Construction savings
Quiet operation
Energy savings
Easy to design
12 –16 °C Conditioned air
under the floor
System redundancy
20 °C Quick installation
Zone Unit
The Zone Unit provides the primary air conditioning to its zone, with each zone
measuring up to 300 m 2. Zone Units are drawn through vertical type, either top return
(ZD type) or bottom return (ZU type) supplying conditioned air into a raised floor void.
Zone Units have all necessary components such as filters, cooling coils, control valves,
microprocessor controllers, and inverter driven fan motors to achieve the required
underfloor condition with the maximum efficiencies. Options include heating (electrical,
low-pressure hot water, or direct expansion), and dehumidification and humidification
using water vapour. Zone Unit configuration can be either top return bottom discharge
or bottom return bottom discharge, and are available in three standard sizes (from
10 kW – 30 kW). Other sizes are available on request.
Chiller
The Chiller is sized to meet the cooling requirements of the entire building.
4 4
4 4 4
Bottom air supply and return (ZU type Zone Unit and LECU)
Where no ceiling is installed or where the integrity of the space above the raised floor
is important, the Zone Unit supplies and returns the air within the access floor space.
This space is simply divided into supply and return air plenums with underfloor
barriers. Cooling and heating can be provided by chilled water and low pressure hot
water or by heat pumps. The space is conditioned by the Zone Unit, and the LECUs
provide the occupants with the ability to control their space.
Benefits at a glance
Almost cost free relocation
Bottom air supply and high level return (ZD type Zone Unit and LECU) capability
The Zone Unit supplies conditioned air into the access floor void and hot air is returned Exceptionally quiet operation
to the Zone Unit at high level. Cooling and heating can be provided by chilled water Local environment control for
and low pressure hot water or by heat pumps. The space is conditioned by the Zone individuals
Unit, and the LECUs provide the occupants with the ability to control their space. Control of temperature and
humidity for a healthier
environment
Bottom air supply and ceiling return (ZD type Zone Unit and LECU) Filtration of both fresh air and
The Zone Unit supplies conditioned air into the access floor void and hot air is returned re-circulated air for a healthier
to the Zone Unit through a suspended ceiling. Cooling and heating can be provided by environment
chilled water and low pressure hot water or by heat pumps. The space is conditioned Economical operation
by the Zone Unit, and the LECUs provide the occupants with the ability to control their Easy maintenance with all
space. services at low level in the
raised floor
Elimination of draughts
Conditioning by external Air Handling Unit (AHU and LECU)
The air conditioning of the space can be done by an externally mounted Air Handling
Unit, which supplies conditioned air through ducts into the access floor. The hot air is
returned to the Air Handling Unit through the ceiling and duct system. The LECUs
provide the occupants with the ability to control their space.
Cooling coils
CW or DX multi-row
constructed
3/8" OD copper tubes
with mechanically
bonded aluminium fins
Coils are tested up to 33 bar
Filter
Heating
Electric heater
250 or 500 W electric heater
LECU
Chilled water control valves
Continously modulated
2- or 3-way valves
Provided with vapour sealed
insulation
Unit size ZD 12 ZD 28 ZD 42
Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended
Air supply Downflow
Cooling capacity
Total (1) kW 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0
Sensible (1) kW 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5
Fan
Fan type Inverter controlled forward curved centrifugal fan
Fan no. n. 1 1 1 2 2 2 3 3
Air flow (4) m3/h 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600
m3/s 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8
Ext. static pressure Pa 25 25 25 25 25 25 25 25
Fan Power kW 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9
Specific fan power W/l/s 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5
Cooling coil Copper tube / aluminium fin
Water flow (3) l/s 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0
Water temperature °C (3) kPa 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Pressure drop-coil & kPa 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0
valve (1)
Electric heater (optional) Low watt density finned tube
Capacity kW 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0
Current A 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0
Heating steps n. 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0
Humidifier (optional) Fail safe electrode boiler
Capacity kg/h 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
Power kW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Power supply
Power source 400 V / 3 Ph / 50 or 60 Hz
Cooling only power kW 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1
Max. power kW 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9
Piping connection Copper tube
Condensate drain mm 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
Humidifier in. mm 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Chilled water in & out mm 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
Dimension
Length mm 647 647 647 1,247 1,247 1,247 1,847 1,847
Depth mm 654 654 654 654 654 654 654 654
Height mm 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
Weight (2) kg 215 215 215 355 355 355 430 430
(1) Rated at return air 26 °C / 50 % and outdoor air temperature 35 °C; (2) For cooling only unit; (3) 7 / 13 °C; (4) Recommended airflows used to maintain office noise level
600 A 0-25
B 26-50 47 This is how efficient
the building is.
Costs in €
400
GEA DENCO ®-OfficeCool C 51-75
200
Traditional D76-100
E 101-125
0 F 126-150
ar r ay n g
Ja
n
Fe
b
M A p M Ju Ju
l
Au Se
p c t N ov D e c G Over 150
O
ZU 12 ZU 28 ZU 42
Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap.
Upflow
42.0 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0
32.7 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7
3 1 1 1 2 2 Text 2 3 3 3
8,700 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700
2.4 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4
25 25 25 25 25 25 25 25 25 25
1.8 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8
0.75 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75
1.4 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4
7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
36.0 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0
6.0 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0
9.0 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0
2.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0
1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
2.0 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0
9.8 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8
22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
1,847 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847
654 850 850 850 800 800 800 800 800 800
1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
430 230 230 230 370 370 370 445 445 445
controller
derfloor sensor. If the underfloor tempera-
ture is below that of the room air, the
damper is modulated open to allow cooling
to the space. The damper is modulated suffi-
heater
(optional) ciently to offset the heat gain to the space.
fan fully modulating floor void
damper sensor
Heating mode
Heating mode If the room sensor detects that the local tem-
return air sensor perature is too cold, it interrogates the under-
independent
raised modular
floor sensor. If the underfloor temperature is
floor
chosen temp
controller
above that of the room air, the damper is
modulated open to allow heating to the space.
The damper is modulated sufficiently to off-
set the heat loss to the space.
heater
(optional)
fan fully modulating
damper
floor void
sensor
Recirculation mode
When the room sensor detects that the local
Recirculation mode temperature matches the set point, the damp-
return air sensor er will be closed and the unit will be in recir-
independent
raised modular
culation mode. An adjustable bleed damper
floor
chosen temp
controller
allows sufficient air from the floor void to
provide the fresh air requirements for the
space.
heater
(optional)
Electric heater mode (optional)
fan fully modulating floor void
damper sensor
Under exceptional circumstances, if the
room sensor detects that the local tempera-
Electric heater mode ture is too cold and upon interrogation of the
return air sensor underfloor sensor it is determined that there
independent
raised modular is insufficient heat available, the controller
floor
controller
chosen temp
The LECU has its own frame and can be used with stringerless raised floors. It exactly
matches a 600 x 600 raised floor panel and only weighs 18 Kg. Relocation of LECUs can
be accomplished in minutes and enables the GEA DENCO ® -OfficeCool Air Conditioning
System to adapt to your changing work space layout.
The Building Management System (BMS) allows monitoring or adjustment of the set
point and fan speed as well as monitoring of the entire system using selectable vari-
ables. When the LECU and the Zone Units are networked, the Zone Unit can be con-
trolled by the average of the readings on the room sensors of the LECUs within any
particular zone.
On Floor Touch
Screen Group
Controller
Data Cable
Building IT
infrastructure
5 m network
cable supplied
with each
LECU
Intranet /
Internet
ZD version ZU version
Model size ZD 12 ZD 28 ZD 42 ZU 12 ZU 28 ZU 42
Weights and dimensions
Weight kg 215 355 430 230 370 445
ZD 12 ZD 28 ZD 42
1,940
1,940
1,940
H
H
647 654 1,247 654 1,847 654
W D W D W D
Unit Front
600 min
Service
Access
ZU 12 ZU 28 ZU 42
1,940
1,940
1,940
H
LECU
H: 222
Top dimension mm 600 x 600
Height (H) mm 222
Width 1 (W1) mm 494
D1: 637
Width 2 (W2) mm 500 D2: 595
Width 3 (W3) mm 595
Depth 1 (D1) mm 637
W3: 595
Depth 2 (D2) mm 595
Quality
Certificates
Quality Assurance – Always focusing on the customer
EN ISO 9001:2008
CE marking for all EU Quality management with HX-Factor from development to after-sales
relevant products We, the GEA experts for climate and environment solutions, are the European market
Safety of Machinery: leaders for the entire spectrum of air treatment. Quality is one of our key success factors.
EN 60204-1:2006+A1:2009 Looking back on more than 100 years of experience we have continuously improved
Safety of Machinery: and optimized our products and business operations, keeping one central goal in focus:
N ISO 12100-1:2003 Exceeding our customers´ expectations. Our major quality feature is the HX-Factor. It
Safety of Machinery: is our performance commitment and stands for unique expertise in heat exchange (HX
EN ISO 12100-2:2003 = HEAT EXCHANGE). The HX-Factor is the one special personal strength that every
EMC Emissions: single employee invests into the production processes. In order to keep our staff as
EN 61000-6-3:2007 healthy and motivated as possible, we are committed to comply with applicable regu-
EMC Immunity: lations and requirements. Regular training ensures that our employees maintain their
EN 61000-6-2:2005 skills in accordance with the latest developments. The HX-Factor is also the sum of all
Refrigeration Systems: attributes that make our products convincing – in the case of DENCO ® -OfficeCool it is
EN 378-1/2/3/4:2008 cost and energy efficiency as well as flexibility. Finally, the HX-Factor is what we live
ASME 9 in the heat exchange business to be engineering for a better world. Numerous certifi-
cations prove our competence.
Aerial photograph showing the factory Production facility in Pune, India The Turkey location in Istanbul
in Liberec, Czech Republic
Manufacturing Centers
Air treatment competence around the globe
Over the past 100 years the GEA experts for room climate solutions have established Global approach
an international network of manufacturing sites. Centers of excellence for air handling International quality standards
units, close control units, decentral air treatment, and clean rooms are located in several Constant improvement
countries throughout Europe and Asia. All of them deal constantly with the continu- Flexible standardization
ous improvement in production processes and optimization according to the latest Just in time production
international standards. With a clear focus on standardization, all sites can assure a Customer in focus
high level of production flexibility. Furthermore, just in time production with short
delivery times helps fulfil customer requirements. With integrated research and devel-
opment facilities, we are able to handle even the most technically demanding projects.
One of our special skills is advanced knowledge in metal sheet processing. No matter
what our customers ask of us – reliability is the most decisive feature that character-
izes all GEA sites.
[ 20 ]
YONHAP Media Center – Korea AgustaWestland Helicopters
This national television company has chosen a complete GEA When AgustaWestland refurbished one of their office blocks
DENCO ® -OfficeCool solution for their air conditioning require- they selected the GEA DENCO ® -OfficeCool underfloor air con-
ments for their new state of the art studios in the centre of ditioning system. The office was air conditioned by 14 Zone
Seoul. The system was supplied by GEA Middle East FZE and Units and a number of Local Environmental Control Units
encompasses 24 x GEA Air Handling Units all of which were (LECU), which allows employees control over their workspace
manufactured in our GEA Wurzen Plant in Germany, addition- temperature. When AgustaWestland install any new air con-
ally there are 48 x GEA DENCO Ultra Zone Units and 1,500
®
ditioning system, they carefully review the energy efficiency
GEA LECUs which were manufactured in our Liberec plant in of the system. The GEA DENCO ® -OfficeCool System with each
the Czech Republic. Zone Unit is connected to a reverse cycle heat pump which pro-
vides a very energy efficient cooling and heating system. The
fresh air for the system is provided by two GEA Air Handling
Units, with heat recovery, which provide additional energy
savings.
[ 21 ]
Your GEA experts for air treatment systems