Part descriptions

Specifications

Warning Serious injury may result if instructions are not followed.


Caution Product may be damaged, or injury may result if instructions are not followed.
The following is an explanation of the symbols used in the operation manual.
Caution: Injury or danger may occur under special conditions.

Warning
1. In case of using this unit with machinery(Ex: nuclear power control, medical equipment, ship,
vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention
equipment, etc) which may cause damages to human life or property, it is required to install
fail-safe device.
It may cause fire, human injury or damage to property.
2. Do not disassemble and modify this unit. Please contact us if it is required.
It may cause an electric shock, fire or damage to product.
3. Do not connect, check or repair this unit when power is ON.
It may cause an electric shock.
4. Power input voltage must be within the rated range and power line should be used as the
rated wire standard by each model.
It may cause an electric shock, or fire.
5. Please check the connection before operating.
It may cause an electric shock, fire, or damage to product.
6. Please observe the rated specification.
It may cause fire, damage to product.
7. Do not insert fingers or other object into the open part.
It may cause an electric shock, injury, or damage to product.
8. Do not use this unit where it is outside or there are flammable or explosive gases, danger
of corrosion, water, vibration etc.
It may cause an electric shock, fire or injury.
9. Grounding wire should be grounded alone and be over than AWG16.
It may cause an electric shock.
10. This unit must be mounted DIN rail or on the panel.
It may cause an electric shock.

Dielectric strength
Insulation resistance
Vibration
Shock
Output indicator
Output low-voltage indicator
EMS
EMI
Safety
Weight5

Dimensions

SPB-060 Series

5-M3.5

SPB-120 Series

When opening terminal cover

2 2. Output power [-] terminal

3
4

5 4. Output low-voltage(DC LOW)

3. Output(DC ON) indicator(Green)


indicator(Red)

8. F.G. (Frame Ground) terminal

1. Do not put obstacles for well ventilation around this product.


It may cause damage to this product or malfunction of peripheral equipment by heating.
2. Do not touch this product during operation or after stopping.
It may cause burn due to high surface temperature of this product.
3. Please stop this unit when mechanical trouble occurs.
It may cause fire or damage to product.
4. Tighten terminal screws with 1.0 to 1.2 N.m torque.
It may cause fire or damage to product.
5. Do not touch the terminals during insulation resistance test or insulation dielectric
strength test.
It may cause an electric shock.
6. Do not use this unit in a place with severe vibration.
It may cause damage to product.
7. In cleaning the unit, do not use water or organic solvent. And use dry cloth.
It may cause an electric shock and fire.
8. Please separate as an industrial waste when discarding this unit.
9. This unit shall not be used outdoors.
It may shorten the life cycle of the product or cause an electric shock.
10. Do not inflow dust or wire dregs into the unit.
It may cause fire or malfunction.

Model
SPB - 120 - 24
Output voltage

Output power

50

110

36

Mounting

1. Mounting to and Removing from DIN rail


Mounting to DIN rail
First put the unit on the part of the rail and then
press it for the direction .

Caution for using

58.0V10%

1. Caution for operating


This product does not have the function for parallel or series operation.
The output current must be used within the rated specification.
If over current is applied to the product, over current protection is operating.
It causes shorten the life cycle of the product.
The output voltage must be used within the rated output specification.
For the product, which has the control function for over-voltage, if making the output voltage
adjuster(V.ADJ) to over rated voltage, the function starts to work.
This product has the function of over-heating protection.
The over-heating protection operates when the product has over-heating condition.
The product normally operates if the load is removed for over 5 minutes.
In case of the SPB-060, it does not have the harmonics suppression and power factor
improvement circuit. To improve harmonics suppression and power factor, install the additional
device.
In case of the SPB-060, it uses condenser rectification, and power factor is within 0.4 to 0.6
range. To use a cabinet panel or a electric transformer, select input power capacity of this
product as below formula.
Output active power[W]
Input apparent power[VA] =
Power factorEfficiency
This product is provided with a noise filter, but noise is variable according to operating
conditions such as installation environment and wiring.
When the inner fuse is damaged, replace the fuse of same specification.
2. Caution for mounting
Mount this product on the surface of metal panel vertically for the reliability.
Please mount this product at a well-ventilated place in order to increase the heat radiation efficiency.
Effective mounting
Natural cooling mounting
Forced air cooling mounting

43.0V10%

When installing more than two power supplies, min.


20mm distance is required to radiate heat effectively.
Assure min. 75mm distance of the upper or the lower
product and mount the products as following figure.
Air flow

12VDC
24VDC
48VDC

060
120
240

60W
120W
240W

SPB

Switching Mode Power Supply

The above specifications are subject to change and some models may be discontinued
without notice.

2-4.2

When mounting this unit


on the rail, place the
unit at least 30mm above
from the floor to remove it
easily.

+V -V

FG

Min. 30mm

Rail hook
2-M4

Recommended power
input voltage wire

Model

AWG21-19

AWG18-16

SPB-060-12

SPB-240-12

SPB-060-24

SPB-240-24

SPB-120-24

SPB-240-48

Output derating curve by ambient temperature


Load 120
ratio
[%] 100

Forced air cooling


(Air volume: 0.878m3/min)

80

Natural cooling

60
50
40
20
0
-10

10

20

30

40

For effective heat radiation, assure min. 75mm


distance of the upper and lower product to flow
air as the below figure. Install a fan which min.
air volume is 0.878m3/min within 50mm from the
product to maintain the reliability of the product.
Air flow

Min. 75mm

+V -V

Min. 75mm

+V -V

FG

FG

Min. 75mm

50 60 70 80 90
Ambient temperature[]

FG

Max. 50mm

Min. 75mm

FAN

110

When there is no rail


This unit has two hooks. If pushing these at the arrows direction as
the below figure, you can mount this unit with general bolts.

Removing from DIN rail


First put a screw driver into the part and
push it downward.

If the inner temperature of the switching element is around 140 by overheat, it stops
switching operation and becomes open state. Output voltage is not output.

2. Panel mounting

Recommended power input voltage wire for model


12
24
48

80

Over-heating protection

7-M3.5

110

Max. 1%

Min. 20mm
2-4.2

3
4

6. Input power [L] terminal


8 7. Input power [N] terminal

+V -V

2-4.2

5. Output voltage adjuster(V.ADJ)

SPB-240 Series

7-M3.5

48VDC
5A

1: It is for the rated input voltage 100-240VAC and 100% load.


2: Adjusting voltage by the output voltage adjuster (V.ADJ), it is changed the below voltage adjustment range (5%).
3: It is for the rated input voltage 100-240VAC (85-264VAC) and 100% load.
4: It is for the rated input voltage 100-240VAC.
5: This weight is with packaging and the weight in parentheses is only unit weight.
Environment resistance is rated at no freezing or condensation.

Caution

Item

1. Output power [+] terminal

35.4

Please observe the cautions that follow;

SPB-120/240 Series

SPB-060 Series

SPB-240-48

115

Please keep these instructions and review them before using this unit.

125

Caution for your safety

132

Thank you very much for selecting Autonics products.


For your safety, please read the following before using.

35.4

115

132

125

35.4

SPB-060-12
SPB-060-24
SPB-120-24
SPB-240-12
SPB-240-24
60W
120W
240W
100-240VAC(85-264VAC)
50/60Hz
Min. 75%
Min. 80%
Min. 86%
Min. 88%
Min. 0.9
Max. 1.6A
Max. 1.9A
Max. 3.8A
Built-in
Built-in
12VDC
24VDC
24VDC
12VDC
24VDC
5A
2.5A
5A
20A
10A
Max. 5%
Max. 0.5%
Max. 1%
Max. 1.5%
Max. 1%
Max. 3%
Max. 1.5%
Max. 600ms
Max. 1000ms
Min. 10ms
Min. 20ms
Max. 25A (100VAC), Max. 40A(240VAC)
Max. 50A (100VAC), Max. 50A(240VAC)
Min. 105%
30.0V10%
16.0V10%
30.0V10%
Max. 10ms
9.6V10%
20.0V10%
10.0V10%
20.0V10%
-10 to 50, Storage: -25 to 65
25 to 85%RH, Storage: 25 to 90%RH
IP20(IEC Standard)
3000VAC 50/60Hz for 1min(Between all input and output terminals)
1500VAC 50/60Hz for 1min(Between all input terminals and F.G)
Min. 100M (at 500VDC megger between all input and output terminals)
0.75mm amplitude at frequency of 10 to 55Hz in each of X, Y, Z directions for 2 times
300m/s in X, Y, Z directions for 3 times
Green LED
Red LED
Conforms to EN61000-6-2
Conforms to EN61000-6-4
Conforms to IEC60950, IEC50178
Approx. 570g
Approx. 347g(Approx. 274g)
Approx. 866g(Approx. 736g)
(Approx. 466g)

100

110

SPB SERIES

Voltage
Frequency
Input
Efficiency1
condition
Power factor1
Current consumption
Power factor correction circuit
Voltage
Current
Voltage adjustment range2
Input variation3
Output
characteristics Load variation1
Ripple&Ripple noise1
Start-up time1
Hold time1
Inrush current protection
Output over current protection4
Output over voltage protection
Protection
Output short-circuit protection
Output low-voltage indicate
Ambient temperature
Environment
Ambient humidity
Protection

117

SWITCHING MODE POWER SUPPLY

Model
Output power

Air flow

3. Dielectric or insulation resistance test when this unit is installed in the control panel.
Separate the unit completely from a control panel circuit.
Short all terminals of the unit.
4. Caution for connecting the input power terminal
Connect input line (AC) to the input terminal correctly.
When you connect this to the other terminal, it may cause damage to the power supply.
5. Do not use this unit at below places.
Place where there are severe vibration or impact.
Place where strong alkalis or acids are used.
Place where there is direct ray of the sun.
Place where strong magnetic field or electric noise are generated.
6. Installation environment
It shall be used indoor
Altitude max. 2000m
Pollution Degree 2
Installation Category II
It may cause malfunction if above instructions are not followed.

Major products
Photoelectric sensors
Temperature controllers
Fiber optic sensors
Temperature/Humidity transducers
Door sensors
SSR/Power controllers
Door side sensors
Counters
Area sensors
Timers
Proximity sensors
Panel meters
Pressure sensors
Tachometer/Pulse(Rate)meters
Rotary encoders
Display units
Connector/Sockets
Sensor controllers
Switching mode power supplies
Control switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper motors/drivers/motion controllers
Graphic/Logic panels
Field network devices
Laser marking system(Fiber, CO, Nd:YAG)
Laser welding/soldering system

http://www.autonics.com
Satisfiable Partner For Factory Automation
HEAD QUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan, Korea
OVERSEAS SALES:
#402-404, Bucheon Techno Park, 655, Pyeongcheon-ro,
Wonmi-gu, Bucheon, Gyeonggi-do, Korea
TEL: 82-32-610-2730 / FAX: 82-32-329-0728
E-mail: sales@autonics.com

EP-KE-15-0014B