. No matter
what our customers ask of us – reliability is the most decisive feature that character-
izes all GEA sites.

PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 19 ]


References
Solutions for every climatic demand

MEPC Limited Public Authority for Applied Education and


MEPC manages some of the UK's best known commercial prop- Training (PAAET) – AESS Building, Kuwait
erty, with seven Business Estates set in prime locations through- PAAET selected the GEA DENCO ® -OfficeCool underfloor air
out the UK. Together they provide over 7 million sq ft of high conditioning system for its new education campus in the Shu-
quality space for more than 1,000 organizations, employing over waikh district of Kuwait. GEA Middle East FZE supplied 416 x
20,000 people. MEPC chose the GEA DENCO ® -OfficeCool un- Zone type Air Handling Units and 5,000 x GEA LECUs for
derfloor air conditioning system for over 10,000 sq m office ac- the central tower and administrative wings of this building.
commodation, across 6 new buildings. In total, GEA installed All of the equipment supplied for this project was manufac-
70 Zone Units and 850 Local Environmental Control Units tured at our GEA Liberec factory in the Czech Republic. This
(LECU). MEPC desired the flexibility offered by GEA DENCO - ®
system is independently controlled via GEA’s own central con-
OfficeCool system, due to the relatively high fit-out alteration trol system which is fully integrated into the PAAET building
requirements of their tenants. The system also met MEPC’s cor- management system.
porate sustainability objectives. GEA has worked closely with
MEPC to deliver the energy efficient solution, through chilled
water cooling and DX heat pumps systems, which will achieve
Class B Energy Performance Certification.

[ 20 ]
YONHAP Media Center – Korea AgustaWestland Helicopters
This national television company has chosen a complete GEA When AgustaWestland refurbished one of their office blocks
DENCO ® -OfficeCool solution for their air conditioning require- they selected the GEA DENCO ® -OfficeCool underfloor air con-
ments for their new state of the art studios in the centre of ditioning system. The office was air conditioned by 14 Zone
Seoul. The system was supplied by GEA Middle East FZE and Units and a number of Local Environmental Control Units
encompasses 24 x GEA Air Handling Units all of which were (LECU), which allows employees control over their workspace
manufactured in our GEA Wurzen Plant in Germany, addition- temperature. When AgustaWestland install any new air con-
ally there are 48 x GEA DENCO Ultra Zone Units and 1,500
®
ditioning system, they carefully review the energy efficiency
GEA LECUs which were manufactured in our Liberec plant in of the system. The GEA DENCO ® -OfficeCool System with each
the Czech Republic. Zone Unit is connected to a reverse cycle heat pump which pro-
vides a very energy efficient cooling and heating system. The
fresh air for the system is provided by two GEA Air Handling
Units, with heat recovery, which provide additional energy
savings.

[ 21 ]
Your GEA experts for air treatment systems
Sales network

Europe

GEA Klimatechnik GmbH GEA Klimatizacia s.r.o.


Gaspoltshofen, Austria Bratislava, Slovakia

GEA Happel Belgiuim N.V./S.A. GEA Klimatizacijska tehnika d.o.o.


Brussels, Belgium Ljubljana, Slovenia

GEA Klima-rashladna tehnika d.o.o. GEA Isisan Tesisat Insaat


Zagreb, Croatia Taahhüt Ticaret ve Sanayi A.S.
Istanbul, Turkey
GEA Heat Exchangers a.s.
Liberec, Czech Republic TOV GEA-Ukrayina
Kiev, Ukraine
GEA Happel S.A.S.
Roncq, France
Our competence centers for
GEA Delbag S.A.S. GEA DENCO® -OfficeCool systems
Montry, France
Middle East
GEA Air Treatment GmbH
Herne, Germany GEA Middle East FZE
P.O. Box 261236, JAFZA Building LOB 17
GEA Air Treatment Production GmbH 4th Floor, Suite 412, Jebal Ali Free Zone, Dubai, UAE
Wurzen, Germany
Europe
GEA Klimatechnika Kft
Budapest, Hungary GEA Heat Exchangers Limited
Dolphin House, Moreton Business Park, Moreton-on-Lugg
GEA Klimatechnik UAB Hereford HR4 8DS, United Kingdom
Vilnius, Lithuania
China
GEA Happel Nederland B.V.
Capelle an der Ijssel, Netherlands GEA Industrial Heat Exchangers Systems
R535/538, South Block, Tower C, Raycom Info Tech Park
GEA Klimatyzacja Sp. z.o.o. No. 2 Kexueyuan South Road, Zhong Guanchun
Wroclaw, Poland Beijing 100190, China

SC GEA Klimatechnik s.r.l. India


Timisoara, Romania
Sales / Distribution
GEA Ecoflex India Pvt Ltd
GEA Klimatechnik GmbH & Co. KG Air Treatment Business Unit
Moscow, Russia Service
713, 7th Floor, 98, Hemkunt Tower
Nehru Place, New Delhi – 110019, India
GEA Klimatechnik GmbH Srbija Production / Manufacturing
Belgrad, Serbia

[ 22 ] PR-2013-0008-GB · Subject to modification · K0-11/2013


PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 23 ]
We live our values.
Excellence Passion Integrity Responsibility GEA-versity

GEA Group is a global engineering company with multi-billion euro sales and operations in more than
50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and
process technology. GEA Group is listed in the STOXX® Europe 600 Index.

© GEA Heat Exchangers. Subject to modification. 11/2013 – PR-2013-0008-GB